Professional Documents
Culture Documents
TAQATI Notes Unit 4 HVAC
TAQATI Notes Unit 4 HVAC
TAQATI Notes Unit 4 HVAC
For different refrigerants, there are different values for condenser pressure, condenser temperature,
and evaporator pressure and evaporator temperature.
Working of VPC
The refrigerant (for example R-717) enters the The condenser is essentially a heat exchanger. Heat is
compressor at low temperature and low pressure. It is transferred from the refrigerant to a flow of
in a gaseous state. Here, compression takes place to water. This water goes to a cooling tower for cooling
raise the temperature and refrigerant pressure. The in the case of water-cooled condensation. Note that
refrigerant leaves the compressor and enters to the seawater and air-cooling methods may also play this
condenser. Since this process requires work, an role. As the refrigerant flows through the condenser, it
electric motor may be used. Compressors themselves is in a constant pressure.
can be scroll, screw, centrifugal or reciprocating types.
When the refrigerant enters the throttling valve, it At this stage of the Vapor Compression Refrigeration
expands and releases pressure. Consequently, the Cycle, the refrigerant is at a lower temperature than its
temperature drops at this stage. Because of these surroundings. Therefore, it evaporates and absorbs
changes, the refrigerant leaves the throttle valve as a latent heat of vaporization. Heat extraction from the
liquid vapor mixture, typically in proportions of refrigerant happens at low pressure and temperature.
around 75 % and 25 % respectively. Compressor suction effect helps maintain the low
pressure.
Throttling valves play two crucial roles in the vapor
compression cycle. First, they maintain a pressure There are different evaporator versions in the market,
differential between low- and high-pressure sides. but the major classifications are liquid cooling and air
Second, they control the amount of liquid refrigerant cooling, depending whether they cool liquid or air
entering the evaporator. respectively.
CHILLER
Combine evaporator,
condenser and
compressor into a single
unit
2300+ kJ of heat go into the atmosphere for each kilogram of water evaporated.
FANS
HUMIDITY CONTROL
AIR DELIVERY (SECONDARY SYSTEMS)
SAMPLE PROBLEMS
ABSORPTION CHILLERS
Answer = D. The Coefficient of Performance is the Powermoved/Powerinput. With a 250 ton chiller,
this machine is capable of moving 250 tons of cooling, therefore the Powerinput would be:
4.2=Pm/Pi
4.2=250 tons/Pi
Pi = 59.52 tons
But “tons” must be converted into kW to answer the question. A “ton” is a rate of energy
flow equal to 12,000 BTUs per hour and we also know that 1 kW = 3412 BTUs/hour. Thus the amount
of kW can be found by:
=(59.52 tons)(12,000 BTU/hr*ton)(kW/3412BTU/hr)
=209 kW
Q2. The refrigerant in a vapour compression air conditioner is always in the vapour state.
(A) True (B) False
Q3. An absorption chiller system with a COP of 0.8 is powered by hot water that enters at 90°C and
leaves at 80° C at a rate of 2 L/s. The chilled water operates on a 5°C temperature difference and the
condenser water on a 10°C temperature difference. Calculate the water flow.
(A) 0.8 L/s
(B) 1.6 L/s
(C) 3.2 L/s
(D) 3.6 L/s
(E) 2.4 L/s
Answer: (C)
q = LPS x 4.2 x DT
q in = (2)(4.2)(90-80) = 84 kW
q out = COP x q in = 0.8 x q in = 67.2 kW
67.2 = (LPS)(4.2)(5)
LPS out = 3.2 LPS
Q4. 5000 L/s of air leaves an air handler at 10°C. It is delivered to a room at 18°C. How many kW of air
conditioning capacity was lost in the ductwork? (A) 48 kW (B) 20 kW (C) 36 kW (D) 60 kW (E) 3 kW
Answer: (A)
q = LPS x 1.2 x DT
= 5000 x 1.2 x 10 = 48,000 W = 48 kW
Q5. Given the parameters below, estimate the percent outside air in this simple single zone heating
system. Outside Air Temperature = 5 °C Return Air Temperature = 22 °C Mixed Air Temperature= 18.3
°C (A) 27.2 % (B) 21.8 % (C) 36.5 % (D) 5.0% (E) 86.5 %
Answer: (B)
% = (RAT – MAT)/(RAT – OAT)
= (22 – 18.3)/(22 – 5) = 21.8%