Professional Documents
Culture Documents
Fuzzy based Tie-Line and LFC of a Two-Area Interconnected System
Fuzzy based Tie-Line and LFC of a Two-Area Interconnected System
Fuzzy based Tie-Line and LFC of a Two-Area Interconnected System
Abstract:- In order to restore the balance between load and essentially shut down the whole northern region, affecting
generation in each control region, the load-frequency control all eight states. This resulted from the traditional
(LFC) uses speed control. Reducing the steady state error and controllers' poor control measures, and some states kept
transient deviations to zero in advance is the main goal of using more electricity than they required in spite of the
LFC. This study investigated LFC for two area systems using
fuzzy inference system (FIS) and conventional controllers. The
warnings. An adaptive control system is required to
results of the two controllers are compared using the recognize changes in load and stabilize the frequency
MATLAB/Simulink application. The findings are displayed deviation. In this study, an autonomous control action is
from comparisons between fuzzy inference systems and provided by a fuzzy inference system (FIS) technology.
conventional controllers. After contrasting the recommended controller with the
conventional controller, the results are shown.
Keywords:- Fuzzy Inference System (FIS), Conventional
Controller, and Load Frequency Control. II. SINGLE AREA POWER SYSTEM
I. INTRODUCTION A. Modelling of System Model
Modern power systems are divided into a number of
These days, producing electricity is essential due to categories. For example, the Eastern, Western, Northern,
the increasing demand for it. The dynamic behavior of the Southern, and North-Eastern grids are among the five
system depends on perturbations and modifications to the regional grids in India. Every one of these regional areas
operating point. The quality of the energy generated in has a common connection to the regions around it.
power plants is determined by the system's output, which Transmission lines that connect one region to its
needs to maintain the scheduled power and have a neighboring one are known as tie-lines. The purpose of
consistent frequency. Thus, load frequency control, or LFC, these tie-lines is to divide power between two locations. As
is essential to the power system's capacity to produce the name implies, load frequency control regulates the
consistent, high-grade electricity. While traditional power flow between different sites while keeping the
controllers such as PD, PID, and PI can offer control frequency constant.
actions for a single operating condition, in practice, the
parameters are never static. Setting up the require
adjustments to achieve zero frequency variation is so
difficult. Therefore, providing automatic correction is
crucial. Load frequency controllers have been designed
using a range of control algorithms to enhance dynamic
performance. Conventional controllers are the most
common and widely used of the several types of load
frequency controllers. Conventional controllers generate a
large amount of frequency variation despite being simple to
design. Most state feedback controllers based on linear
optimal control theory have been provided in order to
increase performance. Because fixed gain controllers are
Fig 1: Inter Connected Power System
designed for nominal operating settings, they are unable to
provide the best control performance throughout a range of
As long as "Δ𝑃𝑟𝑒ƒ" is set at zero, the system
operating conditions. Thus, to keep system performance
frequency will increase as the load reduces.
near maximum, it is desirable to keep an eye on operating
conditions and compute the control using the most recent
parameters. Adaptive controllers offer self-adjusting gain
setting. It is commonly known that the load frequency
control problem led to the collapse of the Northern grid.
This is the outcome of both excessive generation and
excessive grid demand. It resulted in a blackout that
The ACE refers to the frequency shift in a single-area IV. PID CONTROLLER
scenario. In an integral-control loop with ACE, the steady
state error in frequency will be zero, or V_st = 0. In a two- Conventional PID Controller on i-th AreaThe control
area example, ACE is the linear combination of the input 𝑈i is constructed as follows:
frequency change and the tie-line power change. To obtain 𝑇 T
the steady-state tie-line power zero (i.e., Δ𝑃𝑡i𝑒= 0), a 𝑈i = −𝐾i ∫ 𝐴𝐶𝐸i 𝑑𝑡 = − ∫ (Δ𝑃𝑡i𝑒 i + 𝐵iΔ𝐹i) (3)
second integrator loop for each region must be added in
addition to the integral frequency loop in order to integrate Taking the derivative of the equation yields
the incremental tie-line power signal and send it back to the 𝑈i = −𝐾i(𝐴𝐶𝐸i) = −𝐾i(Δ𝑃𝑡i𝑒 i + 𝐵i Δ𝐹i) (4)
speed changer.
The constants 𝐾i(1, 2) are the gain of the integrator. It
There requirements of the integral control action are: is observed that for decrease in both frequency and tie-line
power generation should decrease, i.e., if the ACE is
ACE must be equal to zero atleast one time in all 10- negative, the speed-changer position decreases and hence
minute periods. Average deviation of ACE from zero must the power generation should decrease, i.e., if the ACE is
be within specified limits based on percentage of system negative, then the area should increase its generation, so
generation forall10-minute periods. negative is assigned to the right-hand side term.
V. FUZZY INTERFACE
VI. SIMULATION AND RESULTS the frequency regulation of a two-area load without a
controller. with the 10% variation (growth) in the area's
A. Simulation Model for Two-Area Load Frequency load.1 illustrates the impact on both the area's frequency
Control and area. Moreover, it illustrates the effect on the area. tie
The two area load frequency control simulation block line power and two frequencies. Both the area1,2 and tie
diagram was created in MATLAB using the parameters line power Ptie1,2 frequency responses in their transient
listed in the table and modeled using Fig. 5. and the and stable states exhibit some instability. The tie-line power
simulation provides the findings for frequency and tie line exhibits more oscillations in Fig. 6. as a result of the abrupt
power changes in response to load changes. Figure 6 shows shift in load.
Fig 5: Simulink Model of Two Area Load Frequency Control with Conventional PID Controller
B. Simulation Results Without Controller of the control zones of 1%. With no controller, Figure 6.
The power system frequency will fluctuate illustrates the significant oscillations in its transient
proportionately from its typical steady state operating conditions and the steady state error of -1.378.
circumstances as a result of an abrupt change in load in one
The process design of fuzzy if-then rule knowledge output control input (CI) are used for two region LFC:
bases and membership functions for inputs and outputs are frequency error (E) and change in frequency error (CE). A
crucial components of fuzzy logic control system designs. three-member and a seven-member rule base are developed
When it comes to fuzzy logic control, they are crucial. Fig. for this purpose. Tables display the rule foundation for the
8 shows the fundamental architecture of the fuzzy logic seven membership functions.
controller. Two inputs for the fuzzy controller and one
The fuzzy logic based control system has been studied eliminating steady state error. Fuzzy logic membership
by simulation in order to validate the design and to evaluate functions, which are used by a novel kind of controller
the performance. Simulation result gotten by a fuzzy logic called a fuzzy logic controller, are transient.
controller which gives good performance in a constant load
case .When one need only design the FLC to provide REFERENCES
control command. It is seen that FLC provides faster
response and less overshoot. Fig.10. Shows the output [1]. Modern Power Systems Control and Operation”
response two area LFC with FLC Kothari, DP and I J Nagrath, Power System
Engineering, 2nd edn, Tata ... Debs, A S, KAP, New
E. Two Area Load Frequency Control Results with FUZZY York, 1988.
Controller [2]. “Power system analysis” by Haadi Sadat, Tata
Fuzzy controller gives better response in both McGraw- illcompany’s Inc. 1999
transient and steady state period: [3]. “Electrical Power System Analysis”. Front Cover
·Sivanagaraju, B. V. Rami Reddy. Firewall Media,
Jan 1, 2007- 345 pages.
[4]. “Power Generation, Operation and Control”, 3rd
Edition Allen J. Wood, Bruce F. Wollenberg, Gerald
B. Sheble ISBN: 978-0-471-79055-6 656 pages
October 2013
[5]. “Tuning of PID controller using particle swarm
optimization” Mahmud Iwan Solihin, Lee Fook
Tack and Moey Leap Kean 2011
[6]. “Load frequency control using optimal PID
controller for Non-Reheated thermal power system
with TCPS units” A.R.Rajkumar, T.Jayabharathi,,
june-2012.
[7]. “Automatic load frequency control of two area
Fig 10: Output response two area LFC with FLC power system with conventional and fuzzy logic
control” Nilay N.Shah, Anant.R.Suthar, nov-2012.
VII. CONCLUSION [8]. “Load frequency control of interconnected hydro
power system using fuzzy and conventional PI
In this study, MATLAB simulation was used to mimic controllers” Sachin Khajuria, Jaspreet Kaur, oct.
the two area load frequency control. The tie line power 2012.
varies as a result of an abrupt shift (increase) in load. By
boosting steady state response, integral controllers lower tie
line power oscillations and guarantee that steady state error
equals zero. A derivative controller reduces transient
oscillations. The best controller is the classic PID
controller, which is coupled in series with the tie line and
reduces transient tie line power oscillation while