Air System Sizing Summary for SPLIT UNITS

Project Name: Genna Villa 05/09/2024


Prepared by: ahmed sh 10:09am

Air System Information


Air System Name SPLIT UNITS Number of zones 4
Equipment Class TERM Floor Area 71,9 m²
Air System Type SPLT-FC Location Riyadh, Saudi Arabia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Hourly Analysis Program v4.90 Page 1 of 10


Zone Sizing Summary for SPLIT UNITS
Project Name: Genna Villa 05/09/2024
Prepared by: ahmed sh 10:09am

Air System Information


Air System Name SPLIT UNITS Number of zones 4
Equipment Class TERM Floor Area 71,9 m²
Air System Type SPLT-FC Location Riyadh, Saudi Arabia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 10,6 1004 1004 Oct 1500 3,8 14,9 67,40
Zone 2 7,3 690 690 Aug 1700 1,8 21,0 32,88
Zone 3 4,1 388 388 Sep 1800 1,9 21,3 18,22
Zone 4 8,9 846 846 Sep 1400 3,8 14,7 57,52

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5,6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 10,6 10,6 24,9 / 13,4 15,4 / 9,6 - Sep 1500
Zone 2 7,7 7,7 25,1 / 13,7 15,2 / 9,7 - Jul 1800
Zone 3 4,2 4,2 25,2 / 13,5 15,6 / 9,7 - Sep 1700
Zone 4 8,9 8,9 24,6 / 13,3 15,2 / 9,5 - Sep 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11,1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 4,0 20,7 / 24,3 - 1004 0,000 0,000 14
Zone 2 2,3 20,6 / 23,6 - 690 0,000 0,000 28
Zone 3 2,1 20,4 / 25,2 - 388 0,000 0,000 11
Zone 4 3,8 20,6 / 24,6 - 846 0,000 0,000 9

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
004 GF OFFICE 1 10,6 Oct 1500 1004 3,8 14,9 67,40
Zone 2
005 GF DIRTY KITCHEN 1 7,3 Aug 1700 690 1,8 21,0 32,88
Zone 3
008 L1 BED ROOM 1 4,1 Sep 1800 388 1,9 21,3 18,22
Zone 4
010 L2 BED ROOM(2) 1 8,9 Sep 1400 846 3,8 14,7 57,52

Hourly Analysis Program v4.90 Page 2 of 10


Ventilation Sizing Summary for SPLIT UNITS
Project Name: Genna Villa 05/09/2024
Prepared by: ahmed sh 10:09am

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
004 GF OFFICE 1 14,9 4,0 1004,3 2,50 0,30 0,0 0,0 14,5
Zone 2
005 GF DIRTY KITCHEN 1 21,0 4,0 690,5 3,80 0,60 0,0 0,0 27,8
Zone 3
008 L1 BED ROOM 1 21,3 2,0 388,0 2,50 0,30 0,0 0,0 11,4
Zone 4
010 L2 BED ROOM(2) 1 14,7 2,0 845,5 2,50 0,30 0,0 0,0 9,4
Totals (incl. Space Multipliers) 2928,4 63,1

Hourly Analysis Program v4.90 Page 3 of 10


Air System Design Load Summary for SPLIT UNITS
Project Name: Genna Villa 05/09/2024
Prepared by: ahmed sh 10:09am

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 43,8 °C / 18,9 °C HEATING OA DB / WB 6,2 °C / 1,2 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 69 m² 10148 - 69 m² - -
Wall Transmission 207 m² 5373 - 207 m² 3942 -
Roof Transmission 15 m² 418 - 15 m² 150 -
Window Transmission 69 m² 4033 - 69 m² 3458 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 1 m² 24 - 1 m² 20 -
Floor Transmission 36 m² 0 - 36 m² 0 -
Partitions 16 m² 0 - 16 m² 0 -
Ceiling 57 m² 0 - 57 m² 0 -
Overhead Lighting 1315 W 1314 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3275 W 3275 - 0 0 -
People 12 885 815 0 0 0
Infiltration - 5010 -635 - 3754 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 30480 180 - 11324 0
Zone Conditioning - 29791 180 - 11186 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 63 L/s 1361 -175 63 L/s 1045 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 31152 5 - 12232 0
Terminal Unit Cooling - 31152 0 - 0 0
Terminal Unit Heating - 0 - - 12232 -
>> Total Conditioning - 31152 0 - 12232 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 10


Zone Design Load Summary for SPLIT UNITS
Project Name: Genna Villa 05/09/2024
Prepared by: ahmed sh 10:09am

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41,0 °C / 17,3 °C HEATING OA DB / WB 6,2 °C / 1,2 °C
OCCUPIED T-STAT 23,9 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 33 m² 6083 - 33 m² - -
Wall Transmission 29 m² 586 - 29 m² 550 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 33 m² 1598 - 33 m² 1626 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 2 - 0 m² 3 -
Floor Transmission 15 m² 0 - 15 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 15 m² 0 - 15 m² 0 -
Overhead Lighting 75 W 74 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 80 W 80 - 0 0 -
People 4 270 141 0 0 0
Infiltration - 1920 -279 - 1669 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 10614 -139 - 3848 0

Zone 2 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 43,5 °C / 19,1 °C HEATING OA DB / WB 6,2 °C / 1,2 °C
OCCUPIED T-STAT 23,9 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 10 m² 1052 - 10 m² - -
Wall Transmission 66 m² 1971 - 66 m² 1267 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 10 m² 580 - 10 m² 484 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 9 - 0 m² 8 -
Floor Transmission 21 m² 0 - 21 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 21 m² 0 - 21 m² 0 -
Overhead Lighting 340 W 340 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3000 W 3000 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7298 533 - 1758 0

Hourly Analysis Program v4.90 Page 5 of 10


Zone Design Load Summary for SPLIT UNITS
Project Name: Genna Villa 05/09/2024
Prepared by: ahmed sh 10:09am

Zone 3 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 40,8 °C / 18,0 °C HEATING OA DB / WB 6,2 °C / 1,2 °C
OCCUPIED T-STAT 23,9 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 347 - 3 m² - -
Wall Transmission 71 m² 2318 - 71 m² 1361 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 174 - 3 m² 164 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 5 - 0 m² 5 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 21 m² 0 - 21 m² 0 -
Overhead Lighting 533 W 532 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 115 W 115 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 474 -76 - 417 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4101 -5 - 1947 0

Zone 4 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 43,4 °C / 18,8 °C HEATING OA DB / WB 6,2 °C / 1,2 °C
OCCUPIED T-STAT 23,9 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 24 m² 3475 - 24 m² - -
Wall Transmission 40 m² 880 - 40 m² 764 -
Roof Transmission 15 m² 470 - 15 m² 150 -
Window Transmission 24 m² 1344 - 24 m² 1183 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 6 - 0 m² 5 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 16 m² 0 - 16 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 368 W 367 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 79 W 79 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 2180 -281 - 1669 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 8936 -210 - 3771 0

Hourly Analysis Program v4.90 Page 6 of 10


Space Design Load Summary for SPLIT UNITS
Project Name: Genna Villa 05/09/2024
Prepared by: ahmed sh 10:09am

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 004 GF OFFICE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41,0 °C / 17,3 °C HEATING OA DB / WB 6,2 °C / 1,2 °C
OCCUPIED T-STAT 23,9 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 33 m² 6083 - 33 m² - -
Wall Transmission 29 m² 586 - 29 m² 550 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 33 m² 1598 - 33 m² 1626 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 2 - 0 m² 3 -
Floor Transmission 15 m² 0 - 15 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 15 m² 0 - 15 m² 0 -
Overhead Lighting 75 W 74 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 80 W 80 - 0 0 -
People 4 270 141 0 0 0
Infiltration - 1920 -279 - 1669 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 10614 -139 - 3848 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 004 GF OFFICE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 17 1,280 - 253 - 319
DOOR 0 1,703 - 2 - 3
S EXPOSURE
WALL 3 1,280 - 106 - 56
WINDOW 1 14 3,339 0,811 678 3041 690
E EXPOSURE
WALL 5 1,280 - 149 - 103
WINDOW 1 9 3,339 0,811 420 947 427
W EXPOSURE
WALL 4 1,280 - 78 - 72
WINDOW 1 10 3,339 0,811 500 2095 509

Hourly Analysis Program v4.90 Page 7 of 10


Space Design Load Summary for SPLIT UNITS
Project Name: Genna Villa 05/09/2024
Prepared by: ahmed sh 10:09am

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' 005 GF DIRTY KITCHEN '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 43,5 °C / 19,1 °C HEATING OA DB / WB 6,2 °C / 1,2 °C
OCCUPIED T-STAT 23,9 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 10 m² 1052 - 10 m² - -
Wall Transmission 66 m² 1971 - 66 m² 1267 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 10 m² 580 - 10 m² 484 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 9 - 0 m² 8 -
Floor Transmission 21 m² 0 - 21 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 21 m² 0 - 21 m² 0 -
Overhead Lighting 340 W 340 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3000 W 3000 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7298 533 - 1758 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' 005 GF DIRTY KITCHEN '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 24 1,280 - 580 - 450
WINDOW 1 1 3,339 0,811 68 59 57
DOOR 0 1,703 - 3 - 3
S EXPOSURE
WALL 25 1,280 - 749 - 470
DOOR 0 1,703 - 6 - 5
E EXPOSURE
WALL 5 1,280 - 168 - 92
WINDOW 1 9 3,339 0,811 512 994 427
W EXPOSURE
WALL 13 1,280 - 474 - 256

Hourly Analysis Program v4.90 Page 8 of 10


Space Design Load Summary for SPLIT UNITS
Project Name: Genna Villa 05/09/2024
Prepared by: ahmed sh 10:09am

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' 008 L1 BED ROOM '' IN ZONE '' Zone 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 40,8 °C / 18,0 °C HEATING OA DB / WB 6,2 °C / 1,2 °C
OCCUPIED T-STAT 23,9 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 347 - 3 m² - -
Wall Transmission 71 m² 2318 - 71 m² 1361 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 174 - 3 m² 164 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 5 - 0 m² 5 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 21 m² 0 - 21 m² 0 -
Overhead Lighting 533 W 532 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 115 W 115 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 474 -76 - 417 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4101 -5 - 1947 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' 008 L1 BED ROOM '' IN ZONE '' Zone 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 17 1,280 - 381 - 321
DOOR 0 1,703 - 5 - 5
S EXPOSURE
WALL 14 1,280 - 511 - 261
WINDOW 1 3 3,339 0,811 174 347 164
E EXPOSURE
WALL 20 1,280 - 649 - 389
W EXPOSURE
WALL 20 1,280 - 777 - 389

Hourly Analysis Program v4.90 Page 9 of 10


Space Design Load Summary for SPLIT UNITS
Project Name: Genna Villa 05/09/2024
Prepared by: ahmed sh 10:09am

TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' 010 L2 BED ROOM(2) '' IN ZONE '' Zone 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 43,4 °C / 18,8 °C HEATING OA DB / WB 6,2 °C / 1,2 °C
OCCUPIED T-STAT 23,9 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 24 m² 3475 - 24 m² - -
Wall Transmission 40 m² 880 - 40 m² 764 -
Roof Transmission 15 m² 470 - 15 m² 150 -
Window Transmission 24 m² 1344 - 24 m² 1183 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 6 - 0 m² 5 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 16 m² 0 - 16 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 368 W 367 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 79 W 79 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 2180 -281 - 1669 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 8936 -210 - 3771 0

TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' 010 L2 BED ROOM(2) '' IN ZONE '' Zone 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 16 1,280 - 284 - 303
DOOR 0 1,703 - 3 - 3
S EXPOSURE
WALL 4 1,280 - 125 - 79
WINDOW 1 12 3,339 0,811 672 1906 591
E EXPOSURE
WALL 4 1,280 - 136 - 79
WINDOW 1 12 3,339 0,811 672 1569 591
W EXPOSURE
WALL 16 1,280 - 335 - 303
DOOR 0 1,703 - 3 - 3
H EXPOSURE
ROOF 15 0,685 - 470 - 150

Hourly Analysis Program v4.90 Page 10 of 10