Professional Documents
Culture Documents
A Novel Virtual Synchronous Generator Control Sche - 2024 - International Journa
A Novel Virtual Synchronous Generator Control Sche - 2024 - International Journa
A R T I C L E I N F O A B S T R A C T
Keywords: This paper focuses on the research of virtual synchronous generator (VSG) control technology for the doubly-fed
Doubly-fed induction generator induction generator (DFIG)-based wind turbines. The key for DFIG VSG operation is to construct an internal
Virtual synchronous generator (VSG) electromotive force (EMF) with the virtual rotor motion characteristic in the stator. The existing control schemes
Wind generation
use the rotor or mutual flux-induced EMF as the internal EMF. Since the flux corresponds to a composite
Internal voltage
Rotor current control
magnetic field generated together by the stator and rotor current. Any variations in the stator current caused by
external disturbances will reflect on the rotor current to keep the flux constant. The rotor overcurrent is inevi
table under a large external disturbance, threatening the safety of the rotor-side converter (RSC). Moreover, the
flux is immeasurable. The accurate flux control depends on flux observers, increasing the complexity; while the
control without observers cannot ensure the effectiveness, leading to control failure. To address these problems, a
novel DFIG VSG control scheme with the rotor current-induced EMF as the internal EMF is proposed in this
paper. The internal EMF is corresponded to the single magnetic field generated only by the rotor current. This
can lead to the following benefits: the rotor current will not vary with the stator current and can be limited under
large external disturbances, ensuring the safety of the RSC; the rotor current can be directly measured without
the need for extra observers, reducing the difficulty of control implementations; the underlying controlled vector
is unified with the traditional grid-following DFIG, favoring the retrofit of the installed DFIGs. Compared to the
existing schemes, this scheme has a larger equivalent internal impedance. An additional rotor current-terminal
voltage magnitude droop control is added to effectively restrain the problems brought by this larger impedance.
Simulation and analysis results demonstrate that the proposed DFIG VSG control scheme effectively addresses
problems in the existing schemes. Moreover, the results also exhibit that the scheme has a robust adaptability
across a wide range of short-circuit ratios and possesses the grid-forming ability independent of SGs.
1. Introduction generator (VSG) control [8,9] enables WTGs to participate in the fre
quency and voltage construction of the grid by emulating the external
At present, almost all wind-turbine generators (WTGs) are operating characteristics of SGs. At present, studies have been extensively con
in the phase-locked-loop (PLL)-based grid-following control mode, ducted on the VSG control of grid-connected converters [10–14].
which faces the following three problems: However, for widely-used doubly-fed induction generator (DFIG)-based
WTGs [15], there is a noticeable lack of research on the VSG control.
• It tends to maintain constant output power after grid disturbance and To realize the DFIG VSG operation, an internal electromotive force
thereby lacks spontaneous inertia response, which leads to frequency (EMF) with the virtual rotor motion characteristic should be established
stability problems of the grid [1–3]. in the stator. For the DFIG, there are several available approaches to
• It has poor adaptability to grid with low short-circuit ratio (SCR), construct such an internal EMF. The following constructing approaches
which is easy to cause oscillation problems [4–7]. are mentioned in literatures:
• It cannot operate independently in an islanded system without syn
chronous generators (SGs). 1) Constructing through the stator flux-induced EMF
To address the above problems, the grid-forming control of WTGs has In references [16,17], a kind of control scheme utilizing the stator
received more and more attention from academia and industry. As a flux-induced EMF as the internal EMF to realize the operation of a stand-
representative kind of grid-forming control, the virtual synchronous alone DFIG with loads was proposed. However, this internal EMF
https://doi.org/10.1016/j.ijepes.2023.109688
Received 29 August 2023; Received in revised form 26 October 2023; Accepted 26 November 2023
Available online 12 December 2023
0142-0615/© 2023 The Author(s). Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-
nc-nd/4.0/).
X. Gao et al. International Journal of Electrical Power and Energy Systems 156 (2024) 109688
constructing approach does not adapt well to the grid-connected sce the rotor current no longer uncontrollably vary with the stator cur
narios, since the stator flux of the grid-connected DFIG is mainly rent. It is much easier to limit the max magnitude of the rotor cur
determined by the external grid voltage. The control of the stator flux rent, keeping the RSC away from the threat of the overcurrent under
through the modulation voltage of the DFIG’s rotor-side converter (RSC) variable operating conditions.
can be very weak, leading to unsatisfactory dynamic performance or • The rotor current can be determined independently by the DFIG with
even instability problems of the internal EMF control. To be summa the mature rotor current vector control technology, which is widely
rized, this kind of internal EMF constructing approach can realize the used in the grid-following DFIG. There is no need to redesign the
independent operation of a stand-alone DFIG with loads, but it cannot vector control structure for the grid-following DFIG when they are
meet the large demand for the grid-connected operation of the DFIG going to be retrofitted into VSG control. This leads to good practical
VSG. As a result, though the control schemes in the references [16,17] value in engineering.
were presented earlier, but they are generally not recognized as the first
kind of DFIG VSG control scheme. This internal EMF constructing approach has the above advantages,
helping address the problems in the existing schemes, but it also has a
2) Constructing through the rotor or mutual flux-induced EMF larger equivalent internal impedance compared to the other construct
ing approaches. This feature can bring some challenges for DFIG VSG
The commonly recognized first DFIG VSG control scheme, selecting operation in terms of active power transmission capacity and static
the rotor flux as the controlled vector and the rotor flux-induced EMF as voltage levels. It is found in this paper that a rotor current-terminal
the internal EMF, was proposed in [18]. Several enhanced schemes voltage magnitude droop control can restrain the drawbacks, effec
based on this scheme were proposed in [19–22]. The implementation for tively enhancing the performance of the proposed scheme, without
controlling the rotor flux can be divided into two kinds. The first kind of compromising the mentioned advantages. This droop control is an
implementation is an open-loop control based on an approximate linear indispensable part of the VSG control scheme in which the rotor current-
relationship between the modulation voltage of the RSC and the rotor induced EMF is deemed as the VSG internal EMF.
flux [18–21]. The second kind of implementation requires the flux The contributions of this paper are summarized as follows:
observer for closed-loop feedback control on the rotor flux [22].
Another kind of scheme using the mutual flux-induced EMF as the • Various available approaches for constructing the internal EMF in
internal EMF was proposed in [23,24], the implementation of which the DFIG VSG control are discussed, highlighting the features of each
only presents the closed-loop control on the mutual flux. approach.
The VSG control schemes under these two internal EMF constructing • A novel DFIG VSG control scheme utilizing the rotor current-induced
methods enable the DFIG to obtain external characteristics similar to EMF as the VSG internal EMF is proposed, with a rotor current-
that of the SG. However, there are two main problems with these terminal voltage magnitude droop control to enhance its perfor
schemes as follows. mance from the larger equivalent internal impedance. It is verified
that the proposed control scheme effectively addressing problems of
• It is difficult for the two kinds of schemes to reliably limit the rotor the unsatisfying effectiveness or high complexity of the control
current within the safe range, especially under grid fault conditions, implementation, and the rotor overcurrent risk in existing schemes.
which will seriously affect the safety of the equipment and the reli • The static and dynamic characteristic of the proposed VSG control
ability of operation. The controlled flux vectors in the above- scheme is studied. The existence and the voltage level of the static
mentioned schemes are all corresponded to a composite magnetic operating point are analyzed. The stability criterion of static oper
field generated together by the stator current and the rotor current. ating points, the dynamic performance under small-signal distur
Any variations in the stator current caused by external disturbances bances and the tolerance to large-signal disturbances are studied.
will lead to corresponding changes in the rotor current to keep the Comprehensively considering the static and dynamic operating
flux constant. These changes depended on the external disturbance characteristic, and the demand of the grid to the VSG WTGs, rec
are uncertain. A large disturbance will inevitably cause a severe rotor ommended ranges for some key parameters are provided.
overcurrent, posing safety problems to the RSC.
• The implementation of the schemes faces a contradiction between The subsequent arrangement of this paper is as follows:
complexity and effectiveness. Since the flux cannot be directly In Section II, the multiple approaches of internal EMF selection
measured, achieving accurate control of the flux requires a flux within the DFIG VSG control are firstly discussed, based on which, the
observer in the implementation based on the flux closed-loop con basic control principles of the VSG control scheme proposed in this
trol, which increases the complexity of the control system. On the paper are introduced. The static operating characteristics of the control
other hand, the implementation based on the flux open-loop control, scheme have been analyzed, and the necessity of the rotor current-
which can avoid the need for the flux observer, cannot ensure the terminal voltage magnitude droop control for obtaining reasonable
effectiveness of the control on the flux. For the implementation based static operating points has been verified. In Section III, the dynamic and
on the open-loop control in [18–21], when the actual rotor speed stability of the proposed control scheme has been investigated, including
varies, there are potential risks of control failure. the conditions for reducing system order, stability criteria under the
order- reducing conditions, and the influences of parameter variations
The choice of the approach to constructing the internal EMF is vital on dynamic performance under small-signal disturbances and the
to the DFIG VSG control scheme. The above-mentioned several kinds of tolerance to large-signal disturbances. Recommended ranges for some
constructing approaches bring many problems to the operation of the key parameters are provided in this section. In Section IV, the problems
DFIG VSG operation. In view of this, a novel DFIG VSG control scheme is faced by the DFIG VSG control schemes proposed in previous studies,
proposed in this paper, which uses the rotor current-induced EMF as the using the rotor or mutual flux-induced EMF as the internal EMF, are
VSG internal EMF and can bring the following benefits: analyzed and it is pointed out that the method proposed in this paper can
effectively avoid these problems with simulation verifications. In Sec
• The rotor current can be directly measured without the need for extra tion V, simulation case studies are presented to examine the perfor
observer, reducing the difficulty of the implementation. mance of the proposed VSG control scheme in different operation
• The internal EMF is only determined by the single magnetic field scenarios, including operation in grid-connected scenarios with different
generated by the rotor current instead of the composite magnetic SCRs, parallel operation with SGs in microgrids, and parallel operation
field generated together by the stator and rotor current. This makes among DFIG VSGs without SGs in microgrids. Section VI is the
2
X. Gao et al. International Journal of Electrical Power and Energy Systems 156 (2024) 109688
conclusion. Table 1
Summary of the several internal EMF constructing methods.
2. The proposed DFIG VSG control scheme Internal Internal Features
EMF impedance
2.1. Selection of the internal EMF It is largely determined by the external grid. The
controllability of the DFIG to this internal EMF is
There are multiple electromagnetic inductions between current-flux- unsatisfying.
voltage in the windings of the DFIG. The induced EMF in the stator can The rotor overcurrent cannot be reliably limited,
threatening the safety of the RSC. The
be decomposed into many kinds of combination, and theoretically, implementation of the flux control is with the
controlling any one of these components can realize the VSG control. contradiction between the complexity and
The stator voltage equation of the DFIG under a rotational dq coor effectiveness.
dinate system is shown in (1), The large equivalent internal impedance can
influence the operation characteristic, which
→ → 1 d→
ψs need to be improved by extra control measures.
U s = Rs I s + + jω→
ψs (1)
ωB dt
→ → making it difficult to reliably constrain the rotor current into the safe
where I s is the stator current, → ψ s is the stator flux, U s is the stator range of the RSC. Besides, the immeasurability of the flux brings a
voltage, Rs is the stator resistance ω is the angular velocity of the co contradiction between the complexity and effectiveness of the imple
ordinate system and ωB is the base value of the angular velocity. mentation. It means the implementation with good control dynamics of
Ignoring the derivative of the stator flux, equation (1) can be written the flux requires a flux observer, increasing the control complexity,
into many kinds of equivalent forms, as shown in (2), while the implementation without the flux observer couples the flux
→ → control with the actual rotor speed, posing the risk of control failure
U s = Rs I s + jω→
ψs
during actual rotor speed variations. The drawbacks of these two con
Lm2 → structing methods will be discussed in detail in Section IV.
= [Rs + jω(Ls − )] I s + jω→
ψr
Lr (2) →
According to the fourth equation in (2), jωLm I r can be regarded as
→
= (Rs + jωLσs ) I s + jω→ ψm the internal EMF and thus the rotor current is the corresponding
→ → controlled vector. The control implementation is simpler. Firstly, the
= (Rs + jωLs ) I s + jωLm I r
rotor current can be directly measured without the need of extra
observer. Secondly, the rotor current is consistent with the controlled
where → ψ m and →ψ r are the mutual and rotor flux respectively, Ls, Lm, Lr
vector of grid-following DFIGs, which is convenient for the retrofit of
and Lσs are the stator, mutual, rotor and stator leakage inductance
existing units. In addition, the rotor current no longer uncontrollably
respectively. According to this equation, we have several options for the
vary with the external disturbance. The rotor overcurrent can be limited,
internal EMF of the DFIG VSG operation. We suggest that the selection of
which effectively ensures the safety of the RSC.
the internal EMF of the DFIG VSG should follow three principles:
From the above four internal EMF construction methods evolved
Controllability: the controlled vector corresponding to the con
from the stator voltage equation of the DFIG, it is more consistent with
structing of this internal EMF need to be weakly correlated with the
the above-mentioned principles to realize the DFIG VSG operation by
external grid state and can be independently determined by the DFIG; →
Security: the weak part of the DFIG is its RSC, the control needs to regarding jωLm I r as the internal EMF and the rotor current as the
reliably ensure the safety of the RSC from overcurrent under variable corresponding controlled vector. However, it is worth noting that this
operating conditions. internal EMF construction method can obtain a larger equivalent in
Complexity: it is better to design an effective control implementation ternal impedance compared with other constructing methods, which
as simple as possible. will bring other problems in operation and need special attention in the
According to the first equation in (2), jω→ ψ s can be regarded as the design of the control scheme.
internal EMF and thus the stator flux is the corresponding controlled The features of the several constructing methods are summarized as
vector. However, according to (1), the stator flux is largely determined shown in Table. 1.
by the stator voltage (ignoring the stator resistance, the stator flux will
be totally determined by the stator voltage), which depends on the 2.2. Basic control principles
external grid to a large degree. It means that the stator flux will show a
strong correlation with the external grid state, and the control of the In the previous subsection, among the approaches of constructing the
stator flux through the RSC modulation voltage can be very weak, internal EMF of the DFIG VSG, the analysis results show that selecting
leading to unsatisfactory dynamic performance or even instability →
jωLm I r as the internal EMF has advantages. In this subsection, the basic
problems of the internal EMF control. This internal EMF constructing control principle is designed based on this kind of internal EMF con
approach has been proposed to realize a stand-alone DFIG operated with struction.
loads [16,17], but it cannot well adapt to grid-connected scenarios. →
To use jωLm I r as the internal EMF for VSG operation, it is primary to
According to the second equation in (2), jω→ ψ r can be regarded as the
give it a virtual rotor motion characteristic. The construction of the
internal EMF and thus the rotor flux is the corresponding controlled
virtual rotor motion characteristic is shown in (3), where Jv is the virtual
vector. This is the constructing method selected by the references
inertia, D is the damping factor, Pref is the stator active power reference,
[18–22]. According to the third equation in (2), jω→ ψ m can be regarded Ps is the stator active power, ωrv is the virtual rotor speed, ω0 is the rated
as the internal EMF and thus the mutual flux is the corresponding grid angular velocity, and θrv is the angle of the virtual rotor.
controlled vector, this is the constructing method selected by the
reference [23,24]. Under both above-mentioned internal EMF choices, Jv
dωrv Pref − Ps
=
the controlled vectors correspond to a composite magnetic field gener dt ωrv
ated together by the stator current and the rotor current. Any variations Pref = Pref 0 + D(ω0 − ωrv )ωrv (3)
in the stator current caused by external disturbances will lead to cor dθrv
responding changes in the rotor current to maintain the control over the = ωrv
dt
flux. These changes depended on the external disturbance are uncertain,
3
X. Gao et al. International Journal of Electrical Power and Energy Systems 156 (2024) 109688
→ →
E eq = jωrv Lm I r (5)
Zeq = Rs + jωrv Ls
Fig. 2. Static Ps-δ and Us-Ps curves of the DFIG under the proposed VSG control scheme.
4
X. Gao et al. International Journal of Electrical Power and Energy Systems 156 (2024) 109688
Fig. 3. Static Ps-δ and Us-Ps curves of the DFIG under the proposed VSG control scheme with ird_ref-Us droop control.
minal voltage magnitude (ird_ref-Us droop control) can reshape the static actual current capacity of the RSC is generally greater than its rated
Ps-δ and Us-Ps characteristics and help solve the above problems. The capacity). The static Ps-δ and Us-Ps curves can be obtained as shown in
principle of the droop control is shown in (6), where T is the time con Fig. 3.
stant of the droop control, Ku is the gain of the droop control, Us_ref is the √̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅
( )2
terminal voltage reference and ird_ref0 is the basic value of the rotor − a1 + a21 − 4a2 a0 2
Usys 2
Xeq Lm Ir ref 0
Eeq = a0 = − Uref + a1
current reference. 2a2 (Xeq + Xsys )2
Ku Lm
ird ref = ird ref droop + ird ref 0 − 2Usys Xeq Xsys cosδ 2(Uref Ku Lm + E0 )
= − a2
dird ref droop Ku (Us ref − Us ) − ird ref droop
(6) (Xeq + Xsys )2 Ku2 Lm2
= 2
dt T Xsys 1
= − Eeq max ⩽Lm ird ref max (7)
When the ird_ref-Us droop control is added, the static internal EMF (Xeq + Xsys )2 Ku2 L2m
expression of the DFIG is shown in (7). Considering the effect of limiting
the DFIG’s rotor current for RSC safety, there is an upper limit to the Under the influence of both the ird_ref-Us droop control and the rotor
maximum value of Eeq. When Us_ref = 1.05, Ku = 30, ird_ref0 = 1.05/Lm current limitation, the static Ps-δ curves are no longer sinusoidal curves
(the terminal voltage magnitude is equal to 1.05p.u. at no-load opera (dashed lines represent the Ps-δ curves without considering the rotor
tion), and the rotor current limiting value of ird_ref_max is 1.5 p.u. (the current limit). The maximum active power transmission is greater than
5
X. Gao et al. International Journal of Electrical Power and Energy Systems 156 (2024) 109688
Fig. 5. Static Ps-δ and Us-Ps curves at Xsys = 0.4p.u. with different Ku.
the rated active power for different system impedances. As a result, as for the proposed VSG control scheme.
the system impedance varies from 0.1p.u. to 1p.u., static operating As for the control of the GSC of the DFIG, it is consistent with the GSC
points can be found for active power outputs below the rated value, control of the grid-following DFIG, which is used to maintain the sta
which is a prerequisite for system stability. Additionally, for different bilization of the DC link voltage and keeps unit power factor operation.
active power outputs and system impedances, the voltage level of the The control block diagram of the proposed DFIG VSG control scheme
static operating points remains within a small normal range. can be obtained as shown in Fig. 6, where the related control of the GSC
When the value of Ku is changed to 5 or 50, the corresponding curves is omitted.
changes are shown in Fig. 4. The value of Ku should not be too small,
otherwise it will make the rated active power output impossible under 3. Dynamic and stability analysis of the proposed control
too large or too small system impedance (marked in red line in Fig. 4), scheme
and the terminal voltage variation range of the static operation point is
large. The difference of the static Ps-δ curves is not obvious when Ku is In this section, a study on the dynamic and stability of the proposed
taken to be 30 and 50. In fact, when Ku is sufficiently large, the variation control scheme will be carried out. Firstly, the reduced-order condition
of the Ps-δ curve with Ku is no longer apparent, which can be observed of the DFIG grid-connected system with the proposed control scheme is
visually in Fig. 5. analyzed, and a simplified reduced-order model when satisfying this
In summary, the ird_ref-Us droop control can overcome the effect of the condition is established. On the basis of this model, the stability criterion
large steady-state internal impedance to ensure the existence of static of the static operating point is obtained. Then the dynamic performance
operating points and the stabilization of the terminal voltage level at of the system for small-signal disturbances as well as the tolerance to
static operating points over a wide range of SCR, which is indispensable large-signal disturbances are analyzed, and the value ranges of some key
6
X. Gao et al. International Journal of Electrical Power and Energy Systems 156 (2024) 109688
established as shown in (9). Where δ here means the angle of the q-axis
of the virtual rotor coordinate system in the rotating coordinate system
oriented at the infinite bus voltage.
Δẋ = A9×9 Δx
(8)
Δx = [Δisd Δisq Δird Δirq Δuid Δuiq Δird ref droop Δδ Δωrv ]T
Fig. 9. The eigenvalue trajectory as Zsys varying and the participation factor.
7
X. Gao et al. International Journal of Electrical Power and Energy Systems 156 (2024) 109688
Fig. 11. The eigenvalue trajectories and the damping ratios as Jv, D, and Ku varying.
8
X. Gao et al. International Journal of Electrical Power and Energy Systems 156 (2024) 109688
Fig. 12. Acceleration and deceleration areas under different Xsys and different Ku.
9
X. Gao et al. International Journal of Electrical Power and Energy Systems 156 (2024) 109688
consider the inertia demand of the grid and the allocation of re analyzed, respectively. In 4.3, the rotor overcurrent problem faced
sponsibility for frequency regulation, rather than pursuing the rapidity together by the two schemes is analyzed. In 4.4, the effectiveness of the
of DFIG’s own dynamics. proposed scheme in addressing these problems is verified.
A too small Jv will make the VSG control unable to provide sufficient
inertia response for the system to reduce the rate of change of the grid 4.1. Scheme 1 based on the internal EMF constructed by the rotor flux
frequency after the disturbance, and it will also make the dynamic-
decoupling prerequisite destroyed, which may bring other aspects of The schemes mentioned in [18–21] use the rotor flux as the
stability problems that cannot be reflected in the second-order simpli controlled vector to constructing the VSG internal EMF. There are two
fied model. Therefore, it is not advisable to set Jv too small to pursue a kinds of implementation for controlling the rotor flux.
faster dynamic response. The value of Jv can be referred to the inertial
time constant H of the SG, which is typically 3 ~ 5 s, thus taking Jv to be • Implementation 1 [18–21]: open-loop control of the rotor flux,
2HSN/ω20 . which is performed to directly control the RSC modulation voltage
An excessive D will cause the DFIG to take on too much active power according to an approximately linear relationship between the RSC
regulation when the grid frequency deviates from the rated frequency. It modulation voltage and the rotor flux.
can greatly exceed the power regulation range of the DFIG, leading to a • Implementation 2 [22]: closed-loop control of the rotor flux, which is
continuous drop or rise in the actual rotor speed. It is also not advisable performed to observe and feedback the rotor flux to adjust the RSC
to set D too large to pursue a faster dynamic response. The value of D can modulation voltage.
be taken with reference to the coefficient of the primary frequency
regulation of the SG, and is recommended to take 4 %~6% rated torque/ Implementation 1 is based on the simplification of the DFIG’s rotor
(rad/s), thus enabling a more consistent distribution of active power voltage equation. The DFIG’s rotor voltage equation is shown in (11).
regulation requirements with SGs.
→ → d→ ψr
As for the effect of Ku change on the dynamic performance, the in U r = Rr I r + + jωslip →
ψr (11)
dt
crease of Ku hardly makes the eigenvalues move left or right, but makes
the damping ratio decrease. It is not advisable to keep Ku as small as The effect of rotor resistance can be neglected when ωslip is large, and the
possible in order to pursue a larger damping ratio on the premise that the approximated relationship shown in (12) can be deduced.
stable static operating point exists. On the one hand, the aforementioned
→
static voltage level is difficult to be guaranteed under a small Ku, on the U r ≈ jωslip →
ψ r = j(ωrv − ωr )→
ψr (12)
other hand, the tolerance to large-signal disturbances is also one of the
very important factors to be considered for stability. According to this equation, supposing the actual rotor speed is constant,
As mentioned before, when the dynamic-decoupling prerequisite is to get a certain magnitude rotor flux, the magnitude and the phase of the
satisfied, the Ps-δ curve can reflect the real-time relationship between Ps RSC modulation voltage need to be fixed under the virtual rotor coor
and δ in dynamics. This allows the usage of the acceleration and dinate system.
deceleration areas for the discussion of large-signal disturbance toler However, in practical operation, the actual rotor speed of the DFIG is
ance. When there is a large change in the system voltage angle, the varying. The obtained rotor flux of Implementation 1 will be affected by
maximum magnitude of the angle change that can be tolerated at the variation of the actual rotor speed. The correction of the RSC mod
different Ku is discussed below. ulation voltage by real-time measurement of the actual rotor speed has
The Ps-δ curves under Ku equaling to 10 and 30 with Xsys equaling to been proposed in the literature [] to help solve this problem, but when
0.25p.u. and 0.5 p.u. are shown in Fig. 12. The unstable static operating the rotor resistance has a non-negligible effect as ωslip approaches 0, the
point (as shown by the black dashed line perpendicular to the δ-axis in relationship between the RSC modulation voltage and the rotor flux no
the figure) is the same for different Ku. This point and the stable static longer satisfies Eq. (12), and this correction method will be invalidated.
operating point determine the maximum deceleration area. It can be Implementation 2 establishes closed-loop feedback control of the
seen that a larger Ku results in a larger maximum deceleration area, and rotor flux based on (11), as shown in (13), using a more accurate rela
the stable static operating point is further to the left. Thus, when δ re tionship to adjust the RSC modulation voltage to get a rotor flux with the
duces, the maximum disturbance angle δd1_max which makes the accel virtual rotor motion characteristic.
eration area equal to the maximum deceleration area will be larger ∫
under a larger Ku. When δ increases, the maximum disturbance angle urd = Kp (ψ rd ref − ψ rd ) + Ki (ψ rd ref − ψ rd ) + Rr ird − ωslip ψ rq
δd2_max which does not cross the unstable static operating point will also
∫ (13)
be larger under a larger Ku. Thus, a larger Ku can get a larger tolerance to urq = Kp (ψ rq ref − ψ rq ) + Ki (ψ rq ref − ψ rq ) + Rr irq + ωslip ψ rd
large-signal disturbances. However, as mentioned in the last section,
when Ku is large to a certain degree, its effect on the Ps-δ curve becomes To be summarized, Implementation 1 has a simpler control structure
less pronounced, that is, the effect on the tolerance to large-signal dis compared to Implementation 2. However, variations in the actual rotor
turbances is no longer obvious. speed can cause variations in the magnitude and phase of the rotor flux
Considering the influence of several aspects, the recommended value under the virtual rotor coordinate system, which in turn affects the
range of Ku is 20 ~ 40 to ensure the existence of stable static operating magnitude and phase of the internal EMF. Particularly, when ωslip
point and normal static voltage level over a wide range of SCR and crosses 0, the relationship between the RSC modulation voltage and the
within the rated active power output. Meanwhile, a good balance be rotor flux no longer satisfies the linear relationship shown in (12), and a
tween the dynamic performance of the small-signal disturbances and the large change in the rotor flux and the internal EMF can occur, resulting
tolerance to large-signal disturbances can be get with Ku in this range. in the out-of-control of the output power of the DFIG. This makes DFIG
risky in the face of, for example, sudden and large changes of the wind
4. Comparative study with other DFIG VSG control schemes power.
In contrast, Implementation 2 is able to address the influence of the
In this section, a comparative study between the proposed scheme actual rotor speed variations on the rotor flux control. However,
and other DFIG VSG control schemes is carried out. In 4.1 and 4.2, the Implementation 2 faces problems in practical application. The rotor flux
VSG schemes based on the internal EMF constructed by the rotor and the cannot be measured directly and needs to be obtained by a flux observer.
mutual flux are introduced and the problems on the implementation are Although the open-loop flux observer is simpler to implement [25], it is
easily affected by the errors of the integration initial value and the
10
X. Gao et al. International Journal of Electrical Power and Energy Systems 156 (2024) 109688
Table 3
Summary of Scheme 1 and Scheme 2.
Scheme The Implementation Problems
controlled
vector to
form the
internal EMF
Fig. 14. Simulation system diagram.
Scheme Rotor flux Implementation 1: Adaptability to Hard to
1 open-loop RSC actual rotor reliably
modulation speed variations limit the
Table 4
voltage control is not satisfying rotor
Parameters of the simulation system.
Implementation 2: Dependence on current
rotor flux closed- the flux observer within a 0.69/35 kV Transformer Parameters
loop feedback in practical safe range
RT1 0.001p.u. LT1 0.05p.u.
control applications,
Scheme Mutual flux Mutual flux closed- brings errors and 35/110 kV Transformer Parameters
2 loop feedback more complexity RT2 0.001p.u. LT2 0.05p.u.
control into the control System Impedance Parameters
system RL 0.047p.u. LL 0.233p.u.
parameters, which can invalidate the flux observation results. In order to the Implementation 2 of Scheme 1, i.e., the challenges associated with
exclude the errors of the integration initial value and the parameters, it the practical application of the flux observer.
is necessary to use a closed-loop feedback flux observer such as the
Luenberger observer, which needs to find a suitable error gain matrix,
4.3. Rotor overcurrent problems faced by the above two kinds of schemes
making the design of the entire control system more complicated.
In the two aforementioned schemes, the controlled vectors corre
spond to a composite magnetic field generated together by the stator
4.2. Scheme 2 based on the internal EMF constructed by the mutual flux
current and the rotor current. Under the effect of the internal EMF,
external disturbances will cause variations in the stator current. In order
In addition to the Scheme 1 in which the internal EMF is constructed
to maintain the control objective of the flux, the rotor current will adjust
by controlling the rotor flux, there is also a scheme in which the internal
accordingly in response to the changes in the stator current. This vari
EMF is constructed by utilizing the mutual flux [23,24]. The closed-loop
ation in the rotor current depends on the degree of the external distur
feedback control methods for the mutual flux will be introduced in the
bances and possesses strong uncertainty. A large external disturbance
following.
like a grid fault will inevitably cause a large rotor current. This poses a
The relationships among the mutual, stator and rotor flux are shown
significant threat to the safe operation of the DFIG, since the RSC is a
in (14), and thus the stator and rotor voltage equation can be re-written
vulnerable part of the DFIG and with strict limitations on its overcurrent.
as shown in (15).
It is worth noting that there are several kinds of magnitude target of
→ → →
ψ m = Lm ( I s + I r ) the controlled flux, which have influences on the rotor overcurrent. The
→ → →
ψ s = ψ m + Lσ s I s (14) three magnitude control modes of the flux will be covered when sub
→ →
ψ = ψ +L I
r m
→
σr r
sequently studying the rotor overcurrent phenomenon of the two
schemes through simulations.
1 d→
ψm 1 d I s
→ The analysis of Scheme 1 and 2 is summarized as shown in Table. 3.
→ → →
U s = Rs I s + + Lσs + jωrv → ψ m + jωrv Lσs I s
ωB dt ωB dt
(15) 4.4. Verification of the improvement of the scheme proposed in this paper
→
→ → 1 d→
ψm 1 d I r →
U r = Rr I r + + Lσr + jωslip →
ψ m + jωslip Lσr I r for the above problems
ωB dt ωB dt
According to (14)(15), we can get (16). In the above two kinds of schemes, there is a contradiction between
[ ] the complexity and effectiveness of flux control implementation. Addi
→ 1 Lr Lσr d→ ψm Lσr Lσr Lσr tionally, the rotor current is susceptible to uncertain current components
Ur = ( + ) + Rs + j(ωslip + ωrv + ωrv ) → ψm
ωB Lm Lσs dt Lm Lσs Lσs Lm due to external disturbances, posing a threat to the safety of the RSC.
Lσr → Lσr → The proposed scheme in this paper achieves VSG operation by uti
+(Rr − Rs − jωr Lσr ) I r − Us
Lσs Lσs lizing the rotor current-induced EMF as the internal EMF. The controlled
(16) vector, rotor current, can be directly measured and is unified with the
grid-following DFIGs’, eliminating the need for extra observer and
According to (16), the closed-loop feedback control of the mutual
redesigning the vector control structure. This significantly reduces the
flux can be designed as shown in (17).
∫ complexity of control implementation.
Lσr Lσr Furthermore, this vector control structure ensures fast and accurate
urd = Kp (ψ md ref − ψ md ) + Ki (ψ md ref − ψ md ) − (ωslip + ωrv + ωrv )ψ mq
Lσs Lm control of the rotor current under actual rotor speed variations, effec
Lσr Lσr tively eliminating the impact of actual rotor speed changes on VSG
+(Rr − Rs )ird + ωr Lσr irq − usd
Lσs Lσs operation.
∫
Lσr Lσr Lastly, by directly using the rotor current as the controlled vector to
urq = Kp (ψ mq ref − ψ mq ) + Ki (ψ mq ref − ψ mq ) + (ωslip + ωrv
Lσs
+ ωrv )ψ md
Lm construct the internal EMF, the rotor current no longer uncontrollably
vary with the external disturbance. It can effectively prevent rotor
Lσr Lσ r
+(Rr − Rs )irq − ωr Lσr ird − usq overcurrent under various operating conditions by limiting the rotor
Lσs Lσ s
current reference within its hardware constraints. The DFIG can provide
(17)
support to the grid by regulating the magnitude of the internal EMF,
This kind of VSG scheme, called Scheme 2, faces similar problems as while ensuring its own safety.
11
X. Gao et al. International Journal of Electrical Power and Energy Systems 156 (2024) 109688
Fig. 15. Simulation results for Scheme 1 Implementation 1, Scheme 1 Implementation 2, Scheme 2 and the proposed scheme under actual rotor speed variations.
Fig. 16. Simulation results for Scheme 1 Implementation 2 and Scheme 2 under the grid fault.
The verification of the above contents will be conducted through simulations are the same, with the DFIG rotor speed at 1.2p.u., stator
simulation. An electromagnetic transient simulation system as shown in outputting 3 MW and 0.4 MVar power, and the GSC providing a corre
Fig. 14 is built in the DIgSILENT PowerFactory software. The parameters sponding 0.6 MW active power output to maintain the DC link voltage.
of the DFIG are listed in Table. 2, while the other system parameters can
be found in Table. 4. The initial conditions for the subsequent
12
X. Gao et al. International Journal of Electrical Power and Energy Systems 156 (2024) 109688
Fig. 17. Simulation results for the proposed scheme under the grid fault.
4.4.1. Operating comparison during actual rotor speed variations maintain a constant flux, the magnitude of the rotor current will increase
At t = 1 s, there is a sudden decrease in wind power by 1.5 MW. The significantly. The average magnitude of the rotor current vector during
actual rotor speed of the DFIG starts to decrease. Firstly, we will conduct the fault period is close to 2.5p.u. for Scheme 1 and close to 2.8p.u. for
a study on the performance of Scheme 1 Implementation 1, together Scheme 2. This increase in rotor current can cause damage to the RSC,
with the adoption of real-time rotor speed correction measures under which has limited overcurrent capability. In practical operation, it will
this operating condition. This will validate the earlier analysis on how continuously trigger the crowbar protection, which is detrimental to
actual rotor speed variations affect this implementation. The rotor flux system stability.
magnitude control target is constant. The simulation results are shown For Mode 2 and Mode 3, the performance of the rotor current during
in Fig. 15. It can be observed that when the wind power decreases and the fault period will differ. In Mode 2 control mode, after the fault oc
the rotor speed does not show a significant drop, the rotor flux can be curs, the flux magnitude will inevitably increase further, resulting in a
maintained at a relatively constant level. However, as the rotor speed higher level of rotor current. However, at the same time, it provides
gradually decreases and approaches zero, the rotor flux undergoes sig stronger voltage support to the grid.
nificant changes and eventually evolves into oscillations. Consequently, In Mode 3, depending on the value of Ku and the fault situation, the
the internal EMF also experiences oscillations, causing oscillations in the flux magnitude may either increase or decrease. If Ku is set to 5 and
DFIG’s power output. under the simulation fault conditions, the flux magnitude decreases,
For Scheme 1 Implementation 2, Scheme 2, and the proposed scheme leading to a decrease in the level of the rotor current during the fault
in this paper, such problems do not exist. The corresponding simulation period. The average magnitude is limited to below 2p.u. However, this
results are shown in Fig. 15. As the actual rotor speed changes, the active decrease in flux magnitude also corresponds to a decrease in voltage
power output from the stator remains constant for all schemes, and the support to the grid. When the fault conditions change, the current level
controlled vectors maintain stability. Under these schemes, there is a during the fault period will also vary accordingly.
good decoupling relationship between the external characteristics of the There is one more thing need to be noted. Regarding Scheme 2, as
DFIG VSG and its actual rotor speed. It is essential to emphasize that the mentioned in reference [23], an additional rotor current limiting mea
proposed scheme achieves this decoupling characteristic at a much sure is taken during grid faults. This measure is equivalent to adding a
lower control complexity compared to the other two schemes. virtual rotor resistance by the RSC, which slows down the control dy
namics of the mutual flux during the initial stage after the fault. As a
4.4.2. Operating comparison during grid faults result, the magnitude and phase of the mutual flux in the virtual rotor
During the simulation, a three-phase short circuit occurs at the 110 coordinate system cannot be maintained quickly and accurately, which
kV bus with a fault impedance of 300 + j150 Ω. The fault lasts for 1 s slows down the increase in rotor current. However, under the closed-
before being cleared. Firstly, we will investigate the performance of loop control of the mutual flux, if the fault persists for a long dura
Scheme 1 Implementation 2, and Scheme 2 under this scenario. As tion, the rotor current will still increase to a dangerous level.
mentioned earlier, different control modes for the flux magnitude will In summary, for Scheme 1 and Scheme 2, it is challenging to reliably
affect the rotor current during the fault period. We conducted simula limit the rotor current within a safe range during grid fault conditions.
tions for all three control modes shown in Fig. 13, and the results are This difficulty poses a significant impact on the reliability of operation
presented in Fig. 16. For the simulation, the action of the rotor-side and the lifespan of the DFIG RSC with limited capacity.
hardware protection device crowbar [26,27] is not considered. The performance of the proposed scheme in the above-mentioned
For Mode 1, after the disturbance occurs, both VSG control schemes fault scenario is comparatively studied through simulation. In this
can accurately control their chosen flux along the d-axis of the virtual simulation, the crowbar protection is implemented with an action cur
rotor coordinate system. However, during the fault duration, in order to rent of 1.8p.u., and each time it is activated for 20 ms. The limit of the
13
X. Gao et al. International Journal of Electrical Power and Energy Systems 156 (2024) 109688
Fig. 18. Simulation results under system voltage 10◦ phase disturbance with different SCRs.
Fig. 19. Simulation results under system voltage − 10◦ phase disturbance with different SCRs.
rotor current magnitude ird_ref_max is set to 1.5p.u. The simulation results reflects on the rotor windings, constituting the rotor frequency transient
are presented in Fig. 17. component of the rotor current. This transient component causes rotor
After the fault occurs, due to the stator flux conservation, a DC overcurrent in the short time after the fault occurs. After the crowbar
transient component is induced in the stator current. This current also protection acts once to bypass this transient current, the RSC promptly
14
X. Gao et al. International Journal of Electrical Power and Energy Systems 156 (2024) 109688
15
X. Gao et al. International Journal of Electrical Power and Energy Systems 156 (2024) 109688
recommended ranges for several key parameters are provided. Declaration of competing interest
Simulation and analysis results demonstrate that the proposed DFIG
VSG control scheme effectively addresses problems in the existing The authors declare that they have no known competing financial
schemes, including overcurrent in the RSC, out-of-control during actual interests or personal relationships that could have appeared to influence
rotor speed variations, and reliance on flux observers for implementa the work reported in this paper.
tion. The simulation and analysis results also demonstrate the robust
adaptability across a wide range of short-circuit ratios, the parallel Data availability
operating ability with SGs, and the independent grid-forming operating
ability without SGs of the proposed scheme. No data was used for the research described in the article.
Xuesong Gao: Conceptualization, Methodology. Zhihao Wang: This work was supported by National Natural Science Foundation of
Conceptualization, Methodology. Lei Ding: Supervision, Writing – re China (U22B20101).
view & editing. Weiyu Bao: Writing – review & editing. Zhijun Wang:
Writing – review & editing. Quanrui Hao: Writing – review & editing.
16
X. Gao et al. International Journal of Electrical Power and Energy Systems 156 (2024) 109688
References [14] Rodriguez P, Candela I, Luna A. Control of PV generation systems using the
synchronous power controller. IEEE Energy Convers Congress Expos 2013;2013:
993–8.
[1] Bao W, Wu Q, Ding L, Huang S, Terzija V. A hierarchical inertial control scheme for
[15] Jadhav HT, Roy R. A comprehensive review on the grid integration of doubly fed
multiple wind farms with BESSs based on ADMM. IEEE Trans Sustain Energy April
induction generator. Int J Electr Power Energy Syst Jul. 2013;49:8–18.
2021;12(2):751–60.
[16] Van-Tung Phan, Sung-Hyo Kwak and Hong-Hee Lee, “An improved control method
[2] Morren J, de Haan SWH, Kling WL, Ferreira JA. Wind turbines emulating inertia
for DFIG-based wind system supplying unbalanced stand-alone loads,” 2009 IEEE
and supporting primary frequency control. IEEE Trans Power Syst Feb. 2006;21(1):
International Symposium on Industrial Electronics, Seoul, Korea (South), 2009, pp.
433–4.
1081-1086.
[3] J. Liu, Z. Yang, J. Yu, J. Huang, and W. Li, “Coordinated control parameter setting
[17] Phan V-T, Lee H-H. Control strategy for harmonic elimination in stand-alone DFIG
of DFIG wind farms with virtual inertia control, ” in International Journal of
applications with nonlinear loads. IEEE Trans Power Electron Sept. 2011;26(9):
Electrical Power & Energy Systems, vol. 122, Nov. 2020.
2662–75.
[4] Huang L, et al. Grid-synchronization stability analysis and loop shaping for PLL-
[18] Wang S, Hu J, Yuan X. Virtual synchronous control for grid-connected DFIG-based
based power converters with different reactive power control. IEEE Trans Smart
wind turbines. IEEE J Emerg Selected Topics Power Electron Dec. 2015;3(4):
Grid Jan. 2020;11(1):501–16.
932–44.
[5] Wen B, Dong D, Boroyevich D, Burgos R, Mattavelli P, Shen Z. Impedance-based
[19] Wang S, Hu J, Yuan X, Sun L. On inertial dynamics of virtual-synchronous-
analysis of grid-synchronization stability for three-phase paralleled converters.
controlled DFIG-based wind turbines. IEEE Trans Energy Convers Dec. 2015;30(4):
IEEE Trans Power Electron Jan. 2016;31(1):26–38.
1691–702.
[6] X. Zhang, Y. Zhang, R. Fang, and D. Xu, “An improved virtual inductance control
[20] X. Cheng, X. Sun, J. Chai and Y. Zhao, “Virtual synchronous control strategy for
method considering PLL dynamic based on impedance modeling of DFIG under
doubly-fed induction generator under asymmetrical grid faults,” 2017 20th
weak grid,” in International Journal of Electrical Power & Energy Systems, Vol.
International Conference on Electrical Machines and Systems (ICEMS), 2017, pp. 1-
118, Jun. 2020.
6.
[7] Shen Y, Ma J, Wang L. Study on DFIG dissipation energy model and low-frequency
[21] Zhao Y, Chai J, Sun X. Virtual synchronous control of grid-connected DFIG-based
oscillation mechanism considering the effect of PLL. IEEE Trans Power Electron
wind turbines. IEEE Appl Power Electron Conf Expos (APEC) 2015;2015:2980–3.
April 2020;35(4):3348–64.
[22] Shao H, et al. Equivalent modeling and comprehensive evaluation of inertia
[8] J. Driesen and K. Visscher, “Virtual synchronous generators,” 2008 IEEE Power and
emulation control strategy for DFIG wind turbine generator. IEEE Access 2019;7:
Energy Society General Meeting - Conversion and Delivery of Electrical Energy in
64798–811.
the 21st Century, Pittsburgh, PA, USA, 2008, pp. 1-3.
[23] Nian H, Jiao Y. Improved virtual synchronous generator control of DFIG to ride-
[9] T. V. Van et al., “Virtual synchronous generator: An element of future grids,” 2010
through symmetrical voltage fault. IEEE Trans Energy Convers Jun. 2020;35(2):
IEEE PES Innovative Smart Grid Technologies Conference Europe (ISGT Europe),
672–83.
Gothenburg, Sweden, 2010, pp. 1-7.
[24] Y. Jiao, F. Li, H. Dai, H. Nian, “Analysis and Mitigation of Sub-Synchronous
[10] Zhang L, Harnefors L, Nee H-P. Power-synchronization control of grid-connected
Resonance for Doubly Fed Induction Generator under VSG Control,” in Energies,
voltage-source converters. IEEE Trans Power Syst May 2010;25(2):809–20.
vol.13, no. 7, Apr. 2020.
[11] Zhong Q-C, Weiss G. Synchronverters: Inverters that mimic synchronous
[25] Rostami M, Madani SM, Ademi S. Sensorless closed-loop voltage and frequency
generators. IEEE Trans Ind Electron April 2011;58(4):1259–67.
control of stand-alone DFIGs introducing direct flux-vector control. IEEE Trans Ind
[12] Delghavi MB, Yazdani A. A unified control strategy for electronically interfaced
Electron July 2020;67(7):6078–88.
distributed energy resources. IEEE Trans Power Delivery April 2012;27(2):803–12.
[26] Yang S, Zhou T, Sun D, Xie Z, Zhang X. A SCR crowbar commutated with power
[13] I. Cvetkovic, D. Boroyevich, R. Burgos, Chi Li, M. Jaksic and P. Mattavelli,
converter for DFIG-based wind turbines. Int J Electric Power Energy Syst Oct 2016;
“Modeling of a virtual synchronous machine-based grid-interface converter for
81:87–103.
renewable energy systems integration,” 2014 IEEE 15th Workshop on Control and
[27] Gholizadeh M, Tohidi S, Oraee A, Oraee H. Appropriate crowbar protection for
Modeling for Power Electronics (COMPEL), 2014, pp. 1-7.
improvement of brushless DFIG LVRT during asymmetrical voltage dips. Int J
Electr Power Energy Syst Feb. 2018;95:1–10.
17