MAJOR CONSTRUCTION FEATURES AND ITEMS REQUIRED IN LV PCC/MCC PANEL

1. Both LV PCC/MCC shall be of the indoor type, floor mounted and cable entry from the
bottom.
2. Each of the MCCB and ACB shall be housed in a separate metal enclosed compartment.
3. All the feeders with ACB shall have a 2core ring type in each of the phases (R, Y, and B)
a. For CT 1 core with 5P20 for protection and another core with 0.5 accuracy for
metering purposes
b. Similarly, an incoming Line PT for each of the incoming feeder and bus PT shall
be provided in each of the bus section
4. Short circuit (RMS) current rating of bus-bar and switchgear components shall be not less
than 50kA for 3s.
5. Digital multi-function meter 0.5 class and analogue Ammeter with a selector switch shall
be provided for each incomer circuit and bus-tie circuit.
6. ON, OFF and TRIP indication LEDs shall be provided for each of the incoming, outgoing
and Bus Tie-Feeder.
7. Panel sheet thickness shall not be less than 2.5mm and sandblasting or powder coating
paint with 7 tank process to be followed and the panel sheet material shall be CRCA steel.
8. LV panels shall be manufactured to withstand an arcing fault of 300mili seconds duration
at least.
9. The height of the LV panels shall be limited to 1600mm.
10. All the panel doors shall be hinged type and cable alleys are to be provided in each of the
panels.
11. Any specific construction features mentioned in the general TS of Coal India or Eastern
Coal fields or DGMS shall also be adopted during the detailed design.
20 FEEDER PCC PANEL

SL Interruption Nos. of Device Fault Current rating


Feeder Type Release or Relay Qty(Ea)
NO Device Pole current level (kA) (Amp)
1 Incomer ACB 4 50 1600 Micro-Processor Numerical Relay 2
2 Bus-Sectionalizer ACB 4 50 1600 Micro-Processor Numerical Relay 2
3 Outgoing MCCB 3 50 400 Thermo-Magnetic Release 14
4 Outgoing ACB 3 50 1250 micro-Processor Release 2
20

20 FEEDER PCC PANEL (ALTERNATE OPTIONS)

SL Interruption Nos. of Device Fault Current rating


Feeder Type Release or Relay Qty(Ea)
NO Device Pole current level (kA) (Amp)

1 Incomer ACB 4 50 1600 Micro-Processor Numerical Relay 2


2 Bus-Sectionalizer ACB 4 50 1600 Micro-Processor Numerical Relay 2
3 Outgoing MCCB 3 50 400 Thermo-Magnetic Release 14
4 Outgoing MCCB 3 50 400 micro-Processor Release 2
20

PUMP MCC PANEL

SL Interruption Nos. of Device Fault Current rating


Feeder Type Release or Relay Qty(Ea)
NO Device Pole current level (kA) (Amp)

1 Incomer ACB 3 50 1250 micro-Processor Release 2


2 Bus-Sectionalizer ACB 3 50 1250 micro-Processor Release 1
3 Outgoing MCCB 3 50 400 Thermo-Magnetic Release 12
Incoming from DG
4 ACB 4 50 2500 Micro-Processor Numerical Relay 3
and Bus-Coupler
18

PUMP MCC PANEL (ALTERNATE OPTIONS)

SL Interruption Nos. of Device Fault Current rating


Feeder Type Release or Relay Qty(Ea)
NO Device Pole current level (kA) (Amp)
1 Incomer MCCB 3 50 400 micro-Processor Release 2
2 Bus-Sectionalizer MCCB 3 50 400 micro-Processor Release 1
3 Outgoing MCCB 3 50 100 Thermo-Magnetic Release 12
Incoming from DG
4 ACB 4 50 2500 Micro-Processor Numerical Relay 3
and Bus-Coupler