Control and monitoring modules for use with the Raychem NGC-40 system
Installation Instructions
Description
A The NGC-40-HTC (for single-phase heaters) and NGC-40-HTC3
(for three-phase heaters) modules are used to control either
a solid-state relay or contactor within the NGC-40 control and
B monitoring system. This module also has one alarm output and
one digital input. The alarm output can be used to control an
external annunciator. The digital input is programmable and may
be used for various functions such as forcing outputs on and
off. Other features of this module include ground-fault and line
current sensing for both HTC and HTC3. The front panel of the
HTC module has LED indicators for various status conditions. The
front panel also provides a ground-fault and heater test button.
HTC
Tools Required
or • Small flat-blade screwdriver
HTC3
Additional Materials Required
• Power supply 24 Vdc @100 mA per NGC-40-HTC/HTC3
Approvals • Custom built CAN cables with RJ-45 connections
Hazardous Locations • CAN Termination Resistor
Class I, Div. 2, Groups A,B,C,D T4 Conforms to:
Class I, Zone 2, AEx nC IIC T4 IP20 FM Class Number 3600 (11/98)
FM Class Number 3611 (10/99)
Kit Contents
Ex nL nC IIC T4 X
–40˚C ≤ Ta ≤ +65˚C ANSI/UL STD. 60079-15-2009
9700701
UL STD. 61010-1 Item Qty Description
Certified to:
CAN/CSA STD. C22.2 No. 213-M1987 (R2004) A 1 NGC-40-HTC module (single-phase heaters)
CAN/CSA STD. C22.2 No. 61010-1:2004
EN 61010-1 (2001)
CAN/CSA STD. E60079-15:02 (R2006) or
B 1 NGC-40-HTC3 module (three-phase heaters)
WARNING:
This component is an electrical device that must be installed For technical support, call Pentair Industrial Heat Tracing Solutions
correctly to ensure proper operation and to prevent shock or fire. at (800) 545-6258.
1PH
87 mm (3.43 in)
Front Top Bottom Back
45.1 mm (1.78 in) 45.1 mm (1.78 in)
HTC3
3PH
106.4 mm (4.2 in)
87 mm (3.43 in)
87 mm (3.43 in)
Each NGC-40-HTC/HTC3 mounts on a DIN 35 rail. Removal: Push the module upwards
Mounting: Insert the rear bottom of the module into the DIN rail, then push up to disengage the clip, then rotate the
and inwards to engage the clip. module toward you.
2 2
1 1
Power Supply/CAN
CAN termination
here if last one
in chain
For all RTD terminations, the RTD field wires must be HTC
terminated on a panel-mounted terminal block.
13 - T.S. COM (Wht)
Connections are the same for the HTC3. 1PH
14 - T.S. Sense (Red)
15 - T.S. Source (Red)
16 - Not used
HTC RTD
Wiring
13 14 15 16
Terminal block
RTD
For all RTD terminations, the RTD field wires must be HTC
terminated on a panel-mounted terminal block. The RTD cable
shield from the field terminal block to the HTC module should 13 - T.S. COM (Wht)
1PH
14 - T.S. Sense (Red)
be terminated at the earth ground bar located near the module. 15 - T.S. Source (Red)
Connections are the same for the HTC3. 16 - Not used
HTC RTD
Wiring Earth grounding
bar located at the
HTC module
13 14 15 16
Field
terminal block
RTD
HTC Relay Output Connections to Contactors - Single-Phase HTC3 Relay Output to Contactor - Three-Phase
11
9
Contactor
coil
Contactor Coil out
N or L2 Control
L1 11 Coil Out N or L2 L3 L1 (in) power
To heat- Control
tracing N or L2 L1 (in) To heat- L1
9 power
tracing L2
contactor contactor
coil N
WARNING: Shock Hazard. Disconnect from live WARNING: Shock Hazard. Disconnect from live
voltage prior to accessing terminals. voltage prior to accessing terminals.
HTC3
Terminals 5 & 6 switch voltage to the SSR. HTC Three-Phase
L3 L1 L2
HTC
The internal SSR driver will switch the Circuit breaker
internal supply voltage (12 Vdc) to the SSR. 13
N
- T.S. COM (Wht)
1PH
14 - T.S. Sense (Red)
15 - T.S. Source (Red)
16 - Not used
HTC HTC RTD
N Earth grounding
Single-Phase or L2
L3
N
Wiring
bar located at the
L1 HTC module
L1 L2
13 14 15 16
Circuit breaker 3P
H
Field
terminal block
RTD
6
H
5
1P
L1
~ SSR
+
L1
~ –
L2
L1 6 ~ SSR
+
N
To heat- ~ –
5 L2
or L2 12 tracing
Vdc
+ –
L3
~ SSR
~ ~ SSR
+
L3
~ –
N or L2
To heat-
N
tracing L1
Alarm
Note: Exposure to some chemicals may degrade the sealing properties of the alarm relay,
manufactured by NAIS, PN JQ1P-12V. Periodically inspect the alarm relay for degradation of 1PH
1PH 1PH
+ – + –
Terminal Terminal
block block
+ – + –
HTC HTC
Provide Suitable Panel Enclosure and Determine Locations for NGC-40-HTC or NGC-40-HTC3 Assembly in Panel*
CBM
I/O1
I/O2
I/O3
I/O4
I/O5
PS1
HTC1
HTC2
HTC3
HTC4
HTC5
HTC6
HTC7
HTC8
HTC9
PS2
C2
C3
C4
C5
C6
C7
C8
C9
HTC12
HTC13
HTC14
HTC15
HTC16
HTC17
HTC18
HTC19
HTC20
PTM3
PS3
C12
C16
C17
C18
C19
C20
C5
HTC22
HTC23
HTC24
HTC25
HTC26
HTC27
HTC28
HTC29
HTC30
PTM4
PS4
C22
C23
C24
C25
C26
C27
C28
C29
C30
Termination Termination
Block CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc Block
* Power supply shall have a means for dicsonnect from line voltage
Termination
Block CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc
CAN / 24 Vdc
Termination
CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc Block
Power/
Termination
Module IN OUT IN OUT IN OUT IN OUT IN OUT
CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc
HTC/HTC3 HTC/HTC3 HTC/HTC3 HTC/HTC3 HTC/HTC3
or or or or or
I/O I/O I/O I/O I/O
* Power supply shall have a means for disconnect from line voltage
Termination
Block CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc
* Power supply shall have a means for disconnect from line voltage
WARNING: Explosion Hazard - Do not replace NGC-40- AVERTISSEMENT - Risque D'explosion - Couper le
PTM unless power has been switched off or the area is courant ou s'assurer que l'emplacement est désigné
known to be nonhazardous non dangereux avant de replacer le NGC-40-PTM
WWW.PENTAIRthermal.COM
NORTH AMERICA Europe, Middle East, Africa Asia Pacific Latin America
Tel: +1.800.545.6258 Tel: +32.16.213.511 Tel: +86.21.2412.1688 Tel: +1.713.868.4800
Fax: +1.800.527.5703 Fax: +32.16.213.603 Fax: +86.21.5426.2937 Fax: +1.713.868.2333
Tel: +1.650.216.1526 thermal.info@pentair.com cn.thermal.info@pentair.com thermal.info@pentair.com
Fax: +1.650.474.7711
thermal.info@pentair.com
Pentair and NGC are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right
to change specifications without prior notice.
© 2007-2015 Pentair.