S E L EC T I O N G U I D E
—
Darryl Moser A circuit breaker is selected based on its electrical in a power system where the available short-circuit
Sales Enablement
ratings to serve a particular purpose in each fault current on the supply side terminals does not
Manager
application, proper selection of the circuit breaker is exceed its maximum interrupting rating.
ABB Electrification
essential for the safe and correct operation of the
Products Division
electrical system. Two important ratings to consider Short-time current ratings defined
are; short-circuit current rating (this is commonly The short-time current rating of a circuit breaker is
referred to as the maximum interrupting rating) and the ability of the circuit breaker to withstand the
the short-time current rating. In this paper, we will effects of the rated short-time current level over
discuss these circuit breaker ratings and how they can defined time duration. It demonstrates the ability of
affect the protection and selective coordination of the breaker to remain closed for a time interval under
the system. high fault current conditions. The short-time current
rating is used by the engineer to determine the ability
Short-circuit current ratings defined of the circuit breaker to protect itself and to
The short-circuit current rating is the maximum short coordinate with other circuit breakers so the system
circuit current that the circuit breaker is rated to will trip selectively.
safely interrupt at a specific maximum voltage. This
short-circuit current rating is normally expressed in Switchgear ratings
rms symmetrical amperes and is specified by the Users of low-voltage switchgear commonly use the
current magnitude only. If a circuit breaker is provided phrase “bus bracing” to refer to the mechanical
with instantaneous phase trip elements, the strength of the bus bar system in the equipment, but
interrupting capacity is the maximum rating of the when you look into the standards you will not find
device with no intentional delay. If the circuit breaker “bus bracing” defined or listed as a rating. The
is provided without instantaneous phase trip product standards applicable to Metal-Enclosed
elements, or if the instantaneous phase trip elements Power Circuit Breaker Switchgear are IEEE C37.20.10
can be disabled by the user, the interrupting capacity for definitions and IEEE C37.20.1-2018 and C37.51-
is the maximum rating of the device for the rated time 2018 for the ratings; [1] [2] [4].
interval. An engineer can safely apply a circuit breaker
“Rated short-circuit withstand current: The maximum The rated short-time current in LVPCBs is a rating
rms current that a circuit can carry momentarily given to non-automatic circuit breakers, those
without electrical, thermal, or mechanical damage or without trip units, and for non-fused automatic circuit
permanent deformation. The current shall be the rms breakers.
value, including the dc component, at the major peak
of the maximum offset phase as determined from the Note: Rated short-time withstand current is not
envelope of the current wave during a given test time applicable to fused circuit breakers as the fuse will
interval.” [1] open prematurely and not allow the current to flow for
the full duration of the rated short-time withstand
For ratings, reference IEEE C37.20.1 – 2015, IEEE test.
Standard for Metal-Enclosed Low-Voltage (1000 Vac
and below, 3200 Vdc and below) Power Circuit Breaker Trip units
Switchgear. [2]
Circuit breaker ratings Modern electronic trip units allow for maximum time-
current curve shaping which helps you to selectively
coordinate with other circuit breakers. These trip
units are designed with adjustments for long-time
pickup threshold and time delay, shorttime pickup
threshold and time delay, instantaneous pickup, and
ground fault pickup threshold and time delay.
References
[1] IEEE C37.20.10 - 2016, IEEE Standard Definitions for AC (52 kV and below) and DC (3.2 kV and below) Switchgear Assemblies
[2] IEEE C37.20.1 - 2015, IEEE Standard for Metal-Enclosed Low-Voltage (1000 Vac and below, 3200 Vdc and below) Power Circuit
Breaker Switchgear
[3] ANSI C37.50 – 2018, Low Voltage AC Power Circuit Breakers Used in Enclosures— Test Procedures
[4] ANSI C37.51 – 2018, Metal-Enclosed Low-Voltage AC Power Circuit Breaker Switchgear Assemblies— Conformance Test Procedures
[5] UL 1066, Fourth Edition, Low-Voltage AC and DC Power Circuit Breakers Used in Enclosures
— Customer Service
—
ABB Inc. We reserve the right to make technical We reserve all rights in this document
800-816-7809
Electrification Products changes or modify the contents of this and in the subject matter and
7:00 a.m. - 5:30 p.m., CST, Monday-Friday
860 Ridge Lake Blvd., document without prior notice. With illustrations contained therein. Any
elec_custserv@tnb.com
Memphis, TN 38120 regard to purchase orders, the agreed reproduction, disclosure to third parties
Technical Support
United States particulars shall prevail. ABB Inc. does or utilization of its contents – in whole or
888-385-1221, Option 1
not accept any responsibility whatsoever in parts – is forbidden without prior
7:00 a.m. - 5:00 p.m., CST, Monday-Friday
for potential errors or possible lack of written consent of ABB Inc. ©Copyright
lvps.support@us.abb.com
abb.com/lowvoltage information in this document. 2020 ABB. All rights reserved.