Professional Documents
Culture Documents
Urquico ME152L-2 E01 Exp4
Urquico ME152L-2 E01 Exp4
COP
2020103362
INSTRUCTOR
Table of Contents
OBJECTIVES 1
LIST OF APPARATUS 5
PROCEDURES 6
SET – UP OF APPARATUS 7
COMPUTATION 8
CONCLUSION 13
RECOMMENDATION 13
REFERENCES 14
i
OBJECTIVES
1. To be able to acquaint ourselves with the basic components of an air condition system
2. To determine the coefficient of performance of the M.E laboratory air conditioning unit.
Air condition is the technique of regulating the condition of air in order to provide a comfortable environment for
man and for making industrial products.According to American Society of heating, Refrigerating and Air
Conditioning Engineers (ASHRAE) it is the process of treating air so as to control its temperature, humidity,
cleanliness and distribution to meet the requirements of a conditioner space. An air conditioning system must be
able to remove heat and moisture from the condition space. The device, which serves this purpose, are cooling and
dehumidifying coils. Most air conditioning coils consist of tubes with fins attached to the outside of the tubes.
refrigerant floss inside the tubes while the air flows over the outside of the tubes. Heat transfer between the coils
and the air causes the air temperature to drop
0-1 Cooling
0-2 Heating
0-3 Humidifying (Isothermal Dryer)
0-4 Dehumidifying
0-5 Cooling and Dehumidifying (Air Conditioner)
0-6 Heating and Humidifying (Cooling tower)
0-7 Cooling and Humidifying (Adiabatic Dryer)
0-8 Heating and Dehumidifying (Chemical Dehumidifying)
1
2
3
4
LIST OF APPARATUS
3. Hygrometer
4. Stop Watch
5
PROCEDURE
Condition #1 (Damper Open)
1. Set-up the T7080 and T7083 assembly
2. Make sure the power switch is in the OFF position
3. Make sure the mode switch is in the STAND-BY position
4. Make sure the dual pressure controller is properly set”
a. Set the cut-out scale setting to 5 psi
b. Set the cut-in scale to 45 psi
c. Set the high pressure cut-out setting to 200 psi
5. Verify the refrigerant valve are set to the following position
a. V1-open
b. V6-Open
6. Plug the electric cord into a standard wall outlet
7. Turn the power switch to ON position (You should see the LCD on the electronic temperature controller
display the room temperature)
8. Perform the following sub-steps to ensure the controller is set properly:
a. Press the button marked SET on the controller
b. Press the SET button once again to enter into the set temperature mode. Use the arrow keys to select
55F for the set point
c. Press the SET button again to enter temperature differential mode. Use the arrow to set this 10F.
This tells the controller at what temperature above the set point to engage the compressor (65F)
d. press the SET button once again to enter into the heating or cooling mode selection. Use the arrows
to select “C1” on the LCD (cooling mode)
e. Finally, press the SEt button again and check the LCd to make sure the ambient temperature is
displayed.
9. Set the flow meter and make sure the know is open fully counterclockwise
10. Remove any components stored inside the EAS (Environment Application System)
11. Verify the window is closed, all dampers are fully open, and both sheets of attic insulation are in place
12. turn the mode switch to COOLING position. the blowers should come on and the compressor should
engage as well.
13. Allow the system to run for 20 minutes to cool and attain steady state.
14. Record the pressure and temperature indicated on the system gauges in the table
ℎ1 − ℎ4
15. Calculate the actual Coefficient of Performance, β= ℎ2 −ℎ1
SET-UP APPARATUS
1.
7
DATA SHEET
COMPUTATION
Pressure Hg Sg
3 h1 s1
h1 = 247.59
s1 = 0.9187
8
Gauge 2; P=1.2mpa and s1=s2=0.9182
0.9066 275.52
0.9187 h2
0.9425 287.44
h2 = 276.28
Gauge 3 and 4; at 1.2 mpa; since we get the exact value on the table
h3=h4=115.76
248.666−3.33 248.66−𝑥
246.10
= 248.66−255.65
x=249.45
2.8 250.67
3 h1’
3.2 249.45
h1’=250.66
h2 at 1.2 and 60C; since we get the exact value on the table then therefore
h2’=291.36
9
interpolate for h3’=h4’ at 31C
30 91.49
31 h3’=h4’
32 94.39
h3’=h4’=92.94
ℎ1−ℎ4 247.59−115.76
𝐶𝑂𝑃𝑖𝑑𝑒𝑎𝑙 = ℎ2−ℎ1
= 276.28−247.59
= 4. 595
ℎ1'−ℎ4' 250.66−92.94
𝐶𝑂𝑃𝑎𝑐𝑡𝑢𝑎𝑙 = ℎ2'−ℎ1'
= 291.36−250.66
= 3. 875
𝑇𝐿 10.33 +273
𝐶𝑂𝑃𝑐𝑎𝑟𝑛𝑜𝑡 = 𝑇𝐻− 𝑇𝐿
= (22.22 +273)−(10.33−273)
= 23. 829
𝑇𝑠𝑎𝑡𝐸𝑣𝑎𝑝 (−1.33+273)
𝐶𝑂𝑃𝑉𝐶 = 𝑇𝑠𝑎𝑡𝐶𝑜𝑛−𝑇𝑠𝑎𝑡𝑒𝑣𝑎𝑝
= (46.23+273)−(−1.33+273)
= 5. 712
10
TEST DATA ANALYSIS
The coefficient value represents how much the mean of the dependent variable changes when the
independent variable is changed by one unit while the other variables in the model remain constant. In this
experiment we have determined the coefficient of performance and the importance of this COP. The value that we
get is more than 2 so therefore the given Pressure and temperature shows great outcome and has a very high COP
in cooling. therefore the Condition 3: evaporator damper adjusted, Higher COPs equate to higher efficiency, lower
11
Question with Answers/Problems with solution
a. Any system's coefficient of performance can be increased by narrowing the temperature gap
between the two reservoirs. In the case of a heat pump, this may be accomplished by one of two
a. The coefficient of performance (cop) in the refrigeration system is a ratio of the heat transfer rate at
the evaporator to the power input to the compressor. The coefficient of performance can be raised by
a. The Coefficient of Performance (CoP) is a ratio that describes a system's efficiency. It is based on
the link between the amount of power (kW) input to a system and the quantity of power produced.
CoP is defined as power output / power input. The greater the number, the better the system.
a. The Coefficient of Performance (COP) of any heat pump will fluctuate when either the intake or
exit temperature of the heat pump changes. As the inflow temperature rises from the earth, so will
the COP.
a. The COP can be less than one. However, COP should be greater than 1. A higher COP indicates
12
CONCLUSION
To prepare for this activity, we went over the air conditioning technique. As part of our Mechanical
Engineering curriculum, we have assigned ourselves the responsibilities of learning about the components of an
HVAC system and analyzing the efficiency of the lab's air conditioner. To begin, we might study the accompanying
literature to discover the fundamentals of what makes an AC (Air Conditioning) machine tick. We can now discuss
the pieces we learnt about in class and how they work together now that we have completed our refrigeration and
air conditioning systems course. The compressor, condenser, expansion valve, and evaporator were all part of the
system. So far, the ideas provided have gone into great depth on the exact roles that each of the pieces performs in
the system. In terms of the second aim, we calculated the M.E. performance coefficient. Air conditioner in the
laboratory. We were provided pressure and temperature parameters, which we utilized to calculate enthalpies.
Using the previously described method, we can calculate the coefficient of performance of the air conditioner. The
results show that the desired objectives were achieved, and the experiment was declared a success.
Recommendation
In this Experiment, I recommend we must perform the experiment because in this experiment the professor
only explains how,why and why are the purposes of the COP, so therefore we did not perform the experiment
however the professor taught us how to use the thermal system and its parts.
13
Referencesπ
● https://www.tutorialspoint.com/coefficient-of-performance#:~:text=The%20value%20of%20the%20coeffic
ient%20of%20performance%20of%20any%20system,by%20increasing%20the%20input%20temperature.
● https://www.ijrte.org/wp-content/uploads/papers/v8i2/B3908078219.pdf
● https://www.designingbuildings.co.uk/wiki/Coefficient_of_Performance_CoP#:~:text=The%20Coefficient
%20of%20Performance%20(CoP,the%20more%20efficient%20the%20system
● https://www.kensaheatpumps.com/wp-content/uploads/2014/03/Factsheet-COP-Variation-V2.pdf
● https://www.researchgate.net/post/Can_the_coefficient_of_performance_be_smaller_than_1#:~:text=COP
%20can%20be%20less%20than,of%20Electrical%20energy%20or%20power.
14
15