GE

Grid Solutions

Kelman™ DGA 900 family


Modbus I/O Registers

Transformer Oil
Dissolved Gas and Moisture Monitor

GEDE-GA_M-DLIS-TE.CG-062 Rev 3.0 18-Dec-20


Contents
1 Introduction ................................................................................................ 3
2 DGA 900 family Modbus Registers .............................................................. 3
3 DGA 900 family Modbus Enumeration ...................................................... 56
Contact & Copyright Details ............................................................................ 58

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 2 of 58
1 INTRODUCTION
This document provides a reference to the DGA 900 family Modbus input / output (I/O)
registers. It is intended to aid system programmers who may need to reference the DGA
900 family Modbus I/O registers to integrate with a DGA 900 family product.

2 DGA 900 FAMILY MODBUS REGISTERS


Table 2-1 is a colour-coded legend for the DGA 900 family Modbus registers. The
firmware deployed depends on the product and its configuration. To identify the relevant
registers, use the colour coding as outlined in Table 2-1 to reference the correct sections
of Table 2-2.
Table 2-1: Legend for DGA 900 family Modbus registers
Colour code Product Configuration Firmware Version
Green DGA 900 (standard) 1.34.4
Orange DGA 900 Plus (Models) 4.17.0
Blue DGA 900 Plus (BMT) 4.17.0

Table 2-2 lists the DGA 900 family Modbus registers.


Note: The following registers are Input Registers and are Read-only. FLOAT32
registers are in the IEEE-754 format.
Table 2-2: DGA 900 family Modbus registers
Data Point
Address Alias Description
Format Type
1 - if door Caution indicator is Discrete
1000 caution_ind_of BOOL
ON, otherwise 0 Input
1 - if door Alarm indicator is ON, Discrete
1001 alarm_ind_of BOOL
otherwise 0 Input
1 - if door Service indicator is ON, Discrete
1002 service_ind_of BOOL
otherwise 0 Input
Discrete
1003 relay1_of 1 - if Relay 1 is ON, otherwise 0 BOOL
Input
Discrete
1004 relay2_of 1 - if Relay 2 is ON, otherwise 0 BOOL
Input
Discrete
1005 relay3_of 1 - if Relay 3 is ON, otherwise 0 BOOL
Input
Discrete
1006 relay4_of 1 - if Relay 4 is ON, otherwise 0 BOOL
Input
Discrete
1007 relay5_of 1 - if Relay 5 is ON, otherwise 0 BOOL
Input
Discrete
1008 relay6_of 1 - if Relay 6 is ON, otherwise 0 BOOL
Input
1 - if Relay 7 is ON, otherwise 0
Discrete
1009 relay7_of (Relay 7 repearts Service BOOL
Input
indicator)

1 if high_high alarm for gas


Discrete
1010 source_1__h2__high_high__alarm source_1__h2 is active, otherwise BOOL
Input
0

1 if high alarm for gas


Discrete
1011 source_1__h2__high__alarm source_1__h2 is active, otherwise BOOL
Input
0

1 if high_high alarm for gas


Discrete
1012 source_1__co2__high_high__alarm source_1__co2 is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1013 source_1__co2__high__alarm source_1__co2 is active, BOOL
Input
otherwise 0

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 3 of 58
Data Point
Address Alias Description
Format Type
1 if high_high alarm for gas
Discrete
1014 source_1__co__high_high__alarm source_1__co is active, otherwise BOOL
Input
0

1 if high alarm for gas


Discrete
1015 source_1__co__high__alarm source_1__co is active, otherwise BOOL
Input
0

1 if high_high alarm for gas


Discrete
1016 source_1__c2h4__high_high__alarm source_1__c2h4 is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1017 source_1__c2h4__high__alarm source_1__c2h4 is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1018 source_1__c2h6__high_high__alarm source_1__c2h6 is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1019 source_1__c2h6__high__alarm source_1__c2h6 is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1020 source_1__ch4__high_high__alarm source_1__ch4 is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1021 source_1__ch4__high__alarm source_1__ch4 is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1022 source_1__c2h2__high_high__alarm source_1__c2h2 is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1023 source_1__c2h2__high__alarm source_1__c2h2 is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1024 source_1__h2o__high_high__alarm source_1__h2o is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1025 source_1__h2o__high__alarm source_1__h2o is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1026 source_1__o2__high_high__alarm source_1__o2 is active, otherwise BOOL
Input
0

1 if high alarm for gas


Discrete
1027 source_1__o2__high__alarm source_1__o2 is active, otherwise BOOL
Input
0

1 if high_high alarm for gas


Discrete
1028 source_1__tdcg__high_high__alarm source_1__tdcg is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1029 source_1__tdcg__high__alarm source_1__tdcg is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1030 source_1__n2__high_high__alarm source_1__n2 is active, otherwise BOOL
Input
0

1 if high alarm for gas


Discrete
1031 source_1__n2__high__alarm source_1__n2 is active, otherwise BOOL
Input
0

1 if high_high alarm for gas


Discrete
1032 source_1__h2__roc__high_high__alarm source_1__h2__roc is active, BOOL
Input
otherwise 0

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 4 of 58
Data Point
Address Alias Description
Format Type
1 if high alarm for gas
Discrete
1033 source_1__h2__roc__high__alarm source_1__h2__roc is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1034 source_1__co2__roc__high_high__alarm source_1__co2__roc is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1035 source_1__co2__roc__high__alarm source_1__co2__roc is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1036 source_1__co__roc__high_high__alarm source_1__co__roc is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1037 source_1__co__roc__high__alarm source_1__co__roc is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1038 source_1__c2h4__roc__high_high__alarm source_1__c2h4__roc is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1039 source_1__c2h4__roc__high__alarm source_1__c2h4__roc is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1040 source_1__c2h6__roc__high_high__alarm source_1__c2h6__roc is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1041 source_1__c2h6__roc__high__alarm source_1__c2h6__roc is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1042 source_1__ch4__roc__high_high__alarm source_1__ch4__roc is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1043 source_1__ch4__roc__high__alarm source_1__ch4__roc is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1044 source_1__c2h2__roc__high_high__alarm source_1__c2h2__roc is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1045 source_1__c2h2__roc__high__alarm source_1__c2h2__roc is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1046 source_1__h2o__roc__high_high__alarm source_1__h2o__roc is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1047 source_1__h2o__roc__high__alarm source_1__h2o__roc is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1048 source_1__o2__roc__high_high__alarm source_1__o2__roc is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1049 source_1__o2__roc__high__alarm source_1__o2__roc is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1050 source_1__tdcg__roc__high_high__alarm source_1__tdcg__roc is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1051 source_1__tdcg__roc__high__alarm source_1__tdcg__roc is active, BOOL
Input
otherwise 0

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 5 of 58
Data Point
Address Alias Description
Format Type
1 if high_high alarm for gas
Discrete
1052 source_1__n2__roc__high_high__alarm source_1__n2__roc is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1053 source_1__n2__roc__high__alarm source_1__n2__roc is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


source_1__relative_saturation__high_hig Discrete
1054 source_1__relative_saturation is BOOL
h__alarm Input
active, otherwise 0

1 if high alarm for gas


source_1__relative_saturation__high__ala Discrete
1055 source_1__relative_saturation is BOOL
rm Input
active, otherwise 0

1 if high_high alarm for gas


Discrete
1056 source_1__ratio_1__high_high__alarm source_1__ratio_1 is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1057 source_1__ratio_1__high__alarm source_1__ratio_1 is active, BOOL
Input
otherwise 0

1 if low alarm for gas


Discrete
1058 source_1__ratio_1__low__alarm source_1__ratio_1 is active, BOOL
Input
otherwise 0

1 if low_low alarm for gas


Discrete
1059 source_1__ratio_1__low_low__alarm source_1__ratio_1 is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1060 source_1__ratio_2__high_high__alarm source_1__ratio_2 is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1061 source_1__ratio_2__high__alarm source_1__ratio_2 is active, BOOL
Input
otherwise 0

1 if low alarm for gas


Discrete
1062 source_1__ratio_2__low__alarm source_1__ratio_2 is active, BOOL
Input
otherwise 0

1 if low_low alarm for gas


Discrete
1063 source_1__ratio_2__low_low__alarm source_1__ratio_2 is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1064 source_1__ratio_3__high_high__alarm source_1__ratio_3 is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1065 source_1__ratio_3__high__alarm source_1__ratio_3 is active, BOOL
Input
otherwise 0

1 if low alarm for gas


Discrete
1066 source_1__ratio_3__low__alarm source_1__ratio_3 is active, BOOL
Input
otherwise 0

1 if low_low alarm for gas


Discrete
1067 source_1__ratio_3__low_low__alarm source_1__ratio_3 is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1068 source_1__ratio_4__high_high__alarm source_1__ratio_4 is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1069 source_1__ratio_4__high__alarm source_1__ratio_4 is active, BOOL
Input
otherwise 0

1 if low alarm for gas


Discrete
1070 source_1__ratio_4__low__alarm source_1__ratio_4 is active, BOOL
Input
otherwise 0

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 6 of 58
Data Point
Address Alias Description
Format Type
1 if low_low alarm for gas
Discrete
1071 source_1__ratio_4__low_low__alarm source_1__ratio_4 is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1072 source_1__ratio_5__high_high__alarm source_1__ratio_5 is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1073 source_1__ratio_5__high__alarm source_1__ratio_5 is active, BOOL
Input
otherwise 0

1 if low alarm for gas


Discrete
1074 source_1__ratio_5__low__alarm source_1__ratio_5 is active, BOOL
Input
otherwise 0

1 if low_low alarm for gas


Discrete
1075 source_1__ratio_5__low_low__alarm source_1__ratio_5 is active, BOOL
Input
otherwise 0
source_1__rcdcm__roc__high_high__alar 1 if high_high alarm for gas Discrete
1076 BOOL
m source_1__rcdcm__roc is active. Input
1 if high alarm for gas Discrete
1077 source_1__rcdcm__roc__high__alarm BOOL
source_1__rcdcm__roc is active. Input
1 if low alarm for gas Discrete
1078 source_1__rcdcm__roc__low__alarm BOOL
source_1__rcdcm__roc is active. Input
1 if low_low alarm for gas Discrete
1079 source_1__rcdcm__roc__low_low__alarm BOOL
source_1__rcdcm__roc is active. Input
1 if high_high alarm for gas
Discrete
1080 source_1__ratio_6__high_high__alarm source_1__ratio_6 is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1081 source_1__ratio_6__high__alarm source_1__ratio_6 is active, BOOL
Input
otherwise 0

1 if low alarm for gas


Discrete
1082 source_1__ratio_6__low__alarm source_1__ratio_6 is active, BOOL
Input
otherwise 0

1 if low_low alarm for gas


Discrete
1083 source_1__ratio_6__low_low__alarm source_1__ratio_6 is active, BOOL
Input
otherwise 0

1 if high_high alarm for gas


Discrete
1084 source_1__ratio_7__high_high__alarm source_1__ratio_7 is active, BOOL
Input
otherwise 0

1 if high alarm for gas


Discrete
1085 source_1__ratio_7__high__alarm source_1__ratio_7 is active, BOOL
Input
otherwise 0

1 if low alarm for gas


Discrete
1086 source_1__ratio_7__low__alarm source_1__ratio_7 is active, BOOL
Input
otherwise 0

1 if low_low alarm for gas


Discrete
1087 source_1__ratio_7__low_low__alarm source_1__ratio_7 is active, BOOL
Input
otherwise 0
1 if high_high alarm for ain_1 is Discrete
3000 ain_1__high_high__alarm BOOL
active, otherwise 0 Input
1 if high alarm for ain_1 is active, Discrete
3001 ain_1__high__alarm BOOL
otherwise 0 Input
1 if low alarm for ain_1 is active, Discrete
3002 ain_1__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_1 is Discrete
3003 ain_1__low_low__alarm BOOL
active, otherwise 0 Input
1 if high_high alarm for ain_2 is Discrete
3004 ain_2__high_high__alarm BOOL
active, otherwise 0 Input

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 7 of 58
Data Point
Address Alias Description
Format Type
1 if high alarm for ain_2 is active, Discrete
3005 ain_2__high__alarm BOOL
otherwise 0 Input
1 if low alarm for ain_2 is active, Discrete
3006 ain_2__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_2 is Discrete
3007 ain_2__low_low__alarm BOOL
active, otherwise 0 Input
1 if high_high alarm for ain_3 is Discrete
3008 ain_3__high_high__alarm BOOL
active, otherwise 0 Input
1 if high alarm for ain_3 is active, Discrete
3009 ain_3__high__alarm BOOL
otherwise 0 Input
1 if low alarm for ain_3 is active, Discrete
3010 ain_3__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_3 is Discrete
3011 ain_3__low_low__alarm BOOL
active, otherwise 0 Input
1 if high_high alarm for ain_4 is Discrete
3012 ain_4__high_high__alarm BOOL
active, otherwise 0 Input
1 if high alarm for ain_4 is active, Discrete
3013 ain_4__high__alarm BOOL
otherwise 0 Input
1 if low alarm for ain_4 is active, Discrete
3014 ain_4__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_4 is Discrete
3015 ain_4__low_low__alarm BOOL
active, otherwise 0 Input
1 if high_high alarm for ain_5 is Discrete
3016 ain_5__high_high__alarm BOOL
active, otherwise 0 Input
1 if high alarm for ain_5 is active, Discrete
3017 ain_5__high__alarm BOOL
otherwise 0 Input
1 if low alarm for ain_5 is active, Discrete
3018 ain_5__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_5 is Discrete
3019 ain_5__low_low__alarm BOOL
active, otherwise 0 Input
1 if high_high alarm for ain_6 is Discrete
3020 ain_6__high_high__alarm BOOL
active, otherwise 0 Input
1 if high alarm for ain_6 is active, Discrete
3021 ain_6__high__alarm BOOL
otherwise 0 Input
1 if low alarm for ain_6 is active, Discrete
3022 ain_6__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_6 is Discrete
3023 ain_6__low_low__alarm BOOL
active, otherwise 0 Input
1 if high_high alarm for
din_1__transition_total__high_high__alar Discrete
3024 din_1__transition_total is active, BOOL
m Input
otherwise 0

1 if high alarm for


Discrete
3025 din_1__transition_total__high__alarm din_1__transition_total is active, BOOL
Input
otherwise 0

1 if high_high alarm for


din_2__transition_total__high_high__alar Discrete
3026 din_2__transition_total is active, BOOL
m Input
otherwise 0

1 if high alarm for


Discrete
3027 din_2__transition_total__high__alarm din_2__transition_total is active, BOOL
Input
otherwise 0

1 if high_high alarm for


din_3__transition_total__high_high__alar Discrete
3028 din_3__transition_total is active, BOOL
m Input
otherwise 0

1 if high alarm for


Discrete
3029 din_3__transition_total__high__alarm din_3__transition_total is active, BOOL
Input
otherwise 0
Discrete
3030 din_1__alarm 1 if alarm for din_1 is active. BOOL
Input

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 8 of 58
Data Point
Address Alias Description
Format Type
Discrete
3031 din_2__alarm 1 if alarm for din_2 is active. BOOL
Input
Discrete
3032 din_3__alarm 1 if alarm for din_3 is active. BOOL
Input
1 if high_high alarm for
din_4__transition_total__high_high__alar Discrete
3033 din_4__transition_total is active, BOOL
m Input
otherwise 0

1 if high alarm for


Discrete
3034 din_4__transition_total__high__alarm din_4__transition_total is active, BOOL
Input
otherwise 0

1 if high_high alarm for


din_5__transition_total__high_high__alar Discrete
3035 din_5__transition_total is active, BOOL
m Input
otherwise 0

1 if high alarm for


Discrete
3036 din_5__transition_total__high__alarm din_5__transition_total is active, BOOL
Input
otherwise 0

1 if high_high alarm for


din_6__transition_total__high_high__alar Discrete
3037 din_6__transition_total is active, BOOL
m Input
otherwise 0

1 if high alarm for


Discrete
3038 din_6__transition_total__high__alarm din_6__transition_total is active, BOOL
Input
otherwise 0

1 if high_high alarm for


din_7__transition_total__high_high__alar Discrete
3039 din_7__transition_total is active, BOOL
m Input
otherwise 0

1 if high alarm for


Discrete
3040 din_7__transition_total__high__alarm din_7__transition_total is active, BOOL
Input
otherwise 0

1 if high_high alarm for


din_8__transition_total__high_high__alar Discrete
3041 din_8__transition_total is active, BOOL
m Input
otherwise 0

1 if high alarm for


Discrete
3042 din_8__transition_total__high__alarm din_8__transition_total is active, BOOL
Input
otherwise 0

1 if high_high alarm for


din_9__transition_total__high_high__alar Discrete
3043 din_9__transition_total is active, BOOL
m Input
otherwise 0

1 if high alarm for


Discrete
3044 din_9__transition_total__high__alarm din_9__transition_total is active, BOOL
Input
otherwise 0
Discrete
3045 din_4__alarm 1 if alarm for din_4 is active. BOOL
Input
Discrete
3046 din_5__alarm 1 if alarm for din_5 is active. BOOL
Input
Discrete
3047 din_6__alarm 1 if alarm for din_6 is active. BOOL
Input
Discrete
3048 din_7__alarm 1 if alarm for din_7 is active. BOOL
Input
Discrete
3049 din_8__alarm 1 if alarm for din_8 is active. BOOL
Input
Discrete
3050 din_9__alarm 1 if alarm for din_9 is active. BOOL
Input
1 if high_high alarm for ain_1 is Discrete
3100 ain_7__high_high__alarm BOOL
active, otherwise 0 Input
1 if high alarm for ain_1 is active, Discrete
3101 ain_7__high__alarm BOOL
otherwise 0 Input
1 if low alarm for ain_1 is active, Discrete
3102 ain_7__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_1 is Discrete
3103 ain_7__low_low__alarm BOOL
active, otherwise 0 Input

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 9 of 58
Data Point
Address Alias Description
Format Type
1 if high_high alarm for ain_8 is Discrete
3104 ain_8__high_high__alarm BOOL
active, otherwise 0 Input
1 if high alarm for ain_8 is active, Discrete
3105 ain_8__high__alarm BOOL
otherwise 0 Input
1 if low alarm for ain_8 is active, Discrete
3106 ain_8__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_8 is Discrete
3107 ain_8__low_low__alarm BOOL
active, otherwise 0 Input
1 if high_high alarm for ain_9 is Discrete
3108 ain_9__high_high__alarm BOOL
active, otherwise 0 Input
1 if high alarm for ain_9 is active, Discrete
3109 ain_9__high__alarm BOOL
otherwise 0 Input
1 if low alarm for ain_9 is active, Discrete
3110 ain_9__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_9 is Discrete
3111 ain_9__low_low__alarm BOOL
active, otherwise 0 Input
1 if high_high alarm for ain_10 is Discrete
3112 ain_10__high_high__alarm BOOL
active, otherwise 0 Input
1 if high alarm for ain_10 is Discrete
3113 ain_10__high__alarm BOOL
active, otherwise 0 Input
1 if low alarm for ain_10 is active, Discrete
3114 ain_10__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_10 is Discrete
3115 ain_10__low_low__alarm BOOL
active, otherwise 0 Input
1 if high_high alarm for ain_11 is Discrete
3116 ain_11__high_high__alarm BOOL
active, otherwise 0 Input
1 if high alarm for ain_11 is Discrete
3117 ain_11__high__alarm BOOL
active, otherwise 0 Input
1 if low alarm for ain_11 is active, Discrete
3118 ain_11__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_11 is Discrete
3119 ain_11__low_low__alarm BOOL
active, otherwise 0 Input
1 if high_high alarm for ain_12 is Discrete
3120 ain_12__high_high__alarm BOOL
active, otherwise 0 Input
1 if high alarm for ain_12 is Discrete
3121 ain_12__high__alarm BOOL
active, otherwise 0 Input
1 if low alarm for ain_12 is active, Discrete
3122 ain_12__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_12 is Discrete
3123 ain_12__low_low__alarm BOOL
active, otherwise 0 Input
1 if high_high alarm for ain_13 is Discrete
3124 ain_13__high_high__alarm BOOL
active, otherwise 0 Input
1 if high alarm for ain_13 is Discrete
3125 ain_13__high__alarm BOOL
active, otherwise 0 Input
1 if low alarm for ain_13 is active, Discrete
3126 ain_13__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_13 is Discrete
3127 ain_13__low_low__alarm BOOL
active, otherwise 0 Input
1 if high_high alarm for ain_14 is Discrete
3128 ain_14__high_high__alarm BOOL
active, otherwise 0 Input
1 if high alarm for ain_14 is Discrete
3129 ain_14__high__alarm BOOL
active, otherwise 0 Input
1 if low alarm for ain_14 is active, Discrete
3130 ain_14__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_14 is Discrete
3131 ain_14__low_low__alarm BOOL
active, otherwise 0 Input

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 10 of 58
Data Point
Address Alias Description
Format Type
1 if high_high alarm for ain_15 is Discrete
3132 ain_15__high_high__alarm BOOL
active, otherwise 0 Input
1 if high alarm for ain_15 is Discrete
3133 ain_15__high__alarm BOOL
active, otherwise 0 Input
1 if low alarm for ain_15 is active, Discrete
3134 ain_15__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_15 is Discrete
3135 ain_15__low_low__alarm BOOL
active, otherwise 0 Input
1 if high_high alarm for ain_16 is Discrete
3136 ain_16__high_high__alarm BOOL
active, otherwise 0 Input
1 if high alarm for ain_16 is Discrete
3137 ain_16__high__alarm BOOL
active, otherwise 0 Input
1 if low alarm for ain_16 is active, Discrete
3138 ain_16__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_16 is Discrete
3139 ain_16__low_low__alarm BOOL
active, otherwise 0 Input
1 if high_high alarm for ain_17 is Discrete
3140 ain_17__high_high__alarm BOOL
active, otherwise 0 Input
1 if high alarm for ain_17 is Discrete
3141 ain_17__high__alarm BOOL
active, otherwise 0 Input
1 if low alarm for ain_17 is active, Discrete
3142 ain_17__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_17 is Discrete
3143 ain_17__low_low__alarm BOOL
active, otherwise 0 Input
1 if high_high alarm for ain_18 is Discrete
3144 ain_18__high_high__alarm BOOL
active, otherwise 0 Input
1 if high alarm for ain_18 is Discrete
3145 ain_18__high__alarm BOOL
active, otherwise 0 Input
1 if low alarm for ain_18 is active, Discrete
3146 ain_18__low__alarm BOOL
otherwise 0 Input
1 if low_low alarm for ain_18 is Discrete
3147 ain_18__low_low__alarm BOOL
active, otherwise 0 Input
1 if high_high alarm for
Discrete
4000 to_temperature_1__high_high__alarm to_temperature_1 is active, BOOL
Input
otherwise 0

1 if high alarm for


Discrete
4001 to_temperature_1__high__alarm to_temperature_1 is active, BOOL
Input
otherwise 0

1 if high_high alarm for


Discrete
4002 to_temperature_2__high_high__alarm to_temperature_2 is active, BOOL
Input
otherwise 0

1 if high alarm for


Discrete
4003 to_temperature_2__high__alarm to_temperature_2 is active, BOOL
Input
otherwise 0

1 if high_high alarm for


Discrete
4004 to_temperature_3__high_high__alarm to_temperature_3 is active, BOOL
Input
otherwise 0

1 if high alarm for


Discrete
4005 to_temperature_3__high__alarm to_temperature_3 is active, BOOL
Input
otherwise 0

1 if high_high alarm for


Discrete
4006 to_temperature_4__high_high__alarm to_temperature_4 is active, BOOL
Input
otherwise 0

1 if high alarm for


Discrete
4007 to_temperature_4__high__alarm to_temperature_4 is active, BOOL
Input
otherwise 0

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 11 of 58
Data Point
Address Alias Description
Format Type
1 if high_high alarm for
Discrete
4008 to_temperature_5__high_high__alarm to_temperature_5 is active, BOOL
Input
otherwise 0

1 if high alarm for


Discrete
4009 to_temperature_5__high__alarm to_temperature_5 is active, BOOL
Input
otherwise 0

1 if high_high alarm for


Discrete
4010 to_temperature_6__high_high__alarm to_temperature_6 is active, BOOL
Input
otherwise 0

1 if high alarm for


Discrete
4011 to_temperature_6__high__alarm to_temperature_6 is active, BOOL
Input
otherwise 0

1 if high_high alarm for


Discrete
4012 to_temperature_7__high_high__alarm to_temperature_7 is active, BOOL
Input
otherwise 0

1 if high alarm for


Discrete
4013 to_temperature_7__high__alarm to_temperature_7 is active, BOOL
Input
otherwise 0

1 if high_high alarm for


Discrete
4014 to_temperature_8__high_high__alarm to_temperature_8 is active, BOOL
Input
otherwise 0

1 if high alarm for


Discrete
4015 to_temperature_8__high__alarm to_temperature_8 is active, BOOL
Input
otherwise 0

1 if high_high alarm for


to_temperature_1__roc__high_high__alar Discrete
5000 to_temperature_1__roc is active, BOOL
m Input
otherwise 0

1 if high alarm for


Discrete
5001 to_temperature_1__roc__high__alarm to_temperature_1__roc is active, BOOL
Input
otherwise 0

1 if high_high alarm for


to_temperature_2__roc__high_high__alar Discrete
5002 to_temperature_2__roc is active, BOOL
m Input
otherwise 0

1 if high alarm for


Discrete
5003 to_temperature_2__roc__high__alarm to_temperature_2__roc is active, BOOL
Input
otherwise 0

1 if high_high alarm for


to_temperature_3__roc__high_high__alar Discrete
5004 to_temperature_3__roc is active, BOOL
m Input
otherwise 0

1 if high alarm for


Discrete
5005 to_temperature_3__roc__high__alarm to_temperature_3__roc is active, BOOL
Input
otherwise 0

1 if high_high alarm for


to_temperature_4__roc__high_high__alar Discrete
5006 to_temperature_4__roc is active, BOOL
m Input
otherwise 0

1 if high alarm for


Discrete
5007 to_temperature_4__roc__high__alarm to_temperature_4__roc is active, BOOL
Input
otherwise 0

1 if high_high alarm for


to_temperature_5__roc__high_high__alar Discrete
5008 to_temperature_5__roc is active, BOOL
m Input
otherwise 0

1 if high alarm for


Discrete
5009 to_temperature_5__roc__high__alarm to_temperature_5__roc is active, BOOL
Input
otherwise 0

1 if high_high alarm for


to_temperature_6__roc__high_high__alar Discrete
5010 to_temperature_6__roc is active, BOOL
m Input
otherwise 0

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 12 of 58
Data Point
Address Alias Description
Format Type
1 if high alarm for
Discrete
5011 to_temperature_6__roc__high__alarm to_temperature_6__roc is active, BOOL
Input
otherwise 0

1 if high_high alarm for


to_temperature_7__roc__high_high__alar Discrete
5012 to_temperature_7__roc is active, BOOL
m Input
otherwise 0

1 if high alarm for


Discrete
5013 to_temperature_7__roc__high__alarm to_temperature_7__roc is active, BOOL
Input
otherwise 0

1 if high_high alarm for


to_temperature_8__roc__high_high__alar Discrete
5014 to_temperature_8__roc is active, BOOL
m Input
otherwise 0

1 if high alarm for


Discrete
5015 to_temperature_8__roc__high__alarm to_temperature_8__roc is active, BOOL
Input
otherwise 0
Discrete
6000 din_1 1 if DIN1 is ON,, otherwise 0 BOOL
Input
Discrete
6001 din_2 1 if DIN2 is ON,, otherwise 0 BOOL
Input
Discrete
6002 din_3 1 if DIN3 is ON,, otherwise 0 BOOL
Input
Discrete
6003 din_4 1 if DIN4 is ON,, otherwise 0 BOOL
Input
Discrete
6004 din_5 1 if DIN5 is ON,, otherwise 0 BOOL
Input
Discrete
6005 din_6 1 if DIN6 is ON,, otherwise 0 BOOL
Input
Discrete
6006 din_7 1 if DIN7 is ON,, otherwise 0 BOOL
Input
Discrete
6007 din_8 1 if DIN8 is ON,, otherwise 0 BOOL
Input
Discrete
6008 din_9 1 if DIN9 is ON,, otherwise 0 BOOL
Input
BMT measured power frequency
Discrete
7000 bd_1_frequency_warning deviation exceeds the specified BOOL
Input
limit
'no signal' detected on the BMT Discrete
7001 bd_1_no_signal_lf_ch1 BOOL
LF channel 1 Input
'no signal' detected on the BMT Discrete
7002 bd_1_no_signal_lf_ch2 BOOL
LF channel 2 Input
'no signal' detected on the BMT Discrete
7003 bd_1_no_signal_lf_ch3 BOOL
LF channel 3 Input
'no signal' detected on the BMT Discrete
7004 bd_1_no_signal_lf_ch4 BOOL
LF channel 4 Input
'no signal' detected on the BMT Discrete
7005 bd_1_no_signal_lf_ch5 BOOL
LF channel 5 Input
'no signal' detected on the BMT Discrete
7006 bd_1_no_signal_lf_ch6 BOOL
LF channel 6 Input
'low bushing current' detected on Discrete
7007 bd_1_low_bushing_current_ch1 BOOL
BMT LF channel 1 Input
'low bushing current' detected on Discrete
7008 bd_1_low_bushing_current_ch2 BOOL
BMT LF channel 2 Input
'low bushing current' detected on Discrete
7009 bd_1_low_bushing_current_ch3 BOOL
BMT LF channel 3 Input
'low bushing current' detected on Discrete
7010 bd_1_low_bushing_current_ch4 BOOL
BMT LF channel 4 Input
'low bushing current' detected on Discrete
7011 bd_1_low_bushing_current_ch5 BOOL
BMT LF channel 5 Input
'low bushing current' detected on Discrete
7012 bd_1_low_bushing_current_ch6 BOOL
BMT LF channel 6 Input
'bushing current saturation'
Discrete
7013 bd_1_bushing_current_saturation_ch1 detected on the BMT LF channel BOOL
Input
1
'bushing current saturation'
Discrete
7014 bd_1_bushing_current_saturation_ch2 detected on the BMT LF channel BOOL
Input
2

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 13 of 58
Data Point
Address Alias Description
Format Type
'bushing current saturation'
Discrete
7015 bd_1_bushing_current_saturation_ch3 detected on the BMT LF channel BOOL
Input
3
'bushing current saturation'
Discrete
7016 bd_1_bushing_current_saturation_ch4 detected on the BMT LF channel BOOL
Input
4
'bushing current saturation'
Discrete
7017 bd_1_bushing_current_saturation_ch5 detected on the BMT LF channel BOOL
Input
5
'bushing current saturation'
Discrete
7018 bd_1_bushing_current_saturation_ch6 detected on the BMT LF channel BOOL
Input
6
'bushing failure' detected on the Discrete
7019 bd_1_bushing_failure_ch1 BOOL
BMT LF channel 1 Input
'bushing failure' detected on the Discrete
7020 bd_1_bushing_failure_ch2 BOOL
BMT LF channel 2 Input
'bushing failure' detected on the Discrete
7021 bd_1_bushing_failure_ch3 BOOL
BMT LF channel 3 Input
'bushing failure' detected on the Discrete
7022 bd_1_bushing_failure_ch4 BOOL
BMT LF channel 4 Input
'bushing failure' detected on the Discrete
7023 bd_1_bushing_failure_ch5 BOOL
BMT LF channel 5 Input
'bushing failure' detected on the Discrete
7024 bd_1_bushing_failure_ch6 BOOL
BMT LF channel 6 Input
'high noise' detected on the BMT Discrete
7025 bd_1_high_hf_noise_ch1 BOOL
HF channel 1 Input
'high noise' detected on the BMT Discrete
7026 bd_1_high_hf_noise_ch2 BOOL
HF channel 2 Input
'high noise' detected on the BMT Discrete
7027 bd_1_high_hf_noise_ch3 BOOL
HF channel 3 Input
'high noise' detected on the BMT Discrete
7028 bd_1_high_hf_noise_ch4 BOOL
HF channel 4 Input
'high noise' detected on the BMT Discrete
7029 bd_1_high_hf_noise_ch5 BOOL
HF channel 5 Input
'high noise' detected on the BMT Discrete
7030 bd_1_high_hf_noise_ch6 BOOL
HF channel 6 Input
'BMT temperature sensor failure'
Discrete
7031 bd_1_temperature_sensor_failure_ch1 detected on LF channel 1 (either BOOL
Input
1-wire or top-oil)
'BMT temperature sensor failure'
Discrete
7032 bd_1_temperature_sensor_failure_ch2 detected on LF channel 2 (either BOOL
Input
1-wire or top-oil)
'BMT temperature sensor failure'
Discrete
7033 bd_1_temperature_sensor_failure_ch3 detected on LF channel 3 (either BOOL
Input
1-wire or top-oil)
'BMT temperature sensor failure'
Discrete
7034 bd_1_temperature_sensor_failure_ch4 detected on LF channel 4 (either BOOL
Input
1-wire or top-oil)
'BMT temperature sensor failure'
Discrete
7035 bd_1_temperature_sensor_failure_ch5 detected on LF channel 5 (either BOOL
Input
1-wire or top-oil)
'BMT temperature sensor failure'
Discrete
7036 bd_1_temperature_sensor_failure_ch6 detected on LF channel 6 (either BOOL
Input
1-wire or top-oil)
'BMT ambient sensor failure' Discrete
7037 bd_1_ambient_sensor_failure BOOL
detected Input
'BMT top oil 1 temperature Discrete
7038 bd_1_top_oil1_failure BOOL
sensor failure' Input
'BMT top oil 2 temperature Discrete
7039 bd_1_top_oil2_failure BOOL
sensor failure' Input
'BMT top oil 3 temperature Discrete
7040 bd_1_top_oil3_failure BOOL
sensor failure' Input
'BMT top oil 4 temperature Discrete
7041 bd_1_top_oil4_failure BOOL
sensor failure' Input
Discrete
7042 bd_1_fpga_failure 'BMT FPGA failure' detected BOOL
Input
Discrete
7043 bd_1_gps_failure 'BMT GPS failure' detected BOOL
Input
Discrete
7044 bd_1_sdcard_failure 'BMT SD-card failure' detected BOOL
Input
Discrete
7045 bd_1_fram_failure 'BMT FRAM failure' detected BOOL
Input

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 14 of 58
Data Point
Address Alias Description
Format Type
Discrete
7046 bd_1_eeprom_failure 'BMT EEPROM failure' detected BOOL
Input
'BMT FPGA temperature' exceeds Discrete
7047 bd_1_high_fpga_temperature BOOL
the specified limit Input
'BMT FPGA power supplier
bd_1_high_fpga_power_supply_temperat Discrete
7048 temperature' exceeds the BOOL
ure Input
specified limit
'BMT MCU temperature' exceeds Discrete
7049 bd_1_high_mcu_temperature BOOL
the specified limit Input
1 if high_high alarm for BMT C1 Discrete
7050 bm_1_c1_ch1__high_high__alarm BOOL
on channel 1 Input
1 if high alarm for BMT C1 on Discrete
7051 bm_1_c1_ch1__high__alarm BOOL
channel 1. Input
1 if low alarm for BMT C1 on Discrete
7052 bm_1_c1_ch1__low__alarm BOOL
channel 1 Input
1 if low_low alarm for BMT C1 on Discrete
7053 bm_1_c1_ch1__low_low__alarm BOOL
channel 1 Input
1 if high_high alarm for BMT C1 Discrete
7054 bm_1_c1_ch2__high_high__alarm BOOL
on channel 2 Input
1 if high alarm for BMT C1 on Discrete
7055 bm_1_c1_ch2__high__alarm BOOL
channel 2 Input
1 if low alarm for BMT C1 on Discrete
7056 bm_1_c1_ch2__low__alarm BOOL
channel 2 Input
1 if low_low alarm for BMT C1 on Discrete
7057 bm_1_c1_ch2__low_low__alarm BOOL
channel 2 Input
1 if high_high alarm for BMT C1 Discrete
7058 bm_1_c1_ch3__high_high__alarm BOOL
on channel 3 Input
1 if high alarm for BMT C1 on Discrete
7059 bm_1_c1_ch3__high__alarm BOOL
channel 3 Input
1 if low alarm for BMT C1 on Discrete
7060 bm_1_c1_ch3__low__alarm BOOL
channel 3 Input
1 if low_low alarm for BMT C1 on Discrete
7061 bm_1_c1_ch3__low_low__alarm BOOL
channel 3 Input
1 if high_high alarm for BMT C1 Discrete
7062 bm_1_c1_ch4__high_high__alarm BOOL
on channel 4 Input
1 if high alarm for BMT C1 on Discrete
7063 bm_1_c1_ch4__high__alarm BOOL
channel 4 Input
1 if low alarm for BMT C1 on Discrete
7064 bm_1_c1_ch4__low__alarm BOOL
channel 4 Input
1 if low_low alarm for BMT C1 on Discrete
7065 bm_1_c1_ch4__low_low__alarm BOOL
channel 4 Input
1 if high_high alarm for BMT C1 Discrete
7066 bm_1_c1_ch5__high_high__alarm BOOL
on channel 5 Input
1 if high alarm for BMT C1 on Discrete
7067 bm_1_c1_ch5__high__alarm BOOL
channel 5 Input
1 if low alarm for BMT C1 on Discrete
7068 bm_1_c1_ch5__low__alarm BOOL
channel 5 Input
1 if low_low alarm for BMT C1 on Discrete
7069 bm_1_c1_ch5__low_low__alarm BOOL
channel 5 Input
1 if high_high alarm for BMT C1 Discrete
7070 bm_1_c1_ch6__high_high__alarm BOOL
on channel 6 Input
1 if high alarm for BMT C1 on Discrete
7071 bm_1_c1_ch6__high__alarm BOOL
channel 6 Input
1 if low alarm for BMT C1 on Discrete
7072 bm_1_c1_ch6__low__alarm BOOL
channel 6 Input
1 if low_low alarm for BMT C1 on Discrete
7073 bm_1_c1_ch6__low_low__alarm BOOL
channel 6 Input
1 if high_high alarm for BMT
bo_1_delta_angle_ch12__high_high__alar Discrete
7074 angle change between channel 1 BOOL
m Input
&2
1 if high alarm for BMT angle Discrete
7075 bo_1_delta_angle_ch12__high__alarm BOOL
change between channel 1 & 2 Input
1 if high_high alarm for BMT
bo_1_delta_angle_ch13__high_high__alar Discrete
7076 angle change between channel 1 BOOL
m Input
&3
1 if high alarm for BMT angle Discrete
7077 bo_1_delta_angle_ch13__high__alarm BOOL
change between channel 1 & 3 Input
1 if high_high alarm for BMT
bo_1_delta_angle_ch45__high_high__alar Discrete
7078 angle change between channel 4 BOOL
m Input
&5

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 15 of 58
Data Point
Address Alias Description
Format Type
1 if high alarm for BMT angle Discrete
7079 bo_1_delta_angle_ch45__high__alarm BOOL
change between channel 4 & 5 Input
1 if high_high alarm for BMT
bo_1_delta_angle_ch46__high_high__alar Discrete
7080 angle change between channel 4 BOOL
m Input
&6
1 if high alarm for BMT angle Discrete
7081 bo_1_delta_angle_ch46__high__alarm BOOL
change between channel 4 & 6 Input
1 if high_high alarm for BMT PD Discrete
7082 bm_1_pd_max_ch1__high_high__alarm BOOL
Max value on channel 1 Input
1 if high alarm for BMT PD Max Discrete
7083 bm_1_pd_max_ch1__high__alarm BOOL
value on channel 1 Input
1 if high_high alarm for BMT PD Discrete
7084 bm_1_pd_max_ch2__high_high__alarm BOOL
Max value on channel 2 Input
1 if high alarm for BMT PD Max Discrete
7085 bm_1_pd_max_ch2__high__alarm BOOL
value on channel 2 Input
1 if high_high alarm for BMT PD Discrete
7086 bm_1_pd_max_ch3__high_high__alarm BOOL
Max value on channel 3 Input
1 if high alarm for BMT PD Max Discrete
7087 bm_1_pd_max_ch3__high__alarm BOOL
value on channel 3 Input
1 if high_high alarm for BMT PD Discrete
7088 bm_1_pd_max_ch4__high_high__alarm BOOL
Max value on channel 4 Input
1 if high alarm for BMT PD Max Discrete
7089 bm_1_pd_max_ch4__high__alarm BOOL
value on channel 4 Input
1 if high_high alarm for BMT PD Discrete
7090 bm_1_pd_max_ch5__high_high__alarm BOOL
Max value on channel 5 Input
1 if high alarm for BMT PD Max Discrete
7091 bm_1_pd_max_ch5__high__alarm BOOL
value on channel 5 Input
1 if high_high alarm for BMT PD Discrete
7092 bm_1_pd_max_ch6__high_high__alarm BOOL
Max value on channel 6 Input
1 if high alarm for BMT PD Max Discrete
7093 bm_1_pd_max_ch6__high__alarm BOOL
value on channel 6 Input
1 if high alarm for BMT Discrete
7094 bm_1_temperature_ch1__high__alarm BOOL
temperature on channel 1 Input
1 if high alarm for BMT Discrete
7095 bm_1_temperature_ch2__high__alarm BOOL
temperature on channel 2 Input
1 if high alarm for BMT Discrete
7096 bm_1_temperature_ch3__high__alarm BOOL
temperature on channel 3 Input
1 if high_high alarm for BMT
Discrete
7097 bm_1_pf_abs_ch1__high_high__alarm absolute power factor on BOOL
Input
channel 1
1 if high alarm for BMT absolute Discrete
7098 bm_1_pf_abs_ch1__high__alarm BOOL
power factor on channel 1 Input
1 if high_high alarm for BMT
Discrete
7099 bm_1_pf_abs_ch2__high_high__alarm absolute power factor on BOOL
Input
channel 2
1 if high alarm for BMT absolute Discrete
7100 bm_1_pf_abs_ch2__high__alarm BOOL
power factor on channel 2 Input
1 if high_high alarm for BMT
Discrete
7101 bm_1_pf_abs_ch3__high_high__alarm bsolute power factor on channel BOOL
Input
3
1 if high alarm for BMT absolute Discrete
7102 bm_1_pf_abs_ch3__high__alarm BOOL
power factor on channel 3 Input
1 if high_high alarm for BMT polar Discrete
7103 bm_1_c1_ch1_pp__high_high__alarm BOOL
plot of C1 on channel 1 Input
1 if high alarm for BMT polar plot Discrete
7104 bm_1_c1_ch1_pp__high__alarm BOOL
of C1 on channel 1 Input
1 if high_high alarm for BMT polar Discrete
7105 bm_1_c1_ch2_pp__high_high__alarm BOOL
plot of C1 on channel 2 Input
1 if high alarm for BMT polar plot Discrete
7106 bm_1_c1_ch2_pp__high__alarm BOOL
of C1 on channel 2 Input
1 if high_high alarm for BMT polar Discrete
7107 bm_1_c1_ch3_pp__high_high__alarm BOOL
plot of C1 on channel 3 Input
1 if high alarm for BMT polar plot Discrete
7108 bm_1_c1_ch3_pp__high__alarm BOOL
of C1 on channel 3 Input
1 if high_high alarm for BMT polar Discrete
7109 bm_1_c1_ch4_pp__high_high__alarm BOOL
plot of C1 on channel 4 Input
1 if high alarm for BMT polar plot Discrete
7110 bm_1_c1_ch4_pp__high__alarm BOOL
of C1 on channel 4 Input
1 if high_high alarm for BMT polar Discrete
7111 bm_1_c1_ch5_pp__high_high__alarm BOOL
plot of C1 on channel 5 Input

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 16 of 58
Data Point
Address Alias Description
Format Type
1 if high alarm for BMT polar plot Discrete
7112 bm_1_c1_ch5_pp__high__alarm BOOL
of C1 on channel 5 Input
1 if high_high alarm for BMT polar Discrete
7113 bm_1_c1_ch6_pp__high_high__alarm BOOL
plot of C1 on channel 6 Input
1 if high alarm for BMT polar plot Discrete
7114 bm_1_c1_ch6_pp__high__alarm BOOL
of C1 on channel 6 Input
1 if high_high alarm for BMT polar Discrete
7115 bm_1_pf_ch1_pp__high_high__alarm BOOL
plot of pf on channel 1 Input
1 if high alarm for BMT polar plot Discrete
7116 bm_1_pf_ch1_pp__high__alarm BOOL
of pf on channel 1 Input
1 if high_high alarm for BMT polar Discrete
7117 bm_1_pf_ch2_pp__high_high__alarm BOOL
plot of pf on channel 2 Input
1 if high alarm for BMT polar plot Discrete
7118 bm_1_pf_ch2_pp__high__alarm BOOL
of pf on channel 2 Input
1 if high_high alarm for BMT polar Discrete
7119 bm_1_pf_ch3_pp__high_high__alarm BOOL
plot of pf on channel 3 Input
1 if high alarm for BMT polar plot Discrete
7120 bm_1_pf_ch3_pp__high__alarm BOOL
of pf on channel 3 Input
1 if high_high alarm for BMT polar Discrete
7121 bm_1_pf_ch4_pp__high_high__alarm BOOL
plot of pf on channel 4 Input
1 if high alarm for BMT polar plot Discrete
7122 bm_1_pf_ch4_pp__high__alarm BOOL
of pf on channel 4 Input
1 if high_high alarm for BMT polar Discrete
7123 bm_1_pf_ch5_pp__high_high__alarm BOOL
plot of pf on channel 5 Input
1 if high alarm for BMT polar plot Discrete
7124 bm_1_pf_ch5_pp__high__alarm BOOL
of pf on channel 5 Input
1 if high_high alarm for BMT polar Discrete
7125 bm_1_pf_ch6_pp__high_high__alarm BOOL
plot of pf on channel 6 Input
1 if high alarm for BMT polar plot Discrete
7126 bm_1_pf_ch6_pp__high__alarm BOOL
of pf on channel 6 Input
1 if high_high alarm for BMT polar Discrete
7127 bm_1_pdi_ch1_pp__high_high__alarm BOOL
plot of PDI on channel 1 Input
1 if high alarm for BMT polar plot Discrete
7128 bm_1_pdi_ch1_pp__high__alarm BOOL
of PDI on channel 1 Input
1 if high_high alarm for BMT polar Discrete
7129 bm_1_pdi_ch2_pp__high_high__alarm BOOL
plot of PDI on channel 2 Input
1 if high alarm for BMT polar plot Discrete
7130 bm_1_pdi_ch2_pp__high__alarm BOOL
of PDI on channel 2 Input
1 if high_high alarm for BMT polar Discrete
7131 bm_1_pdi_ch3_pp__high_high__alarm BOOL
plot of PDI on channel 3 Input
1 if high alarm for BMT polar plot Discrete
7132 bm_1_pdi_ch3_pp__high__alarm BOOL
of PDI on channel 3 Input
bm_1_pd_count_ch1_pp__high_high__ala 1 if high_high alarm for BMT polar Discrete
7133 BOOL
rm plot of PD count on channel 1 Input
1 if high alarm for BMT polar plot Discrete
7134 bm_1_pd_count_ch1_pp__high__alarm BOOL
of PD count on channel 1 Input
bm_1_pd_count_ch2_pp__high_high__ala 1 if high_high alarm for BMT polar Discrete
7135 BOOL
rm plot of PD count on channel 2 Input
1 if high alarm for BMT polar plot Discrete
7136 bm_1_pd_count_ch2_pp__high__alarm BOOL
of PD count on channel 2 Input
bm_1_pd_count_ch3_pp__high_high__ala 1 if high_high alarm for BMT polar Discrete
7137 BOOL
rm plot of PD count on channel 3 Input
1 if high alarm for BMT polar plot Discrete
7138 bm_1_pd_count_ch3_pp__high__alarm BOOL
of PD count on channel 3 Input
bm_1_pd_value_ch1_pp__high_high__alar 1 if high_high alarm for BMT polar Discrete
7139 BOOL
m plot of PD value on channel 1 Input
1 if high alarm for BMT polar plot Discrete
7140 bm_1_pd_value_ch1_pp__high__alarm BOOL
of PD value on channel 1 Input
bm_1_pd_value_ch2_pp__high_high__alar 1 if high_high alarm for BMT polar Discrete
7141 BOOL
m plot of PD value on channel 2 Input
1 if high alarm for BMT polar plot Discrete
7142 bm_1_pd_value_ch2_pp__high__alarm BOOL
of PD value on channel 2 Input
bm_1_pd_value_ch3_pp__high_high__alar 1 if high_high alarm for BMT polar Discrete
7143 BOOL
m plot of PD value on channel 3 Input
1 if high alarm for BMT polar plot Discrete
7144 bm_1_pd_value_ch3_pp__high__alarm BOOL
of PD value on channel 3 Input
1 if high_high alarm for BMT polar Discrete
7145 bm_1_c1_abs_ch1_pp__high_high__alarm BOOL
plot of absolute C1 on channel 1 Input
1 if high alarm for BMT polar plot Discrete
7146 bm_1_c1_abs_ch1_pp__high__alarm BOOL
of absolute C1 on channel 1 Input

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 17 of 58
Data Point
Address Alias Description
Format Type
1 if high_high alarm for BMT polar Discrete
7147 bm_1_c1_abs_ch2_pp__high_high__alarm BOOL
plot of absolute C1 on channel 2 Input
1 if high alarm for BMT polar plot Discrete
7148 bm_1_c1_abs_ch2_pp__high__alarm BOOL
of absolute C1 on channel 2 Input
1 if high_high alarm for BMT polar Discrete
7149 bm_1_c1_abs_ch3_pp__high_high__alarm BOOL
plot of absolute C1 on channel 3 Input
1 if high alarm for BMT polar plot Discrete
7150 bm_1_c1_abs_ch3_pp__high__alarm BOOL
of absolute C1 on channel 3 Input
1 if high_high alarm for BMT polar Discrete
7151 bm_1_pf_abs_ch1_pp__high_high__alarm BOOL
plot of absolute pf on channel 1 Input
1 if high alarm for BMT polar plot Discrete
7152 bm_1_pf_abs_ch1_pp__high__alarm BOOL
of absolute pf on channel 1. Input
1 if high_high alarm for BMT polar Discrete
7153 bm_1_pf_abs_ch2_pp__high_high__alarm BOOL
plot of absolute pf on channel 2 Input
1 if high alarm for BMT polar plot Discrete
7154 bm_1_pf_abs_ch2_pp__high__alarm BOOL
of absolute pf on channel 2 Input
1 if high_high alarm for BMT polar Discrete
7155 bm_1_pf_abs_ch3_pp__high_high__alarm BOOL
plot of absolute pf on channel 3 Input
1 if high alarm for BMT polar plot Discrete
7156 bm_1_pf_abs_ch3_pp__high__alarm BOOL
of absolute pf on channel 3 Input
1 if Hottest Spot Temperature
mo_whst_winding_hottest_hot_spot_te Discrete
8000 High-High alarm is ON,, BOOL
mperature__high_high__alarm Input
otherwise 0
mo_whst_winding_hottest_hot_spot_te 1 if Hottest Spot Temperature Discrete
8001 BOOL
mperature__high__alarm High alarm is ON,, otherwise 0 Input
1 if Water Condensation
mo_mco_water_cond_temp__high_high_ Discrete
8002 Temperature High-High alarm is BOOL
_alarm Input
ON,, otherwise 0

1 if Water Condensation
mo_mco_water_cond_temp__high__alar Discrete
8003 Temperature High alarm is ON,, BOOL
m Input
otherwise 0
mo_mstwind_bubbling_temperature_ma 1 if Bubbling Temperature Margin Discrete
8004 BOOL
rgin__low__alarm Low alarm is ON,, otherwise 0 Input
1 if Bubbling Temperature Margin
mo_mstwind_bubbling_temperature_ma Discrete
8005 Low-Low alarm is ON,, otherwise BOOL
rgin__low_low__alarm Input
0

1 if Moisture Content in
mo_mstinsbar_moisture_insulation_barri Discrete
8006 Insulating Barriers High-High BOOL
er__high_high__alarm Input
alarm is ON,, otherwise 0

1 if Moisture Content in
mo_mstinsbar_moisture_insulation_barri Discrete
8007 Insulating Barriers High alarm is BOOL
er__high__alarm Input
ON,, otherwise 0
mo_csm_cooling_bank_1_deficiency_alar 1 if Cooling Bank 1 Deficiency Discrete
8008 BOOL
m__alarm Alarm is ON,, otherwise 0 Input
mo_csm_cooling_bank_2_deficiency_alar 1 if Cooling Bank 2 Deficiency Discrete
8009 BOOL
m__alarm Alarm is ON,, otherwise 0 Input
mo_csm_cooling_bank_3_deficiency_alar 1 if Cooling Bank 3 Deficiency Discrete
8010 BOOL
m__alarm Alarm is ON,, otherwise 0 Input
mo_csm_cooling_bank_4_deficiency_alar 1 if Cooling Bank 4 Deficiency Discrete
8011 BOOL
m__alarm Alarm is ON,, otherwise 0 Input
mo_csm_cooling_bank_1_over_current_ 1 if Cooling Bank 1 Overcurrent Discrete
8012 BOOL
warning__alarm Warning is ON,, otherwise 0 Input
mo_csm_cooling_bank_2_over_current_ 1 if Cooling Bank 2 Overcurrent Discrete
8013 BOOL
warning__alarm Warning is ON,, otherwise 0 Input
mo_csm_cooling_bank_3_over_current_ 1 if Cooling Bank 3 Overcurrent Discrete
8014 BOOL
warning__alarm Warning is ON,, otherwise 0 Input
mo_csm_cooling_bank_4_over_current_ 1 if Cooling Bank 4 Overcurrent Discrete
8015 BOOL
warning__alarm Warning is ON,, otherwise 0 Input
mo_csm_cooling_bank_1_over_current_a 1 if Cooling Bank 1 Overcurrent Discrete
8016 BOOL
larm__alarm Alarm is ON,, otherwise 0 Input

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 18 of 58
Data Point
Address Alias Description
Format Type
mo_csm_cooling_bank_2_over_current_a 1 if Cooling Bank 2 Overcurrent Discrete
8017 BOOL
larm__alarm Alarm is ON,, otherwise 0 Input
mo_csm_cooling_bank_3_over_current_a 1 if Cooling Bank 3 Overcurrent Discrete
8018 BOOL
larm__alarm Alarm is ON,, otherwise 0 Input
mo_csm_cooling_bank_4_over_current_a 1 if Cooling Bank 4 Overcurrent Discrete
8019 BOOL
larm__alarm Alarm is ON,, otherwise 0 Input
mo_csm_cooling_stage_malfunction__ala 1 if Cooling Stage Malfunction Discrete
8020 BOOL
rm Alarm is ON,, otherwise 0 Input
1 if Cooling Bank 1 Continuous
mo_csm_cooling_bank_1_continuous_no Discrete
8021 Non-Operational Time High-High BOOL
noperational_time_hour__high__alarm Input
Alarm is ON,, otherwise 0

1 if Cooling Bank 2 Continuous


mo_csm_cooling_bank_2_continuous_no Discrete
8022 Non-Operational Time High-High BOOL
noperational_time_hour__high__alarm Input
Alarm is ON,, otherwise 0

1 if Cooling Bank 3 Continuous


mo_csm_cooling_bank_3_continuous_no Discrete
8023 Non-Operational Time High-High BOOL
noperational_time_hour__high__alarm Input
Alarm is ON,, otherwise 0

1 if Cooling Bank 4 Continuous


mo_csm_cooling_bank_4_continuous_no Discrete
8024 Non-Operational Time High-High BOOL
noperational_time_hour__high__alarm Input
Alarm is ON,, otherwise 0
mo_cem_temp_diff_avr__high_high__alar 1 if Cooling Efficiency High-High Discrete
8025 BOOL
m alarm is ON,, otherwise 0 Input
1 if Cooling Efficiency High alarm Discrete
8026 mo_cem_temp_diff_avr__high__alarm BOOL
is ON,, otherwise 0 Input
1 if Short Term Average of OLTC
mo_oltc_temp_oil_short_term_diff__high Discrete
8027 Temperature Differential High- BOOL
_high__alarm Input
High Alarm is ON,, otherwise 0

1 if Short Term Average of OLTC


mo_oltc_temp_oil_short_term_diff__high Discrete
8028 Temperature Differential High BOOL
__alarm Input
Alarm is ON,, otherwise 0

1 if Longt Term Average of OLTC


mo_oltc_temp_oil_long_term_diff__high_ Discrete
8029 Temperature Differential High- BOOL
high__alarm Input
High Alarm is ON,, otherwise 0

1 if Long Term Average of OLTC


mo_oltc_temp_oil_long_term_diff__high_ Discrete
8030 Temperature Differential High BOOL
_alarm Input
Alarm is ON,, otherwise 0

1 if Number of OLTC operations


mo_oltc_tp_operations_per_hour__high_ Discrete
8031 per hour High-High Alarm is ON,, BOOL
high__alarm Input
otherwise 0

1 if Number of OLTC operations


mo_oltc_tp_operations_per_hour__high_ Discrete
8032 per hour High Alarm is ON,, BOOL
_alarm Input
otherwise 0

1 if Number of OLTC operations


mo_oltc_tp_operations_per_day__high_hi Discrete
8033 per day High-High Alarm is ON,, BOOL
gh__alarm Input
otherwise 0

1 if Number of OLTC operations


mo_oltc_tp_operations_per_day__high__ Discrete
8034 per day High Alarm is ON,, BOOL
alarm Input
otherwise 0
mo_oltc_torque_total_time_pct__high_hi OLTC Motor Torque Total Time Discrete
8035 BOOL
gh__alarm (%).High-High Input
mo_oltc_torque_total_time_pct__high__a OLTC Motor Torque Total Time Discrete
8036 BOOL
larm (%).High Input
mo_oltc_torque_inrush_time_pct__high_ OLTC Motor Torque In-Rush Discrete
8037 BOOL
high__alarm Time(%).High-High Input
mo_oltc_torque_inrush_time_pct__high__ OLTC Motor Torque In-Rush Discrete
8038 BOOL
alarm Time(%).High Input
mo_oltc_torque_max_pwr1_pct__high_hi OLTC Motor Torque Maximum 1 Discrete
8039 BOOL
gh__alarm (%).High-High Input

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 19 of 58
Data Point
Address Alias Description
Format Type
mo_oltc_torque_max_pwr1_pct__high__a OLTC Motor Torque Maximum 1 Discrete
8040 BOOL
larm (%). High Input
mo_oltc_torque_max_pwr2_pct__high_hi OLTC Motor Torque Maximum 2 Discrete
8041 BOOL
gh__alarm (%). High-High Input
mo_oltc_torque_max_pwr2_pct__high__a OLTC Motor Torque Maximum 2 Discrete
8042 BOOL
larm (%). High Input
mo_oltc_torque_max_pwr3_pct__high_hi OLTC Motor Torque Maximum 3 Discrete
8043 BOOL
gh__alarm (%).High-High Input
mo_oltc_torque_max_pwr3_pct__high__a OLTC Motor Torque Maximum 3 Discrete
8044 BOOL
larm (%).High Input
mo_oltc_torque_avg_pwr_pct__high_high OLTC Motor Average Torque Discrete
8045 BOOL
__alarm (%).High-High Input
mo_oltc_torque_avg_pwr_pct__high__ala OLTC Motor Average Torque Discrete
8046 BOOL
rm (%).High Input
1 if Cooling Bank 1 is ON,, Discrete
8047 mo_csm_cooling_bank_1_on BOOL
otherwise 0 Input
1 if Cooling Bank 2 is ON,, Discrete
8048 mo_csm_cooling_bank_2_on BOOL
otherwise 0 Input
1 if Cooling Bank 3 is ON,, Discrete
8049 mo_csm_cooling_bank_3_on BOOL
otherwise 0 Input
1 if Cooling Bank 4 is ON,, Discrete
8050 mo_csm_cooling_bank_4_on BOOL
otherwise 0 Input
1000 FLOAT3 Input
source_1__h2 Hydrogen concentration (ppm)
1001 2 Register

1002 Carbon Dioxide concentration FLOAT3 Input


source_1__co2
1003 (ppm) 2 Register

1004 Carbon Monoxide concentration FLOAT3 Input


source_1__co
1005 (ppm) 2 Register

1006 FLOAT3 Input


source_1__c2h4 Ethylene concentration (ppm)
1007 2 Register

1008 FLOAT3 Input


source_1__c2h6 Ethane concentration (ppm)
1009 2 Register

1010 FLOAT3 Input


source_1__ch4 Methane concentration (ppm)
1011 2 Register

1012 FLOAT3 Input


source_1__c2h2 Acetylene concentration (ppm)
1013 2 Register

1014 FLOAT3 Input


source_1__h2o Water concentration (ppm)
1015 2 Register

1016 FLOAT3 Input


source_1__o2 Oxygen concentration (ppm)
1017 2 Register

1018 Total Dissolved Combustible Gas FLOAT3 Input


source_1__tdcg
1019 concentration (ppm) 2 Register

1020 FLOAT3 Input


source_1__n2 Nitrogen concentration (ppm)
1021 2 Register

1022 Total Dissolved Gas FLOAT3 Input


source_1__tdg
1023 concentration (ppm) 2 Register

1024 Total Dissolved Hydrocarbons FLOAT3 Input


source_1__tdh
1025 (ppm) 2 Register

1026 Estimated Safe Handling Limit FLOAT3 Input


source_1__eshl
1027 (%) 2 Register

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 20 of 58
Data Point
Address Alias Description
Format Type
1028 FLOAT3 Input
source_1__oil_pressure Oil pressure (kPa)
1029 2 Register

1030 FLOAT3 Input


source_1__oil_temperature Oil temperature (°C)
1031 2 Register

1032 FLOAT3 Input


source_1__ambient_temperature Ambient temperature (°C)
1033 2 Register

1034 FLOAT3 Input


source_1__norm_temperature Normalization temperature (°C)
1035 2 Register

1036 FLOAT3 Input


source_1__relative_saturation Relative saturation (%)
1037 2 Register

1038 Ratio of Carbon Dioxide and


FLOAT3 Input
source_1__rcdcm Carbon Monoxide. Calculated
1039 2 Register
from: CO2, CO
2000 FLOAT3 Input
source_1__h2__roc Hydrogen ROC (ppm/day)
2001 2 Register

2002 FLOAT3 Input


source_1__co2__roc Carbon Dioxide ROC (ppm/day)
2003 2 Register

2004 Carbon Monoxide ROC FLOAT3 Input


source_1__co__roc
2005 (ppm/day) 2 Register

2006 FLOAT3 Input


source_1__c2h4__roc Ethylene ROC (ppm/day)
2007 2 Register

2008 FLOAT3 Input


source_1__c2h6__roc Ethane ROC (ppm/day)
2009 2 Register

2010 FLOAT3 Input


source_1__ch4__roc Methane ROC (ppm/day)
2011 2 Register

2012 FLOAT3 Input


source_1__c2h2__roc Acetylene ROC (ppm/day)
2013 2 Register

2014 FLOAT3 Input


source_1__h2o__roc Water ROC (ppm/day)
2015 2 Register

2016 FLOAT3 Input


source_1__o2__roc Oxygen ROC (ppm/day)
2017 2 Register

2018 Total Dissolved Combustible Gas FLOAT3 Input


source_1__tdcg__roc
2019 ROC (ppm/day) 2 Register

2020 FLOAT3 Input


source_1__n2__roc Nitrogen ROC (ppm/day)
2021 2 Register

2022 Rate of change for FLOAT3 Input


source_1__rcdcm__roc
2023 source_1__rcdcm 2 Register

2024 FLOAT3 Input


source_1__tdg__roc Rate of change for source_1__tdg
2025 2 Register

2026 FLOAT3 Input


source_1__tdh__roc Rate of change for source_1__tdh
2027 2 Register

2028 Rate of change for FLOAT3 Input


source_1__relative_saturation__roc
2029 source_1__relative_saturation 2 Register

2500 FLOAT3 Input


source_1__ratio_1 Gas ratio 1
2501 2 Register

2502 source_1__ratio_2 Gas ratio 2

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 21 of 58
Data Point
Address Alias Description
Format Type
FLOAT3 Input
2503
2 Register
2504 FLOAT3 Input
source_1__ratio_3 Gas ratio 3
2505 2 Register

2506 FLOAT3 Input


source_1__ratio_4 Gas ratio 4
2507 2 Register

2508 FLOAT3 Input


source_1__ratio_5 Gas ratio 5
2509 2 Register

2510 FLOAT3 Input


ain_1 Ain 1 value (user defined units)
2511 2 Register

2512 FLOAT3 Input


ain_2 Ain 2 value (user defined units)
2513 2 Register

2514 FLOAT3 Input


ain_3 Ain 3 value (user defined units)
2515 2 Register

2516 FLOAT3 Input


ain_4 Ain 4 value (user defined units)
2517 2 Register

2518 FLOAT3 Input


ain_5 Ain 5 value (user defined units)
2519 2 Register

2520 FLOAT3 Input


ain_6 Ain 6 value (user defined units)
2521 2 Register

2522 FLOAT3 Input


source_1__ratio_6 Gas ratio 6
2523 2 Register

2524 FLOAT3 Input


source_1__ratio_7 Gas ratio 7
2525 2 Register

2600 FLOAT3 Input


ain_7 Ain 7 value (user defined units)
2601 2 Register

2602 FLOAT3 Input


ain_8 Ain 8 value (user defined units)
2603 2 Register

2604 FLOAT3 Input


ain_9 Ain 9 value (user defined units)
2605 2 Register

2606 FLOAT3 Input


ain_10 Ain 10 value (user defined units)
2607 2 Register

2608 FLOAT3 Input


ain_11 Ain 11 value (user defined units)
2609 2 Register

2610 FLOAT3 Input


ain_12 Ain 12 value (user defined units)
2611 2 Register

2612 FLOAT3 Input


ain_13 Ain 13 value (user defined units)
2613 2 Register

2614 FLOAT3 Input


ain_14 Ain 14 value (user defined units)
2615 2 Register

2616 FLOAT3 Input


ain_15 Ain 15 value (user defined units)
2617 2 Register

2618 FLOAT3 Input


ain_16 Ain 16 value (user defined units)
2619 2 Register

2620 ain_17 Ain 17 value (user defined units)

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 22 of 58
Data Point
Address Alias Description
Format Type
FLOAT3 Input
2621
2 Register
2622 FLOAT3 Input
ain_18 Ain 18 value (user defined units)
2623 2 Register

3000 TransOpto channel 1 FLOAT3 Input


to_temperature_1
3001 temperature (°C) 2 Register

3002 TransOpto channel 2 FLOAT3 Input


to_temperature_2
3003 temperature (°C) 2 Register

3004 TransOpto channel 3 FLOAT3 Input


to_temperature_3
3005 temperature (°C) 2 Register

3006 TransOpto channel 4 FLOAT3 Input


to_temperature_4
3007 temperature (°C) 2 Register

3008 TransOpto channel 5 FLOAT3 Input


to_temperature_5
3009 temperature (°C) 2 Register

3010 TransOpto channel 6 FLOAT3 Input


to_temperature_6
3011 temperature (°C) 2 Register

3012 TransOpto channel 7 FLOAT3 Input


to_temperature_7
3013 temperature (°C) 2 Register

3014 TransOpto channel 8 FLOAT3 Input


to_temperature_8
3015 temperature (°C) 2 Register

4000 TransOpto channel 1 FLOAT3 Input


to_temperature_1__roc
4001 temperature ROC (°C/day) 2 Register

4002 TransOpto channel 2 FLOAT3 Input


to_temperature_2__roc
4003 temperature ROC (°C/day) 2 Register

4004 TransOpto channel 3 FLOAT3 Input


to_temperature_3__roc
4005 temperature ROC (°C/day) 2 Register

4006 TransOpto channel 4 FLOAT3 Input


to_temperature_4__roc
4007 temperature ROC (°C/day) 2 Register

4008 TransOpto channel 5 FLOAT3 Input


to_temperature_5__roc
4009 temperature ROC (°C/day) 2 Register

4010 TransOpto channel 6 FLOAT3 Input


to_temperature_6__roc
4011 temperature ROC (°C/day) 2 Register

4012 TransOpto channel 7 FLOAT3 Input


to_temperature_7__roc
4013 temperature ROC (°C/day) 2 Register

4014 TransOpto channel 8 FLOAT3 Input


to_temperature_8__roc
4015 temperature ROC (°C/day) 2 Register

5000 high_high alarm limit for gas FLOAT3 Input


source_1__h2__high_high__limit
5001 source_1__h2 (ppm) 2 Register

5002 high alarm limit for gas FLOAT3 Input


source_1__h2__high__limit
5003 source_1__h2 (ppm) 2 Register

5004 high_high alarm limit for gas FLOAT3 Input


source_1__co2__high_high__limit
5005 source_1__co2 (ppm) 2 Register

5006 high alarm limit for gas FLOAT3 Input


source_1__co2__high__limit
5007 source_1__co2 (ppm) 2 Register

5008 source_1__co__high_high__limit

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 23 of 58
Data Point
Address Alias Description
Format Type
high_high alarm limit for gas FLOAT3 Input
5009
source_1__co (ppm) 2 Register
5010 high alarm limit for gas FLOAT3 Input
source_1__co__high__limit
5011 source_1__co (ppm) 2 Register

5012 high_high alarm limit for gas FLOAT3 Input


source_1__c2h4__high_high__limit
5013 source_1__c2h4 (ppm) 2 Register

5014 high alarm limit for gas FLOAT3 Input


source_1__c2h4__high__limit
5015 source_1__c2h4 (ppm) 2 Register

5016 high_high alarm limit for gas FLOAT3 Input


source_1__c2h6__high_high__limit
5017 source_1__c2h6 (ppm) 2 Register

5018 high alarm limit for gas FLOAT3 Input


source_1__c2h6__high__limit
5019 source_1__c2h6 (ppm) 2 Register

5020 high_high alarm limit for gas FLOAT3 Input


source_1__ch4__high_high__limit
5021 source_1__ch4 (ppm) 2 Register

5022 high alarm limit for gas FLOAT3 Input


source_1__ch4__high__limit
5023 source_1__ch4 (ppm) 2 Register

5024 high_high alarm limit for gas FLOAT3 Input


source_1__c2h2__high_high__limit
5025 source_1__c2h2 (ppm) 2 Register

5026 high alarm limit for gas FLOAT3 Input


source_1__c2h2__high__limit
5027 source_1__c2h2 (ppm) 2 Register

5028 high_high alarm limit for gas FLOAT3 Input


source_1__h2o__high_high__limit
5029 source_1__h2o (ppm) 2 Register

5030 high alarm limit for gas FLOAT3 Input


source_1__h2o__high__limit
5031 source_1__h2o (ppm) 2 Register

5032 high_high alarm limit for gas FLOAT3 Input


source_1__o2__high_high__limit
5033 source_1__o2 (ppm) 2 Register

5034 high alarm limit for gas FLOAT3 Input


source_1__o2__high__limit
5035 source_1__o2 (ppm) 2 Register

5036 high_high alarm limit for gas FLOAT3 Input


source_1__tdcg__high_high__limit
5037 source_1__tdcg (ppm) 2 Register

5038 high alarm limit for gas FLOAT3 Input


source_1__tdcg__high__limit
5039 source_1__tdcg (ppm) 2 Register

5040 high_high alarm limit for gas FLOAT3 Input


source_1__n2__high_high__limit
5041 source_1__n2 (ppm) 2 Register

5042 high alarm limit for gas FLOAT3 Input


source_1__n2__high__limit
5043 source_1__n2 (ppm) 2 Register

5044 high_high alarm limit for


source_1__relative_saturation__high_hig FLOAT3 Input
source_1__relative_saturation
5045 h__limit 2 Register
(%)
5046 high alarm limit for
source_1__relative_saturation__high__li FLOAT3 Input
source_1__relative_saturation
5047 mit 2 Register
(%)
5500 high_high alarm limit for FLOAT3 Input
source_1__h2__roc__high_high__limit
5501 source_1__h2__roc (ppm/day) 2 Register

5502 high alarm limit for FLOAT3 Input


source_1__h2__roc__high__limit
5503 source_1__h2__roc (ppm/day) 2 Register

5504 source_1__co2__roc__high_high__limit

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 24 of 58
Data Point
Address Alias Description
Format Type
high_high alarm limit for FLOAT3 Input
5505
source_1__co2__roc (ppm/day) 2 Register
5506 high alarm limit for FLOAT3 Input
source_1__co2__roc__high__limit
5507 source_1__co2__roc (ppm/day) 2 Register

5508 high_high alarm limit for FLOAT3 Input


source_1__co__roc__high_high__limit
5509 source_1__co__roc (ppm/day) 2 Register

5510 high alarm limit for FLOAT3 Input


source_1__co__roc__high__limit
5511 source_1__co__roc (ppm/day) 2 Register

5512 high_high alarm limit for FLOAT3 Input


source_1__c2h4__roc__high_high__limit
5513 source_1__c2h4__roc (ppm/day) 2 Register

5514 high alarm limit for FLOAT3 Input


source_1__c2h4__roc__high__limit
5515 source_1__c2h4__roc (ppm/day) 2 Register

5516 high_high alarm limit for FLOAT3 Input


source_1__c2h6__roc__high_high__limit
5517 source_1__c2h6__roc (ppm/day) 2 Register

5518 high alarm limit for FLOAT3 Input


source_1__c2h6__roc__high__limit
5519 source_1__c2h6__roc (ppm/day) 2 Register

5520 high_high alarm limit for FLOAT3 Input


source_1__ch4__roc__high_high__limit
5521 source_1__ch4__roc (ppm/day) 2 Register

5522 high alarm limit for FLOAT3 Input


source_1__ch4__roc__high__limit
5523 source_1__ch4__roc (ppm/day) 2 Register

5524 high_high alarm limit for FLOAT3 Input


source_1__c2h2__roc__high_high__limit
5525 source_1__c2h2__roc (ppm/day) 2 Register

5526 high alarm limit for FLOAT3 Input


source_1__c2h2__roc__high__limit
5527 source_1__c2h2__roc (ppm/day) 2 Register

5528 high_high alarm limit for FLOAT3 Input


source_1__h2o__roc__high_high__limit
5529 source_1__h2o__roc (ppm/day) 2 Register

5530 high alarm limit for FLOAT3 Input


source_1__h2o__roc__high__limit
5531 source_1__h2o__roc (ppm/day) 2 Register

5532 high_high alarm limit for FLOAT3 Input


source_1__o2__roc__high_high__limit
5533 source_1__o2__roc (ppm/day) 2 Register

5534 high alarm limit for FLOAT3 Input


source_1__o2__roc__high__limit
5535 source_1__o2__roc (ppm/day) 2 Register

5536 high_high alarm limit for FLOAT3 Input


source_1__tdcg__roc__high_high__limit
5537 source_1__tdcg__roc (ppm/day) 2 Register

5538 high alarm limit for FLOAT3 Input


source_1__tdcg__roc__high__limit
5539 source_1__tdcg__roc (ppm/day) 2 Register

5540 high_high alarm limit for FLOAT3 Input


source_1__n2__roc__high_high__limit
5541 source_1__n2__roc (ppm/day) 2 Register

5542 high alarm limit for FLOAT3 Input


source_1__n2__roc__high__limit
5543 source_1__n2__roc (ppm/day) 2 Register

5544 high_high alarm limit for


FLOAT3 Input
source_1__rcdcm__roc__high_high__limit source_1__rcdcm__roc
5545 2 Register
(ppm/day)
5546 high alarm limit for
FLOAT3 Input
source_1__rcdcm__roc__high__limit source_1__rcdcm__roc
5547 2 Register
(ppm/day)
5548 source_1__rcdcm__roc__low__limit

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 25 of 58
Data Point
Address Alias Description
Format Type
low alarm limit for
FLOAT3 Input
5549 source_1__rcdcm__roc
2 Register
(ppm/day)
5550 low_low alarm limit for
FLOAT3 Input
source_1__rcdcm__roc__low_low__limit source_1__rcdcm__roc
5551 2 Register
(ppm/day)
6000 high_high alarm limit for FLOAT3 Input
source_1__ratio_1__high_high__limit
6001 source_1__ratio_1 2 Register

6002 high alarm limit for FLOAT3 Input


source_1__ratio_1__high__limit
6003 source_1__ratio_1 2 Register

6004 low alarm limit for FLOAT3 Input


source_1__ratio_1__low__limit
6005 source_1__ratio_1 2 Register

6006 low_low alarm limit for FLOAT3 Input


source_1__ratio_1__low_low__limit
6007 source_1__ratio_1 2 Register

6008 high_high alarm limit for FLOAT3 Input


source_1__ratio_2__high_high__limit
6009 source_1__ratio_2 2 Register

6010 high alarm limit for FLOAT3 Input


source_1__ratio_2__high__limit
6011 source_1__ratio_2 2 Register

6012 low alarm limit for FLOAT3 Input


source_1__ratio_2__low__limit
6013 source_1__ratio_2 2 Register

6014 low_low alarm limit for FLOAT3 Input


source_1__ratio_2__low_low__limit
6015 source_1__ratio_2 2 Register

6016 high_high alarm limit for FLOAT3 Input


source_1__ratio_3__high_high__limit
6017 source_1__ratio_3 2 Register

6018 high alarm limit for FLOAT3 Input


source_1__ratio_3__high__limit
6019 source_1__ratio_3 2 Register

6020 low alarm limit for FLOAT3 Input


source_1__ratio_3__low__limit
6021 source_1__ratio_3 2 Register

6022 low_low alarm limit for FLOAT3 Input


source_1__ratio_3__low_low__limit
6023 source_1__ratio_3 2 Register

6024 high_high alarm limit for FLOAT3 Input


source_1__ratio_4__high_high__limit
6025 source_1__ratio_4 2 Register

6026 high alarm limit for FLOAT3 Input


source_1__ratio_4__high__limit
6027 source_1__ratio_4 2 Register

6028 low alarm limit for FLOAT3 Input


source_1__ratio_4__low__limit
6029 source_1__ratio_4 2 Register

6030 low_low alarm limit for FLOAT3 Input


source_1__ratio_4__low_low__limit
6031 source_1__ratio_4 2 Register

6032 high_high alarm limit for FLOAT3 Input


source_1__ratio_5__high_high__limit
6033 source_1__ratio_5 2 Register

6034 high alarm limit for FLOAT3 Input


source_1__ratio_5__high__limit
6035 source_1__ratio_5 2 Register

6036 low alarm limit for FLOAT3 Input


source_1__ratio_5__low__limit
6037 source_1__ratio_5 2 Register

6038 low_low alarm limit for FLOAT3 Input


source_1__ratio_5__low_low__limit
6039 source_1__ratio_5 2 Register

6040 source_1__ratio_6__high_high__limit

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 26 of 58
Data Point
Address Alias Description
Format Type
high_high alarm limit for FLOAT3 Input
6041
source_1__ratio_6 2 Register
6042 high alarm limit for FLOAT3 Input
source_1__ratio_6__high__limit
6043 source_1__ratio_6 2 Register

6044 low alarm limit for FLOAT3 Input


source_1__ratio_6__low__limit
6045 source_1__ratio_6 2 Register

6046 low_low alarm limit for FLOAT3 Input


source_1__ratio_6__low_low__limit
6047 source_1__ratio_6 2 Register

6048 high_high alarm limit for FLOAT3 Input


source_1__ratio_7__high_high__limit
6049 source_1__ratio_7 2 Register

6050 high alarm limit for FLOAT3 Input


source_1__ratio_7__high__limit
6051 source_1__ratio_7 2 Register

6052 low alarm limit for FLOAT3 Input


source_1__ratio_7__low__limit
6053 source_1__ratio_7 2 Register

6054 low_low alarm limit for FLOAT3 Input


source_1__ratio_7__low_low__limit
6055 source_1__ratio_7 2 Register

6500 high_high alarm limit for FLOAT3 Input


to_temperature_1__high_high__limit
6501 to_temperature_1 (°C) 2 Register

6502 high alarm limit for FLOAT3 Input


to_temperature_1__high__limit
6503 to_temperature_1 (°C) 2 Register

6504 high_high alarm limit for FLOAT3 Input


to_temperature_2__high_high__limit
6505 to_temperature_2 (°C) 2 Register

6506 high alarm limit for FLOAT3 Input


to_temperature_2__high__limit
6507 to_temperature_2 (°C) 2 Register

6508 high_high alarm limit for FLOAT3 Input


to_temperature_3__high_high__limit
6509 to_temperature_3 (°C) 2 Register

6510 high alarm limit for FLOAT3 Input


to_temperature_3__high__limit
6511 to_temperature_3 (°C) 2 Register

6512 high_high alarm limit for FLOAT3 Input


to_temperature_4__high_high__limit
6513 to_temperature_4 (°C) 2 Register

6514 high alarm limit for FLOAT3 Input


to_temperature_4__high__limit
6515 to_temperature_4 (°C) 2 Register

6516 high_high alarm limit for FLOAT3 Input


to_temperature_5__high_high__limit
6517 to_temperature_5 (°C) 2 Register

6518 high alarm limit for FLOAT3 Input


to_temperature_5__high__limit
6519 to_temperature_5 (°C) 2 Register

6520 high_high alarm limit for FLOAT3 Input


to_temperature_6__high_high__limit
6521 to_temperature_6 (°C) 2 Register

6522 high alarm limit for FLOAT3 Input


to_temperature_6__high__limit
6523 to_temperature_6 (°C) 2 Register

6524 high_high alarm limit for FLOAT3 Input


to_temperature_7__high_high__limit
6525 to_temperature_7 (°C) 2 Register

6526 high alarm limit for FLOAT3 Input


to_temperature_7__high__limit
6527 to_temperature_7 (°C) 2 Register

6528 to_temperature_8__high_high__limit

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 27 of 58
Data Point
Address Alias Description
Format Type
high_high alarm limit for FLOAT3 Input
6529
to_temperature_8 (°C) 2 Register
6530 high alarm limit for FLOAT3 Input
to_temperature_8__high__limit
6531 to_temperature_8 (°C) 2 Register

7000 to_temperature_1__roc__high_high__limi high_high alarm limit for FLOAT3 Input


7001 t to_temperature_1__roc (°C/day) 2 Register

7002 high alarm limit for FLOAT3 Input


to_temperature_1__roc__high__limit
7003 to_temperature_1__roc (°C/day) 2 Register

7004 to_temperature_2__roc__high_high__limi high_high alarm limit for FLOAT3 Input


7005 t to_temperature_2__roc (°C/day) 2 Register

7006 high alarm limit for FLOAT3 Input


to_temperature_2__roc__high__limit
7007 to_temperature_2__roc (°C/day) 2 Register

7008 to_temperature_3__roc__high_high__limi high_high alarm limit for FLOAT3 Input


7009 t to_temperature_3__roc (°C/day) 2 Register

7010 high alarm limit for FLOAT3 Input


to_temperature_3__roc__high__limit
7011 to_temperature_3__roc (°C/day) 2 Register

7012 to_temperature_4__roc__high_high__limi high_high alarm limit for FLOAT3 Input


7013 t to_temperature_4__roc (°C/day) 2 Register

7014 high alarm limit for FLOAT3 Input


to_temperature_4__roc__high__limit
7015 to_temperature_4__roc (°C/day) 2 Register

7016 to_temperature_5__roc__high_high__limi high_high alarm limit for FLOAT3 Input


7017 t to_temperature_5__roc (°C/day) 2 Register

7018 high alarm limit for FLOAT3 Input


to_temperature_5__roc__high__limit
7019 to_temperature_5__roc (°C/day) 2 Register

7020 to_temperature_6__roc__high_high__limi high_high alarm limit for FLOAT3 Input


7021 t to_temperature_6__roc (°C/day) 2 Register

7022 high alarm limit for FLOAT3 Input


to_temperature_6__roc__high__limit
7023 to_temperature_6__roc (°C/day) 2 Register

7024 to_temperature_7__roc__high_high__limi high_high alarm limit for FLOAT3 Input


7025 t to_temperature_7__roc (°C/day) 2 Register

7026 high alarm limit for FLOAT3 Input


to_temperature_7__roc__high__limit
7027 to_temperature_7__roc (°C/day) 2 Register

7028 to_temperature_8__roc__high_high__limi high_high alarm limit for FLOAT3 Input


7029 t to_temperature_8__roc (°C/day) 2 Register

7030 high alarm limit for FLOAT3 Input


to_temperature_8__roc__high__limit
7031 to_temperature_8__roc (°C/day) 2 Register

7500 high_high alarm limit for ain_1 FLOAT3 Input


ain_1__high_high__limit
7501 (user defined units) 2 Register

7502 high alarm limit for ain_1 (user FLOAT3 Input


ain_1__high__limit
7503 defined units) 2 Register

7504 low alarm limit for ain_1 (user FLOAT3 Input


ain_1__low__limit
7505 defined units) 2 Register

7506 low_low alarm limit for ain_1 FLOAT3 Input


ain_1__low_low__limit
7507 (user defined units) 2 Register

7508 ain_2__high_high__limit

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 28 of 58
Data Point
Address Alias Description
Format Type
high_high alarm limit for ain_2 FLOAT3 Input
7509
(user defined units) 2 Register
7510 high alarm limit for ain_2 (user FLOAT3 Input
ain_2__high__limit
7511 defined units) 2 Register

7512 low alarm limit for ain_2 (user FLOAT3 Input


ain_2__low__limit
7513 defined units) 2 Register

7514 low_low alarm limit for ain_2 FLOAT3 Input


ain_2__low_low__limit
7515 (user defined units) 2 Register

7516 high_high alarm limit for ain_3 FLOAT3 Input


ain_3__high_high__limit
7517 (user defined units) 2 Register

7518 high alarm limit for ain_3 (user FLOAT3 Input


ain_3__high__limit
7519 defined units) 2 Register

7520 low alarm limit for ain_3 (user FLOAT3 Input


ain_3__low__limit
7521 defined units) 2 Register

7522 low_low alarm limit for ain_3 FLOAT3 Input


ain_3__low_low__limit
7523 (user defined units) 2 Register

7524 high_high alarm limit for ain_4 FLOAT3 Input


ain_4__high_high__limit
7525 (user defined units) 2 Register

7526 high alarm limit for ain_4 (user FLOAT3 Input


ain_4__high__limit
7527 defined units) 2 Register

7528 low alarm limit for ain_4 (user FLOAT3 Input


ain_4__low__limit
7529 defined units) 2 Register

7530 low_low alarm limit for ain_4 FLOAT3 Input


ain_4__low_low__limit
7531 (user defined units) 2 Register

7532 high_high alarm limit for ain_5 FLOAT3 Input


ain_5__high_high__limit
7533 (user defined units) 2 Register

7534 high alarm limit for ain_5 (user FLOAT3 Input


ain_5__high__limit
7535 defined units) 2 Register

7536 low alarm limit for ain_5 (user FLOAT3 Input


ain_5__low__limit
7537 defined units) 2 Register

7538 low_low alarm limit for ain_5 FLOAT3 Input


ain_5__low_low__limit
7539 (user defined units) 2 Register

7540 high_high alarm limit for ain_6 FLOAT3 Input


ain_6__high_high__limit
7541 (user defined units) 2 Register

7542 high alarm limit for ain_6 (user FLOAT3 Input


ain_6__high__limit
7543 defined units) 2 Register

7544 low alarm limit for ain_6 (user FLOAT3 Input


ain_6__low__limit
7545 defined units) 2 Register

7546 low_low alarm limit for ain_6 FLOAT3 Input


ain_6__low_low__limit
7547 (user defined units) 2 Register

7548 high_high alarm limit for FLOAT3 Input


din_1__transition_total__high_high__limit
7549 din_1__transition_total 2 Register

7550 high alarm limit for FLOAT3 Input


din_1__transition_total__high__limit
7551 din_1__transition_total 2 Register

7552 din_2__transition_total__high_high__limit

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 29 of 58
Data Point
Address Alias Description
Format Type
high_high alarm limit for FLOAT3 Input
7553
din_2__transition_total 2 Register
7554 high alarm limit for FLOAT3 Input
din_2__transition_total__high__limit
7555 din_2__transition_total 2 Register

7556 high_high alarm limit for FLOAT3 Input


din_3__transition_total__high_high__limit
7557 din_3__transition_total 2 Register

7558 high alarm limit for FLOAT3 Input


din_3__transition_total__high__limit
7559 din_3__transition_total 2 Register

7560 high_high alarm limit for FLOAT3 Input


din_4__transition_total__high_high__limit
7561 din_4__transition_total 2 Register

7562 high alarm limit for FLOAT3 Input


din_4__transition_total__high__limit
7563 din_4__transition_total 2 Register

7564 high_high alarm limit for FLOAT3 Input


din_5__transition_total__high_high__limit
7565 din_5__transition_total 2 Register

7566 high alarm limit for FLOAT3 Input


din_5__transition_total__high__limit
7567 din_5__transition_total 2 Register

7568 high_high alarm limit for FLOAT3 Input


din_6__transition_total__high_high__limit
7569 din_6__transition_total 2 Register

7570 high alarm limit for FLOAT3 Input


din_6__transition_total__high__limit
7571 din_6__transition_total 2 Register

7572 high_high alarm limit for FLOAT3 Input


din_7__transition_total__high_high__limit
7573 din_7__transition_total 2 Register

7574 high alarm limit for FLOAT3 Input


din_7__transition_total__high__limit
7575 din_7__transition_total 2 Register

7576 high_high alarm limit for FLOAT3 Input


din_8__transition_total__high_high__limit
7577 din_8__transition_total 2 Register

7578 high alarm limit for FLOAT3 Input


din_8__transition_total__high__limit
7579 din_8__transition_total 2 Register

7580 high_high alarm limit for FLOAT3 Input


din_9__transition_total__high_high__limit
7581 din_9__transition_total 2 Register

7582 high alarm limit for FLOAT3 Input


din_9__transition_total__high__limit
7583 din_9__transition_total 2 Register

7600 high_high alarm limit for ain_7 FLOAT3 Input


ain_7__high_high__limit
7601 (user defined units) 2 Register

7602 high alarm limit for ain_7 (user FLOAT3 Input


ain_7__high__limit
7603 defined units) 2 Register

7604 low alarm limit for ain_7 (user FLOAT3 Input


ain_7__low__limit
7605 defined units) 2 Register

7606 low_low alarm limit for ain_7 FLOAT3 Input


ain_7__low_low__limit
7607 (user defined units) 2 Register

7608 high_high alarm limit for ain_8 FLOAT3 Input


ain_8__high_high__limit
7609 (user defined units) 2 Register

7610 high alarm limit for ain_8 (user FLOAT3 Input


ain_8__high__limit
7611 defined units) 2 Register

7612 ain_8__low__limit

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 30 of 58
Data Point
Address Alias Description
Format Type
low alarm limit for ain_8 (user FLOAT3 Input
7613
defined units) 2 Register
7614 low_low alarm limit for ain_8 FLOAT3 Input
ain_8__low_low__limit
7615 (user defined units) 2 Register

7616 high_high alarm limit for ain_9 FLOAT3 Input


ain_9__high_high__limit
7617 (user defined units) 2 Register

7618 high alarm limit for ain_9 (user FLOAT3 Input


ain_9__high__limit
7619 defined units) 2 Register

7620 low alarm limit for ain_9 (user FLOAT3 Input


ain_9__low__limit
7621 defined units) 2 Register

7622 low_low alarm limit for ain_9 FLOAT3 Input


ain_9__low_low__limit
7623 (user defined units) 2 Register

7624 high_high alarm limit for ain_10 FLOAT3 Input


ain_10__high_high__limit
7625 (user defined units) 2 Register

7626 high alarm limit for ain_10 (user FLOAT3 Input


ain_10__high__limit
7627 defined units) 2 Register

7628 low alarm limit for ain_10 (user FLOAT3 Input


ain_10__low__limit
7629 defined units) 2 Register

7630 low_low alarm limit for ain_10 FLOAT3 Input


ain_10__low_low__limit
7631 (user defined units) 2 Register

7632 high_high alarm limit for ain_11 FLOAT3 Input


ain_11__high_high__limit
7633 (user defined units) 2 Register

7634 high alarm limit for ain_11 (user FLOAT3 Input


ain_11__high__limit
7635 defined units) 2 Register

7636 low alarm limit for ain_11 (user FLOAT3 Input


ain_11__low__limit
7637 defined units) 2 Register

7638 low_low alarm limit for ain_11 FLOAT3 Input


ain_11__low_low__limit
7639 (user defined units) 2 Register

7640 high_high alarm limit for ain_12 FLOAT3 Input


ain_12__high_high__limit
7641 (user defined units) 2 Register

7642 high alarm limit for ain_12 (user FLOAT3 Input


ain_12__high__limit
7643 defined units) 2 Register

7644 low alarm limit for ain_12 (user FLOAT3 Input


ain_12__low__limit
7645 defined units) 2 Register

7646 low_low alarm limit for ain_12 FLOAT3 Input


ain_12__low_low__limit
7647 (user defined units) 2 Register

7648 high_high alarm limit for ain_13 FLOAT3 Input


ain_13__high_high__limit
7649 (user defined units) 2 Register

7650 high alarm limit for ain_13 (user FLOAT3 Input


ain_13__high__limit
7651 defined units) 2 Register

7652 low alarm limit for ain_13 (user FLOAT3 Input


ain_13__low__limit
7653 defined units) 2 Register

7654 low_low alarm limit for ain_13 FLOAT3 Input


ain_13__low_low__limit
7655 (user defined units) 2 Register

7656 ain_14__high_high__limit

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 31 of 58
Data Point
Address Alias Description
Format Type
high_high alarm limit for ain_14 FLOAT3 Input
7657
(user defined units) 2 Register
7658 high alarm limit for ain_14 (user FLOAT3 Input
ain_14__high__limit
7659 defined units) 2 Register

7660 low alarm limit for ain_14 (user FLOAT3 Input


ain_14__low__limit
7661 defined units) 2 Register

7662 low_low alarm limit for ain_14 FLOAT3 Input


ain_14__low_low__limit
7663 (user defined units) 2 Register

7664 high_high alarm limit for ain_15 FLOAT3 Input


ain_15__high_high__limit
7665 (user defined units) 2 Register

7666 high alarm limit for ain_15 (user FLOAT3 Input


ain_15__high__limit
7667 defined units) 2 Register

7668 low alarm limit for ain_15 (user FLOAT3 Input


ain_15__low__limit
7669 defined units) 2 Register

7670 low_low alarm limit for ain_15 FLOAT3 Input


ain_15__low_low__limit
7671 (user defined units) 2 Register

7672 high_high alarm limit for ain_16 FLOAT3 Input


ain_16__high_high__limit
7673 (user defined units) 2 Register

7674 high alarm limit for ain_16 (user FLOAT3 Input


ain_16__high__limit
7675 defined units) 2 Register

7676 low alarm limit for ain_16 (user FLOAT3 Input


ain_16__low__limit
7677 defined units) 2 Register

7678 low_low alarm limit for ain_16 FLOAT3 Input


ain_16__low_low__limit
7679 (user defined units) 2 Register

7680 high_high alarm limit for ain_17 FLOAT3 Input


ain_17__high_high__limit
7681 (user defined units) 2 Register

7682 high alarm limit for ain_17 (user FLOAT3 Input


ain_17__high__limit
7683 defined units) 2 Register

7684 low alarm limit for ain_17 (user FLOAT3 Input


ain_17__low__limit
7685 defined units) 2 Register

7686 low_low alarm limit for ain_17 FLOAT3 Input


ain_17__low_low__limit
7687 (user defined units) 2 Register

7688 high_high alarm limit for ain_18 FLOAT3 Input


ain_18__high_high__limit
7689 (user defined units) 2 Register

7690 high alarm limit for ain_18 (user FLOAT3 Input


ain_18__high__limit
7691 defined units) 2 Register

7692 low alarm limit for ain_18 (user FLOAT3 Input


ain_18__low__limit
7693 defined units) 2 Register

7694 low_low alarm limit for ain_18 FLOAT3 Input


ain_18__low_low__limit
7695 (user defined units) 2 Register

8000 System date time in local time in Input


date_time_local UINT32
8001 UNIX format Register

8002 System date time in UTC in UNIX Input


date_time UINT32
8003 format Register

8004 date_local_ge DATE

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 32 of 58
Data Point
Address Alias Description
Format Type
System date in Local time in GE Input
8005
binary format (see Section 3) Register
8006 System time in Local time in GE Input
time_local_ge TIME
8007 binary format (see Section 3) Register

8008 System date in UTC in GE binary Input


date_utc_ge DATE
8009 format (see Section 3) Register

8010 System time in UTC in GE binary UINT32 Input


time_utc_ge
8011 format (see Section 3) TIME Register

8012 Last DGA Measurement time in Input


source_1__date_time_local UINT32
8013 local time in UNIX format Register

8014 Last DGA Measurement date in


UINT32 Input
source_1__date_local_ge Local time in GE binary format
8015 DATE Register
(see Section 3)
8016 Last DGA Measurement time in
UINT32 Input
source_1__time_local_ge Local time in GE binary format
8017 TIME Register
(see Section 3)
8018 Last DGA Measurement date in
UINT32 Input
source_1__date_utc_ge UTC in GE binary format (see
8019 DATE Register
Section 3)
8020 Last DGA Measurement time in
UINT32 Input
source_1__time_utc_ge UTC in GE binary format (see
8021 TIME Register
Section 3)
8022 source_1__next_measurement_date_tim Next DGA Measurement date Input
UINT32
8023 e_local time in local time in UNIX format Register

8024 Next DGA Measurement date in


source_1__next_measurement_date_loca UINT32 Input
Local time in GE binary format
8025 l_ge DATE Register
(see Section 3)
8026 Next DGA Measurement time in
source_1__next_measurement_time_loca UINT32 Input
Local time in GE binary format
8027 l_ge TIME Register
(see Section 3)
8028 Next DGA Measurement date in
source_1__next_measurement_date_utc UINT32 Input
UTC in GE binary format (see
8029 _ge DATE Register
Section 3)
8030 Next DGA Measurement time in
source_1__next_measurement_time_utc UINT32 Input
UTC in GE binary format (see
8031 _ge TIME Register
Section 3)
8032 DGA scheduler interval in Normal
Input
source_1__normal_interval mode for oil source source_1 UINT32
8033 Register
(seconds)
8034 DGA scheduler interval in
Input
source_1__caution_interval Caution mode for oil source UINT32
8035 Register
source_1 (seconds)
8036 DGA scheduler interval in Alarm
Input
source_1__alarm_interval mode for oil source source_1 UINT32
8037 Register
(seconds)
8038 Input
source_1__pga_error_codes PGA Error Codes (see Section 3) UINT32
8039 Register

8040 Input
source_1__presens_error_code PreSens O2 Sensor Error Codes UINT32
8041 Register

8042 Measurement flags (see Section Input


source_1__measurement_flags UINT32
8043 3) Register

8044 Input
mcb_firmware_version Host Firmware Version UINT32
8045 Register

8500 Input
din_1__transition_total DIN1 transition total UINT32
8501 Register

8502 din_2__transition_total DIN2 transition total UINT32

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 33 of 58
Data Point
Address Alias Description
Format Type
Input
8503
Register
8504 Input
din_3__transition_total DIN3 transition total UINT32
8505 Register

8506 Input
din_4__transition_total DIN4 transition total UINT32
8507 Register

8508 Input
din_5__transition_total DIN5 transition total UINT32
8509 Register

8510 Input
din_6__transition_total DIN6 transition total UINT32
8511 Register

8512 Input
din_7__transition_total DIN7 transition total UINT32
8513 Register

8514 Input
din_8__transition_total DIN8 transition total UINT32
8515 Register

8516 Input
din_9__transition_total DIN9 transition total UINT32
8517 Register

Current DGA scheduler mode for Input


8999 source_1__sched_mode UINT16
oil source 1 (see Section 3) Register
source_1__h2, integer_version Input
9000 source_1__h2__integer_version UINT16
(ppm) Register
source_1__co2, integer_version Input
9001 source_1__co2__integer_version UINT16
(ppm) Register
source_1__co, integer_version Input
9002 source_1__co__integer_version UINT16
(ppm) Register
source_1__c2h4, integer_version Input
9003 source_1__c2h4__integer_version UINT16
(ppm) Register
source_1__c2h6, integer_version Input
9004 source_1__c2h6__integer_version UINT16
(ppm) Register
source_1__ch4, integer_version Input
9005 source_1__ch4__integer_version UINT16
(ppm) Register
source_1__c2h2, integer_version Input
9006 source_1__c2h2__integer_version UINT16
(ppm) Register
source_1__h2o, integer_version Input
9007 source_1__h2o__integer_version UINT16
(ppm) Register
source_1__o2, integer_version Input
9008 source_1__o2__integer_version UINT16
(ppm) Register
source_1__tdcg__div10, Input
9009 source_1__tdcg__div10__integer_version UINT16
integer_version, LSB = 10ppm Register
source_1__tdcg, integer_version Input
9010 source_1__tdcg__integer_version UINT16
(ppm) Register
source_1__n2__div10, Input
9011 source_1__n2__div10__integer_version UINT16
integer_version, LSB = 10ppm Register
source_1__n2, integer_version Input
9012 source_1__n2__integer_version UINT16
(ppm) Register
source_1__tdg__div10, Input
9013 source_1__tdg__div10__integer_version UINT16
integer_version, LSB = 10ppm Register
source_1__tdg, integer_version Input
9014 source_1__tdg__integer_version UINT16
(ppm) Register
source_1__tdh, integer_version Input
9015 source_1__tdh__integer_version UINT16
(ppm) Register
source_1__eshl, integer_version Input
9016 source_1__eshl__integer_version UINT16
(%) Register
source_1__oil_pressure, Input
9017 source_1__oil_pressure__integer_version UINT16
integer_version (kPa) Register

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 34 of 58
Data Point
Address Alias Description
Format Type
source_1__relative_saturation__integer_v source_1__relative_saturation, Input
9018 UINT16
ersion integer_version (%) Register
Input
9019 source_1__presens_error_state PreSens O2 Sensor Error State UINT16
Register

ain_1, integer version, user Input


9200 ain_1__integer_version INT16
defined scaling,user defined units Register

ain_2, integer version, user


Input
9201 ain_2__integer_version defined scaling, user defined INT16
Register
units

ain_3, integer version, user Input


9202 ain_3__integer_version INT16
defined scaling,user defined units Register

ain_4, integer version, user


Input
9203 ain_4__integer_version defined scaling, user defined INT16
Register
units

ain_5, integer version, user


Input
9204 ain_5__integer_version defined scaling, user defined INT16
Register
units

ain_6, integer version, user


Input
9205 ain_6__integer_version defined scaling, user defined INT16
Register
units

ain_7, integer version, user


Input
9206 ain_7__integer_version defined scaling, user defined INT16
Register
units

ain_8, integer version, user


Input
9207 ain_8__integer_version defined scaling, user defined INT16
Register
units

ain_9, integer version, user


Input
9208 ain_9__integer_version defined scaling, user defined INT16
Register
units

ain_10, integer version, user


Input
9209 ain_10__integer_version defined scaling, user defined INT16
Register
units

ain_11, integer version, user


Input
9210 ain_11__integer_version defined scaling, user defined INT16
Register
units

ain_12, integer version, user


Input
9211 ain_12__integer_version defined scaling, user defined INT16
Register
units

ain_13, integer version, user


Input
9212 ain_13__integer_version defined scaling, user defined INT16
Register
units

ain_14, integer version, user


Input
9213 ain_14__integer_version defined scaling, user defined INT16
Register
units

ain_15, integer version, user


Input
9214 ain_15__integer_version defined scaling, user defined INT16
Register
units

ain_16, integer version, user


Input
9215 ain_16__integer_version defined scaling, user defined INT16
Register
units

ain_17, integer version, user


Input
9216 ain_17__integer_version defined scaling, user defined INT16
Register
units

ain_18, integer version, user


Input
9217 ain_18__integer_version defined scaling, user defined INT16
Register
units

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 35 of 58
Data Point
Address Alias Description
Format Type
to_temperature_1, integer Input
9500 to_temperature_1__integer_version INT16
version, (°C) Register
to_temperature_2, integer Input
9501 to_temperature_2__integer_version INT16
version, (°C) Register
to_temperature_3, integer Input
9502 to_temperature_3__integer_version INT16
version, (°C) Register
to_temperature_4, integer Input
9503 to_temperature_4__integer_version INT16
version, (°C) Register
to_temperature_5, integer Input
9504 to_temperature_5__integer_version INT16
version, (°C) Register
to_temperature_6, integer Input
9505 to_temperature_6__integer_version INT16
version, (°C) Register
to_temperature_7, integer Input
9506 to_temperature_7__integer_version INT16
version, (°C) Register
to_temperature_8, integer Input
9507 to_temperature_8__integer_version INT16
version, (°C) Register
source_1__oil_temperature__integer_ver source_1__oil_temperature, Input
9800 INT16
sion integer_version, LSB = 0.1°C Register
source_1__ambient_temperature__integ source_1__ambient_temperature Input
9801 INT16
er_version , integer_version, LSB = 0.1°C Register
source_1__norm_temperature__integer_ source_1__norm_temperature, Input
9802 INT16
version integer_version, LSB = 0.1°C Register
Input
9803 source_1__pga_error_state PGA Error State INT16
Register
9900
9901
9902
9903
9904
9905
9906
9907 Input
mcb_product_id DGA System ID TEXT
9908 Register

9909
9910
9911
9912
9913
9914
9915
9916
9917
9918
9919 Input
mcb_serial_number DGA 900 Serial Number TEXT
9920 Register

9921
9922
9923
10000 Apparent Power in Winding H FLOAT3 Input
mo_mva_apparent_power_h
10001 (MVA) 2 Register

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 36 of 58
Data Point
Address Alias Description
Format Type
10002 Apparent Power in Winding X FLOAT3 Input
mo_mva_apparent_power_x
10003 (MVA) 2 Register

10004 Apparent Power in Winding Y FLOAT3 Input


mo_mva_apparent_power_y
10005 (MVA) 2 Register

10006 Max Apparent Power in Winding FLOAT3 Input


mo_mva_max_apparent_power_h
10007 H since last recording (MVA) 2 Register

10008 Max Apparent Power in Winding FLOAT3 Input


mo_mva_max_apparent_power_x
10009 X since last recording (MVA) 2 Register

10010 Max Apparent Power in Winding FLOAT3 Input


mo_mva_max_apparent_power_y
10011 Y since last recording (MVA) 2 Register

10012 FLOAT3 Input


mo_whst_hot_spot_temp_h Hot Spot Temp n Winding H (°C)
10013 2 Register

10014 FLOAT3 Input


mo_whst_hot_spot_temp_x Hot Spot Temp n Winding X (°C)
10015 2 Register

10016 FLOAT3 Input


mo_whst_hot_spot_temp_y Hot Spot Temp n Winding Y (°C)
10017 2 Register

10018 mo_whst_winding_hottest_hot_spot_te Winding Hottest Hot Spot FLOAT3 Input


10019 mperature Temperature (°C) 2 Register

10020 Deviation of current in Winding H FLOAT3 Input


mo_whst_dev_current_a
10021 (%) 2 Register

10022 Deviation of current in Winding X FLOAT3 Input


mo_whst_dev_current_b
10023 (%) 2 Register

10024 Deviation of current in Winding Y FLOAT3 Input


mo_whst_dev_current_c
10025 (%) 2 Register

10026 FLOAT3 Input


mo_whst_dev_avr_current Average Phase Current (Amp)
10027 2 Register

10028 Relative saturation at a standard FLOAT3 Input


mo_mco_relative_saturation
10029 temperature (%) 2 Register

10030 Temperature of Water FLOAT3 Input


mo_mco_water_cond_temp
10031 condensation in oil (°C) 2 Register

10032 Moisture Content in Winding FLOAT3 Input


mo_mstwind_moisture_in_paper
10033 Paper (%) 2 Register

10034 FLOAT3 Input


mo_mstwind_bubbling_temperature Bubbling Temperature (°C)
10035 2 Register

10036 mo_mstwind_bubbling_temperature_ma Bubbling Temperature Margin FLOAT3 Input


10037 rgin (°C) 2 Register

10038 Reserved for "Remaining Time


until Reliable" in Moisture in
Winding Insulation model (data FLOAT3 Input
Dummy register
10039 point 2 Register
mo_mstwind_remaining_time_un
til_reliable)
10040 mo_mstinsbar_moisture_insulation_barri Moisture Content in Pressboard FLOAT3 Input
10041 er Barrier (%) 2 Register

10042 mo_iam_thermal_aging_acceleration_fac FLOAT3 Input


Thermal aging acceleration factor
10043 tor 2 Register

10044

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 37 of 58
Data Point
Address Alias Description
Format Type
mo_iam_moisture_aging_acceleration_fa Moisture aging acceleration FLOAT3 Input
10045
ctor factor 2 Register
10046 mo_iam_oxygen_aging_acceleration_fact FLOAT3 Input
Oxygen aging acceleration factor
10047 or 2 Register

10048 mo_iam_global_aging_acceleration_facto FLOAT3 Input


Global aging acceleration factor
10049 r 2 Register

10050 Overload value of the Overload


factor for for K (p.u.) = 1.1 in FLOAT3 Input
mo_dlg_overload_value_11
10051 units of the Factor (see Section 2 Register
3).
10052 Overload value of the Overload
factor for for K (p.u.) = 1.2 in FLOAT3 Input
mo_dlg_overload_value_12
10053 units of the Factor (see Section 2 Register
3).
10054 Overload value of the Overload
factor for for K (p.u.) = 1.3 in FLOAT3 Input
mo_dlg_overload_value_13
10055 units of the Factor (see Section 2 Register
3).
10056 Overload value of the Overload
factor for for K (p.u.) = 1.4 in FLOAT3 Input
mo_dlg_overload_value_14
10057 units of the Factor (see Section 2 Register
3).
10058 Overload value of the Overload
factor for for K (p.u.) = 1.5 in FLOAT3 Input
mo_dlg_overload_value_15
10059 units of the Factor (see Section 2 Register
3).
10060 Overload value of the Overload
factor for for K (p.u.) = 1.6 in FLOAT3 Input
mo_dlg_overload_value_16
10061 units of the Factor (see Section 2 Register
3).
10062 Overload value of the Overload
factor for for K (p.u.) = 1.7 in FLOAT3 Input
mo_dlg_overload_value_17
10063 units of the Factor (see Section 2 Register
3).
10064 Overload value of the Overload
factor for for K (p.u.) = 1.8 in FLOAT3 Input
mo_dlg_overload_value_18
10065 units of the Factor (see Section 2 Register
3).
10066 Overload value of the Overload
factor for for K (p.u.) = 1.9 in FLOAT3 Input
mo_dlg_overload_value_19
10067 units of the Factor (see Section 2 Register
3).
10068 Overload value of the Overload
factor for for K (p.u.) = 2.0 in FLOAT3 Input
mo_dlg_overload_value_20
10069 units of the Factor (see Section 2 Register
3).
10070 Temperature difference averaged FLOAT3 Input
mo_cem_temp_diff_avr
10071 for Cooling Efficiency (°C) 2 Register

10072 Short Term Difference in Oil FLOAT3 Input


mo_oltc_temp_oil_short_term_diff
10073 Temperature (°C) 2 Register

10074 Long Term Difference in Oil FLOAT3 Input


mo_oltc_temp_oil_long_term_diff
10075 Temperature (°C) 2 Register

10076 OLTC Motor Torque Total Time FLOAT3 Input


mo_oltc_torque_total_time
10077 (sec) 2 Register

10078 OLTC Motor Torque In-Rush Time FLOAT3 Input


mo_oltc_torque_inrush_time
10079 (sec) 2 Register

10080 OLTC Motor Torque Maximum 1 FLOAT3 Input


mo_oltc_torque_max_pwr1
10081 (W) 2 Register

10082 OLTC Motor Torque Maximum 2 FLOAT3 Input


mo_oltc_torque_max_pwr2
10083 (W) 2 Register

10084 mo_oltc_torque_max_pwr3

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 38 of 58
Data Point
Address Alias Description
Format Type
OLTC Motor Torque Maximum 3 FLOAT3 Input
10085
(W) 2 Register
10086 FLOAT3 Input
mo_oltc_torque_avg_pwr OLTC Motor Average Torque (W)
10087 2 Register

10088 OLTC Motor Torque Total Time FLOAT3 Input


mo_oltc_torque_total_time_pct
10089 (%) 2 Register

10090 OLTC Motor Torque In-Rush Time FLOAT3 Input


mo_oltc_torque_inrush_time_pct
10091 (%) 2 Register

10092 OLTC Motor Torque Maximum 1 FLOAT3 Input


mo_oltc_torque_max_pwr1_pct
10093 (%) 2 Register

10094 OLTC Motor Torque Maximum 2 FLOAT3 Input


mo_oltc_torque_max_pwr2_pct
10095 (%) 2 Register

10096 OLTC Motor Torque Maximum 3 FLOAT3 Input


mo_oltc_torque_max_pwr3_pct
10097 (%) 2 Register

10098 FLOAT3 Input


mo_oltc_torque_avg_pwr_pct OLTC Motor Average Torque (%)
10099 2 Register

10200 High-High limit for


mo_whst_winding_hottest_hot_spot_te FLOAT3 Input
mo_whst_winding-Hottest-
10201 mperature__high_high__limit 2 Register
Hot_spot_temperature
10202 mo_whst_winding_hottest_hot_spot_te High limit for mo_whst_winding- FLOAT3 Input
10203 mperature__high__limit Hottest-Hot_spot_temperature 2 Register

10204 mo_mco_water_cond_temp__high_high_ High-High limit for FLOAT3 Input


10205 _limit mo_mco_water_cond_temp 2 Register

10206 High limit for FLOAT3 Input


mo_mco_water_cond_temp__high__limit
10207 mo_mco_water_cond_temp 2 Register

10208 Low limit for


mo_mstwind_bubbling_temperature_ma FLOAT3 Input
mo_mstwind_bubbling_temperat
10209 rgin__low__limit 2 Register
ure_margin
10210 Low-Low limit for
mo_mstwind_bubbling_temperature_ma FLOAT3 Input
mo_mstwind_bubbling_temperat
10211 rgin__low_low__limit 2 Register
ure_margin
10212 High-High limit for
mo_mstinsbar_moisture_insulation_barri FLOAT3 Input
mo_mstinsbar_moisture_insulati
10213 er__high_high__limit 2 Register
on_barrier
10214 High limit for
mo_mstinsbar_moisture_insulation_barri FLOAT3 Input
mo_mstinsbar_moisture_insulati
10215 er__high__limit 2 Register
on_barrier
10216 High limit for
mo_csm_cooling_bank_1_continuous_no FLOAT3 Input
mo_csm_cooling_bank_1_contin
10217 noperational_time_hour__high__limit 2 Register
uous_nonoperational_time
10218 High limit for
mo_csm_cooling_bank_2_continuous_no FLOAT3 Input
mo_csm_cooling_bank_2_contin
10219 noperational_time_hour__high__limit 2 Register
uous_nonoperational_time
10220 High limit for
mo_csm_cooling_bank_3_continuous_no FLOAT3 Input
mo_csm_cooling_bank_3_contin
10221 noperational_time_hour__high__limit 2 Register
uous_nonoperational_time
10222 High limit for
mo_csm_cooling_bank_4_continuous_no FLOAT3 Input
mo_csm_cooling_bank_4_contin
10223 noperational_time_hour__high__limit 2 Register
uous_nonoperational_time
10224 mo_cem_temp_diff_avr__high_high__limi High-High limit for FLOAT3 Input
10225 t mo_cem_temp_diff_avr 2 Register

10226 High limit for


FLOAT3 Input
mo_cem_temp_diff_avr__high__limit mo_cem_temp_diff_avrHigh limit
10227 2 Register
for
10228

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 39 of 58
Data Point
Address Alias Description
Format Type
High-High limit for
mo_oltc_temp_oil_short_term_diff__high FLOAT3 Input
10229 mo_oltc_temp_oil_short_term_di
_high__limit 2 Register
ff
10230 High limit for
mo_oltc_temp_oil_short_term_diff__high FLOAT3 Input
mo_oltc_temp_oil_short_term_di
10231 __limit 2 Register
ff
10232 mo_oltc_temp_oil_long_term_diff__high_ High-High limit for FLOAT3 Input
10233 high__limit mo_oltc_temp_oil_long_term_diff 2 Register

10234 mo_oltc_temp_oil_long_term_diff__high_ High limit for FLOAT3 Input


10235 _limit mo_oltc_temp_oil_long_term_diff 2 Register

10236 mo_oltc_tp_operations_per_hour__high_ High-High limit for FLOAT3 Input


10237 high__limit mo_oltc_tp_operations_per_hour 2 Register

10238 mo_oltc_tp_operations_per_hour__high_ High limit for FLOAT3 Input


10239 _limit mo_oltc_tp_operations_per_hour 2 Register

10240 mo_oltc_tp_operations_per_day__high_hi High-High limit for FLOAT3 Input


10241 gh__limit mo_tp_oltc_operations_per_day 2 Register

10242 mo_oltc_tp_operations_per_day__high__l High limit for FLOAT3 Input


10243 imit mo_oltc_tp_operations_per_day 2 Register

10244 mo_oltc_torque_total_time_pct__high_hi High-High limit for FLOAT3 Input


10245 gh__limit mo_oltc_torque_total_time_pct 2 Register

10246 mo_oltc_torque_total_time_pct__high__li High limit for FLOAT3 Input


10247 mit mo_oltc_torque_total_time_pct 2 Register

10248 mo_oltc_torque_inrush_time_pct__high_ High-High limit for FLOAT3 Input


10249 high__limit mo_oltc_torque_inrush_time_pct 2 Register

10250 mo_oltc_torque_inrush_time_pct__high__ High limit for FLOAT3 Input


10251 limit mo_oltc_torque_inrush_time_pct 2 Register

10252 mo_oltc_torque_max_pwr1_pct__high_hi High-High limit for FLOAT3 Input


10253 gh__limit mo_oltc_torque_max_pwr1_pct 2 Register

10254 mo_oltc_torque_max_pwr1_pct__high__li High limit for FLOAT3 Input


10255 mit mo_oltc_torque_max_pwr1_pct 2 Register

10256 mo_oltc_torque_max_pwr2_pct__high_hi High-High limit for FLOAT3 Input


10257 gh__limit mo_oltc_torque_max_pwr2_pct 2 Register

10258 mo_oltc_torque_max_pwr2_pct__high__li High limit for FLOAT3 Input


10259 mit mo_oltc_torque_max_pwr2_pct 2 Register

10260 mo_oltc_torque_max_pwr3_pct__high_hi High-High limit for FLOAT3 Input


10261 gh__limit mo_oltc_torque_max_pwr3_pct 2 Register

10262 mo_oltc_torque_max_pwr3_pct__high__li High limit for FLOAT3 Input


10263 mit mo_oltc_torque_max_pwr3_pct 2 Register

10264 mo_oltc_torque_avg_pwr_pct__high_high High-High limit for FLOAT3 Input


10265 __limit mo_oltc_torque_avg_pwr_pct 2 Register

10266 mo_oltc_torque_avg_pwr_pct__high__lim High limit for FLOAT3 Input


10267 it mo_oltc_torque_avg_pwr_pct 2 Register

10400 Input
mo_iam_cumulative_aging Cumulative Aging (hour) UINT32
10401 Register

10402 mo_csm_cooling_bank_1_user_operating Cooling Bank 1 User Operating Input


UINT32
10403 _time Time (sec) Register

10404 UINT32

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 40 of 58
Data Point
Address Alias Description
Format Type
mo_csm_cooling_bank_2_user_operating Cooling Bank 2 User Operating Input
10405
_time Time (sec) Register
10406 mo_csm_cooling_bank_3_user_operating Cooling Bank 3 User Operating Input
UINT32
10407 _time Time (sec) Register

10408 mo_csm_cooling_bank_4_user_operating Cooling Bank 4 User Operating Input


UINT32
10409 _time Time (sec) Register

10410 mo_csm_cooling_bank_1_service_operati Cooling Bank 1 Service Operating Input


UINT32
10411 ng_time Time (sec) Register

10412 mo_csm_cooling_bank_2_service_operati Cooling Bank 2 Service Operating Input


UINT32
10413 ng_time Time (sec) Register

10414 mo_csm_cooling_bank_3_service_operati Cooling Bank 3 Service Operating Input


UINT32
10415 ng_time Time (sec) Register

10416 mo_csm_cooling_bank_4_service_operati Cooling Bank 4 Service Operating Input


UINT32
10417 ng_time Time (sec) Register

10418 mo_csm_cooling_bank_1_continuous_no Cooling Bank 1 Continuous Input


UINT32
10419 noperational_time Nonoperational time (sec) Register

10420 mo_csm_cooling_bank_2_continuous_no Cooling Bank 2 Continuous Input


UINT32
10421 noperational_time Nonoperational time (sec) Register

10422 mo_csm_cooling_bank_3_continuous_no Cooling Bank 3 Continuous Input


UINT32
10423 noperational_time Nonoperational time (sec) Register

10424 mo_csm_cooling_bank_4_continuous_no Cooling Bank 4 Continuous Input


UINT32
10425 noperational_time Nonoperational time (sec) Register

10426 mo_csm_cooling_bank_1_continuous_no Cooling Bank 1 Continuous Input


UINT32
10427 noperational_time_hour Nonoperational time (hour) Register

10428 mo_csm_cooling_bank_2_continuous_no Cooling Bank 2 Continuous Input


UINT32
10429 noperational_time_hour Nonoperational time (hour) Register

10430 mo_csm_cooling_bank_3_continuous_no Cooling Bank 3 Continuous Input


UINT32
10431 noperational_time_hour Nonoperational time (hour) Register

10432 mo_csm_cooling_bank_4_continuous_no Cooling Bank 4 Continuous Input


UINT32
10433 noperational_time_hour Nonoperational time (hour) Register

10434 mo_csm_cooling_bank_1_user_number_s Cooling Bank 1 User Number of Input


UINT32
10435 witching Switching Register

10436 mo_csm_cooling_bank_2_user_number_s Cooling Bank 2 User Number of Input


UINT32
10437 witching Switching Register

10438 mo_csm_cooling_bank_3_user_number_s Cooling Bank 3 User Number of Input


UINT32
10439 witching Switching Register

10440 mo_csm_cooling_bank_4_user_number_s Cooling Bank 4 User Number of Input


UINT32
10441 witching Switching Register

10442 mo_csm_cooling_bank_1_service_numbe Cooling Bank 1 Service Number Input


UINT32
10443 r_switching of Switching Register

10444 mo_csm_cooling_bank_2_service_numbe Cooling Bank 2 Service Number Input


UINT32
10445 r_switching of Switching Register

10446 mo_csm_cooling_bank_3_service_numbe Cooling Bank 3 Service Number Input


UINT32
10447 r_switching of Switching Register

10448 UINT32

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 41 of 58
Data Point
Address Alias Description
Format Type
mo_csm_cooling_bank_4_service_numbe Cooling Bank 4 Service Number Input
10449
r_switching of Switching Register
10450 Input
mo_oltc_tp_operations Total number of OLTC operations UINT32
10451 Register

10452 Total number of OLTC reversing Input


mo_oltc_tp_reversing_operations UINT32
10453 operations Register

10454 Input
mo_oltc_tp_total_operating_time Total OLTC operating time UINT32
10455 Register

10456 Input
mo_oltc_tp_tap_position_counter_1 OLTC Tap Position Counter 1 UINT32
10457 Register

10458 Input
mo_oltc_tp_tap_position_counter_2 OLTC Tap Position Counter 2 UINT32
10459 Register

10460 Input
mo_oltc_tp_tap_position_counter_3 OLTC Tap Position Counter 3 UINT32
10461 Register

10462 Input
mo_oltc_tp_tap_position_counter_4 OLTC Tap Position Counter 4 UINT32
10463 Register

10464 Input
mo_oltc_tp_tap_position_counter_5 OLTC Tap Position Counter 5 UINT32
10465 Register

10466 Input
mo_oltc_tp_tap_position_counter_6 OLTC Tap Position Counter 6 UINT32
10467 Register

10468 Input
mo_oltc_tp_tap_position_counter_7 OLTC Tap Position Counter 7 UINT32
10469 Register

10470 Input
mo_oltc_tp_tap_position_counter_8 OLTC Tap Position Counter 8 UINT32
10471 Register

10472 Input
mo_oltc_tp_tap_position_counter_9 OLTC Tap Position Counter 9 UINT32
10473 Register

10474 Input
mo_oltc_tp_tap_position_counter_10 OLTC Tap Position Counter 10 UINT32
10475 Register

10476 Input
mo_oltc_tp_tap_position_counter_11 OLTC Tap Position Counter 11 UINT32
10477 Register

10478 Input
mo_oltc_tp_tap_position_counter_12 OLTC Tap Position Counter 12 UINT32
10479 Register

10480 Input
mo_oltc_tp_tap_position_counter_13 OLTC Tap Position Counter 13 UINT32
10481 Register

10482 Input
mo_oltc_tp_tap_position_counter_14 OLTC Tap Position Counter 14 UINT32
10483 Register

10484 Input
mo_oltc_tp_tap_position_counter_15 OLTC Tap Position Counter 15 UINT32
10485 Register

10486 Input
mo_oltc_tp_tap_position_counter_16 OLTC Tap Position Counter 16 UINT32
10487 Register

10488 Input
mo_oltc_tp_tap_position_counter_17 OLTC Tap Position Counter 17 UINT32
10489 Register

10490 Input
mo_oltc_tp_tap_position_counter_18 OLTC Tap Position Counter 18 UINT32
10491 Register

10492 mo_oltc_tp_tap_position_counter_19 OLTC Tap Position Counter 19 UINT32

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 42 of 58
Data Point
Address Alias Description
Format Type
Input
10493
Register
10494 Input
mo_oltc_tp_tap_position_counter_20 OLTC Tap Position Counter 20 UINT32
10495 Register

10496 Input
mo_oltc_tp_tap_position_counter_21 OLTC Tap Position Counter 21 UINT32
10497 Register

10498 Input
mo_oltc_tp_tap_position_counter_22 OLTC Tap Position Counter 22 UINT32
10499 Register

10500 Input
mo_oltc_tp_tap_position_counter_23 OLTC Tap Position Counter 23 UINT32
10501 Register

10502 Input
mo_oltc_tp_tap_position_counter_24 OLTC Tap Position Counter 24 UINT32
10503 Register

10504 Input
mo_oltc_tp_tap_position_counter_25 OLTC Tap Position Counter 25 UINT32
10505 Register

10506 Input
mo_oltc_tp_tap_position_counter_26 OLTC Tap Position Counter 26 UINT32
10507 Register

10508 Input
mo_oltc_tp_tap_position_counter_27 OLTC Tap Position Counter 27 UINT32
10509 Register

10510 Input
mo_oltc_tp_tap_position_counter_28 OLTC Tap Position Counter 28 UINT32
10511 Register

10512 Input
mo_oltc_tp_tap_position_counter_29 OLTC Tap Position Counter 29 UINT32
10513 Register

10514 Input
mo_oltc_tp_tap_position_counter_30 OLTC Tap Position Counter 30 UINT32
10515 Register

10516 Input
mo_oltc_tp_tap_position_counter_31 OLTC Tap Position Counter 31 UINT32
10517 Register

10518 Input
mo_oltc_tp_tap_position_counter_32 OLTC Tap Position Counter 32 UINT32
10519 Register

10520 Input
mo_oltc_tp_tap_position_counter_33 OLTC Tap Position Counter 33 UINT32
10521 Register

10522 Input
mo_oltc_tp_tap_position_counter_34 OLTC Tap Position Counter 34 UINT32
10523 Register

10524 Input
mo_oltc_tp_tap_position_counter_35 OLTC Tap Position Counter 35 UINT32
10525 Register

10526 Tap Position 1 Cumulative Time Input


mo_oltc_tp_tap_position_time_1 UINT32
10527 since Last Recording (sec) Register

10528 Tap Position 2 Cumulative Time Input


mo_oltc_tp_tap_position_time_2 UINT32
10529 since Last Recording (sec) Register

10530 Tap Position 3 Cumulative Time Input


mo_oltc_tp_tap_position_time_3 UINT32
10531 since Last Recording (sec) Register

10532 Tap Position 4 Cumulative Time Input


mo_oltc_tp_tap_position_time_4 UINT32
10533 since Last Recording (sec) Register

10534 Tap Position 5 Cumulative Time Input


mo_oltc_tp_tap_position_time_5 UINT32
10535 since Last Recording (sec) Register

10536 mo_oltc_tp_tap_position_time_6 UINT32

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 43 of 58
Data Point
Address Alias Description
Format Type
Tap Position 6 Cumulative Time Input
10537
since Last Recording (sec) Register
10538 Tap Position 7 Cumulative Time Input
mo_oltc_tp_tap_position_time_7 UINT32
10539 since Last Recording (sec) Register

10540 Tap Position 8 Cumulative Time Input


mo_oltc_tp_tap_position_time_8 UINT32
10541 since Last Recording (sec) Register

10542 Tap Position 9 Cumulative Time Input


mo_oltc_tp_tap_position_time_9 UINT32
10543 since Last Recording (sec) Register

10544 Tap Position 10 Cumulative Time Input


mo_oltc_tp_tap_position_time_10 UINT32
10545 since Last Recording (sec) Register

10546 Tap Position 11 Cumulative Time Input


mo_oltc_tp_tap_position_time_11 UINT32
10547 since Last Recording (sec) Register

10548 Tap Position 12 Cumulative Time Input


mo_oltc_tp_tap_position_time_12 UINT32
10549 since Last Recording (sec) Register

10550 Tap Position 13 Cumulative Time Input


mo_oltc_tp_tap_position_time_13 UINT32
10551 since Last Recording (sec) Register

10552 Tap Position 14 Cumulative Time Input


mo_oltc_tp_tap_position_time_14 UINT32
10553 since Last Recording (sec) Register

10554 Tap Position 15 Cumulative Time Input


mo_oltc_tp_tap_position_time_15 UINT32
10555 since Last Recording (sec) Register

10556 Tap Position 16 Cumulative Time Input


mo_oltc_tp_tap_position_time_16 UINT32
10557 since Last Recording (sec) Register

10558 Tap Position 17 Cumulative Time Input


mo_oltc_tp_tap_position_time_17 UINT32
10559 since Last Recording (sec) Register

10560 Tap Position 18 Cumulative Time Input


mo_oltc_tp_tap_position_time_18 UINT32
10561 since Last Recording (sec) Register

10562 Tap Position 19 Cumulative Time Input


mo_oltc_tp_tap_position_time_19 UINT32
10563 since Last Recording (sec) Register

10564 Tap Position 20 Cumulative Time Input


mo_oltc_tp_tap_position_time_20 UINT32
10565 since Last Recording (sec) Register

10566 Tap Position 21 Cumulative Time Input


mo_oltc_tp_tap_position_time_21 UINT32
10567 since Last Recording (sec) Register

10568 Tap Position 22 Cumulative Time Input


mo_oltc_tp_tap_position_time_22 UINT32
10569 since Last Recording (sec) Register

10570 Tap Position 23 Cumulative Time Input


mo_oltc_tp_tap_position_time_23 UINT32
10571 since Last Recording (sec) Register

10572 Tap Position 24 Cumulative Time Input


mo_oltc_tp_tap_position_time_24 UINT32
10573 since Last Recording (sec) Register

10574 Tap Position 25 Cumulative Time Input


mo_oltc_tp_tap_position_time_25 UINT32
10575 since Last Recording (sec) Register

10576 Tap Position 26 Cumulative Time Input


mo_oltc_tp_tap_position_time_26 UINT32
10577 since Last Recording (sec) Register

10578 Tap Position 27 Cumulative Time Input


mo_oltc_tp_tap_position_time_27 UINT32
10579 since Last Recording (sec) Register

10580 mo_oltc_tp_tap_position_time_28 UINT32

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 44 of 58
Data Point
Address Alias Description
Format Type
Tap Position 28 Cumulative Time Input
10581
since Last Recording (sec) Register
10582 Tap Position 29 Cumulative Time Input
mo_oltc_tp_tap_position_time_29 UINT32
10583 since Last Recording (sec) Register

10584 Tap Position 30 Cumulative Time Input


mo_oltc_tp_tap_position_time_30 UINT32
10585 since Last Recording (sec) Register

10586 Tap Position 31 Cumulative Time Input


mo_oltc_tp_tap_position_time_31 UINT32
10587 since Last Recording (sec) Register

10588 Tap Position 32 Cumulative Time Input


mo_oltc_tp_tap_position_time_32 UINT32
10589 since Last Recording (sec) Register

10590 Tap Position 33 Cumulative Time Input


mo_oltc_tp_tap_position_time_33 UINT32
10591 since Last Recording (sec) Register

10592 Tap Position 34 Cumulative Time Input


mo_oltc_tp_tap_position_time_34 UINT32
10593 since Last Recording (sec) Register

10594 Tap Position 35 Cumulative Time Input


mo_oltc_tp_tap_position_time_35 UINT32
10595 since Last Recording (sec) Register

mo_mstinsbar_remaining_time_until_reli Remaining Time until Reliable Input


10700 UINT16
able (day) Register
Input
10701 mo_iam_cumulative_service_time Cumulative Service Time (day) UINT16
Register
Overload time for K (p.u.) = 1.1 Input
10702 mo_dlg_overload_time_11 UINT16
(Min) Register
Overload factor for K (p.u.) = 1.1
Input
10703 mo_dlg_overload_factor_11 (see Dynamic Loading Model UINT16
Register
Overload Factors below)
Overload time for K (p.u.) = 1.2 Input
10704 mo_dlg_overload_time_12 UINT16
(Min) Register
Overload factor for K (p.u.) = 1.2
Input
10705 mo_dlg_overload_factor_12 (see Dynamic Loading Model UINT16
Register
Overload Factors below)
Overload time for K (p.u.) = 1.3 Input
10706 mo_dlg_overload_time_13 UINT16
(Min) Register
Overload factor for K (p.u.) = 1.3
Input
10707 mo_dlg_overload_factor_13 (see Dynamic Loading Model UINT16
Register
Overload Factors below)
Overload time for K (p.u.) = 1.4 Input
10708 mo_dlg_overload_time_14 UINT16
(Min) Register
Overload factor for K (p.u.) = 1.4
Input
10709 mo_dlg_overload_factor_14 (see Dynamic Loading Model UINT16
Register
Overload Factors below)
Overload time for K (p.u.) = 1.5 Input
10710 mo_dlg_overload_time_15 UINT16
(Min) Register
Overload factor for K (p.u.) = 1.5
Input
10711 mo_dlg_overload_factor_15 (see Dynamic Loading Model UINT16
Register
Overload Factors below)
Overload time for K (p.u.) = 1.6 Input
10712 mo_dlg_overload_time_16 UINT16
(Min) Register
Overload factor for K (p.u.) = 1.6
Input
10713 mo_dlg_overload_factor_16 (see Dynamic Loading Model UINT16
Register
Overload Factors below)
Overload time for K (p.u.) = 1.7 Input
10714 mo_dlg_overload_time_17 UINT16
(Min) Register

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 45 of 58
Data Point
Address Alias Description
Format Type
Overload factor for K (p.u.) = 1.7
Input
10715 mo_dlg_overload_factor_17 (see Dynamic Loading Model UINT16
Register
Overload Factors below)
Overload time for K (p.u.) = 1.8 Input
10716 mo_dlg_overload_time_18 UINT16
(Min) Register
Overload factor for K (p.u.) = 1.8
Input
10717 mo_dlg_overload_factor_18 (see Dynamic Loading Model UINT16
Register
Overload Factors below)
Overload time for K (p.u.) = 1.9 Input
10718 mo_dlg_overload_time_19 UINT16
(Min) Register
Overload factor for K (p.u.) = 1.9
Input
10719 mo_dlg_overload_factor_19 (see Dynamic Loading Model UINT16
Register
Overload Factors below)
Overload time for K (p.u.) = 2.0 Input
10720 mo_dlg_overload_time_20 UINT16
(Min) Register
Overload factor for K (p.u.) = 2.0
Input
10721 mo_dlg_overload_factor_20 (see Dynamic Loading Model UINT16
Register
Overload Factors below)
Cooling Stage Currently in Input
10722 mo_csm_cooling_stage UINT16
Service Register
Current OLTC Tap (Mechanical) Input
10723 mo_oltc_tp_current_tap_position UINT16
Position Register
Input
10724 mo_oltc_tp_operations_per_hour OLTC Operations per Hour UINT16
Register
Input
10725 mo_oltc_tp_operations_per_day OLTC Operations per Day UINT16
Register
mo_oltc_tp_current_tap_electrical_positi Current OLTC Tap Electrical Input
10726 UINT16
on Position Register
Final OLTC Tap (Electrical) Input
10727 mo_oltc_final_elec_tap_pos UINT16
Position Register
Previous OLTC Tap (Electrical) Input
10728 mo_oltc_prev_elec_tap_pos UINT16
Position Register
Position before the Previous Input
10729 mo_oltc_prev_prev_elec_tap_pos UINT16
OLTC Tap (Electrical) Position Register
Input
10730 mo_oltc_tap_pos_group OLTC Tap Position Group number UINT16
Register
11000 BMT System main power FLOAT3 Input
bm_1_frequency
11001 frequency 2 Register

11002 BMT measured voltage on LF FLOAT3 Input


bm_1_voltage_ch1
11003 channel 1 2 Register

11004 BMT measured voltage on LF FLOAT3 Input


bm_1_voltage_ch2
11005 channel 2 2 Register

11006 BMT measured voltage on LF FLOAT3 Input


bm_1_voltage_ch3
11007 channel 3 2 Register

11008 BMT measured voltage on LF FLOAT3 Input


bm_1_voltage_ch4
11009 channel 4 2 Register

11010 BMT measured voltage on LF FLOAT3 Input


bm_1_voltage_ch5
11011 channel 5 2 Register

11012 BMT measured voltage on LF FLOAT3 Input


bm_1_voltage_ch6
11013 channel 6 2 Register

11014 BMT measured current on LF FLOAT3 Input


bm_1_current_ch1
11015 channel 1 2 Register

11016 BMT measured current on LF FLOAT3 Input


bm_1_current_ch2
11017 channel 2 2 Register

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 46 of 58
Data Point
Address Alias Description
Format Type
11018 BMT measured current on LF FLOAT3 Input
bm_1_current_ch3
11019 channel 3 2 Register

11020 BMT measured current on LF FLOAT3 Input


bm_1_current_ch4
11021 channel 4 2 Register

11022 BMT measured current on LF FLOAT3 Input


bm_1_current_ch5
11023 channel 5 2 Register

11024 BMT measured current on LF FLOAT3 Input


bm_1_current_ch6
11025 channel 6 2 Register

11026 BMT estimated ΔC1 for the FLOAT3 Input


bm_1_c1_ch1
11027 channel 1 2 Register

11028 BMT estimated ΔC1 for the FLOAT3 Input


bm_1_c1_ch2
11029 channel 2 2 Register

11030 BMT estimated ΔC1 for the FLOAT3 Input


bm_1_c1_ch3
11031 channel 3 2 Register

11032 BMT estimated ΔC1 for the FLOAT3 Input


bm_1_c1_ch4
11033 channel 4 2 Register

11034 BMT estimated ΔC1 for the FLOAT3 Input


bm_1_c1_ch5
11035 channel 5 2 Register

11036 BMT estimated ΔC1 for the FLOAT3 Input


bm_1_c1_ch6
11037 channel 6 2 Register

11038 BMT measured phase angle FLOAT3 Input


bm_1_angle_ch12
11039 between channels 1 & 2 2 Register

11040 BMT measured phase angle FLOAT3 Input


bm_1_angle_ch13
11041 between channels 1 & 3 2 Register

11042 BMT measured phase angle FLOAT3 Input


bm_1_angle_ch45
11043 between channels 4 & 5 2 Register

11044 BMT measured phase angle FLOAT3 Input


bm_1_angle_ch46
11045 between channels 4 & 6 2 Register

11046 BMT measured phase angle FLOAT3 Input


bm_1_angle_ch14
11047 between channels 1 & 4 2 Register

11048 BMT Estimated Δδ (%PF) for the FLOAT3 Input


bm_1_pf_ch1
11049 channel 1 2 Register

11050 BMT Estimated Δδ (%PF) for the FLOAT3 Input


bm_1_pf_ch2
11051 channel 2 2 Register

11052 BMT Estimated Δδ (%PF) for the FLOAT3 Input


bm_1_pf_ch3
11053 channel 3 2 Register

11054 BMT Estimated Δδ (%PF) for the FLOAT3 Input


bm_1_pf_ch4
11055 channel 4 2 Register

11056 BMT Estimated Δδ (%PF) for the FLOAT3 Input


bm_1_pf_ch5
11057 channel 5 2 Register

11058 BMT Estimated Δδ (%PF) for the FLOAT3 Input


bm_1_pf_ch6
11059 channel 6 2 Register

11060 Estimated bushing temperature


for channel 1 (based on 1-wire
FLOAT3 Input
bm_1_temperature_ch1 temperature sensors or top oil
11061 2 Register
temperature sensors, depending
on configuration)

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 47 of 58
Data Point
Address Alias Description
Format Type
11062 Estimated bushing temperature
for channel 2 (based on 1-wire
FLOAT3 Input
bm_1_temperature_ch2 temperature sensors or top oil
11063 2 Register
temperature sensors, depending
on configuration)
11064 Estimated bushing temperature
for channel 3 (based on 1-wire
FLOAT3 Input
bm_1_temperature_ch3 temperature sensors or top oil
11065 2 Register
temperature sensors, depending
on configuration)
11066 Estimated bushing temperature
for channel 4 (based on 1-wire
FLOAT3 Input
bm_1_temperature_ch4 temperature sensors or top oil
11067 2 Register
temperature sensors, depending
on configuration)
11068 Estimated bushing temperature
for channel 5 (based on 1-wire
FLOAT3 Input
bm_1_temperature_ch5 temperature sensors or top oil
11069 2 Register
temperature sensors, depending
on configuration)
11070 Estimated bushing temperature
for channel 6 (based on 1-wire
FLOAT3 Input
bm_1_temperature_ch6 temperature sensors or top oil
11071 2 Register
temperature sensors, depending
on configuration)
11072 (mW) PDI for high frequency FLOAT3 Input
bm_1_pdi_ch1
11073 channel 1 2 Register

11074 (mW) PDI for high frequency FLOAT3 Input


bm_1_pdi_ch2
11075 channel 2 2 Register

11076 (mW) PDI for high frequency FLOAT3 Input


bm_1_pdi_ch3
11077 channel 3 2 Register

11078 (mW) PDI for high frequency


channel 1, calculated based on FLOAT3 Input
bm_1_pdi_ch1_nless
11079 PD events that has no associated 2 Register
event from neutral CT
11080 (mW) PDI for high frequency
channel 2, calculated based on FLOAT3 Input
bm_1_pdi_ch2_nless
11081 PD events that has no associated 2 Register
event from neutral CT
11082 (mW) PDI for high frequency
channel 3, calculated based on FLOAT3 Input
bm_1_pdi_ch3_nless
11083 PD events that has no associated 2 Register
event from neutral CT
11084 Average number of PD events on
FLOAT3 Input
bm_1_pd_count_ch1 the main frequency cycle for high
11085 2 Register
frequency channel 1
11086 Average number of PD events on
FLOAT3 Input
bm_1_pd_count_ch2 the main frequency cycle for high
11087 2 Register
frequency channel 2
11088 Average number of PD events on
FLOAT3 Input
bm_1_pd_count_ch3 the main frequency cycle for high
11089 2 Register
frequency channel 3
11090 Average number of PD events on
FLOAT3 Input
bm_1_pd_count_ch4 the main frequency cycle for high
11091 2 Register
frequency channel 4
11092 Average number of PD events on
FLOAT3 Input
bm_1_pd_count_ch5 the main frequency cycle for high
11093 2 Register
frequency channel 5
11094 Average number of PD events on
FLOAT3 Input
bm_1_pd_count_ch6 the main frequency cycle for high
11095 2 Register
frequency channel 6
11096 Average number of PD events on
the main frequency cycle for high
FLOAT3 Input
bm_1_pd_count_ch1_nless frequency channel 1, calculated
11097 2 Register
based on PD events that has no
associated event from neutral CT
11098 bm_1_pd_count_ch2_nless

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 48 of 58
Data Point
Address Alias Description
Format Type
Average number of PD events on
the main frequency cycle for high
FLOAT3 Input
11099 frequency channel 2, calculated
2 Register
based on PD events that has no
associated event from neutral CT
11100 Average number of PD events on
the main frequency cycle for high
FLOAT3 Input
bm_1_pd_count_ch3_nless frequency channel 3, calculated
11101 2 Register
based on PD events that has no
associated event from neutral CT
11102 (pC) Average PD value for the FLOAT3 Input
bm_1_pd_value_ch1
11103 high frequency channel 1 2 Register

11104 (pC) Average PD value for the FLOAT3 Input


bm_1_pd_value_ch2
11105 high frequency channel 2 2 Register

11106 (pC) Average PD value for the FLOAT3 Input


bm_1_pd_value_ch3
11107 high frequency channel 3 2 Register

11108 (pC) Average PD value for the FLOAT3 Input


bm_1_pd_value_ch4
11109 high frequency channel 4 2 Register

11110 (pC) Average PD value for the FLOAT3 Input


bm_1_pd_value_ch5
11111 high frequency channel 5 2 Register

11112 (pC) Average PD value for the FLOAT3 Input


bm_1_pd_value_ch6
11113 high frequency channel 6 2 Register

11114 (pC) Average PD value for high


frequency channel 1, calculated FLOAT3 Input
bm_1_pd_value_ch1_nless
11115 based on PD events that has no 2 Register
associated event from neutral CT
11116 (pC) Average PD value for high
frequency channel 2, calculated FLOAT3 Input
bm_1_pd_value_ch2_nless
11117 based on PD events that has no 2 Register
associated event from neutral CT
11118 (pC) Average PD value for high
frequency channel 3, calculated FLOAT3 Input
bm_1_pd_value_ch3_nless
11119 based on PD events that has no 2 Register
associated event from neutral CT
11120 (pC) Maximum PD value detected
FLOAT3 Input
bm_1_pd_max_ch1 on high frequency channel 1
11121 2 Register
since last reporting
11122 (pC) Maximum PD value detected
FLOAT3 Input
bm_1_pd_max_ch2 on high frequency channel 2
11123 2 Register
since last reporting
11124 (pC) Maximum PD value detected
FLOAT3 Input
bm_1_pd_max_ch3 on high frequency channel 3
11125 2 Register
since last reporting
11126 (pC) Maximum PD value detected
FLOAT3 Input
bm_1_pd_max_ch4 on high frequency channel 4
11127 2 Register
since last reporting
11128 (pC) Maximum PD value detected
FLOAT3 Input
bm_1_pd_max_ch5 on high frequency channel 5
11129 2 Register
since last reporting
11130 (pC) Maximum PD value detected
FLOAT3 Input
bm_1_pd_max_ch6 on high frequency channel 6
11131 2 Register
since last reporting
11132 (pC) Maximum PD value detected
on high frequency channel 1
FLOAT3 Input
bm_1_pd_max_ch1_nless since last reporting, calculated
11133 2 Register
based on PD events that has no
associated event from neutral CT
11134 (pC) Maximum PD value detected
on high frequency channel 2
FLOAT3 Input
bm_1_pd_max_ch2_nless since last reporting, calculated
11135 2 Register
based on PD events that has no
associated event from neutral CT
11136 bm_1_pd_max_ch3_nless

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 49 of 58
Data Point
Address Alias Description
Format Type
(pC) Maximum PD value detected
on high frequency channel 3
FLOAT3 Input
11137 since last reporting, calculated
2 Register
based on PD events that has no
associated event from neutral CT
11138 Measured noise threshold level
FLOAT3 Input
bm_1_hf_noise_ch1 for HF channel 1 (in the range
11139 2 Register
from 0 to 65535.0)
11140 Measured noise threshold level
FLOAT3 Input
bm_1_hf_noise_ch2 for HF channel 2 (in the range
11141 2 Register
from 0 to 65535.0)
11142 Measured noise threshold level
FLOAT3 Input
bm_1_hf_noise_ch3 for HF channel 3 (in the range
11143 2 Register
from 0 to 65535.0)
11144 Measured noise threshold level
FLOAT3 Input
bm_1_hf_noise_ch4 for HF channel 4 (in the range
11145 2 Register
from 0 to 65535.0)
11146 Measured noise threshold level
FLOAT3 Input
bm_1_hf_noise_ch5 for HF channel 5 (in the range
11147 2 Register
from 0 to 65535.0)
11148 Measured noise threshold level
FLOAT3 Input
bm_1_hf_noise_ch6 for HF channel 6 (in the range
11149 2 Register
from 0 to 65535.0)
11150 FLOAT3 Input
bm_1_ambient_temperature BMT Ambient temperature
11151 2 Register

11152 FLOAT3 Input


bm_1_ambient_humidity BMT Ambient relative humidity
11153 2 Register

11154 BMT Top oil temperature from FLOAT3 Input


bm_1_top_oil1
11155 the sensor 1 2 Register

11156 BMT Top oil temperature from FLOAT3 Input


bm_1_top_oil2
11157 the sensor 2 2 Register

11158 BMT Top oil temperature from FLOAT3 Input


bm_1_top_oil3
11159 the sensor 3 2 Register

11160 BMT Top oil temperature from FLOAT3 Input


bm_1_top_oil4
11161 the sensor 4 2 Register

11162 FLOAT3 Input


bm_1_fpga_temp BMT FPGA temperature
11163 2 Register

11164 BMT FPGA power supplier FLOAT3 Input


bm_1_fpga_psu_temp
11165 temperature 2 Register

11166 FLOAT3 Input


bm_1_cpu_temp BMT Internal CPU temperature
11167 2 Register

11168 BMT measured voltage (Vref) for FLOAT3 Input


bm_1_vref_ch1
11169 the channel 1 2 Register

11170 BMT measured voltage (Vref) for FLOAT3 Input


bm_1_vref_ch2
11171 the channel 2 2 Register

11172 BMT measured voltage (Vref) for FLOAT3 Input


bm_1_vref_ch3
11173 the channel 3 2 Register

11174 (%) Measured absolute power FLOAT3 Input


bm_1_pf_abs_ch1
11175 factor for frequency channel 1 2 Register

11176 (%) Measured absolute power FLOAT3 Input


bm_1_pf_abs_ch2
11177 factor for frequency channel 2 2 Register

11178 (%) Measured absolute power FLOAT3 Input


bm_1_pf_abs_ch3
11179 factor for frequency channel 3 2 Register

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 50 of 58
Data Point
Address Alias Description
Format Type
11180 (pF) Measured absolute C1 for FLOAT3 Input
bm_1_c1_abs_ch1
11181 the channel 1 2 Register

11182 (pF) Measured absolute C1 for FLOAT3 Input


bm_1_c1_abs_ch2
11183 the channel 2 2 Register

11184 (pF) Measured absolute C1 for FLOAT3 Input


bm_1_c1_abs_ch3
11185 the channel 3 2 Register

11186 FLOAT3 Input


bo_1_delta_angle_ch12 Phase Angle Delta, channels 1-2
11187 2 Register

11188 FLOAT3 Input


bo_1_delta_angle_ch13 Phase Angle Delta, channels 1-3
11189 2 Register

11190 FLOAT3 Input


bo_1_delta_angle_ch45 Phase Angle Delta, channels 4-5
11191 2 Register

11192 FLOAT3 Input


bo_1_delta_angle_ch46 Phase Angle Delta, channels 4-6
11193 2 Register

11194 Correlation between channel 1 FLOAT3 Input


bo_1_ch1_pdi_rh_correlation
11195 PDI and Relative Humidity 2 Register

11196 Correlation between channel 2 FLOAT3 Input


bo_1_ch2_pdi_rh_correlation
11197 PDI and Relative Humidity 2 Register

11198 Correlation between channel 3 FLOAT3 Input


bo_1_ch3_pdi_rh_correlation
11199 PDI and Relative Humidity 2 Register

11300 Value of limit high_high for BMT FLOAT3 Input


bm_1_c1_ch1__high_high__limit
11301 C1 on channel 1 2 Register

11302 Value of limit high for BMT C1 on FLOAT3 Input


bm_1_c1_ch1__high__limit
11303 channel 1 2 Register

11304 Value of limit low for BMT C1 on FLOAT3 Input


bm_1_c1_ch1__low__limit
11305 channel 1 2 Register

11306 Value of limit low_low for BMT C1 FLOAT3 Input


bm_1_c1_ch1__low_low__limit
11307 on channel 1 2 Register

11308 Value of limit high_high for BMT FLOAT3 Input


bm_1_c1_ch2__high_high__limit
11309 C1 on channel 2 2 Register

11310 Value of limit high for BMT C1 on FLOAT3 Input


bm_1_c1_ch2__high__limit
11311 channel 2 2 Register

11312 Value of limit low for BMT C1 on FLOAT3 Input


bm_1_c1_ch2__low__limit
11313 channel 2 2 Register

11314 Value of limit low_low for BMT C1 FLOAT3 Input


bm_1_c1_ch2__low_low__limit
11315 on channel 2 2 Register

11316 Value of limit high_high for BMT FLOAT3 Input


bm_1_c1_ch3__high_high__limit
11317 C1 on channel 3 2 Register

11318 Value of limit high for BMT C1 on FLOAT3 Input


bm_1_c1_ch3__high__limit
11319 channel 3 2 Register

11320 Value of limit low for BMT C1 on FLOAT3 Input


bm_1_c1_ch3__low__limit
11321 channel 3 2 Register

11322 Value of limit low_low for BMT C1 FLOAT3 Input


bm_1_c1_ch3__low_low__limit
11323 on channel 3 2 Register

11324 bm_1_c1_ch4__high_high__limit

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 51 of 58
Data Point
Address Alias Description
Format Type
Value of limit high_high for BMT FLOAT3 Input
11325
C1 on channel 4 2 Register
11326 Value of limit high for BMT C1 on FLOAT3 Input
bm_1_c1_ch4__high__limit
11327 channel 4 2 Register

11328 Value of limit low for BMT C1 on FLOAT3 Input


bm_1_c1_ch4__low__limit
11329 channel 4 2 Register

11330 Value of limit low_low for BMT C1 FLOAT3 Input


bm_1_c1_ch4__low_low__limit
11331 on channel 4 2 Register

11332 Value of limit high_high for BMT FLOAT3 Input


bm_1_c1_ch5__high_high__limit
11333 C1 on channel 5 2 Register

11334 Value of limit high for BMT C1 on FLOAT3 Input


bm_1_c1_ch5__high__limit
11335 channel 5 2 Register

11336 Value of limit low for BMT C1 on FLOAT3 Input


bm_1_c1_ch5__low__limit
11337 channel 5 2 Register

11338 Value of limit low_low for BMT C1 FLOAT3 Input


bm_1_c1_ch5__low_low__limit
11339 on channel 5 2 Register

11340 Value of limit high_high for BMT FLOAT3 Input


bm_1_c1_ch6__high_high__limit
11341 C1 on channel 6 2 Register

11342 Value of limit high for BMT C1 on FLOAT3 Input


bm_1_c1_ch6__high__limit
11343 channel 6 2 Register

11344 Value of limit low for BMT C1 on FLOAT3 Input


bm_1_c1_ch6__low__limit
11345 channel 6 2 Register

11346 Value of limit low_low for BMT C1 FLOAT3 Input


bm_1_c1_ch6__low_low__limit
11347 on channel 6 2 Register

11348 bo_1_delta_angle_ch12__high_high__limi Value of limit high_high for BMT FLOAT3 Input


11349 t angle between channels 1 & 2 2 Register

11350 Value of limit high for BMT angle FLOAT3 Input


bo_1_delta_angle_ch12__high__limit
11351 between channels 1 & 2 2 Register

11352 bo_1_delta_angle_ch13__high_high__limi Value of limit high_high for BMT FLOAT3 Input


11353 t angle between channels 1 & 3 2 Register

11354 Value of limit high for BMT angle FLOAT3 Input


bo_1_delta_angle_ch13__high__limit
11355 between channels 1 & 3 2 Register

11356 bo_1_delta_angle_ch45__high_high__limi Value of limit high_high for BMT FLOAT3 Input


11357 t angle between channels 4 & 5 2 Register

11358 Value of limit high for BMT angle FLOAT3 Input


bo_1_delta_angle_ch45__high__limit
11359 between channels 4 & 5 2 Register

11360 bo_1_delta_angle_ch46__high_high__limi Value of limit high_high for BMT FLOAT3 Input


11361 t angle between channels 4 & 6 2 Register

11362 Value of limit high for BMT angle FLOAT3 Input


bo_1_delta_angle_ch46__high__limit
11363 between channels 4 & 6 2 Register

11364 Value of limit high_high for BMT FLOAT3 Input


bm_1_pd_max_ch1__high_high__limit
11365 PD max on channel 1 2 Register

11366 Value of limit high for BMT PD FLOAT3 Input


bm_1_pd_max_ch1__high__limit
11367 max on channel 1 2 Register

11368 bm_1_pd_max_ch2__high_high__limit

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 52 of 58
Data Point
Address Alias Description
Format Type
Value of limit high_high for BMT FLOAT3 Input
11369
PD max on channel 2 2 Register
11370 Value of limit high for BMT PD FLOAT3 Input
bm_1_pd_max_ch2__high__limit
11371 max on channel 2 2 Register

11372 Value of limit high_high for BMT FLOAT3 Input


bm_1_pd_max_ch3__high_high__limit
11373 PD max on channel 3 2 Register

11374 Value of limit high for BMT PD FLOAT3 Input


bm_1_pd_max_ch3__high__limit
11375 max on channel 3 2 Register

11376 Value of limit high_high for BMT FLOAT3 Input


bm_1_pd_max_ch4__high_high__limit
11377 PD max on channel 4 2 Register

11378 Value of limit high for BMT PD FLOAT3 Input


bm_1_pd_max_ch4__high__limit
11379 max on channel 4 2 Register

11380 Value of limit high_high for BMT FLOAT3 Input


bm_1_pd_max_ch5__high_high__limit
11381 PD max on channel 5 2 Register

11382 Value of limit high for BMT PD FLOAT3 Input


bm_1_pd_max_ch5__high__limit
11383 max on channel 5 2 Register

11384 Value of limit high_high for BMT FLOAT3 Input


bm_1_pd_max_ch6__high_high__limit
11385 PD max on channel 6 2 Register

11386 Value of limit high for BMT PD FLOAT3 Input


bm_1_pd_max_ch6__high__limit
11387 max on channel 6 2 Register

11388 Value of limit high for BMT FLOAT3 Input


bm_1_temperature_ch1__high__limit
11389 temperature on channel 1 2 Register

11390 Value of limit high for BMT FLOAT3 Input


bm_1_temperature_ch2__high__limit
11391 temperature on channel 2 2 Register

11392 Value of limit high for BMT FLOAT3 Input


bm_1_temperature_ch3__high__limit
11393 temperature on channel 3 2 Register

11394 Value of limit high_high for BMT FLOAT3 Input


bm_1_pf_abs_ch1__high_high__limit
11395 absolute pf on channel 1 2 Register

11396 Value of limit high for BMT FLOAT3 Input


bm_1_pf_abs_ch1__high__limit
11397 absolute pf on channel 1 2 Register

11398 Value of limit high_high for BMT FLOAT3 Input


bm_1_pf_abs_ch2__high_high__limit
11399 absolute pf on channel 2 2 Register

11400 Value of limit high for BMT FLOAT3 Input


bm_1_pf_abs_ch2__high__limit
11401 absolute pf on channel 2 2 Register

11402 Value of limit high_high for BMT FLOAT3 Input


bm_1_pf_abs_ch3__high_high__limit
11403 absolute pf on channel 3 2 Register

11404 Value of limit high for BMT FLOAT3 Input


bm_1_pf_abs_ch3__high__limit
11405 absolute pf on channel 3 2 Register

11406 bo_1_c1_primary_modulo__high_high__li Value for BMT C1 primary FLOAT3 Input


11407 mit high_high 2 Register

11408 FLOAT3 Input


bo_1_c1_primary_modulo__high__limit Value for BMT C1 primary high
11409 2 Register

11410 bo_1_c1_secondary_modulo__high_high_ Value for BMT C1 secondary FLOAT3 Input


11411 _limit high_high 2 Register

11412 bo_1_c1_secondary_modulo__high__limit Value for BMT C1 secondary high

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 53 of 58
Data Point
Address Alias Description
Format Type
FLOAT3 Input
11413
2 Register
11414 bo_1_pf_primary_modulo__high_high__li Value for BMT pf primary FLOAT3 Input
11415 mit high_high 2 Register

11416 FLOAT3 Input


bo_1_pf_primary_modulo__high__limit Value for BMT pf primary high
11417 2 Register

11418 bo_1_pf_secondary_modulo__high_high_ Value for BMT pf secondary FLOAT3 Input


11419 _limit high_high 2 Register

11420 FLOAT3 Input


bo_1_pf_secondary_modulo__high__limit Value for BMT pf secondary high
11421 2 Register

11422 bo_1_pdi_primary_modulo__high_high__li Value for BMT PDI primary FLOAT3 Input


11423 mit high_high 2 Register

11424 FLOAT3 Input


bo_1_pdi_primary_modulo__high__limit Value for BMT PDI primary high
11425 2 Register

11426 bo_1_pd_count_primary_modulo__high_h Value for BMT PD count primary FLOAT3 Input


11427 igh__limit high_high 2 Register

11428 bo_1_pd_count_primary_modulo__high__ Value for BMT PD count primary FLOAT3 Input


11429 limit high 2 Register

11430 bo_1_pd_value_primary_modulo__high_h Value for BMT PD value primary FLOAT3 Input


11431 igh__limit high_high 2 Register

11432 bo_1_pd_value_primary_modulo__high__l Value for BMT PD value primary FLOAT3 Input


11433 imit high 2 Register

11434 bo_1_c1_abs_primary_modulo__high_hig Value for BMT absolute C1 FLOAT3 Input


11435 h__limit primary high_high 2 Register

11436 bo_1_c1_abs_primary_modulo__high__li Value for BMT absolute C1 FLOAT3 Input


11437 mit primary high 2 Register

11438 bo_1_pf_abs_primary_modulo__high_hig Value for BMT absolute pf FLOAT3 Input


11439 h__limit primary high_high 2 Register

11440 bo_1_pf_abs_primary_modulo__high__lim Value for BMT absolute pf FLOAT3 Input


11441 it primary high 2 Register

11500 Nominal phase angle between FLOAT3 Input


bs_1_nominal_phase_1_2_angle
11501 channels 1 and 2 (aka A-B) 2 Register

11502 Nominal phase angle between FLOAT3 Input


bs_1_nominal_phase_1_3_angle
11503 channels 1 and 3 (aka A-C) 2 Register

11504 Rated peak voltage for channels FLOAT3 Input


bs_1_operational_voltage_primary
11505 1...3 (aka primary) 2 Register

11506 Rated peak voltage for channels FLOAT3 Input


bs_1_operational_voltage_secondary
11507 4..6 (aka secondary) 2 Register

11508 Rated RMS voltage for channels FLOAT3 Input


bh_1_operational_voltage_rms_primary
11509 1...3 (aka primary) 2 Register

11510 bh_1_operational_voltage_rms_secondar Rated RMS voltage for channels FLOAT3 Input


11511 y 4..6 (aka secondary) 2 Register

11550 Input
bp_1_serial_number BMT Unit serial number UINT32
11551 Register

11600 bh_1_device_id BMT Device ID TEXT

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 54 of 58
Data Point
Address Alias Description
Format Type
11601
11602
11603
Input
11604
Register
11605
11606
11607

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 55 of 58
3 DGA 900 FAMILY MODBUS ENUMERATION
Table 3-1 lists the DGA scheduler modes.
Table 3-1: DGA scheduler mode
Output Mode
0 Normal Mode
1 Caution Mode
2 Alarm Mode
3 Suspended Mode

Table 3-2 lists the binary date format for the Multilin device.
Table 3-2: Multilin device date format
Format Description
Reg MMDD(hex) MM = Month from 1 to 12 in High Byte of the Register, Binary format
Reg+1 YYYY (hex) YYYY = Year, Binary format (valid range from 1990 to 2089)

Table 3-3 lists the binary time format for the Multilin device.
Table 3-3: Multilin device time format
Format Description
Reg HHMM (hex) HH = Hours from 0 to 23 in High Byte of the Register, Binary format
Reg+1 SSSS (hex) SSSS = Seconds from 0 to 59 and milliseconds from 0 to 999 in Binary
format.

Table 3-4 lists the PGA error codes. To decode the error code, convert the decimal error
code into binary. The bits with a value of 1 will represent the active errors described in
Table 3-4. For example, an error code of 21 will be 00000000 00000000 00000000
00010101 in binary. In the example (from right to left), the 0, 2 and 4 bits are denoted
with a 1 so their associated alarms will be on.
Table 3-4: PGA error codes
Bit Description
25 1 = Oil pump not turning
24 1 = Oil pump tacho count too low
23 1 = Manual oil sampling switch
22 1 = Oil pump speed out of range
21 1 = Oil pump pressure too low
20 1 = Oil pump tacho count too high
19 1 = Oil pressure too high
18 1 = Oil pressure too low
17 1 = Oil temperature too high
16 1 = Oil temperature too low
15 N/A
14 1 = Gas leak test: Pressure decay too high
13 1 = Gas leak test: Pump pressure too low
12 1 = Bad communication with controlboard
11 1 = PGA Air temperature outside limits
10 1 = Levelsensor2 signal (oil level alert)
9 1 = Levelsensor1 signal (oil level)
8 1 = No Levelsensor3 signal (oil drain)
7 1 = No levelsensor1 signal (oil level)

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 56 of 58
Bit Description
6 1 = Microphone test failed
5 1 = Background noise/vibration too high
4 1 = Gas flow lower than limit
3 1 = PGA IR-source outside range
2 1 = PGA chopper frequency outside range
1 1 = PGA power supply voltage too low
0 1 = Missing mains input

Table 3-5 lists the measurement flags. To decode the error code, convert the decimal
error code into binary. The bits with a value of 1 will represent the active flags described
in Table 3-5. For example, an error code of 21 will be 00000000 00000000 00000000
00010101 in binary. In the example (from right to left), the 0, 2 and 4 bits are denoted
with a 1 so their associated flags will be on.
Table 3-5: Measurement flags
Bit Description
15 1 = TDH Valid
14 1 = External Alarm ON
13 1 = Measured with PreSens
12 1 = Strong NHC Indication
11 1 = Weak NHC Indication
10 1 = Measurement Manually Stopped
9 1 = Manual Sample
8 1 = Spurious alarm suspected
7 1 = Oil switch failed
6 1 = TDG valid
5 1 = Nitrogen valid
4 1 = Error checking disabled
3 1 = Sampling skipped
2 1 = First measurement after reset
1 1 = PPM values are valid
0 1 = ESHL Valid

CG-062 — DGA 900 family Modbus I/O Registers – Rev 3.0 18-Dec-20 Page 57 of 58
Contact & Copyright Details

GE Grid Solutions (UK) Ltd


Lissue Industrial Estate East
Unit 1, 7 Lissue Walk, Lisburn, Co. Antrim
Northern Ireland, United Kingdom BT28 2LU
www.gegridsolutions.com/md.htm

For further assistance or queries please contact:

Customer Service Centre (24 hours a day, 365 days a year)


T +44 1785-250-070 (United Kingdom)
T 1-800-361-3652 (United States and Canada)
T +1 514-420-7460 (worldwide)
GA.support@ge.com

GE, the GE monogram and Kelman are trademarks of the General Electric Company.
Other company or product names mentioned in this document may be trademarks
or registered trademarks of their respective companies.

GE reserves the right to make changes to specifications of products described at any


time without notice and without obligation to notify any person of such changes.

This material is accurate at the time of writing.

Copyright, General Electric Company, 2020. All Rights Reserved.