CHILLER ECONOMICS
2020103362
Submitted To:
Engr. John Isaiah Torres
INSTRUCTOR
CHILLER ECONOMICS
Yu, Raynard L.
ME150-2_E01
D. Economics – Comparison of Air-cooled & Water-cooled chillers (155 Ton Capacity)
EQUIPMENT FIRST COST
Items First Cost
Air-Cooled Water-Cooled
Air-Conditioning Chiller Php 1,175,974.5 Php 2,485,381.72
Cooling Tower N/A Php 76,752.20
Cooling Water Pump N/A Php 586,350.87
Total Cost Php 1,175,974.5 Php 3,148,584.79
Cost Difference Php 1,972,610.29
Water-cooled chiller unit: 30HXC 161
( )( )
→
2
L V
Suction Head=z−hfs =z−f
D 2g
( ) ( )
2
ft
3.52
Suction Head=131.2 ft −0.02 ( 131.2 ft
0.5 ft ) 2 x 32.2 ft =130.19 '
s
→
P V2
Discharge Head= + z + +h fs
γ 2g
Assuming free discharge,
( )( )
→ → →
V2 V2 L V2
Discharge Head=z + +hfs =z + + f
2g 2g D 2g
( ) +0.02 131.2 ft ( )
( )
2 2
ft ft
3.52 3.52
Discharge Head=144.364+
2 x 32.2
ft
s
( 0.5 ft ) 2 x 32.2 ft s
2
=145.57 '
s s❑
' '
Total Head=145.57 −130.19 =15.38 '
'
310 x 15.38 x 62.34
BHP= =2 hp
33,000 x 7.481 x 0.6
FRP Cooling Tower
ENVIRONMENTAL CONSIDERATION
155 TON CAPACITY
Items Energy and Cost
Air-Cooled Water-Cooled
Total Energy Consumption 1620.9 kWh 1294.7 kWh
Annual Energy Cost Php 5,835,240 Php 3,987,720
Annual Energy in kWh 583,524 kWh 398,772 kWh
Annual Greenhouse effect 4942.45 3377.60
CO 2
@8.47 Ton kWh
1000
Annual Savings 1564.85