1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 004 GF OFFICE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41,0 °C / 17,3 °C HEATING OA DB / WB 6,2 °C / 1,2 °C
OCCUPIED T-STAT 23,9 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 33 m² 6083 - 33 m² - -
Wall Transmission 29 m² 586 - 29 m² 550 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 33 m² 1598 - 33 m² 1626 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 2 - 0 m² 3 -
Floor Transmission 15 m² 0 - 15 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 15 m² 0 - 15 m² 0 -
Overhead Lighting 75 W 74 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 80 W 80 - 0 0 -
People 4 270 141 0 0 0
Infiltration - 1920 -279 - 1669 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 10614 -139 - 3848 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 004 GF OFFICE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 17 1,280 - 253 - 319
DOOR 0 1,703 - 2 - 3
S EXPOSURE
WALL 3 1,280 - 106 - 56
WINDOW 1 14 3,339 0,811 678 3041 690
E EXPOSURE
WALL 5 1,280 - 149 - 103
WINDOW 1 9 3,339 0,811 420 947 427
W EXPOSURE
WALL 4 1,280 - 78 - 72
WINDOW 1 10 3,339 0,811 500 2095 509
TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' 005 GF DIRTY KITCHEN '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 43,5 °C / 19,1 °C HEATING OA DB / WB 6,2 °C / 1,2 °C
OCCUPIED T-STAT 23,9 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 10 m² 1052 - 10 m² - -
Wall Transmission 66 m² 1971 - 66 m² 1267 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 10 m² 580 - 10 m² 484 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 9 - 0 m² 8 -
Floor Transmission 21 m² 0 - 21 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 21 m² 0 - 21 m² 0 -
Overhead Lighting 340 W 340 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3000 W 3000 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7298 533 - 1758 0
TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' 005 GF DIRTY KITCHEN '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 24 1,280 - 580 - 450
WINDOW 1 1 3,339 0,811 68 59 57
DOOR 0 1,703 - 3 - 3
S EXPOSURE
WALL 25 1,280 - 749 - 470
DOOR 0 1,703 - 6 - 5
E EXPOSURE
WALL 5 1,280 - 168 - 92
WINDOW 1 9 3,339 0,811 512 994 427
W EXPOSURE
WALL 13 1,280 - 474 - 256
TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' 008 L1 BED ROOM '' IN ZONE '' Zone 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 40,8 °C / 18,0 °C HEATING OA DB / WB 6,2 °C / 1,2 °C
OCCUPIED T-STAT 23,9 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 347 - 3 m² - -
Wall Transmission 71 m² 2318 - 71 m² 1361 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 174 - 3 m² 164 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 5 - 0 m² 5 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 21 m² 0 - 21 m² 0 -
Overhead Lighting 533 W 532 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 115 W 115 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 474 -76 - 417 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4101 -5 - 1947 0
TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' 008 L1 BED ROOM '' IN ZONE '' Zone 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 17 1,280 - 381 - 321
DOOR 0 1,703 - 5 - 5
S EXPOSURE
WALL 14 1,280 - 511 - 261
WINDOW 1 3 3,339 0,811 174 347 164
E EXPOSURE
WALL 20 1,280 - 649 - 389
W EXPOSURE
WALL 20 1,280 - 777 - 389
TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' 010 L2 BED ROOM(2) '' IN ZONE '' Zone 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 43,4 °C / 18,8 °C HEATING OA DB / WB 6,2 °C / 1,2 °C
OCCUPIED T-STAT 23,9 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 24 m² 3475 - 24 m² - -
Wall Transmission 40 m² 880 - 40 m² 764 -
Roof Transmission 15 m² 470 - 15 m² 150 -
Window Transmission 24 m² 1344 - 24 m² 1183 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 6 - 0 m² 5 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 16 m² 0 - 16 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 368 W 367 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 79 W 79 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 2180 -281 - 1669 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 8936 -210 - 3771 0
TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' 010 L2 BED ROOM(2) '' IN ZONE '' Zone 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 16 1,280 - 284 - 303
DOOR 0 1,703 - 3 - 3
S EXPOSURE
WALL 4 1,280 - 125 - 79
WINDOW 1 12 3,339 0,811 672 1906 591
E EXPOSURE
WALL 4 1,280 - 136 - 79
WINDOW 1 12 3,339 0,811 672 1569 591
W EXPOSURE
WALL 16 1,280 - 335 - 303
DOOR 0 1,703 - 3 - 3
H EXPOSURE
ROOF 15 0,685 - 470 - 150