Professional Documents
Culture Documents
OU500560985 0 PSI300i Connection To Automation System
OU500560985 0 PSI300i Connection To Automation System
This document is proprietary to Outotec Oyj and its affiliated companies (“Outotec”). This document is intended for the use of Outotec's customers only for the purposes of the
agreement under which the document is submitted and no ownership rights are hereby transferred. No part of the document shall be used, reproduced, translated, converted,
adapted, stored in a retrieval system, communicated or transmitted by any means, for any commercial purpose, including without limitation, sale, resale, licence, rental or lease,
without the prior express written consent of Outotec.
Customer understands and accepts that the information in this document is subject to any change without notice. It is the customer's responsibility to determine whether there have
been any such updates or amendments.
The document has been prepared to be used by professional and properly trained personnel, and the customer assumes full responsibility when using it. Despite the fact that every
effort has been made to ensure that the information in this document is accurate Outotec does not make any representations, warranties or guarantees, express or implied, as to the
accuracy or completeness of the document. In case of any discrepancies between different language versions English version shall prevail. Outotec shall not be liable in contract, tort
or in any other manner whatsoever to any person for any loss, damage, injury, liability, cost or expense of any nature, including without limitation incidental, special, direct or
consequential damages arising out of or in connection with the use of the document. Outotec's liability for any errors in the document is limited to the documentary correction of
errors.
Other product names mentioned in this document may be trademarks of their respective companies, and they are mentioned for identification purposes only.
Outotec Oyj
Internet: www.outotec.com
04
03
02
01
00 Tiikas 13.4.2015 ARA 23.06.2015 JKY 23.06.2015 New document created
Rev Name Date Name Date Name Date Revision Text
Prepared Checked Released
Status: Original Size:
Document Title:
MANUAL
PSI 300i
Language: EN
Contents
Contents ............................................................................................................................. 3
1 Introduction.............................................................................................................. 4
1.1 Connection to automation system .............................................................. 4
1.2 Remote connection to analyzer ................................................................. 4
1.3 Remote connection for Outotec support .................................................... 4
3 Profibus DP ............................................................................................................ 10
3.1 Connecting Profibus DP ........................................................................... 11
3.2 GSD file .................................................................................................... 13
3.3 Configuring Profibus DP connection ........................................................ 13
3.3.1 Station address ................................................................................... 13
3.3.2 Variables ............................................................................................. 13
3.4 Testing connection ................................................................................... 14
1 Introduction
This document describes interfacing PSI 300i particle size analyzer to third party
automation systems (DCS) and to analyzer. This manual provides information on how to
install and configure the connections.
When the connection to the plant automation system is being established, co-operation
between both customer and PSI 300i supplier (Outotec) is required for a successful
project. The customer is responsible for configuring the plant automation system.
PSI 300i will be delivered with a standard communication configuration. The standard
communication configuration is described in this document and it is highly
recommended that these communication settings are applied to the communication
interface to the automation system.
If other than standard PSI 300i communication settings need to be applied for some
reason, these settings have to be negotiated with Outotec. This document describes
only PSI 300i standard communication settings.
Note that the configurations described in this document apply only to PSI 300i software
from version 0.1.0.34 onwards. Older software versions are configured according to
previous revisions of this document.
2 Modbus TCP/IP
PSI 300i uses master-slave type Modbus communication where the master initiates a
transaction. Transactions can be either queries or responses.
After the cable is connected, make sure that the Modbus slave is enabled in PSI 300i:
IP address: 192.168.2.202
Network mask: 255.255.255.0
Default gateway: -
If you want to change the IP address or use the DHCP server to configure the IP
address of Modbus TCP/IP connection, contact Outotec service center.
browser should open with the page that can be seen in Figure Figure 4.
Modbus scanner view when connection is active.
7. Configure the connection settings of the scanner. If the IP address of the LAN2 port
has been set according to customer requirements during configuration, use that IP
address. If the IP address has not been changed, the default settings for the LAN2
interface are:
- IP address: 192.168.2.202.
- Port: 502
8. Set the connection settings by selecting the Set ip button.
3 Profibus DP
PSI 300i Profibus DP (Decentralized Peripherals) connection allows the plant DCS
system to access PSI 300i analyzer data. The following instructions explain how to
prepare the connection and describe the connection parameters that need to be set in
the DCS system.
The information provided here is not specific to any particular automation system but
describes only the PSI 300i Profibus DP option properties.
The following figure shows a typical Profibus connection between PSI 300i and the plant
DCS. PSI 300i acts always as a slave in the communication network.
The following figure shows the location of Profibus DP connector on the I/O module.
Connect the Profibus DP cable of the plant automation system to the Profibus DP
connector as shown in the following figure and table.
5 PB_GND Ground
The Profibus segment must be terminated at both ends with cable terminations in line
with the Profibus standard. The termination is passive and is supplied by the bus
subscribers. It ensures a defined level on the bus when no subscriber is active, in other
words, when all subscribers are in “Tri-state”.
When installing the GSD file, please refer to the information provided in the
documentation of the configuration software which you are using.
3.3.2 Variables
The total amount of Profibus data is 144 bytes of input and 2 bytes of output.
NOTE: PSI 300i Profibus DP slave devices use byte addressing, so a Profibus DP
master must use byte addressing as well.
A Profibus DP slave always transmits the whole 139 bytes of input and 3 bytes of output
in the order shown in Table 7.
1 byte = 8 bit
1 word = 2 byte
IW = Input word (reserves 2 bytes) (range: 0–32767)
IB = Input byte (range: 0–255)
I = Input bit (range: 0–1)
Q = Output bit (range: 0–1)
QB = Output byte (range: 0–255)
For more details about registers, refer to Table 7 in Appendix B: Profibus variable data.
Using 4-20mA analog signal option requires installing additional analog output modules
on the WAGO I/O module assembly. WAGO I/O module assembly is located inside
PCS.
The module assembly can include a maximum of eight analog output modules. Each
module has two outputs, which means that the available number of channels is 2–16.
For more information about the wiring of analog output modules, refer to electrical
drawings provided with PSI 300i.
For more details on assay configuration, refer to the analyzer Operation manual.
You can enable a remote connection to the analyzer from your PC as follows:
1. Connect an Ethernet cable between your PC and the Ethernet port (LAN3) of the
PSI 300i PC.
2. Make sure that your PC and PSI 300i PC are in the same subnetwork. For example,
in Windows 7 you can do this as follows:
- Select Start > Control Panel > Network and Sharing Center.
- Select Change adapter settings.
- Right-click Local Area Connection and select Properties.’
- On the Networking tab, select Internet Protocol version 4 (TCP/IPv4) and
select Properties.
- On the General tab, select Use the following IP address.
- Enter the IP address of your PC in the IP address field so that the first three
decimal numbers are the same as in the PSI 300i LAN3 port IP address. The
default IP address of the PSI 300i LAN3 port is 192.168.15.203. Set the new
IP address so that the last decimal number is any number between 1 and 255,
but not 203. For example, you could set the address as 192.168.15.204.
- Set the Subnet mask to 255.255.255.0.
- You can leave the Default gateway field empty.
- Select OK to save the settings.
3. Type the default IP address 192.168.15.203 to the address field of Google Chrome
web browser (from the browser version 40.0.2214.115 m onwards).
- The IP address is shown on the PSI 300i screen.
CAUTION
. After enabling remote connection, every command you type on your PC affects the
analyzer operation.
The following figure shows the remote connection view of PSI 300i analyzer.
Assay values are scaled by the assay type. The following table shows the multiplier for
the assays:
4. Density x100 2
5. Solids % x100 2
6. pH x100 2
00002 BOOL Alarm Standard deviation in zero check too high on/off
00013 BOOL Warning Standard deviation in zero check too high on/off
Assay values are scaled by the assay type. This is needed because Profibus cannot
transmit floating point (REAL) data. The following table shows the multiplier for the
assays:
4. Density x100 2
6. Ph x100 2
I0.1 BIT BOOL Standard deviation in zero check too high on/off
I1.4 BIT BOOL Standard deviation in zero check too high on/off
I1.5 BIT BOOL Warning zero level over high limit on/off
I1.6 BIT BOOL Warning zero level below low limit on/off