SECTION 230513
COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including Conditions of
Contract and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes basic requirements for factory-installed and field-
installed motors.
1.3 SUBMITTALS
A. Product Data: Show nameplate data and ratings; characteristics; mounting
arrangements; size and location of winding termination lugs, conduit entry,
and grounding lug; and coatings.
B. Factory Test Reports: For specified tests.
C. Field Test Reports: Indicate and interpret test results for compliance with
performance requirements.
1.4 QUALITY ASSURANCE
A. Comply with related electrical Standards, referred to in Division 26.
PART 2 - PRODUCTS
2.1 BASIC MOTOR REQUIREMENTS
A. Basic requirements apply to mechanical equipment motors, unless otherwise
indicated.
B. Motors shall be of the energy efficient design.
C. Motors 0.37 kW (1/2 HP) and larger: Three phase.
D. Motors smaller than 0.37 (1/2 HP): Single phase.
E. Frequency Rating: 60 Hz, unless otherwise indicated.
F. Voltage Rating: Determined by voltage of circuit to which motor is
connected.
G. Service Factor: According to IEC 60034 and 60072, unless otherwise
indicated.
H. Capacity and Torque Characteristics: Rated for continuous duty and
sufficient to start, accelerate, and operate connected loads at designated
speeds, in indicated environment, with indicated operating sequence, and
without exceeding nameplate ratings or considering service factor.
Project: MBG Multi Purpose Building
Location: New Capital, Egypt
Rev: 0
PART 3 - EXECUTION
3.1 ADJUSTING
A. Use adjustable motor mounting bases for belt-driven motors.
B. Align pulleys and install belts.
C. Tension according to manufacturer's written instructions.
D. Install power feeders to motors in raceways. Locate raceways close to motor
terminal box and use liquid tight flex for final connection to motor terminal
box.
E. Motors located in classified areas shall be installed in accordance with IEC
recommendations for “Hazardous (classified) Locations”.
3.2 COMMISSIONING
A. Check operating motors for unusual conditions during normal operation.
Coordinate with the commissioning of the equipment for which the motor is
a part.
B. Take measurements and prepare a log of voltage, current, frequency, and
power.
C. Report unusual conditions.
D. Report current deficiencies of field-installed units.