TIB-102 7/08h

TECHNICAL INFORMATION BULLETIN

Alternator Data Sheet


Alternator Model: 4P7B
Frequency: 50 Hz
Speed: 1500 RPM
Leads: 12
kW* (kVA)
Voltage Power 90°C 95°C 105°C 130°C 150°C
L-N/L-L Phase Factor Connection 80°C Lloyds ABS Prime 125°C Standby Standby
120/208 33.0 34.4 35.6 37.6 40.8 41.4 43.0
3 0.8 Wye
240/416 (41.3) (43.0) (44.5) (47.0) (51.0) (51.8) (53.8)
115/200 32.9 35.1 36.2 38.1 41.2 41.9 43.8
3 0.8 Wye
230/400 (41.1) (43.9) (45.2) (47.6) (51.6) (52.4) (54.8)
110/190 34.0 36.0 36.9 38.7 41.8 42.5 44.9
3 0.8 Wye
220/380 (42.5) (45.0) (46.1) (48.4) (52.3) (53.1) (56.1)
34.0 36.0 36.9 38.7 41.8 42.5 44.9
110/220 3 0.8 Delta
(42.5) (45.0) (46.1) (48.4) (52.3) (53.1) (56.1)
29.0 30.5 31.0 32.5 34.5 35.5 35.5
110/220 1 1.0 Dogleg
(29.0) (30.5) (31.0) (32.5) (34.5) (35.5) (35.5)
18.0 19.5 20.5 22.0 25.0 25.5 25.5
110/220 1 0.8 Dogleg
(22.5) (24.4) (25.6) (27.5) (31.3) (31.9) (31.9)

* All data tested in accordance with IEEE Standard 115. Kohler Co. reserves the right to change the design or specifications without notice
and without any obligation or liability whatsoever.

Submittal Data: 120/208 Volts, 0.8 PF, 1500 RPM, 50 Hz, 3-Phase, 130°C Rise
Symbol Per Unit Ohms Symbol Value
Typical Resistances Typical Time Constants
Phase Resistance 0.045 0.042 Armature Short Circuit Ta 0.008 sec.
Rotor Resistance 4.834 4.462 Transient Short Circuit T’d 0.082 sec.
Typical Reactances Transient Open Circuit T’do 0.849 sec.
Synchronous Typical Field Current
Direct Xd 2.741 2.291 Full Load IfFL 17.01 amps
Quadrature Xq 1.331 1.113 No Load IfNL 4.96 amps
Transient Typical Short Circuit Ratio 0.551
Unsaturated X’du 0.300 0.250
Harmonic Distortion
Saturated X’d 0.264 0.220
RMS Total Harmonic Distortion 2.7%
Subtransient
Max. Single Harmonic 5th
Direct X”d 0.125 0.104
Deviation Factor (No Load, L-L) 4.9%
Quadrature X”q 0.113 0.095
Telephone Influence Factor <50
Negative Sequence X2 0.119 0.099
Insulation Material Class
Zero Sequence X0 0.009 0.008
per NEMA MG1-1.66 H
Phase Rotation ABC

TIB-102 7/08h 19
4P7B 50 Hz

TYPICAL ALTERNATOR EFFICIENCY*


120/208, 240/416 Volts, Wye
% Efficiency

Output (kW)

TYPICAL MOTOR STARTING CHARACTERISTICS*


120/208, 240/416 Volts, Wye
% Voltage Dip

Locked Rotor kVA


* All data tested in accordance with IEEE Standard 115. Kohler Co. reserves the right to change the design or specifications without notice
and without any obligation or liability whatsoever.

20 TIB-102 7/08h