Professional Documents
Culture Documents
Fire Suppression
Fire Suppression
Fire Suppression
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 2 of 36
PREFACE
This Manual is intended to provide interpretation on the system componentry / operations, recharge
process, and inspection / test procedures of the Wormald “Loss of Pressure” Vehicle Foam Water
Spray Vehicle Fire Suppression Systems. Personnel, who operate, recharge, inspect or maintain these
fire suppression systems, should read this entire manual.
As with Fire Protection, the “Loss of Pressure” Foam Water Spray Fire Suppression System requires
periodic maintenance to help ensure that it will operate effectively and safely. Inspection frequency
should be based on the need of the vehicle on which the System is installed. Maintenance should be
conducted at intervals no longer than six months and follow the maintenance procedures in Section 5
of this Manual.
The Wormald “Loss of Pressure” Vehicle Foam Water Spray Fire Suppression System is limited to the
uses described herein. For other applications, contact your Technical Services Group for advice.
As an operation, recharging and maintenance document, this manual is for information purposes only
to assist the reader in understanding the operation and maintenance requirements for this type of Fire
Suppression System.
Only competent accredited Wormald staff should carry out the recharge and maintenance of a
Wormald “Loss of Pressure” Vehicle Foam Water Spray Vehicle Fire Suppression System. Advice and
assistance should be sought from Wormald.
COPYRIGHT
The content of this Manual is the exclusive property of Wormald and is protected by copyright laws. No part of this Manual
maybe reproduced, photocopied, stored on a retrieval system, or transmitted without the prior written consent of Wormald.
The Wormald “Loss of Pressure” Vehicle Foam Water Spray Fire Suppression System is a pre-
engineered fixed nozzle installation for protection of specialised vehicles and equipment. Typical
applications include surface mining equipment, underground mining machines, forestry machines,
construction equipment, waste disposal and agricultural machinery.
The Wormald “Loss of Pressure” Vehicle Foam Water Spray Fire Suppression (VFS) System consists
of three major components; firstly, a pressurised agent storage container assembly containing 6%
Aqueous Film Forming Foam (AFFF) concentrate mixed with potable water and pressurised with dry
nitrogen to 1620 kPa at 20oC; secondly, a detection and actuation system to trigger the installation; and
thirdly, a delivery network to carry the foam solution from the pressurised container to the nozzles and
onto the fire. The VFS System is effective on Class A (carbonaceous materials) and Class B
(flammable liquid) Fires and limited Class E Fires.
The system would be expected to perform effectively in environmental temperatures between 2°C and
60°C.
The VFS System can be actuated manually by the cabin actuator or the ground/external level actuator.
Automatic Detection and Actuation are also available.
The extinguishing agent, AFFF foam solution, is delivered from a container pressurised with dry
nitrogen through the hydraulic hose / stainless steel tube network and pre-set (non - aspirating) nozzles
onto the fire prone surfaces/areas. The foam nozzles provide direct impingement and coverage at the
selected fire risks in the risk area to be protected.
The Wormald ‘Loss of Pressure’ Vehicle Foam Water Spray Fire Suppression System is Activfire listed
to be compliant with Australian Standard AS5062-2006: Fire protection for mobile and transportable
equipment.
Note that NO substitution of any components is allowed as it will void the Activfire listing.
(5) Pressure
Switches
(1) Cabin Actuator
with Gauge
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 5 of 36
2.2 Components
2.2.1 Agent Storage Assembly
The storage containers are manufactured to AS 2030.1 (SAA Gas Container Code, Part
1: Containers for compressed gases other than acetylene). The Containers are
constructed of grade 316 stainless steel and externally powder coated red (shade R13
of AS 2700). They are available in four sizes of water capacity (25, 45, 65 and 106 litres)
designed to contain 19, 35, 50 and 80 litres respectively of foam solution.
Storage Containers
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 6 of 36
Container Details
The refill plugs are manufactured from brass for all the container sizes. On the 45, 65
and 106 Litre Containers, an 'O' Ring is fitted to the Plug to obtain an effective seal
between the Container and the Plug.
This Container Control Valve is a high flow, single action pressure differential piston
valve. The actuation of the container control valve is dependent on the release of
nitrogen pressure in the actuation hose that maintains the container control valve in
the normally closed position. This valve can only be used with the container mounted in
the vertical position.
Incorporated into the container control valves are a pressure gauge, a burst disc and a
Schrader pressurising valve. The valve stem has a 32nb BSP parallel thread fitted with a
nitrile “O” Ring that seals in the container neck ring. The Container Control Valve is
factory assembled and set, and must be returned to the manufacturer for any repairs.
The control valve is available as a combination of 304 Stainless Steel and Brass Valve,
or as a fully 316 Stainless Steel Valve for regions where the water has a high saline
content.
Valve Specification
Container brackets are of the saddle type with a front clamp. The brackets are
constructed of mild steel for each container size and are powder coated red to match the
container. Brackets may be either welded or bolted to the vehicle structure. Specially
designed brackets are available on request.
Brackets that are shown include the 106L and 65L. The 65L Bracket typically represents
the 45L and 25L Bracket with a single clamp which fits around the Container.
A bracket is not available for the 45L HP - High Profile Container. This container was
developed for the Forestry Industry and is supplied and installed within a fully enclosed
box complete with a cover plate.
The base plate is available for mounting under the 45L, 65L and 106L Brackets. The
base plate is manufactured from mild steel and has five (5) x 10 mm tapped holes in the
plate. Two base plates are available. The shaped base plate has the same configuration
of the container bracket base and should be utilised on Dozers, Loaders, Graders, etc.
The round base plate should be utilised on the ‘deck’ of trucks or excavators to prevent
any ‘stressing’ of the ‘deck’ plate.
Part Number: FOBASEPL Shaped Base Plate for 45L, 65L and 106L
Part Number: FOBASEPL-R Round Base Plate for 45L, 65L and 106L
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 10 of 36
2.2.2 Actuators, Fire Panels and Pressure Switches
Each System requires at least one manual actuator. Options include the Cabin type for
installation in the vehicle's operator compartment, as well as an internal / external
actuator for access outside the vehicle and at ground level. Optional visual and audible
alarms are available for discharge of Fire Suppression System.
The Manual Actuator is manufactured from brass with a stainless steel centre puncture
pin (an all stainless steel unit is available for more aggressive environments). The centre
pin has three o-rings which are located on the shaft. The top ‘0’-Ring is a seal to prevent
any ingress of dust while the two lower o-rings are pressure seals.
There are two types of actuators. One actuator is manufactured with a gauge. The other
actuator has no gauge and is best used in ‘high risk’ areas where a gauge may be prone
to accidental damage.
FOLIQGAUGE Gauge
The solenoid can be interconnected into the control valve actuation hose or the manifold
block, and used on machines that require remote actuation via a transmitter / receiver or
a ‘hard wired’ remote actuation device.
Tube Tee The detection tube tee is a unit that can be spliced into the tube to increase
the coverage of detection tube within the area that is being protected or to allow the
detection tube to be installed in a ‘loop’.
Hose to Tube Tee The Hose to Tube Tee is a unit that interconnects the detection tube
to the 1/4” hydraulic hose.
The Status Indicator Panel is used in conjunction with the Linear Pneumatic Detection
Tube and two pressure switches and incorporates both visual and audible alarms to
indicate a fire may have occurred in the protected area. The Status Indicator Panel
enables the operator to have visual and audible information in the vehicles cabin of the
operation status of the fitted fire suppression system.
Every system is fitted with a pressure switch that shuts down the engine when the Foam
Water Spray VFS System is activated (either manually or automatically) reducing the
supply of fuel to the fire. The switch has an IP65 rating, and can be interconnected with
the Status Indicator Panel to provide visual and audible alarms.
Two pre-set pressure switches are used, depending on the system configuration. One is
pre-set to operate at 900 kPa; the other at 1200 kPa. The 900kPa pressure switch has
a dual function which can activate the engine shutdown, and or provide an alarm to
indicate that the foam water spray is about to discharge.
The 1200kPa pressure switch function is to provide an alarm for when the foam water
spray system is low in pressure.
The pressure switch has three (3) terminals. One connector is neutral, while the other
connections are for normally ‘open’ (NO) or normally ‘closed’ (NC) connections.
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 13 of 36
2.2.2 f) Manifold Block
The brass manifold block is fitted with a mounting plate for attaching the manifold block
to the machine through welding, tapping or bolting. Two manifold blocks are available.
The manifold block for pressure switches can locate the 1200kPa & 900 kPa pressure
switches within the block. The manifold block has two ¼” BSP (F) inlets which allow the
actuation hose to be connected within the actuation system. The manifold block for
pressure switches shall be mounted as close as possible to the Status Indicator Panel.
The manifold block for the actuators can be located at a central point or adjacent to the
Container Containers. All manifold blocks have the same fittings for ease of mounting.
This manifold has six ¼” BSP (F) inlets which allows up to four actuators to connected.
The nozzle is a full cone, non-aspirating spray type nozzle manufactured from brass (a
stainless steel model is available for corrosive environments). The conical spray pattern
is achieved with internal swirl plates. The nozzles are located in a closed ring main and
directed to discharge onto the fire prone surfaces/areas, such as turbo chargers,
exhaust manifolds, starter motors and any other areas that could be a source of ignition.
A blow off cap is supplied with the each nozzle to prevent external foreign matter from
blocking the nozzle orifice. The Blow Off Cap is manufactured of stainless steel and
includes a stainless steel wire connection
fitted around the nozzle. Dow Corning #4
Silicon Grease should be applied to the
nozzle to assist the blow off cap in the prevention of external foreign matter blocking the
nozzle.
On system discharge the blow off cap is thrown free of the nozzle, and the wire
connection retains the blow off cap for further use.
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 14 of 36
The nozzle bracket is manufactured from 3 mm thick mild steel and secured to the
vehicle structure by welding, self-tapping screws or nuts and bolts. The nozzle bracket is
adjusted to aim the nozzle at the target. Corrosion protection (cold galvanising or similar)
is to be applied after installation.
The minimum pressure rating for hydraulic hose and fittings is SAE 100R1. For
underground mining applications, the hydraulic hose must comply with VSBM, MSHA
2G-11C and all other SAE requirements including an operating temperature ranging
from -54°C (-65°F) to 121°C (250°F). The stainless steel tubing meets the appropriate
minimal ratings of DIN 17440, 2391 and 2413.
2.2.3 c) Fittings
Only Hose fittings, tees and connectors that are manufactured from steel and zinc
dichromate electro plated for corrosion protection can be used in the VFS System.
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 15 of 36
3.0 IN CASE OF FIRE
When a fire event occurs, the response of the operator is very important. As soon as a fire is observed,
the following actions should be taken:
2. Actuate the Wormald foam water spray VFS System by pulling the ring pin and pushing down the
plunger knob on the actuator. If the machine is fitted with an automatic detection system, system
discharge may have already been initiated.
3.1 Explanation
If vehicle/machine is left running, it may add fuel to the fire and or the fire may re-ignite.
Leave the fire area immediately to gain protection from windblown flames, potential explosions or
other dangers created by the fire.
Heat remaining from the fire could cause re-ignition after the Wormald VFS System has
discharged. It is important that operator or colleague stand by, at a safe distance, with a portable
extinguisher.
4.1 General
Prior to the recharging of any System, the system pressure status of the System Container must
be established.
The Container will require periodic internal and external examination and hydrostatic pressure
testing by an authorised Gas Container Test Station. The test interval should not exceed five (5)
years after the latest test date stamped on the container.
Many Systems have Automatic Detection and Actuation. Section 3 provides procedures for the
Automatic Detection and Actuation and Section 5 for recharging the fire suppression systems.
In case of a fire or accidental discharge of the system, inspect linear pneumatic detection tube,
the1/4” actuation hose, adaptors and the VFS components and connect the pressure test jig to
confirm what has occurred.
a) Where the linear pneumatic detection tube has been damaged, if this is a small section that
has been damaged, the linear pneumatic detection tube can be joined together using an
detection tube union; however no more than two (2) connections can be fitted in the linear
pneumatic detection tube and / or,
b) Check both the 900kPa and the 1200kPa Pressure Switches and where fitted into the
manifold block or adaptors, check for leaks and / or
c) Check all manual actuators, adaptors and gauges if fitted. Any leaks within the actuator/s,
remove the centre pin and replace with actuation o-ring kit and / or
d) Check all control valves, adaptors, gauge and schrader valve. Any leaks with or within the
control valve, replace the external components where required, or if the leak is internal,
replace with the piston o-ring kit and / or.
e) Check all stems and ferrules and adaptors on the actuation hose where leaks may occur
Note: Where leaks could occur, and components, adaptors, and /or stems on actuation
hoses, remove any Lochtite on threads, clean threads and reapply with Lochtite 577 on the
NPT, BSP, and JIC (M) threads
The Container will require periodic internal and external examination and hydrostatic
pressure testing by an authorised Gas Container Test Station. The test interval should
not exceed five (5) years after the latest test date stamped on the container.
1. Operate the actuator to ensure that the system has operated and is depressurised.
2. Carefully remove the Fill Plug from the shoulder of the extinguishing container.
Note: If audible release of gas is oberserved, do not fully remove the plug from
the container until all pressure is released. This will be indicated when the audible
release of gas ceases.
3. Inspect all Linear Pneumatic Detection Tube, and replace any broken or damaged
sections. Do Not fit more than two connections to the Detection Tube
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 18 of 36
4. Disconnect the Actuation Hose from the Control Valve and connect the Pressure
Test Tool to the1/4” Actuation Hose pressurising the Hose to approximately
1000kpa for 3 minutes. Any Hoses that have been disconnected will need to be
capped in order for the test to work correctly.
5. Disconnect Discharge Hose from lower port of the Container Control Valve and
attach the Safety Cap with Isolation Valve and Safety Vent Plug to prevent any
accidental discharges. Flush the Fire Suppression System with water through the
discharge and distribution hoses and / or stainless steel tube to remove excess
foam solution and any trapped debris.
6. During the discharge of water from the system, check the discharge from all
Nozzles to ensure that they are not blocked, and the nozzle/s has a uniform spray
pattern.
8. Fit the correct overfill tube into the control valve inlet.
9. Add the appropriate quantity of potable water into the overfill tube. Once the
correct amount of water has been filled into the container, remove the overfill tube
and add the Ansul ICAO-B 6% AFFF foam concentrate to the container through
the control valve inlet, as per Table 4.2.
Volume of 6% AFFF
Agent Foam Container Potable Water Concentrate
Solution (litres) Volume (litres) (litres) (litres)
19 25 17 2
35 45 31.5 3.5
50 65 45 5
80 106 72 8
Table 4.2
10. Once the water and foam concentrate has been added, check the siphon tube is
properly connected to the control valve; that there is no wear and tear on or near
the ball joint and that the o-ring on the end of the siphon tube is in place and not
worn.
11. Remove the overfill tube and refit the Control Valve and siphon tube to the control
valve port, tighten as required and re-connect the Discharge Hose to the outlet port
of the Control Valve.
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 19 of 36
12. Lightly lubricate the Fill Plug ‘O’ ring with #4 Dow Corning silicon lubricant, refit the
Fill Plug to the Container, then “nip up” to ensure that it has made face to face
contact with the Container collar fitting.
13. Pressurise the Container with dry nitrogen to 1620 kPa @ 20°C (Refer to Table
5.3) via the Schrader valve fitted to Container Control Valve.
Note: Use the Vehicle Systems Charging Rig (which has independent gauges,
regulator and pressure relief valve) to pressurise system. A calibrated pressure
gauge of the charge rig must be used in the nitrogen supply line to determine that
the system pressure is 1620kPa @ 20°C. Do Not use the pressure gauge fitted to
the Container Control Valve or pressure gauges on the Nitrogen Cylinder. When
applying pressure to Container fitted with Control Valves through the Schrader
valve, adjust the regulator so the gauge reads 1000 kpa and wait for bubbling
reaction to settle in the container. Increase pressure rates at 200kpa intervals and
do not exceed 2200kpa. At each 200kpa interval, wait to the bubbling reaction
settles before proceeding to the next interval. After system has been pressurised
to the correct pressure / temperature (see temperature chart – table 4.3), check
that the Container Control Valve pressure gauge is reading within the green zone
and to the nearest 50kpa increment on the high side.
14. Test all of the System connections for leaks using AFFF in water solution or ‘Blue’.
Ensure all Hose and Detection fittings, Fill Plug, Control Valve connections,
Schrader Valve and Gauge are tested.
16. Lubricate the nozzles with Dow Corning #4 silicon grease and refit the Blow Off
Caps to all system nozzles.
17. Record details on Record of Service Sheet. See sample in the Appendix
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 20 of 36
Settled Pressure for AFFF VFS System Containers
-20 1385
-15 1414
-10 1444
-5 1473
0 1503
5 1532
10 1561
15 1591
20 1620
25 1649
30 1679
35 1708
40 1737
45 1767
50 1796
55 1826
60 1855
65 1884
Table 4.3
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 21 of 36
5.0. INSPECTION AND TESTING PROCEDURE
Maintenance of the fire suppression system shall be undertaken as per the Inspection, Test, and
Preventative Maintenance Schedules of AS 5062-2006 and the following:-
2. Check the cabin status pressure gauge if fitted on the manual actuator assembly to
ensure that it is in the correct operating range.
3. Ensure the safety pin and anti tamper tie are intact.
4. Inspect and ensure manual actuators are clean, undamaged and accessible.
5. System Status Indicator Panel determine all secure, clean undamaged and accessible.
3. Ensure the safety pin and anti tamper tie are intact.
2. Inspect the mounting bracket for any damage and ensure the container is tightly
secured.
3. Check the pressure gauge on the container control valve to ensure it is in the
operating range.
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 22 of 36
5.2.3 Hose, Stainless Steel Tube and Fittings
1. Inspect all hoses and stainless steel tube for any abrasion or excessive wear.
2. Ensure that all hoses and stainless steel tube are firmly fastened.
a) Flush all hoses (except the 1/4" actuation hoses), stainless steel tube and
nozzles with water.
b) Check 1/4” actuation hoses and linear pneumatic detection tube for any
leaks.
2. Remove the nozzle caps and check all nozzle outlets for debris and foreign
materials.
3. Lubricate each nozzle with “Dow Corning #4” silicon grease and refit the nozzle
caps - replace any damaged nozzles or caps.
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 23 of 36
5.2.7 Linear Pneumatic Detection Tube
1. Check the condition of the Linear Pneumatic Detection Tube
2. Check for any Leaks at Unions and Tee Joints.
3. Check that the Linear Pneumatic Detection Tube does not have more than two
connections otherwise. Replace the Linear Pneumatic Detection Tube if required.
4. Check that the Linear Pneumatic Tube is properly clamped.
2. See Note below for Remote Control Function, if fitted, before carrying out the following
procedures.
3. a) Discharge Test the Fire Suppression System and time the discharge to ensure it
does not exceed, where the maximum permissible number of nozzles are fitted for
a standard discharge of 60 seconds +/- 10%.
b) Discharge Test the Fire Suppression System and time the discharge to ensure it
does not exceed, where the maximum permissible number of nozzles are fitted for
an extended discharge of 90 seconds +/- 10%.
5. Check and lubricate the 'O' Rings on the Filler Plug and Control Valve using Dow
Corning #4 silicon grease.
6. Remove the Control Valve, lubricate ‘O’ Rings using Dow Corning #4 silicon grease and
check the operation.
7. Check Engine Shutdown operation, discharge to release and the override switch
functions.
8. Lubricate all nozzles using Dow Corning #4 silicon grease and refit the nozzle blow-off
caps.
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 24 of 36
5.3.1 Record on Record of Service Sheet
Note: If the Remote Control Function is interconnected with the Foam Fire Suppression
System through a transmitter/receiver adaptor or cable connection, check and test the
fire system by actuating the Fire System by Remote Control Operation and simulate a
test of discharge utilising the Test Control Module.
2. In accordance with AS 2030.1, hydrostatic pressure test containers every five (5) years
at an Australian Standards approved pressure test station container.
3. Where fitted, replace Linear Pneumatic Detection Tube every five (5) years, or in an
aggressive environment, as required.
It is important that each six monthly, twelve monthly and five yearly inspections, along with system
discharges and hydrostatic container tests, be recorded on the Record of Service Sheet.
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 25 of 36
7.0 WARRANTY
The components of the Wormald Vehicle Foam Water Spray Fire Suppression System supplied by the
Wormald are warranted to you as the original purchaser for one year from the date of delivery against
defects in workmanship and materials. Wormald will replace or repair any Wormald supplied
component which, in its opinion, is defective and has not been tampered with or subjected to misuse,
abuse, exposed to highly corrosive conditions or extreme high temperature provided that written notice
of the alleged defect shall have been given to the Wormald within 30 days after discovery thereof and
prior to the expiration of one year after delivery, and further provided that if Wormald so instructs, such
article or part thereof is promptly returned to Wormald with shipping charges prepaid.
The above warranty is the only one given by Wormald concerning this system and applies only to the
Wormald Vehicle Foam Water Spray Fire Suppression Systems that have been installed and
maintained in accordance with all directions and requirements provided by Wormald in the Manual
created for the type of system in operation. THIS WARRANTY IS IN LIEU OF ALL OTHER
WARRANTIES WHETHER EXPRESSED OR IMPLIED, INCLUDING BUT NOT LIMITED TO FITNESS
OR PURPOSE AND MERCHANTABILITY, AND WORMALD DOES NOT ASSUME, OR AUTHORISE
ANY OTHER PERSON TO ASSUME FOR IT, ANY OTHER LIABILITY IN CONNECTION WITH THE
SALE OF ITS PRODUCTS. WORMALD SHALL NOT BE LIABLE FOR CONSEQUENTIAL OR
SIMILAR DAMAGES.
For repairs, parts and service of the Wormald Vehicle Fire Suppression System, contact your local
Wormald representative, or Wormald, Unit 1, 2-8 South Street, Rydalmere, NSW Australia 2116.
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 26 of 36
8.0 APPENDIX
8.1 Product
8.1.1 Assemblies
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 27 of 36
45LHPASSC 45L Assembly with 'C' Valve & Flex Tube
PART NUMBER ASSEMBLY
FO45LCYLHP 45L Container High Profile
FO45LABEL 35L Label
FO45BOX 45L Box for HP 45L Container
FO50PLUG 50mm Plug for 45/65/106L Container
FODNTU45HP Flex Syphon Tube - 45 High Profile
FOAMCHEAD Control Valve LOP
FOBAND2 Vivid Blue Band - Suit 25L, 45HP & 65L Container
FOINCASE Label - In Case of Fire
FOWARNFOAM Foam Warning Label
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 28 of 36
RCTSIPASSY Status Indicator Panel (RCT) with 900
& 1200kpa Pressure Switches
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 29 of 36
PART NUMBER COMPONENT
FOBAND1 Vivid Blue Band - Suit 16L & 45L Containers
FOBAND2 Vivid Blue Band - Suit 25L, 45HP & 65L Containers
FOBAND3 Vivid Blue Band - Suit 106L Container
FOBASEPL Base Plate - Shaped
FOBASEPL-R Base Plate - Round
FOBNM16NOZ Nozzle
FOCLAMP Clamp Suit 45L 65L 106L Bracket
FODETEE Union Tee (each)
FODETGROM Detection Tube Grommet
FODETHYDTEE Hydraulic Hose to Detection Tube Tee
FODETUB100 Detection Tube 100 Metre Roll
FODNTU45 Flex Syphon Tube - 16/45
FODNTU45HP Flex Syphon Tube - 45 High Profile
FODNTU65 Flex Syphon Tube - 25/65
FODNTUORING O'ring - Spare - Suit Siphon Tubes
FOHEADCAP Brass Cap to suit Control Valve
FOHEADPIST Control Valve Piston & 'O' Ring Set
FOINCASE Label - In Case of Fire
FOKNOB Actuator Knob & Pull Pin
FOLIQGAUGE 1620kpa Liquid Filled Gauge
FOMANIFLOP Manifold Block LOP
FOMANIFOLD Manifold Block1/4 BSPT x 6 Way
FONOZBKT Nozzle Bracket
FONOZBKTF Nozzle Bracket - Flat
FOPRESSW12 Pressure Switch 1200KPA
FOPRESSW9 Pressure Switch 900 kpa
FORCTMIMIC RCT Status Indicator Panel
FORCTTAILS 2 Metre Lead for RCT Panel
FOSCHVAL Schrader Cap with Valve
FOSIPMIMIC AME Status Indicator Panel
FOSOLNOID Solenoid for Remote Loss of Pressure Actuation
FOSS16NOZ Nozzle - 316 Stainless
FOSS20PLUG 20mm Stainless Steel Plug for 16/25L Cyl
FOSSACTVAL S/S Actuator Valve with Gauge
FOSSACTVNN S/S Actuator Valve without Gauge
FOSSCAP Metal Blow Off Cap -Stainless
FOSSCHEAD Control Valve LOP 316 Stainless
FOSYSACTLABEL Fire Suppression System Activation Label
FOWARNFOAM Foam Warning Label
G1620 1620kpa Gauge
79559 Alarm Horn – Audible Alarm
419208 Alarm Strobe – Visual Alarm
430042 AFFF 6% ICAO-B 20 Litre Drum
NZFO106LABEL 106L Label - New Zealand with FERN Approval
NZFO25LABEL 25L Label - New Zealand with FERN Approval
NZFO45LABEL 45L Label - New Zealand with FERN Approval
NZFO65LABEL 65L Label - New Zealand with FERN Approval
45L High Profile Label - New Zealand with FERN
NZFO45HPLABEL Approval
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 30 of 36
8.1.3 VFS Safety Tools
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 31 of 36
8.2 Detection Tube Fluid Chemical Resistance
In general, nylons exhibit a good resistance to bases, salt solutions, salt water, marine
atmospheres, oils, greases and petroleum products. Nylon is not affected by electrolytic corrosion
as found in and around salt water and industrial atmospheres. The resistance to mineral salts,
organic acids and strong oxidizing agents varies with the chemical group involved, concentration
and temperature. Use of Nylon products in chemical environments should be service tested to
determine suitability. The same applies to mixtures of chemicals which alone do not attack Nylon,
but when mixed together can produce synergistic reactions.
Legends
+ Swelling Action
A Good
B Limited Resistance- The extent of attack depends on conditions and can range from
swelling to dissolving.
X Unsatisfactory - attacked
CHEMICAL CONCENTRATION
20°C(68°F) 40°C(104°F) 60°C(140°F)
Acetaldehyde A B X
Acetic Acid 5% A A A
Acetic Acid 10% A A B
Acetic Acid 50% B X
Acetic Anhydride B X X
Acetone Pure A A+ B
Acetylene A A A
Aluminum Sulfate Sat. Sol. A A A
Ammonia Liquid or Gas A A A
Amonium Hydroxide Concentrated A A A
Ammonium Nitrate A A A
Ammonium Sulfate Sat. Sol. A A B
Amyl Acetate A A A
Aniline Pure B+ X X
Barium Chloride A A A
Beer A
Benzaldehyde A B X
Benzene A A+ B
Benzyl Alcohol B X X
Bromine X X
Butane A A A
Butyl Alcohol A+ B X
Calcium Arsenate Concentrated A A A
Calcium Chloride Sat. Sol. A A A
Calcium Nitrate A
Camphor A
Carbon Disulphide A+ B+ X
Carbon Tetrachloride B X
Chlorine X X X
Chloroform B X X
Chromic Acid 10% X X X
Cider A
Citric Acid A A B
Copper Sulfate A A A
Cresol X X X
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 32 of 36
CHEMICAL CONCENTRATION
20°C(68°F) 40°C(104°F) 60°C(140°F)
Cyclohexane A A B
Cyclohexanol A B X
Cyclohexanone A B X
D.D.T. Preparations A
Diammonium Phosphate A A B
Dichloroethylene B X
Diethanolamine 20% A A+ A+
Diethyl Ether A
Dioctylphosphate A A A
Dioctylphthalate A A A
Ethanol Pure A+ B X
Ethyl Acetate A A A
Ethylene Chlorydrin X X
Ethylene Glycol A+ A+ B
Ethylene Oxide A A B
Fatty Acid Esters A A A
Fluorine X X X
Formaldehide Technical A B X
Formic Acid X X X
Freon 12 A A
Freon 22 A A
Freon 502 A A
Fruit Juices A A
Furfuryl Acohol A A+ B
Gas (Coal) A A
Gasoline (High Octane) A A A+
Glucose A A A
Glycerine Pure A A B
Glycol A A B
Greases A A A
Heptane A A A+
Hydrogen A A A
Hydrogen Peroxide 20% A B
Hydrochloric Acid 10% A B X
Hydrochloric Acid 20% B X X
Hydroxy Quinoline A
Isocyanites B
Isopropyl Alcohol A
Kerosene A A A+
Lactic Acid A A A
Linseed Cake A A A
Magnesium Chloride 50% A A A
Mercury A A A
Methane A A A
Methanol Pure A+ B X
Methyl-Cellosolve A A A
Methyl Acetate A A A
Methyl Bromide A X
Methyl Chloride A X
Methyl Sulfate A B
Methyl Ethyl Ketone A A B
Methyl Isobutyl Ketone A A B
Milk A A A
Monochlorobenzene B X X
Mustard A
Naphta A A A+
Naphtalene A A A
Nitric Acid All Concentrations X X X
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 33 of 36
CHEMICAL CONCENTRATION
20°C(68°F) 40°C(104°F) 60°C(140°F)
Oils Crude A A A+
Oils Refined A A A
Oleic Acid A A A
Oxalic Acid A A B
Oxygen A A B
Perchloroethylene B X
Phenol X X X
Phosphoric Acid 40% A B X
Picric Acid B X X
Potassium Carbonate A A B
Potassium Hydroxide 50% A B X
Potassium Nitrate A+ B+ X
Potassium
Permanganate 5% X X
Potassium Sulfate A A A
Propane A A A
Pydraul F9 A A A
Pyridine Pure B X X
Soap Solution A
Sodium Carbonate Concentrate A A B
Sodium Chloride Saturated A A A
Sodium Hydroxide 50% A B X
Sodium Hypochlorite Concentrated B X X
Sodium Hypochlorite Dilute Commercial
Grade A B X
Sodium Sulfide A B B
Stearin A A A
Stearic Acid A A A
Styrene Monomer A A+
Sulfuric Anhydride B X X
Tartaric Acid Saturated A A A
Tetraethyl Lead A
Tetrahydrofurane A A B
Tolulene A A+ B
Trichloroethane B X
Trichloroethylene B X
Tricresyl Phosphate A A A
Tributyl Phospahte A A A
Trisodium Phosphate A A A
Triphenyl Phosphate A A B
Turpentine A A A+
Urea A A B
Uric Acid A A A
Vinegar A A A
Water A A A
Water Sea A A A
Water Soda A A A
Wine A
Xylene A A+ B
Zinc Chloride A A B
Information contained in this appendixis for guidance only. User is advised to test and determine the suitability of the product in the
particular environment / application. No liability whatsoever can be accepted with regard to handling, processing or use of the
product or products concerned, which must in all cases be employed with due regard to all relevant regulations and / or legislation in
the country or countries concerned.
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 34 of 36
8.3 Sample of Record of Service (ROS) Sheet
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 35 of 36
Revision 1.1 November 2013 Company Confidential Copyright © 2013 Wormald Page 36 of 36
FOR NOTES