PCS-9700 HMI System Configuration Instruction_V1.00
PCS-9700 HMI System Configuration Instruction_V1.00
Configuration Instruction
CONTENTS
2.2. Check the configuration of maintenance node with dataenv tool. ...................................5
2.3. Make the special elements in graph with icon tool. (Chapter 3).......................................6
2.6. The other functions module such as sub-graph and reports etc. (Chapter 6) ..............12
1. Access to HMI
Power on the monitor. The desktop is displayed as shown in the following figure.
As shown in the above figure, click the shortcut “ ” to pop up a dialog shown as below.
Note! It’s only an example to explain how to access HMI, the actual version may be different. E.g.: the
shortcut may be displayed as “PCS-9700 HMI System R1.09”, etc.
1
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
Select user name, input corresponding password, and then modify the effective login
duration,
Click “ ” to access PCS-9700 HMI system as shown in the following figure.
2
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
The console locates at the bottom of the screen, similar to the task bar in windows operating system. It
consists of the start menu, shortcut program buttons, and status display etc., as shown below.
Click the “Start” button on the console to pop up the system menu. Contents of the start menu can be
configured by user.
3
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
4
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
2. Process of Configuration
Make sure that all appliations run normally. All appliations will be on duty or standby state. And in one
substation only one computer is on duty. The others are standby. When there is only one computer,it’s
normal that the net state is stop. If not, the net state is not good.
5
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
2.3. Make the special elements in graph with icon tool. (Chapter 3)
6
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
3) Change the link node number, color decision, customized attributes and symbol decision
7
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
8
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
9
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
10
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
11
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
2.6. The other functions module such as sub-graph and reports etc. (Chapter 6)
12
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
.
Add the report of data referring to the requirement of custom.
13
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
14
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
3. Primitive Editor
3.1. General
Primitive Editor is the tool used to create and modify primitives. It has the same basic functions as graph
editor and can draw points, lines, circles, and text information etc. However, the purpose and method of
realization of the two tools are different. Primitives generated by Primitive Editor are called by graph
editor and online tools. A primitive may consist of points, lines, circles, and texts. After being generated,
the primitive cannot be divided. Topological link node number and positions of primary equipment are
also determined in Primitive Editor.
2) Start by command
In the command line window, enter “icon “and press Enter to start Primitive Editor.
15
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
After successful start, main interface of Primitive Editor will be entered, as shown below.
Select a primitive type and right click mouse. In the menu popped up, select “New icon”
16
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
In the dialog box that pops up later, enter primitive name and other necessary parameters to complete
addition of new primitive, as shown below.
In the dialog box that pops up later, select the primitive file to be imported. After preview of the primitive
to be imported at the right side, click OK to complete import of the primitive.
17
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
1) Add pattern. Select “Add”menu item; The dialog box shown below will pop up. You can enter name
of new pattern.
2) Rename pattern. Select “Rename”menu item to enter a new name of the pattern.
3) Edit pattern. Select “Edit”menu item to pop up a dialog box shown below. The “Display
Pattern” box shows existing pattern(s) of this primitive. The “Available items” box shows currently usable
basic primitives drawn in the drawing area of this primitive. The “Selected Display Pattern” box shows
basic primitives selected by current style.
Click “Edit” to pop up a Color Decision selection dialog box as shown blow.
Some default color decisions of the system can be selected. User can also click “Add” to customize a
color decision. Or, user can select an item and click “Modify “to modify attributes of this selected color
decision. Clicking of both “Add “and “Modify “will pop up “Color Decision Editor” window as shown below.
User can modify name of color decision, select a table corresponding to the color decision, and add,
delete, move up, and move down color decision items.
19
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
Double click cell “Condition “of color decision item to pop up the “Condition Editor” window shown below
for selection of conditions.
4) Symbol decision. Click the button at right side of the Symbol Decision label to pop up a menu that
includes 2 items: Edit “and “Delete”, as shown below.
20
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
Click “Edit” to pop up a Symbol Decision Editor Dialog box as shown below. User can modify name of
symbol decision, select name of table corresponding to the symbol decision, and “Add “or “Delete”
symbol decision item. Double click cell Condition “of symbol decision item.
A “Condition Editor” window similar to that of color decision will pop up. User can select conditions. Click
cell “Display Pattern” to select style of the primitive.
5) Customized attributes. In Primitive Browser, select a primitive and select “Custom attributes” in menu
“Edit”; A dialog box as shown below will pop up. User can set attributes of each part of the primitive. As
shown below, attribute types include color and integer etc. At present, the main purpose of this function
is to set “color” attribute of different windings of transformer. For default 2-winding and 3-winding
transformer primitives, the color attribute has been defined and cannot be changed. If you wish to draw a
transformer primitive at a place beyond default types, take 2-winding transformer as an example, select
the primitive under 2-winding transformer and set two customized attributes wind1 and wind2 as shown
in the figure below; type of attribute is color
21
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
After clicking OK, double click transformer winding in primitive drawing area to pop up the dialog box
shown below. Click “Associate” tab to associate winding attributes, as shown below. For internal attribute,
select Line Color”; for external attribute, select customized attribute. If the two windings are associated to
the same external attribute, they will have the same color in online display. If they are associated to
different external attributes, the windings can be differentiated by different voltage level colors in online
display.
22
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
4. Graph Editor
4.1. General
The graph editor is an important part of PCS-9700 system MMI. It is graphic software suitable for power
system automation. It is used to generate various monitoring graphs, including substation diagram,
system single line diagram, load flow diagram, geographic map, configuration graph, contents graph,
menu graph, navigation graphs of various applications in automation system, and other graphs that
reflect status of power equipment and computer equipment etc.
is selected, user can further select version of the file to be imported. If “Import folder” is selected, user
will be prompted to import draft or latest version. Click OK to import selected graph into current graph
type.
25
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
26
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
Select Connecting line and then left click the graph. User can continue to left click repeatedly, and end
with a right click, to draw a connecting line.
2) Power equipment
Select required power equipment and drag it to the drawing area. An Equipment Attribute Setup dialog
box will pop up:
27
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
28
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
29
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
30
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
31
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
32
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
33
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
In case this graph has a number of planes, user can define the plane to be displayed.
3) Command
(1) Command: enter full path of the program to be executed here. User can also click “Browse”
button to pop up a File dialog box, in which a program can be selected. After clicking OK, its path will
be automatically filled in the command box.
(2) Blocking mode: operation can only continue after command execution
(3) Non-blocking mode: operation can continue before end of command execution.
(4) Message mode: This mode allows interaction with command execution after hot point is clicked
in the Graph Browser, e.g. call of Curve tool to open specific curve.
4) Control
5) PAS Here, you can set hot point actions of PAS such as VQC and CVT etc. Click “Search” button to
select related actions of PAS.
6) Graph operation
(1) Ack all alarms in substation: after clicking the hot point, perform alarm acknowledgement for this
substation
(2) Ack alarms this graph: after clicking the hot point, perform alarm acknowledgement for this graph.
7) Customize In this mode, user edits script of hot point actions for himself.
4.2.3.11. Fill Model for Substation Diagram
On the toolbar, click button “ ” (Fill Model) to perform Fill Model operation.
34
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
At end of Fill Model, the following dialog box will pop up for prompt; click “Yes “to publish database.
After successful publishing, prompt “Published success fully” dialog box will appear.
4.2.3.12. Check of Online Viewing of Graph
Start Graph Editor and open substation graph drawn. Click Preview button “ ”on toolbar for online
browsing of the graph. If all equipment and connecting lines are shown in pearl (color for non-live), and a
cross is displayed on circuit breaker, switch, and ES (indicating that status of current position is invalid),
then drawing of the graph is successful.
35
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
5. Database Editor
5.1. General
36
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
37
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
38
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
39
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
In the dock window, when switched to primary equipment configuration mode, the topmost layer nodes
are “primary equipment branch” nodes. Substation objects that have been added are sub-nodes. In the
primary equipment configuration environment, substation objects cannot be added, deleted, or modified.
Select and open a substation node; there will be two sub-nodes under it in default: voltage level” and
transformer list”, displaying list of voltage levels and list of transformers under this substation.
41
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
42
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
In the IED pull-down list, user can select different IED for measuring point association. In the Point type
pull -down list, select corresponding measuring point type. User can realize configuration of relevant
measurement, relevant BI, relevant control, relevant TP, and relevant metering under primary equipment.
To display completed measuring point names, select Display IED name; complete descriptive names of
measuring points to be selected will be displayed in the Optional points list at left side. After measuring
points are associated to primary equipment, measuring point descriptive names will be changed from
IED name measuring point name ”format to [bay name] measuring point name” format, used to clarify if
this measuring point has been associated and under what bay. If such format conversion is not required,
cancel selection of “Replace IED name”. For replacement of bay name, name of target bay will be
displayed in the editing box corresponding to “Replace bay name” in default. User can modify its content
and customize bay name for replacement.
For association of CB -Switch with BI points, if there are only two BI points to be set, and both are CB or
DS, the database configuration tool will first prompt to set them to double point BI.
Alarm database configuration includes alarm level setup and alarm group configuration. In case of
43
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
change of status of measuring point object, the SCADA application will prompt Alarm application to
generate corresponding warning or prompt operation according to set alarm group.
alarm groups, names can be specified according to site conditions, e.g. CB status change, and
communication status etc. Later, corresponding group type can be selected.
5.5.1.2. Alarm Item Configuration
After alarm group type is set, alarm items under the alarm group are automatically added. SCADA
application generates alarm events according to defined alarm items.
In addition to above basic attributes, an alarm item can have definition of subsequent handling.
In the dock window, each alarm item always includes nodes “definition of popup graph “and “Definition of
alarm Ack”, which set subsequent operation after alarm. Select one of these nodes to display
corresponding items in the list window. User can add, delete, and modify settings of corresponding
items.
45
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
6. Report Editor
The report editor main interface includes 4 parts: menu bar, tools bar, report list, and report editing area
(refer to figure below).
46
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
On the report list tree, user can create a new report group or delete an existing report group. Grouping of
reports can be carried out.
Create a new report group: select report list tree root node “Report list” and right click mouse. In the
context menu popped up, select “New report group”; an input dialog box will pop up. Enter name of the
group and press OK.
Delete report group: select the report group to be deleted and right click mouse. In the context menu
popped up, select “Delete report group”. After confirming the inquiry, this report group will be deleted. If
this report group is not empty (there is at least one report of this group attached), then this report group
cannot be deleted.
Report groups “normal model” and “custom model” are automatically created when Report is started and
user cannot delete them.
6.2.1. New Report
There are two modes to create a new report: create a new blank report and use the New Report wizard.
Use menu “File”->“New” or click the button “ ”on the tools bar or select the report group in the
Report List and select context menu item new report”.
6.2.1.2. Use the report wizard to generate a Report
Use menu “File”->“New report wizard” or click the button “ ”on the tools bar or select the report group
in the report list and right click mouse and select “New report wizard” in the context menu.
47
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
Select a report in the report list tree and right click mouse. In the context menu, select “Modify report”.
The Attributes Modification dialog box will pop up, in which user can modify attributes that can be
modified. Click OK.
Select the report in the report list tree and right click mouse. In the context menu, select “Delete report”.
After confirmation, this report will be deleted, as well as the report record, version record, and report file
saved locally.
48
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
Data association is the most important part of report creation. Only when data association is defined, can
real-time data or history data be displayed during browsing of the report, hence realizing the function of
report.
Data association is provided in 3 types: real-time association, history association, and time
association.
49
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
50
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
51
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
52
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
7.1. General
System parameter setup shows common functions and configuration parameters of the system in a
friendly interface, to facilitate user to adjust system operating status at any time. In addition, online
adjustment of system parameters is supported, without the need of system reboot.
System configuration includes 3 main parts: graph setup, alarm setup, and SCADA setup.
53
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
54
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
Floating
Voltage level Set color displayed for each voltage level kV
point
Data
Configuration item Description Unit
type
Enable automatic Set system class: if automatic printing event report is
BOOL N/A
printing enabled.
Enable automatic
Set system class: if automatic graph pop-up is enabled. BOOL N/A
pop-up graph
Enable audio alarm Set system class: if audio function is enabled. BOOL N/A
Enable voice alarm Set system class: if voice function is enabled. BOOL N/A
Enable SMS
Set system class: if SMS message function is enabled. BOOL N/A
message alarm
Save in to history Set system class: if saving in history database function is
BOOL N/A
database enabled.
Avalanche duration Duration of judgment of avalanche Integer s
55
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
Avalanche flow
In avalanche duration, number of events judged Integer item
generation setting
If number of events is less than “release avalanche flow”
Rls avalanche flow during avalanche duration, avalanche status is deemed Integer item
canceled
Avalanche auto
Automatic printing interval in case of avalanche Integer s
print interval
56
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
8. Authority Management
8.1. General
57
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
Enter privmanager at command line or click “Authority management tool” on the console to activate
authority management tool. If only user password needs to be changed, this can be done directly without
log-in the authority management tool.
58
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
Add object: In list zone, select upper layer object of the object to be added, and then right click and
select Add or click Add button on the Tools bar.
Example: add user
59
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuratio
on Instruction
60
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
The following is an authority comparison table used by all applications of PCS-9700, for your reference.
Domain Functional point Process/application used
System configuration configmain
Authority management priv_manager
Database maintenance pcsdbdef
sysman
Graph editor Drawgraph, icon
Switch applications sm_console
PDR pdr
Telecontrol online
Guard online
Ack alarm online alarm
Report editor report
Modify history data report
MMI Force measurement online
Telecontrol unlock online
Tag online
Exit HMI system online pcscon
Login HMI system online pcscon
Set flag online
Modify settings RelayMMI
Switch setting group No.
RelayMMI
Modify VEBI
Reset relay
Run VQC VQC
VQC Maintain VQC
VQC system configuration
Run CVT CVT
CVT Maintain CVT
CVT system configuration
Login operation sheet system optab
Logout operation sheet system
Open wiring diagram
Set default wiring diagram
Force measurement
optab Maintain typical sheet
Edit operation sheet
Save prepared sheet
Delete operation sheet
Execute operation sheet
Invalidate operation sheet
61
V 1.00 NR ELECTRIC CO., LTD.
PCS-9700 HMI System Configuration Instruction
62
NR ELECTRIC CO., LTD. V 1.00
PCS-9700 HMI System Configuration Instruction
Glossary
63
V 1.00 NR ELECTRIC CO., LTD.