Company: Cannon Page: 1
Address: Specifier:
Phone I Fax: E-Mail:
Design: Grating Beams Connection Date: 4/24/2024
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter: HIT-HY 200 V3 + HAS-V-36 (ASTM F1554 Gr.36) 3/4
Item number: 2198028 HAS-V-36 3/4"x6" (element) / 2334276 HIT-HY
200-R V3 (adhesive)
Effective embedment depth: hef,act = 4.000 in. (hef,limit = - in.)
Material: ASTM F1554 Grade 36
Evaluation Service Report: ESR-4868
Issued I Valid: 11/1/2022 | 11/1/2024
Proof: Design Method ACI 318-19 / Chem
Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.500 in.
Anchor plate :
R lx x ly x t = 9.000 in. x 8.000 in. x 0.500 in.; (Recommended plate thickness: not calculated)
Profile: W shape (AISC), W8X15; (L x W x T x FT) = 8.110 in. x 4.010 in. x 0.245 in. x 0.315 in.
Base material: cracked concrete, 3000, fc' = 3,000 psi; h = 8.000 in., Temp. short/long: 32/68 °F
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: not present, shear: not present; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.93
www.hilti.com
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 220542.02-12 in (2) Date: 4/24/2024
Fastening point: Short wall Posts to 24" MAT
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [lb] Capacity f Nn [lb] Utilization bN = Nua/f Nn Status
Steel Strength* N/A N/A N/A N/A
Bond Strength** N/A N/A N/A N/A
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Failure** N/A N/A N/A N/A
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.93
www.hilti.com
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 220542.02-12 in (2) Date: 4/24/2024
Fastening point: Short wall Posts to 24" MAT
4 Shear load
Load Vua [lb] Capacity f Vn [lb] Utilization bV = Vua/f Vn Status
Steel Strength* 1,781 7,566 24 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength controls)** 7,123 14,953 48 OK
Concrete edge failure in direction ** N/A N/A N/A N/A
Variables
2
Ase,V [in. ] futa [psi]
0.33 58,000
Calculations
Vsa [lb]
11,640
Results
Vsa [lb] f steel f Vsa [lb] Vua [lb]
11,640 0.650 7,566 1,781
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.93
www.hilti.com
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 220542.02-12 in (2) Date: 4/24/2024
Fastening point: Short wall Posts to 24" MAT
Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ] ACI 318-19 Eq. (17.7.3.1b)
f Vcpg ³ Vua ACI 318-19 Table 17.5.2
ANa see ACI 318-19, Section 17.6.5.1, Fig. R 17.6.5.1(b)
2
ANa0 = (2 cNa) ACI 318-19 Eq. (17.6.5.1.2a)
t uncr
cNa = 10 da √ 1100
ACI 318-19 Eq. (17.6.5.1.2b)
( )
1
'
y ec,Na = eN £ 1.0 ACI 318-19 Eq. (17.6.5.3.1)
1+
cNa
Na
ACI 318-19 Eq. (17.6.5.4.1b)
= MAX(
c ) £
c c a,min Na
y cp,Na , 1.0 ACI 318-19 Eq. (17.6.5.5.1b)
c ac ac
Nba = l a · t k,c · p · da · hef ACI 318-19 Eq. (17.6.5.2.1)
Variables
kcp aoverhead t k,c,uncr [psi] da [in.] hef [in.] ca,min [in.] t k,c [psi]
2 1.000 2,261 0.750 4.000 3.500 1,283
Calculations
cNa [in.]
2
ANa [in. ] ANa0 [in. ]
2
y ed,Na
10.704 507.12 458.28 0.798
Results
Vcpg [lb] f concrete f Vcpg [lb] Vua [lb]
21,361 0.700 14,953 7,123
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.93
www.hilti.com
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 220542.02-12 in (2) Date: 4/24/2024
Fastening point: Short wall Posts to 24" MAT
5 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential
concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout
or pryout strength governs.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-19,
Section 26.7.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.93
www.hilti.com
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 220542.02-12 in (2) Date: 4/24/2024
Fastening point: Short wall Posts to 24" MAT
6 Installation data
Anchor type and diameter: HIT-HY 200 V3 + HAS-V-36
(ASTM F1554 Gr.36) 3/4
Profile: W shape (AISC), W8X15; (L x W x T x FT) = 8.110 in. x 4.010 in. x Item number: 2198028 HAS-V-36 3/4"x6" (element) /
0.245 in. x 0.315 in. 2334276 HIT-HY 200-R V3 (adhesive)
Hole diameter in the fixture: df = - in. Maximum installation torque: 1,200 in.lb
Plate thickness (input): 0.500 in. Hole diameter in the base material: 0.875 in.
Recommended plate thickness: not calculated Hole depth in the base material: 4.000 in.
Drilling method: Hammer drilled Minimum thickness of the base material: 5.750 in.
Cleaning: Compressed air cleaning of the drilled hole according to instructions
for use is required
3/4 Hilti HAS Carbon steel threaded rod with Hilti HIT-HY 200 V3 Safe Set System
y
4.500 4.500
1.500
3 4
4.000
5.000
x
4.000
1 2
1.500
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.93
www.hilti.com
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 220542.02-12 in (2) Date: 4/24/2024
Fastening point: Short wall Posts to 24" MAT
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan