Before using the air conditioner, please read this manual carefully.
Please keep this manual properly for future use.
Contents
indoor unit
Installation Procedure.............................................................................. 18-29
outdoor unit
Name of Parts .............................................................................................. 30
Safety Cautions ....................................................................................... 31-32
1
Cautions
All electrical repairs must be carried out
3. The wiring method should be in line with the
by qualified electricians. Inadequate repairs
local wiring standard.
may result in a major source of danger for
4. The power cable and connecting cable are
the user of the air conditoiner.
self-provided. The requirement of the power
Do not damage any parts of the air cable:
conditioner that carry refrigerant by Power Cable
Model
piercing or perforating the air conditioner's
tubes with sharp or pointed items, crushing HBU-18CA03T3 5G 2.5mm2
or twisting any tubes, or scraping the HBU-24CA03T3
coatings off the surfaces. If the refrigerant HBU-36CA03T3
spurts out and gets into eyes, it may result HBU-42CA03T3
5G 4.0mm2
in serious eye injuries. HBU-50CA03T3
Do not obstruct or cover the ventilation HBU-60CA03T3
grille of the air conditioner. Do not put
fingers or any other things into the All the cables shall have got the European
inlet/outlet and swing louver. authentication certificate.
5. The breaker of the air conditioner should be
Do not allow children to play with the air all-pole switch; and the distance between its two
conditioner. In no case should children be contacts should be no less 3mm. Such means for
allowed to sit on the outdoor unit. disconnection must be incorporation in the fixed
wiring.
Specifications 6. The waste battery shall be disposed properly.
The refrigerating circuit is leak-proof. 7. The indoor unit installation height is at least
The machine is adaptive in following 2.5m.
situation
1. Applicable ambient temperature range:
2
Cautions
Safety cautions
Carefully read the following information in order to operate the airconditioner correctly.
Below are listed three kinds of Safety Cautions and Suggestions.
WARNING! Incorrect operations may result in severe consequences of death or serious injuries.
CAUTION! Incorrect operations may result in injuries or machine damages; in some cases may
cause serious consequences.
INSTRUCTIONS: These information can ensure the correct operation of the machine.
Be sure to conform with the following important Safety Cautions.
The Safety Cautions should be at hand so that they can be checked at any time when needed.
If the conditioner is transferred to the new user, this manual should be as well transferred to the new user.
WARNING!
Don't blow the human body with the cooling Please let the dealer be responsible for installing
air too long, and don't let the room tempera- the conditioner.
ture decrease too low Incorrect installation may cause water leak, elec-
either. trical shock and fire hazard.
Otherwise the one
will feel unpleasant Don't put fingers or any other things into the
or harm ones' health. inlet/outlet and swing louver while the condi-
tioner is in operation.
If any abnormal phenomena is found (e. g.
Because the highspeed
smell of firing), please cut off the power
fan is very dangerous
supply immediately, and contact the dealer
and may cause injuries.
to find out the handling method.
In such case, to continue
using the conditioner will Call the dealer to take measures to prevent the
switch
damage the conditioner, off
refrigerant from leaking.
and may cause electrical If conditioner is installed in a small room be sure
shock or fire hazard. to take every measure in order to prevent suffoca-
tion accident even in case of refrigerant leakage.
When need maintenance and repairment,
call dealer to handle it.
Incorrect mainten- When conditioner is deinstalled or reinstalled
ance and repairment dealer should be responsible for them.
may cause water Incorrect installation may cause water leaking,
leak, electrical shock electrical shock and fire hazard.
and fire hazard.
3
Cautions
CAUTIONS!
Conditioner should not be used for any other Don't operate the air-con-
purpose other than airconditioning. ditioner with damp hands.
Don't use air-conditioner for any other special Otherwise will be shocked.
purposes, e.g. the preservation and protection
Only use correctly-typed fuse.
of food, animals, plants,
May not use wire or any other
pecision apparatus as well
materials replacing fuse, other-
as work of art, otherwise
wise may cause faults or fire
the qualities of these
accidents.
stuffs may be damaged.
Don't place any burning unit
Don't dismantle the outlet of the outdoor unit.
in the air flow of air-conditioner,
The exposure of fan is
which may cause incomplete
very dangerous which
combustion.
may harm human be-
ings. No inflammable spray fluid
should be permitted to be
When air-conditioner is co-used with other placed or used near to air-
heat-radiator the frequent replacement of conditioner otherwise may
room atmosphere should be required. cause fire accidents.
Inefficient venti-
lation may cause Air-conditioner should be
suffocation. cleaned only after power
supply is cut off to keep
After a long time use of air-conditioner the
from shock or hurt.
base should be checked for any damages.
If the damaged base is
Don't clean air-conditioner
not repaired, the unit
with water.
may fall down and
Otherwise may cause
cause accidents.
shock.
No goods or nobody is permitted to placed on
or stand on outdoor unit. When use the fumigating insecticide don't
The falling of goods and open air-conditioner.
people may cause acci- Otherwise the poisonous chemicals may settle
dents. in air-conditioner which harm the health of
chemical-allergic people.
Pets and plants should not be blowed directly
in the air flow.
Otherwise will suffer
damage.
4
Cautions
Installation
Please ask the dealer or specialist to install, never try by the users themselves. After the installation
please be sure of the following conditions.
WARNING !
Please call dealer to install the air-conditioner.
Incorrect installation may cause water leaking, shock and fire hazard.
CAUTION !
Air-conditioner can't be installed in the envi- Connect earthing wire.
ronment with inflammable gases because the Earthing wire should not be con-
inflammable gases near to air-conditioner may nected to the gas pipe, water pipe,
cause fire hazard. lightning rod or phone line, in-
correct earthing may cause shock. Earthing
Installed electrical-leaking circuit breaker.
Use discharge pipe correctly to ensure efficient
It easily cause electrical shock without circuit
discharge.
breaker. Incorrect pipe use may cause water leaking.
[Location]
Air-conditioner should be located in well-vented As required, take measures against heavy snow.
and easily-accessible place.
Air-conditioner should not be located in the [Wiring]
following places:
Air-conditioner should be equipped with special
(a) Places with machine oils or other oil vapours.
power supply wire.
(b) Seaside with high salt content in the air.
(c) Near to hot spring with high content of sulfide
[Operating noise]
gases.
(d) Area with frequent fluctuation of voltage e.g. Chose the following locations:
factory, etc. (a) Capable of supporting air-conditioner weight,
(e) In vehicles or ships. don't increase operating noise and vibration.
(f) Kitchen with heavy oil vapour or humidity. (b) Hot vapour from outdoor unit outlet and ope-
(g) Near to the machine emitting electric-magnetic rating noise don't disturb neighbour.
waves. No obstacles around the outdoor unit outlet.
(h) Places with acid, alkali vapuor.
TV, radio, acoustic appliances etc are at least 1 m
far away to the indoor unit, outdoor unit, power
supply wire, connecting wire, pipes, otherwise
images may be disturbed or noises be created.
5
Introduction to Spare Parts
Indoor unit
HBU-18CA03T3
Swing louver
HBU-24CA03T3
HBU-36CA03T3 (Air flow direction can be adjusted by using
HBU-42CA03T3 the SWING button on the remote controller)
HBU-50CA03T3
HBU-60CA03T3
Discharge unit (built in)
In cooling operation, Drain Hose
to discharge the
water from inside the
room.
Swing fender
(located in the outlet)
Refrigerant pipe
Outlet Cable line
Earthing line
Air filter
(located in the suction grill)
Suction grill
6
Maintenance
[Clean air filter]
NOTE
When having to clean, don't dismantle air-filter,otherwise may cause faults.
In the environment where there is too much dust, air filter should be cleaned for more times.
(about half a year one time)
clip cpening
7
Maintenance
5. Close inlet grill [Clean inlet grill]
the reverse sequance of 1. 1. Open inlet grill
6. Open inlet grill Press the elliptical "PUSH" knob, the inlet grill
Press the elliptical "PUSH" knob, the inlet grill will will automatically drop. (the inlet grill is catched
automatically drop. (the inlet grill is catched with with two pothooks)
two pothooks) Press the elliptical knob
Press the elliptical knob the inlet grill will
PUSH
automatically drop
automatically drop
8
Maintenance
5. Install inlet grill see 3 [Dismantle and install swing plate ]
6. Install air filter see "Clean air filter"
3. Install swing plate
7. Close inlet grill see 1
Lightly rotate swing plate to insert the ridge
at both ends of the outlet into the groove
[Clean outlet and shell] and then screw up.
CAUTION!
CAUTION!
9
Maintenance
Seasonal Reserve
Post-season Care
Operate the unit with FAN mode on a fair day for about half
a day to dry the inside of the unit well.
Stop operation and turn off the power supply switch .Electric
power is consumed even the air conditioner is in stop.
Clean the air filter, indoor unit and outdoor unit,and cover
the unit with dustcoat.
Pre-season Care
Be sure to install the air filter, ensure that the air filter is not dirty. Otherwise may result in
machine damages or cause malfunciton due th dust inside the unit
NOTE
1. The inner part of indoor unit must be cleaned. Consult dealer, because clean must be done by
technician.
2. In cooling operation, discharging system discharge water in room.
10
Trouble Shooting
The followings are not malfunction
Water flowing sound is heard When the air conditoner is started, when the
compressor starts or stops during operation
or when the air conditioner is stopped,it som-
Hua etimes sounds "Bi- Bi-"or "Godo-Godo". It is
Hua the flowing sound of the refrigerant , not a
malfunction.
During operation, white fog comes out of When in COOL or DRY mode, a thin water
indoor unit. fog can be seen blown out of unit ,this is the
condensed fog because the suddenly cooled
indoor air is blown out.
Automatically switch into FAN mode during To prevent frost from being accumulated on the
cooling. indoor unit heat exchanger, it sometimes auto-
matically switched into the FAN mode,but it will
soon back to the cooling mode.
The air conditioner cannot be restarted soon This is because of the self-protection function
after it stops. of the system, therefore,it cannot be restarted
Air conditioner does not start? for about three minutes after it stops.
11
Trouble Shooting
Air does not blow or the fan speed cannot be In DRY mode, when room temperature
changed during drying. becomes 2 ¡ higher than temperature setting,
unit rill run intermittently at LO speed regardless
of FAN setting
Water or vapor generated from the outdoor This happens when the frost accumulated on
unit during heating. the outdoor unit is removed (during defrosting
operation).
Defrosting operation
During heating,indoor fan is still running even To get ride of the excess heat, indoor fan will
unit is stopped. continue running for a while after unit autom-
atically stops.
Please check the following things about your air conditioner before making a
service call.
**?
ON
OFF
12
When Trouble Happens
Insufficient cooling or heating
The operation controller Air filter too dirty ? Horizontal swing louver
adjusted as required upward ? (in HEAT mode)
Insufficient cooling
Any other heat sources in the Sunlight direct into the Too crowed in the room ?
room? room ?
13
When Trouble Happens
Failure code list
Failure code Power lamp flash
on wired times/LED on failure description Reasons
controller PCB flash times
E0 10 Fault in drain system Float switch is open
14
Customer Need-to-know
Customer Need-to-know
Please install the air conditioner according to the requirements specified in this manual
to ensure the air conditioner work well.
Be careful not to scratch the surface of the case during moving the air conditioner.
Please keep the installation manual for future reference when maintenance and changing
installation place.
After installation ,please use the air conditioner according to the specification in the
operation manual.
Using Directions
Optimal
temper-
ature
15
Precaution For Installation
CAUTIONS:
To ensure proper installation,read"Cautions" carefully before working.After installation,start
the unit correctly and show customers how to operate and maintain the unit.
Meanings of Warning and Cautions:
Warning! Serious injury or even death might happen,if it is not observed.
Caution! Injury to people of damages to machine might happen, if it is not observed.
WARNING!
Installation shall be done by professional people, don't install unit by yourself. Incorrect installation
will cause water leakage, electric shock or fire.
Install unit as per the Manual. Incorrect installation will cause water leakage, electric shock or fire
accident.
Be sure to use specified accessaries and parts. Otherwise, water leakage, electric shock, fire accident
or unit falling down may happen.
Unit should be placed on a place strong enough to hold the unit. Or, unit will fall down causing injuries.
When install the unit, take in consideration of storms, typhoom, earthquake. Incorrect installation
may cause unit to fall down.
All electric work shall be done by experienced people as per eocal code, regulations and this Manual.
Use exclusive wire for the unit. Incorrect installation or undersized electric wire may cause electric
shock or fire accident.
All the wires and circuit shall be safe. Use exclusive wire firmly fixed. Be sure that external force
will not affect terminal bolck and electric wire. Poor contact and installation may cause fire accident.
Arrange wire correctly when connectin indoor and outdoor power supply. Fix terminal cover firmly
to avoid overheat, electric shock or even fire accident.
In case retrigerant leakage occurred during unit installation, keep a good ventilation in the room.
Poisonous gas will occur when meet with fire.
Check the unit upon installation. Be sure there is no leakage. Refrigerant will induce poisonous gas
when meet heat source as heater, oven, etc.
Cut power supply before touching terminal bolck.
CAUTION!
Unit shall be grounded. But grounding shall not be connected to gas pipe water pipe,
telephone line. Poor grounding will cause electric shock. Earthing
Be sure to install a leakage breaker to avoid electric shock.
Arrange water drainage according to this Manual. Cover pipe with insulation materials in case dew may
occur. Unproper installation of water drainage will cause water leakage and wet your furniture.
To maintain good picture or reduce noise, keep at least 1 m from T.V. radio, when install indoor and outdoor
unit, connecting wire and power cable. (If the radio wave is relatively strong, 1 m is not enough to reduce
noise).
Don't install unit in following places:
(a) Oil mist or oil gas exists, such as kitchen, or, plastic parts may get aged, or water leakage.
(b) Where there is corrosive gas. Copper tube and welded part may be damaged due to corrosion,causing
leakage.
(c) Where there is strong radiation. This will affect unit's control system, causing malfunction of the unit.
(d) Where flamable gas, dirt, and volatile matter (thinner, gasoline) exist, These mattermight cause fire
accident.
Refer to paper pattern when installing unit.
Cautions for the installation personnel
Don't fail to show customers how to operate unit.
16
Installation Tools
Installation tools
The installation tools listed in the following sheet can be used as required.
1. Screw driver
2. Hacksaw
3. Drill with a diameter of 60mm
4. Inner hexagon spanner,shifting spanner
5. Spanner (14, 17, 19,24,27mm)
6. Pipe cutter
7. Pipe expander
8. Knife
9. Pincers
10. Leakage detector or soapy water
11. Band tape
12. Scraper
13. Refrigerant oil
Standard accessories
The following parts mentioned in this manual are the installation accessories we prepared.
A Adhesive tape
B Pipe clamp
C Connecting hose
D Drainage hose
F Gypsum powder
17
Installation Procedure indoor unit
(3) Install suspending bolt. Check if the installation place is strong enough to hold weight. Take
necessary measures in case it is not safe. (Distance between holes are marked on paper pattern.
Refer to paper pattern for place which need be reinforced)
2500 Over
HBU-18CA03T3(H=260) HBU-36CA03T3
HBU-24CA03T3(H=240) HBU-42CA03T3
HBU-50CA03T3
HBU-60CA03T3
18
Installation Procedure indoor unit
890mm(Ceiling opening)
950mm(Ornament panel)
suspending bolts 690mm
840mm(Indoor unit)
Distance between
Distance between
suspending bolts 535mm
Indoor unit 570mm Distance between
suspending bolts 790mm
Ceiling opening 650mm 840mm(Indoor unit)
Ornament panel 700mm 890mm(Ceiling opening)
950mm(Ornament panel)
Overlap between ceiling and
ornament panel shall be 25mm
Suspending bolts Ceiling Suspending bracket
150mm
320mm
150mm
H
Ceiling 25mm
Ornament panel
60mm
Ornament panel
60mm
Type H(mm)
HBU-60CA03T3
HBU-24CA03T3 300
1280mm(Ceiling opening)
HBU-36CA03T3 HBU-42CA03T3
1070mm 370
(Distance between suspending bolts) HBU-50CA03T3
515mm
Note:
(Distance between suspending bolts)
860mm(Ceiling opening)
20mm Over
515mm
19
Installation Procedure indoor unit
(2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.)
Refer to paper pattern for dimension of ceiling hole.
Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before installation.
Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent vibration.
Contact your real estate dealer
(3) Install a suspending bolt.
(Use a M10 bolt)
To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For
new ceiling, use built-in type bolt or parts prepared in the field.
Before going on installing adjust space between ceiling.
<Installation example>
Anchor bolt
Roof
50~150
Long nut
Suspending bolt
Ceiling Note: All the above mentioned parts shall be prepared in field.
20
Installation Procedure indoor unit
Insert
5 Refrigerant piping (As for outdoor piping, please refer to installation Manual of outdoor unit.)
Outdoor is precharged with refrigerant.
Be sure to see the Fig.1, when connecting and removing piping from unit.
For the size of the flare nut, please refer to Table 1.
Apply refrigerant oil at both inside and outside of flare nut. Tighten it band tight 3-4 turns then tighten it.
Use torque specified in Table 1. (Too much force may damage flare nut, causing gas leakage).
Check piping joints for gas leakage. Insulate piping as shown in Fig. below.
Cover joint of gas piping and insulator 7 with seal.
Apple refrigerant oil Medium size seal pad 11 (accessory)
(Cover the piping joint with seal pad.)
Clamp
Torque spanner
21
Installation Procedure indoor unit
1-1.5m
Use the self-provided stiff pipe and clamp 1 with unit. Insert water pipe into water plug until it reaches
the white tape. Tighten the clip until head of the screw is less than 4mm from hose.
Wind the drain hose to the clip using seal pad 9 .
Insulate drain hose in the room. Large size seal pad 9
Clamp 1 (accessory)
Clamp
(accessory)
Drain hose
75 below
(accessory)
500 below
Clamp Unit:mm
(accessory)
(Note)
The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it.
If several water hoses join together, do as per following proceedures.
Over 100mm
Specifieations of the water hoses shall meet the requirements for the unit running.
Check if water drainage is smooth after installation.
Charge, through air outlet or inspecting hole, 1200cc water to see water drainage.
22
Installation Procedure indoor unit
Wiring
All supplied parts. materials and wiring operation must in appliance with local code and regulations.Use
copper wire only.
When make wiring, please refer to wiring diagram also.All wiring work must be done by qualified electricians.
A circuit breaker must be installed, which can cut power supply to all system.
Connecting of unit
Remove cover of control box , connect wires of correct pole to the terminal block inside,please connect the
wires in right way.
Upon connecting, replace control box cover and inlet grill .
Note:remember to connect the blue terminal of indoor unit with the white terminal of outdoor unit properly using
the connecting wire in the accesory bag(For heat pump model).Otherwise the "Run" light on indoor remote
receiver will flash four times refer to Page.14.
Wiring diagram
For HBU-18CA03T3 For HBU-24CA03T3
Indoor unit terminal block
Indoor unit terminal block
L N 1 2 3 4 Y/G
1 2 3 4 5 Y/G
LN
Power supply
1PH,220-230V~,50Hz 1(L) 2(N) 3 4 Power supply
Y/G
1PH,220- 1 2 3 4 5 Y/G
230V~,50Hz
Outdoor unit terminal block
Outdoor unit terminal block
For HBU-36CA03T3
Indoor unit terminal block For HBU-42/50/60CA03T3
1 2 3 Indoor unit terminal block
Y/G
1 2 3
LN 1 2 3 R S T N 1 2 3
Y/G
Outdoor unit terminal block
Outdoor unit terminal block
Power supply Power supply
1PH,220-230V~,50Hz
1PH,220-240V~,50Hz
<<WARNING>>
Obscrve the following when connecting power supply Connect wires of the Don't connect wires of Don't connect wires
same specifications the same specifications of the different
terminal block: at two sides. at one side. specifications.
Don't connect wires of different specifications to
the same terminal block.
(Loose wire may cause overheating of circuit)
Connect wires of same specifications as shown in
right Fig.
23
Installation Procedure indoor unit
WIRING EXAMPLE
As for outdoor unit circuit, please see Installation Manual of outdoor unit.
Note: All electric wires have their own poles, poles must match that on terminal block.
Check if the indoor unit is horizontal with level apparatus,and also check if the size of ceiling opening is right.
Remember to take off the level apparatus before installation.
Fix the ornament panel onto the indoor unit temporarily with two screws,make sure that the height difference of the
indoor unit's two sides should be no more than 5mm.
Screw other two screws and tighten all of the four screws to fix up the ornamnet panel.
7 WIRING
All supplied parts. materials and wiring operation must in appliance with local code and regulations.Use copper
wire only.
When make wiring, please refer to wiring diagram also.All wiring work must be done by qualified electricians.
A circuit breaker must be installed, which can cut power supply to all system.
Connecting of unit (Take HBU-24CA03T3 For example).
Remove cover of switch box (1) , drag wires into rubber tube A, then, after proper wiring with other wires,
tighten clamp A. Connect wires of correct pole to the terminal block inside.
Wind seal 12 around wires. (Be sure to do that, or, dew may occur).
Upon connecting, replace control box cover (1) and (2).
Moreover,connect the black terminal of indoor unit with the black terminal of outdoor unit properly using the
connecting wire which has both white terminals in the accesory bag,and connect the blue terminal of indoor
unit with the white terminal of out terminal as the same(For heat pump model).For cooling only unit,just connect
the black terminalof indoor unit with the black terminal
of outdoor unit properly. For HBU-42CA03T3
8 WIRING EXAMPLE
As for outdoor unit circuit, please see Installation Manual of outdoor unit.
Note: All electric wires have their own poles, poles must match that on terminal block.
24
Installation Procedure indoor unit
Fig.2 Bar
Fig. 3
Fig.1 remove the air inlet grill
Adbesive tape
45
For HBU-60CA03T3. Remove air inlet grill from ornament panel
1 Push in the bar on inlet grill and lift it up. (Refer to Fig. 3) Fig. 4
2 Lift it up for about 45 degree and remove it from ornament. Tear off adhesive
tape fixing air filter on the back of the air inlet grill. (Refer to Fig. 4)
(2) Remove cover plate at corner Slide
Tear off the adhesive tape, and slide it off. (Refer to Fig. 5)
Fig. 5
7. WIRING
All supplied parts. materials and wiring operation must in appliance with local code and regulations.Use
copper wire only.
When make wiring, please refer to wiring diagram also.All wiring work must be done by qualified electricians.
A circuit breaker must be installed, which can cut power supply to all system.
Connecting of unit (Take HBU-24CA03T3 For example).
Remove cover of switch box (1) , drag wires into rubber tube A, then, after proper wiring with other wires, tighten
clamp A. Connect wires of correct pole to the terminal block inside.
Wind seal 12 around wires. (Be sure to do that, or, dew may occur).
Upon connecting, replace control box cover (1) and (2).
Moreover,connect the black terminal of indoor unit with the black terminal of outdoor unit properly using the
connecting wire which has both white terminals in the accesory bag,and connect the blue terminal of indoor
unit with the white terminal of out terminal as the same(For heat pump model).For cooling only unit,just connect
the black terminalof indoor unit with the black terminal
of outdoor unit properly.
Terminal block
Clip A
<<WARNING>> Connect wires of the Don't connect wires of Don't connect wires
Obscrve the following when connecting power supply same specifications the same specifications of the different
terminal block: at two sides. at one side. specifications.
Don't connect wires of different specifications to the same
terminal block.
(Loose wire may cause overheating of circuit)
Connect wires of same specifications as shown in right Fig.
11 WIRING EXAMPLE
As for outdoor unit circuit, please see Installation Manual of outdoor unit.
Note: All electric wires have their own poles, poles must match that on terminal block.
25
Installation Procedure indoor unit
Fig. 6 b
a 50 100
Be sure to show customers Operation Manual and guide them how to operate unit
correctly. Before installation. read also the Installation Manual of indoor unit. Bar
With this ornament , 2 or 3 air flow direction is not available. Fig. 11
Suitable height is 3 m. Accessory Pad
Pad
Ornament panel shall not be placed face down or against wall, Adhesive tape
45
neither on an uneven object.
Don' t bend carelessly the swing flap, or, problem may occur.
Fig. 12
(1) Remove air inlet grill from ornament panel
1 Push in the bar on inlet grill and lift it up. (Refer to Fig. 11)
2 Lift it up for about 45 degree and remove it from ornament. Tear off adhesive
tape fixing air filter on the back of the air inlet grill. (Refer to Fig. 12)
Slide
(2) Remove cover plate at corner
Tear off the adhesive tape, and slide it off. (Refer to Fig. 13)
Fig. 13
HBU-60CA03T3
26
Installation Procedure indoor unit
Hook
(3) As shown in Fig.14, match the position of swing Holding ring 1
flap motor with that of the indoor unit piping hole ,
2 Piping hole position
so that ormament panel can be placed on to indoor
unit.
(4) Installation of ornament panel
2
1 Place the holding ring on swing flao motor side
teporarily on hooks of the indoor unit. (2 pcs)
Swing flap motor
2 Put the other two holding rings on the hooks at both
side of the indoor unit. (Care should be taken not to 3
push wiring of swing flap motor into seals).
3 Screw in all 4 screws under holding ring for about
15mm. (Pancl will rise). 4
4 Adjust the ornament panel as per Fig. 14 to cover Fig. 14
Indoor unit Seal
opening on the ceiling.
5 Tighten screws to redrce the thickness of seals Ceiling material
HBU-60CA03T3
Caution
If screws are not tighten tight, If there are still space after tightening If indoor unit is at horizontal level and
problems in Fig.15 might occur. of screws, please readjust the water drainage is smooth, then, indoor
Tighten screws properly. heightof indoor unit. unit height can be adjusted throrgh holes
(Refer to Fig. 16) at corners of ornament panel.
Gas leakage
from roof.
When installing inlet grill, take care not to twist wiring of swing flap motor.
27
Installation Procedure indoor unit
Check whether indoor unit is horizontal with leveler or polythene pipe filled with water , and check that the dimension of the
ceiling opening is correct. Take off the lever gauge before install the ornament panel.
Fasten the screws to make the height difference between the two sides of
indoor unit less than 5mm.
First fix it with screws temporally.
where the swing motor locates in the figure of
panle just is the location of liquide pipe.
Fasten the two temporally fixing screws Electric control box
and other two, and tighten the four screws.
Connect the wires of synchro-motor.
Connect the wire of signal.
If no response of remote controller,
check whether the wiring is correct,
restart remote controller 10 seconds
after shut off power supply.
Tighten screws to redrce the thickness of seals
between ornament and indoor unit to 5-8mm. Indoor unit Seal
Ceiling material
If connecting is not made, error code 5 _ 8mm
(A7) appears on remote controller. So, Ornament panel
make proper connecting.
Caution
If screws are not tighten tight, If there are still space after tightening If indoor unit is at horizontal level and
problems in Fig.19 might occur. of screws, please readjust the water drainage is smooth, then, indoor
Tighten screws properly. heightof indoor unit. unit height can be adjusted throrgh holes at
(Refer to Fig. 20) corners of ornament panel.
Gas leakage
from roof.
Fig. 19 Fig. 20
28
Installation Procedure indoor unit
29
Name of Parts Outdoor unit
Air inlet
HBU-18CA03T3
HBU-24CA03T3
Air outlet
Compressor
(Inside of the unit)
Air outlet
Compressor
(Inside of the unit)
HBU-42CA03T3
HBU-50CA03T3 Air inlet
HBU-60CA03T3
Air outlet
Compressor
(Inside of the unit)
30
Safety Cautions Outdoor unit
CAUTION! Incorrect operations may result in injuries or machine damages; in some cases
maycause serious consequences.
INSTRUCTIONS: These information can ensure the correct operation of the machine.
Be sure to conform with the following important Safety Cautions.
The Safety Cautions should be at hand so that they can be checked at any time
when needed.
If the conditioner is transferred to the new user, this manual should be as well transferred
to the new user.
WARNING!
If any abnormal phenomena is Don't dismantle the outlet of the
found (e. g.smell of firing), please outdoor unit.
cut off the power supply The exposure of fan is very dangerous
immediately, and contact the dealer whichmay harm human beings.
to find out the handling method.
In such case, to continue using the
conditioner will damage the
conditioner, and may cause electrical
shock or fire hazard.
switch
off
When need maintenance and
repairment, call dealer to handle it.
After a long time use of air
conditioner the base should be Incorrect maintenance and repairment
checked for any damages. may cause water leak, electrical shock
and fire hazard.
If the damaged base is not repaired,
the unit may fall down and cause
accidents.
31
Safety Cautions Outdoor unit
WARNING!
Installed electrical-leaking circuit No goods or nobody is permitted to
breaker. placed on or stand on outdoor unit.
It easily cause electrical shock without The falling of goods and people may
circuit breaker. cause accidents.
32
Installation Procedure Outdoor unit
1. Accessories Edging
obstacle is
over 150
over 150
shorter than
outdoor
over 1000
over 500
over 150
over 1000
unit: mm
Upside and the two sides should be open; obstacle at least on either of front side and back side should be
shorter than outdoor.
33
Installation Procedure Outdoor unit
over 200
over 150 over 300 over 300 over 300
over 200
over 1000
Upside and the two sides should be open; obstacle at least on either of front side and back side should
be shorter than outdoor.
34
Installation Procedure Outdoor unit
Unit Unit
Concrete
Anchor bolt foundation
Concrete
foundation
Anchor bolt
Note:
To fix by bolts
Note: (1) Place the concrete foundation deep
(1) Give enough room for the concrete enough.
foundation to fix by anchor bolts.
Install the unit so that the angle of inclination must be less than 3 degrees.
(2) Installation sketch of outdoor unit
unit: mm 810 Power Wiring Terminal
Power Wiring
Distribution Hole
680
HBU-18CA03T3
580
315
288
35
Installation Procedure Outdoor unit
HBU-24CA03T3
860
Power Wiring
Terminal
630
Power Wiring
Distribution
308
335
730 Hole
HBU-36CA03T3
1008 Power Wiring Terminal
Power Wiring
Distribution Hole
447
410
830
580
1250
380
340
25
36
Installation Procedure Outdoor unit
2.When indoor unit is installed below outdoor unit,connecting pipe is installed as below figure.
(an oil return bending mut be set for gas pipe)
Outdoor unit
Requiments of setting oil return bending:
Set an oil returen bending every10m hight gap,if height
Liquid pipe gap is less than 20m set an oil return between at the
midle position of the height gap.Detailed requiments
of setting oil return bending is as follows:
31.8 60 90
L
38.1 60 100
R
3.When indoor unit is installe above the outdoor unit, indoor unit
installation of connecting pipe is as follows.
(an bending mut be set for gas pipe)
Note:
Please strictly act according to
this installation requirement
37
Installation Procedure Outdoor unit
5. Refrigerant piping
(1) Piping diagram Flare connection Stop valve
Gas pipe
Indoor Outdoor
unit unit
(3) Limitations for one way piping length and vertical height difference.
One way piping Vertical height difference
Model length (between indoor and outdoor)
HBU-18CA03T3 HBU-24CA03T3 less than 20 m less than 10 m
38
Installation Procedure Outdoor unit
Completely tightened
Manhole
Flare part
Indoor units
Outdoor units Nitrogen tank
2-way or 3-way valve totally closed
(Liquid side)
Cylinder
Line pressure gauge pressure
gauge
First step: 0.3MPa (3.0kg/cm2g)
pressurize over 3 minutes. Tubing bring brazed
Second step: 1.5Mpa (15kg/cm2g)
pressurize over 3 minutes. Large
leakage will be found.
Sweat joint
Third step: 3.0 MPa (30kg/cm2g)
pressurize about 24 hours. Little Large slip-on
leakage will be found. connector
Service house
Check if the pressure drops Cylinder of nitrogen
The pressure does not drop-passed.
The pressure drops-check the leaking point.
From pressurizing to 24 hours later, each 1 difference of ambient temperature will make
0.01MPa (0.1kg/cm2g) pressure change. It shall be corrected during test.
Checking the leaking point
In the first to third test steps, if the pressure drops, check the leakage in each joint use
sense of hearing, feeling and soap water, etc. methods to find the leaking point.
After confirming the leaking point, welding it again or tighten the nut tightly again.
39
Installation Procedure Outdoor unit
Indoor units
Outdoor units
2-wayor 3-way valve totally closed
(Liquid side)
It shall use the vacuum pump of (lower than -755mmHg)high vacuum degree and large air
discharging (over 40l/min).
The vacuumizing time depends on the length of the connecting pipe, generally is 1~2 hours.
When vacuumizing, it shall be confirmed both gas and liquid side valves are closed.
If after 2 hours vacuumizing, it cannot reach the vacuum degree below -755mmHg, it can be
vacuumized for other 1 hour.
If after 3 hours vacuumizing, it still cannot reach the vacuum degree below -755mmHg, check
if there is any leaking point and repair the them.
If after over 2 hours vacuumizing, the vacuum degree is below -755mmHg, close the VL and
VH on the meter separator and stop vacuumizing. 1 hour later to confirm if the vacuum degree
changes. If changes, it indicates there is leaking point in the system. Check the leaking point
and repair.
After finishing the above vacuumizing, change the vacuum pump into refrigerant pump to charge
the refrigerant.
40
Installation Procedure Electric wiring
5. Electric wiring
WARNING
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE
MAKING ANY ELECTRIC CONNECTIONS.
GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING
LINE VOLTAGE CONNECTIONS.
(1) Selection of size of power supply and interconnecting wires.
Precautions for Electric wiring
Electric wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type
crimped terminal lugs with insulated grip on the ends of the wires.
Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20m length
wires with less than 2% voltage drop.)
HBU-24CA03T3
HBU-36CA03T3 2 20 20 4.0mm2 20 30mA
HBU-42CA03T3
HBU-50CA03T3 3 30 30 4.0mm2 30 30mA
HBU-60CA03T3
41
Installation Procedure Outdoor unit
6. Test run
CAUTION
THIS UNIT WILL BE STARTED INSTANTLY WITHOUT "ON" OPERATION WHEN
ELECTRIC POWER IS SUPPLIED.BE SURE TO EXECUTE "OFF" OPERATION BEFORE
ELECTRIC POWER IS DISCONNECTED FOR SERVICING.
This unit has a function of automatic restart system after recovering power stoppage.
42