Compiled from Electrical4u, My Tech Info, ETechnoG website
By Ir. Tan Yoke Lee MIEM, Mi-FIRE E yokeleetan71@gmail.com SOLID GROUNDING Solid grounding is used when system voltage on the secondary side is less than 1kV or more than 15kV. It is suitable to be used in system with high impedance.
The neutral point of the system is directly connected to the
ground system using large conductors with negligible resistance and thus is held at constant ground voltage at all conditions during normal and fault.
During fault, the faulty phase voltage goes to zero while the remaining phase voltages remain.
The heavy fault current IF nullifies the effect of the
capacitive current IR + IY AT THE FAULT LOCATION and thus prevents ground arching and overvoltage.
However, solid grounding allows large fault current to flow
through and can burn the contact of circuit breakers. SIZING NEUTRAL GROUNDING RESISTOR
• The Short form of NGR is Neutral Grounding
Resistor. • NGRs are used in an electrical power system to protect the star connected alternator/generator or the transformer. • NGR is constructed by inserting a resistor between the star connected neutral terminal and ground terminal. • NGR is used to limit the fault current in a generator or a transformer during earth faults. This is normally used when the voltage of the generator set or secondary voltage of transformer is of magnitude 3.3/6.6/11/ 15kV. • It becomes quite expensive to implement beyond 15kV as the resistor becomes more expensive. SIZING NEUTRAL GROUNDING RESISTOR
• The fault current is normally limited to be between
200Amps to 400Amps as earth fault relay can detect from 5% up to 20% of fault current.
• The Resistor is generally rated for 10 seconds with a
maximum temperature rise of 760 °C.
• Resistor = Vphase/ Ifault, where Vphase is voltage
between phase and neutral.
• For 11kV system, resistor = 11 x 1000/ (1.73x 400)