BOILER-1 LIGHT-UP ( 25-09-2016 ) LDO CONSUMPTION CALCULATION DETAILS

LDO tank hight Meter 4.500


LDO tank Diameter Meter 4.000
LDO tank Radius Meter 2.000
LDO Density Kg/m3 0.880
Cylindrycal tank formula π*r2*h
Tank full Volume M3 56.571
Tank full capacity KL 49.783

Tank initial (Before light-up ) level Meter 2.130


Tank final ( After light-up ) level Meter 2.060
Level difference Meter 0.070
As per tank level, LDO consumption KL 0.774

OIL BURNER-1 OIL FLOW OIL BURNER-2 OIL FLOW

Oil burner-1 started at Hours 14:34:00


Oil burner-2 started at Hours 14:35:00
Oil burner-1 sopped at Hours 17:02:00
Oil burner-2 sopped at Hours 17:02:00
Oil burner - 1 running hours In numbers 2.47
Oil burner - 2 running hours In numbers 2.45
Each burner oil flow KL/Hr 0.160
As per Oil burners running hours with respective of oil flow, LDO consumption KL 0.787