Hydrotest Report LOADING DOCK
Hydrotest Report LOADING DOCK
Destination of test :
- Pipe - Tank
- Header - Sprinkler
5 bar
10mins holding time
0 bar 0 bar
note:
- Minimum holding time is 2 hours as per Keputusan Dirjen Migas No. 84 K/38/DJM/1998
- Tyco Series TY-B – 2.8,5.6, and 8.0 K-factor upright, pendent, and recessed pendent sprinkler standard response, standard
coverage
- The maximum working pressure Sprinkler is 12,5 bar & 17,2 bar only applies to the listing by underwriters laboratories
HYDRO TEST RECORD
Data :
No Start of Temp(°C) Start of Finish of Keep of Name of Remark/Result
test Pressure pressure Pressure Tester/personal
1 14.45 29 10 10 120 minutes Hafidz (QCI) ACC
Omo (SPV)
Irfan (Helper)
Result : leakage founded at line 11 in 5 bar pressure, no more leakage found after repair and stay at 10 bar
pressure for 3 hours
Note :
1. To increase or decrease, please contact authorized personnel and fill the name who to change
the pressure
2. Change the pressure without notice is forbidden
3. Planning and finishing testing please contact QUALITY CONTROL –Personnel for witnessing
Sign
Date
HYDRO TEST RECORD
Pressure gauge
5 bar
Time : 14.45 PM
10 bar
Time : 17.15 PM