Sys. No.: AHU-01 Qty.: 1 Nos.

Casing Construction Detail:


Casing Panels 43 mm thick Double Skin Panels with PUF Panel Inner Skin : 0.8 mm Thick Pre Coated G.I.
F.A. Cutout having density 38±2 kg/m3 Panel Outer Skin : 0.8 mm Thick Pre Coated G.I.
40 MPT With Damper Panel Colour Pebble Gray (Reference - RAL 7032) Skid : 75 x 40 mm - 2 mm thick G.I. Fabricated
Drain 310(H)x300(L) Unit Structure Extruded Aluminum Hollow Profile
With Thermal Break & Internal Coving
N P P
T T
Dampers Opposed blade type Low leakage Aerofoil
Design with concealed gears
R.H.S Coil (Heat Exchanger):
Coil Type Fin & Tube Type Coil For Direct Expansion Application
DX Coil Header Liquid Line - _ _ _ _ , Suction Line - _ _ _ _ & Refrigerant - _ _ _ _
Drain Pan S.S. 304 with 19 mm thick close cell Nitrile rubber Insulation
Cooling Capacity 18.0 TR (At Specified Condition) Coil Tubes : 9.52 mm Dia, 0.3 mm wall
DX Coil Size & Depth 1016 x 1280 (40"H x 50.40"L) - 6 RD thickness Plain Copper
DX Circuit details - - - TR x - - - No. Circuit Coil Fins : 0.13 thick, Smooth Finish Corrugated
- - - TR x - - - No. Circuit Aluminum, Fin Spacing: (11 to 12 FPI)
Face Area 1.30 Sq. Mt. (14.00 Sq. Ft.) Velocity : 2.54 M/S (Max. Permissible)
Coil Base, Blank Off, Casing, Hardware Material Details :- GI

DX Coil
Air Flow Qty.:
1686
Fan Air qty. 11900 CMH (7000 CFM) Fresh Air qty. 1190 CMH (700 CFM)
Supply Air qty. 11900 CMH (7000 CFM) Return Air qty. 10710 CMH (6300 CFM)
Dehum. Air qty. 11900 CMH (7000 CFM)
Fan:
Type Plug Fan (Non Spark Proof)
Fan Model BNC-Q560/DI (I)
Designed Static Pr. 80 mm of WC
Designed Speed 1527 RPM
Shaft Power 3.71 BKW
Drive Motor:
Type 415 V, 3 Ph. TEFC, Sq. Cage, Foot Mounted, Induction Motor
Rating 5.5 KW - 4 Pole (IE-2 - Non FLP)
L.H.S Air Filter:
Pre Filter G-3 + G-4 : Combination
Access Door Cable Access Door Size - Qty. & Type 610 x 610 x 100 - 4 No. Flange Type
Openble
Entry 610 x 305 x 100 - 2 No. Flange Type
500x750 Panel 500x750
Velocity : 2.03 M/S (Max. Permissible)
Filter Holding Frame Gl
PLAN Standard Accessories:
Bulk head (Non FLP) Provided In fan section
Limit Switch (Non FLP) Provided for fan section
Pre Inspection Glass Provided on fan section
S.A. Cutout Filter
With Damper Bulk Pressure Mea. Port Provided across filters & fan
410(H)x1050(L) Head AVM Rubber Pad Provided Below AHU
P P Cable Entry Provided for fan section
Spring Isolator Provided below fan and motor

Insp.
Make Details:
Glass R.A. Cutout Fan Make Kruger / Nicotra / Greenheck / Equi.
With Damper Motor Make Hindustan / CG / Equi.
410(H)x950(L) Filter Make AAF / Equi.
Unit Dispatch Condition : SKD
T T
1356
1431

P P

PH01&5.7 - 065 -reknuP

AHU Panel
AHU Drain
Size as per Drawing
Openable Drain Cover Drain Pan
Jali Type
75

Fan Static x 2
RCC Block
300

U-Trap Detail For Drain Connection (Blow Through Type CSU)


(By Client)

Consultant
300 Client M/s. Freeze India - Rajkot
1293 500 150 543 Project M/s. RIL New Guesthouse, Jamnagar
CITIZEN INDUSTRIES PVT. LTD. DRN. BHAVESH S
2486 a member of DAIKIN group
1002-1003, 10th Floor, A-Wing, Commerce House-5, CHD.
Beside Vodafone House, Corporate Road, Prahladnagar,
ELEVATION Citizen
a member of DAIKIN group Off S.G.Highway, Ahmedabad-380051 APPD.
Notes :- Floor Mounted Air Handling Unit
(1) Dimensional tolerance ± 5 mm.
DATE 01.11.2023
(2) RCC Block not in citizen scope. Legends
Temperature
Development Plan (GAD) SCALE SHEET NO. MAT. REV. NO. 00
(3) Air flow to be measured with Anemometer across air path before coil or filter face. T
Sensing Port Doc. No. : CIL/DND/FR-01
(4) Pressure to be measured across fan with appropriate manometer. P Pressure
Rev. No. : 00 1:1 1 OF 1 --- UNIT NO./
(5) In case of plug fans it is mandatory to run the fans using VFD. Sensing Port 689/01-23
(Supply of VFD is not in M/s. Citizen scope)
Cable
Entry Port Rev. No. Comments Issue Date : 01/03/2012 All Dimension are in MM DRG NO.