GROUND FAULT MONITOR GM-A2HR


VFD & BWTS SYSTEM LINE WIRING & DESCRIPTION

WIRING & DESCRIPTION


Un-grounded AC line

WIRING
1 - Connect to System Line (L2), (L1) or (L3)
4 - External Meter (FS 1mA), separated from alarm circuit
5 - External reset T.B : Device reset
6 - Protective earth (connect to equipment ground) DISPLAY & CONTROL
11 - Alarm output (DPDT) 2 - Power LED light 3 - Alarm LED light
12 - Remote function control as below (use if necessary) 14 - Reset Button : Device reset
C - T1 : Self test mode, meter will indicate zero 7 - Alarm set selector (16steps - digital)
C - T2 : Fault finding mode, use to find grounding points 8 - DC fault LED light
13 - Auxiliary Supply voltage 9 - Meter zero adjust with VR at test mode
A1-A2 : External supply voltage AC110 / 220V 50/60Hz 10 - Mode selector as below
A1-A3 : External supply voltage AC440V 50/60Hz
TEST mode : Self test mode, meter will indicate zero(0)
500uF mode : Measuring at VFD, BWTS(Ce=up to 500uF) runing
1,000uF mode : Measuring at VFD, BWTS
(Ce=up to 1,000uF) running.
FAULT FINDING mode : Use to find grounding points
Note : Ce means leakage capacitance between cable and hull.

Design and specifications can be change for quility improvement without notice. Ask factory for the current technical specifications before purchase and / or use.
If any problems caused by this product, please be sure to contact us immediately. www.bmtk.co.kr / E-mail bmtk@bmtk.co.kr Mar. 2019.
8
GROUND FAULT MONITOR GM-A2HR
VFD & BWTS SYSTEM LINE WIRING APPLICATION

EPB를 누르면 Sensor 내부의 Relay가 접지(E)를


차단하고 LAMP(EL)를 통하여 Line에 분포돼있는
정전용량이 방전되며 Sensor는 현재 측정돼있는
절연값을 Reset하고 EPB복귀 후 다시 측정합니다.

Pressing the EPB, the relay inside of the sensor


cuts off the ground (E) and discharges the
capacitance distributed in the line through
the LAMP (EL). The sensor resets the current
insulation value and measures it again after
returning to the EPB.

EPB를 누르면 LAMP(EL)를 통하여 Line에 분포돼


있는 정전용량이 방전되며 Sensor는 방전되기 전의
절연값을 기억, 표시를 계속하는 상태에서 측정을
합니다.

Pressing the EPB, the capacitance discharges


distributed in the line through the LAMP (EL).
The sensor memorizes the insulation value
before discharging and measures it while
continuing to display.

Design and specifications can be change for quility improvement without notice. Ask factory for the current technical specifications before purchase and / or use.
If any problems caused by this product, please be sure to contact us immediately. www.bmtk.co.kr / E-mail bmtk@bmtk.co.kr Mar. 2019.
9
GROUND FAULT MONITOR GM-A2HR
VFD & BWTS SYSTEM LINE FUNCTION DESCRIPTION

표준 결선도
비접지 교류통전선로

접지상(Phase)표시등 시험
상 접지 램프 테스트는 접지된 위상을 확인
하는 기능으로 IRM과 독립적입니다.

EL버튼을 누르면 Monitor 접지단자(E)가 내


부적으로 분리되고 Reset 단자(K1, K2)는
내부 장치를 RESET 합니다. 접지 TEST 후
Monitor는 방전된 시스템 정전용량을 17초
간 재충전 후 다시 측정을 시작합니다.

오류찾기 모드는 즉시 측정을 시작합니다.

주의
오류찾기, 자체 TEST
후에는 원래위치
(500-1,000uF)에
Self-grounding test & Meter "0" set SET 하십시오.
MODE SELECTOR를 TEST로 설정하면, 외부접지 단자(E)가
차단되고 내부 접지저항이 "0"으로 전환 연결되며 500uF mode
METER는 즉시 "0"을 표시하고 경보가 발생됩니다. VFD, BWTS 가동시 외부에서 혼입된 다양한 외란 요인
이 때 VR로 미터 "0"점을 조정할 수 있습니다. (직류 서지, 고주파, 누설 정전 용량 등)을 제거하고 순수한 절연
저항을 측정하기 위해 특별한 동작을 수행합니다.
Reset : Button or T.B (K1,K2)
1,000uF mode
EL TEST를 할 때 Device를 Reset 시켜줍니다.
용량이 큰 BWTS 가동시 누설 정전용량 및 Surge가 커지므로
이때 사용합니다.
Fault finding mode
500uF, 1,000uF 모드에서는 외란 요인의 상태에 따라 많은 시간이
오류 찾기 모드는 접지된 위치를 찾는데 사용되며,
소요되며 순수한 절연 저항값만이 내부 처리 과정을 통해 측정
VFD, BWTS 모드에서는 응답시간이 길어지므로
되고 표시되며 측정시간은 수십초~수십분입니다.
응답시간이 빠른 오류 찾기 모드를 사용합니다.

그러나 VFD, BWTS 운전 중에는 적용되지 않습니다. Remote & Meter connection
오류찾기 모드는 측정을 빨리 하기 위해 외란 요인을 제거하지 원격 모드에서는 외부 도어나 콘솔에서 원격으로 기능을 수행할
않기 때문에 측정에 오류를 일으킬 수 있습니다. 수 있습니다. Meter(M+,M-) 출력은 정전류 출력이므로 2~3개
VFD, BWTS가 운전중 일때는 오류찾기 모드를 사용하지 마십시오. 의 Meter를 직렬로 연결해도 지시 값은 동일합니다.

Design and specifications can be change for quility improvement without notice. Ask factory for the current technical specifications before purchase and / or use.
If any problems caused by this product, please be sure to contact us immediately. www.bmtk.co.kr / E-mail bmtk@bmtk.co.kr May. 2019.
10
GROUND FAULT MONITOR GM-A2HR
VFD & BWTS SYSTEM LINE FUNCTION DESCRIPTION

STANDARD CONNECTION
DISTURBANCE FACTOR
SUPERIMPOSED Un-grounded AC line

Grounded phase lamp test.


Phase grounding lamp test is function
to check which phase is grounded and
independent of IRM.
When the EL button is pressed, Monitor
ground(E) is disconnected internally and
T.B(K1,K2) reset device.
After ground lamp test, monitor recharge
the system leakage capacitance
discharged by EL test for 17 seconds and
start measuring again.
Fault finding mode responds immediately.

Caution
Please set to
orginal setting
500-1,000uF
after done fault
finding or self test.

Self-grounding test & Meter "0" set 500uF mode


When MODE SELECTOR is set to TEST, the external In VFD, BWTS mode, special operation is performed in order to
detection terminal(L) is cut off and the internal ground remove various disturbance factors(DC surge, high-frequency,
resistance is switched to "0". The Meter immediately leakage capacitance, etc.) superimposed from the outside and
displays "0" and an alarm is generated. to measure the pure insulation resistance.
At this time, you can set the meter "0" point with VR.
1,000uF mode
Reset : Button or T.B (K1,K2) This is used when BWTS with large capacity is operated because
Reset device when EL test. leakage capacitance and surge increase.
In 500uF and 1,000uF mode, It takes a lot of time depending
Fault finding mode on the state of the disturbance factor. Only the pure insulation
Fault Finding mode is used to find the grounded position, resistance value is measured and displayed through the Internal
processing, and the measurement time is several tens of
In VFD, BWTS mode, the response time can be long, Use fault
seconds to several tens of minutes.
finding mode to fast response time.
However, the fault finding mode is not applied during VFD Remote & Meter connection
running or BWTS operation.
In remote mode, you can perform functions remotely from an
This can cause measurement problems because it dose not
external door or console. Since the output of Meter (M+,M-)is
eliminate disturbance factors.
constant current output, the indicated value is the same even if
Don't use Fault Finding at VFD, BWTS running.
2 or 3 meters are connected in series.

Design and specifications can be change for quility improvement without notice. Ask factory for the current technical specifications before purchase and / or use.
If any problems caused by this product, please be sure to contact us immediately. www.bmtk.co.kr / E-mail bmtk@bmtk.co.kr May. 2019.
6
GROUND FAULT MONITOR METER SCALES &
EXTERNAL METER PANEL CUTTING SIZE

TYPE : D110 SCALE : 0-0.02 - 1MΩ USE FOR..HRX TYPE


CUTTING SIZE
WIDE RANGE SCALE : 0-0.2 - 5MΩ SCALE : 0 - 1 - 5MΩ
110 x 110
240。ANGLE

SCALE : 0-0.02 - 1MΩ USE FOR..HRX TYPE


TYPE : D96B
SCALE : 0-0.2 - 5MΩ SCALE : 0 - 1 - 5MΩ
WIDE RANGE
96 x 96
240。ANGLE

SCALE : 0-0.02 - 1MΩ USE FOR..HRX TYPE


TYPE : D300 SCALE : 0-0.2 - 5MΩ SCALE : 0 - 1 - 5MΩ
98 x 98
90。ANGLE

TYPE : D200 SCALE : 0-0.2 - 5MΩ


72 x 72
90。ANGLE

SCALE : 0-0.2 - 5MΩ

TYPE : DCF12Na
OPTION
120 x 110

Design and specifications can be change for quility improvement without notice. Ask factory for the current technical specifications before purchase and / or use.