Manual Rosemount DP Level Transmitters Diaphragm Seal Systems en 76026 - 1 - 1 - 42 - 1

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Reference Manual Configuration

00809-0100-4002 September 2022

4.1.5 Non-zero based lower range value (Tuned-System


assembly)
Figure 4-5: Tuned-System™

L max
108 in.
SGF = 0.934

dL = 120 in.
SGP = 0.75

L min
0 in.

dH = vertical distance from transmitter to high pressure seal


dL = vertical distance from transmitter to low pressure seal
Lmax = the maximum level of process above the high pressure seal and typically the 20
mA lower range value
Lmin = the minimum level of process above the high pressure seal and typically the 4 mA
lower range value
SGF = specific gravity of fill fluid
SGP = specific gravity of process fluid

Tank span = Lmax × SGP – Lmin × SGP


= (108 in. × 0.75) = 81 inH2O
4 mA = Lmin × SGP – (dL × SGF)
= (0 in. × 0.75) – (120 in. × 0.934) = –112.08 inH2O
20 mA = Lmax × SGP – (dL × SGF)
= (108 in. × 0.75) – (120 in. × 0.934) = –31.08 inH2O
Span = 81 inH2O (–112.08 to –31.08 inH2O)

Note
Silicone 200 has a specific gravity of 0.934.

Rosemount DP Level 83

You might also like