Gas Consumption and Genset Outputs

S.no time (hrs) Readings CM GCV(as MAY 2019) mmBTU kWhrs P.F kW kVA Volts Amps Amount
1 1600 7698909 0 0 619 0.79 619 783.5443 1108.7733204 0
2 1700 7699088 179 6.63855 492 0.81 492 607.4074 859.52654455 5178.069
3 1800 7699252 164 6.082247 583 0.8 583 728.75 1031.2353154 4744.153

1044.88

408
4 1900 7699418 166 6.156421 474 0.81 474 585.1852 828.08045145 4802.008
5 2000 7699584 166 6.156421 324 0.81 324 400 566.02967568 4802.008
6 2100 7699753 169 6.267682 688 0.77 688 893.5065 1264.3779768 4888.792
7 2200 7699955 202 7.491548 680 0.78 680 871.7949 1233.6544213 5843.408

Averages for 7 hrs


Average MMBTU/hrs = 5.541838
Average CM= 149.4286
Average P.F= 0.795714
Average kVA= 695.7412
Average Current= 984.5254
Voltage on Load= 370 in some Areas
Average kWhrs= 551.4286
Total Amount= 30258.44 Only Rate is included i.e. 780 PKR/MMBTU
Average Amount= 4322.634
*The MMBTU's are calculated as per written Equation on SSCG Gas Bill, in which GCV is predefined.
*The kVA is abbreviated for kilo Volt Amps. A Standard Unit for Electrical Power