Professional Documents
Culture Documents
MFP3_3-44_M00015
MFP3_3-44_M00015
Rev. 06 - 04/2009
Aqua-Cleer
MFP/3
MFP/3 - 44
TECHNICAL MANUAL
SAFETY WARNINGS
All handling, maintenance and repair of systems must be carried out by suitably trained staff.
The room which is to house the systems, the accessory material and the consumable products must
comply with the safety, use and storage requirements envisaged by the regulations in force.
The water produced by each device must be used for the specific purpose for which it was
intended. Culligan is not liable for the consequences of improper use of the water produced by its
equipment.
All system malfunctions must be reported to the Culligan Service Centre immediately. Culligan is
not liable for the consequences of protracted use of a system on which malfunctions have
occurred.
Where necessary, chemicals must be selected, dosed and handled by professional qualified staff,
in accordance with the Culligan instructions and the Safety Technical Information.
The system must be disconnected from the electricity and water supplies during all maintenance or
repair operations.
Waste or consumable materials from water treatment systems must be disposed of in accordance
with the regulations in force.
Aqua-Cleer
MFP/3
MFP/3 - 44
INDEX
- General Page 1
- Principles of Operation “ 3
- Flow Diagram ” 4
- Technical Specifications “ 7
- Installation Instruction ” 8
- Pre-assembling Instructions ” 8
- Electronical Connections ” 10
- Preparatory Instructions ” 13
- Start-up Instructions ” 15
- Sanitization ” 18
- Instructions for Sanitization with Pressurized
Distribution of Osmotized Water ” 19
- Trouble-Shooting Chart ” 20
Aqua-Cleer MFP/3
MFP/3 - 44
Models 400 - 800 - 1200 - 1600
2200 – 2800 - 3300
GENERAL
Aqua-Cleer MFP/3 plants are Reverse Osmosis The electronic control unit, complete with
(R.O.) plants specially designed to treat brackish control/monitoring display, receives and
water, or water considered unsuitable because displays all informative and alarm data.
of its excessive salt content for drinking and for What's more, the display can be used to
technological purposes. show other data useful for correct operation
of the system, such as:
Product and intake water conductivity, Saline
removal rate, Product and rejection water flow-
rate, System recovery ratio.
When a pressure of 13 or 18 bar according to
the model is applied to the water for treatment,
the passage through the osmotic membrane
removes 90-95% of salts (depending on the
nature of the salts themselves).
Since the membrane is able to "reject"
substances dissolved in ionic form, it is even
more effective in preventing the passage of
undissolved materials (colloids, bacteria, etc.) or
organic molecules larger in size than the ions.
However, it is important to remember that the
concentration of both these substances and the
dissolved salts increases strongly on the surface
of the membrane, and may give rise to
undesirable phenomena.
For example:
- the undissolved substances may deposit on
the surfaces of the membrane, clogging it and
thus reducing its efficiency.
- Some types of salts (particularly Calcium
salts) are only moderately soluble, so as the
concentration increases they may precipitate
and create a scale on the membrane, with
effects similar to those mentioned above.
Plug the unit in. The switch "0/1" must be on "1" If the overload cut-out is tripped and the pump-
position. motor unit cuts out, the red "Trip" lamp on the
The "Start/Power" touch will flash. control panel illuminates to indicate excessive
power absorption.
Press on the "Start/Power" touch. The
equipment will start the operation. The pump-motor cut-out for overload takes place
thanks to a signal given to the electronic control
In this condition the normally closed solenoid
panel by the thermic probe installed on the
valve (7) opens and the inlet water enters the
pump-motor unit.
plant. The pressure switch (4) checks its
pressure, and only if the preset values are Note: In case of overload it is possible to reset
reached it enables the automatic start-up of the the acoustic alarm.
motor-pump unit (5-6). Once the causes of the thermic cut-out
This prevents the pump from breaking because are eliminated, switch off the general
of lack of water and/or insufficient pressure. electronic board by turning to "0" position
When the pressure is low, the yellow "low the main switch. This will enable you to
pressure" lamp on the panel also illuminates. restore the "Overload" position.
- Once the motor-pump unit (5-6) has started
up, the water is pressurized and sent to the Standard MFP/3 model are the following:
osmotic membrane (or membranes, if the MFP - 400 = 1 membrane
pump supplies more than one).
On contact with the membrane, some of the MFP - 800 = 2 membranes, operating in
water passes through it and loses a large series
proportion of its salts (osmotized water), MFP - 1200 = 3 membranes, operating 2 in
while the remainer, with higher salt content, is parallel and 1 in series (double
rejected. stage with 3 membranes)
In order to reduce the quantity of reject water,
MFP - 1600= 4 membranes, operating 2 in
some of it can be recycled, with the regulating
parallel and 2 in series (double
valves (8-9) appropriately set on the basis of
stage with 4 membranes)
the information given by the flow meter (11).
When the pump is in operation, the green MFP - 2200 = 4 membranes, operating 2 in
"Pump Run" fixed lamp illuminates. parallel and 2 in series (double
- The pressure gauges (2A - 2B) allow stage with 4 membranes)
constant control of the pressures entering MFP - 2800 = 5 membranes, operating 2 in
and leaving the membrane, or regular checks parallel and 2 + 1 in series
on the pressure values can be used to (triple stage with 5
highlight any anomalies (such as scale and membranes)
deposits on the membrane itself).
MFP - 3300 = 6 membranes, operating 2 in
- The membranes used for Aqua-Cleer MFP/3 parallel and 2+2 in series
plants have a "spiral" configuration, and there (triple stage with 6
may be from 1 to 6 of them depending on the membranes)
model.
When more than one membrane is used, they
may be arranged in series, or in series-
parallel in order to optimize efficiency.
PLANT COMPONENTS
Note - The number of each point refers to the Note: both manometers allow the checking
flow diagrams in Figures Nos 1A – 1B. of the pressure loss across the osmotic
membranes, to optimize the setting and to
immediately detect an excessive pressure
1) Osmotic membranes: salt rejection from drop due to improper feed water
90% to 95%, 100% for substances with characteristics (Iron presence, high
molecular weight > 200 and 99% for bacteria turbidity, scaling agents, etc.). A prompt
and pyrogen. The membrane is housed into anomalous pressure reading permits to
a fiberglass vessel. The estimated life length intervene in order to avoid irreversible
of the membranes in normal working damages.
conditions is 24 months
Nominal Flow
Rates Product Connections Dimensions
Max Max inlet
Model Inlet max (1)
Flow water
flow Max Shipping
Rate of pressure Electric
MFP/3 rates Max energy
MFP/3 Drain membran 3-ph + Freque Weight
min MFP/3 adsorbed consu Width Depth Heigh.
44 (2) e earth + ncy
MFP/3 44 power mpion.
neutral
(Imax)
l/h l/h l/h l/h Psi (bar) V Hz KW A mm mm mm kg
400 2000 500 450 1685 200 (14) 380 50 1.6 2.7 500 660 1550 115
800 2000 1000 900 1370 200 (14) 380 50 1.6 2.7 500 660 1550 140
1200 3600 1500 1350 2655 200 (14) 380 50 2.3 3.9 500 660 1550 170
1600 3600 2000 1800 2340 200 (14) 380 50 2.3 3.9 500 660 1550 190
2200 5500 2500 2350 3925 261 (18) 380 50 4.2 7.1 500 660 1800 220
2800 5500 3000 2850 3610 261 (18) 380 50 4.2 7.1 500 660 1800 250
3300 5500 3500 3350 3295 261 (18) 380 50 4.2 7.1 500 660 1800 280
1) Average values based on the following standard conditions: temperature 20°C, operating pressure 14 or 18
bar (200 or 261 psi), recovery ratio 75%; TDS 500 ppm as NaCl; product water pressure 0 bar; new
membranes.
2) Maximum values based on the following conditions: temperature 10°C, operating pressure 200 or 261 psi (14
or 18 bar), taking into consideration the models, rejet recirculation closed and old membranes.
Installation Instructions
SHIPMENT
Aqua-Cleer MFP/3 desalinators are shipped in a 3) The room must have adequate lighting and
single package and mounted on a wooden ventilation, and must have a suitable drain.
support.
WATER CONNECTIONS FOR DIRECT USE OF - a 1” pipeline for the unit feed, connected with
THE OSMOTIZED WATER "WITHOUT the potable water to be trated, equipped with a
STORAGE TANK" closing valve;
- a water drain, sized upon the max discharge
This special water connection has been flow-rate of the connected unit, as per Table N.
developed in particular for medical applications 1;
(e.g. Dialysis Centres) and makes the following - if possibile, a gravity drain should be provided
operations possible: in the floor, in order to preved flooding in the
equipment room during maintenance
operations, when the pipes must be
1) Supply of osmotized water at pre-set
disconnected.
pressure with automatic recycling of the
excess water produced.
1) Make the water connections as shown in
Figure No. 2 (pre-assembling instructions).
2) Easy sanitization or chemical flushing of the
osmotic membranes by manual operation of
the PVC valves. 2) Check that the desalinator water supply
pressure is not less than 0.5 bar.
3) The plant can be by-passed without water
stagnating along the water circuit during 3) Check that the back-pressure downstream of
normal operation. the desalinator does not exceed 3 bar.
Key
A) Pretreated water inlet: 1" steel collar G) PVC check valve, ¾": for installation O) Pressure switch 0-3 bar with manual
B) Osmotized water outlet: ½" steel in the opposite direction to the inlet reset
collar water flow direction P) PVC ball valve, ¾"
C) Reject water outlet: ½” steel collar or H) Pressure gauge 0-10 bar: product Q) PVC ball valve, ¾"
¾” for models 2200, 2800 and 3300 (osmotized) water outlet R) PVC ball valve, ¾"
D) PVC ball valve, ½” or ¾” for models I) Horizontal check valve in PVC, ¾": S) PVC ball valve, ¾"
2200, 2800 and 3300 (for installation in the osmotized T) Drain
E) Pressure gauge 0-10 bar: pretreated water flow direction)
19) Three-pole switch with fuses +
water inlet L) PVC ball valve, ¾" neutral + earth
F) Bronze pressure reducer ¾" M) PVC hose connection, ¾"
N) Reinforced polyethylene hose, ¾"
MFP/3 230/50 Voltage 3-ph 380/50 Voltage 3-ph 230/50 Voltage 1-ph
Figure No. 4
Key
INDICATOR TYPE COLOUR FUNCTION
OVERLOAD Lamp red Thermical Cut-out
CLEAN Touch yellow Sanitization Start
LOW PRESS Lamp yellow Inlet Low Pressure
RESET Touch -- Acustic Alarm Switch-off
PUMP RUN Lamp green HP Pump in Operation
START/POWER Touch green Unit Start-up
When the plant is put into operation for the first 9) Open the valve (D) on the pretreated water
time, it is essential to fill the water circuit and inlet line.
flush out the membranes to remove the 10) Check on the pressure gauge (E) that the
disinfectant solution they contain (Aldehyde, inlet water pressure is between 0.7 and 3
Bisulphites or other substances). bar.
During this operation it is vital that the 11) Turn the switch (13) to "1" (ON).
osmotized water should be sent directly to
Note - The green "Start/Power" light (14)
the drain.
on the control panel illuminates and
at the same time the NC solenoid
valve (7) on the pretreated water
FILLING THE WATER CIRCUIT inlet is activated, allowing the water
to fill both the water circuit and the
high pressure pump (6).
1) Check that the valves (D-L) on the
This operation can be considered complete
pretreated water inlet line and on the
when water has been flowing from the valve
osmotized water line are closed.
(S) for a few minutes.
2) Open the valve (R) and check that the valve
12) Turn the main switch (13) back to "0" (OFF)
(S) is closed.
and check that the green "Start/Power" light
3) Fit the plastic pipe into the hose-connection (14) has switched off.
of the valve (Q) and connect it to the drain.
4) Open the valve (Q) and check that the valve
(P) is closed.
PRESET DELAYS
5) Completely open the needle valve (8) on the
reject water line (drain) and close the
needle valves (3-9). Whenever the plant is started up the high
6) Ensure that the power master switch (19) on pressure pump (6) comes into operation with the
the power supply line is turned off. delay preset (30 seconds).
7) Check that the white screw (U) called "Off This delay is necessary to allow the hydraulic
Limit Stop" on the head of the NC solenoid circuit to pressurize after the solenoid valve (7)
valve (7) is completely unscrewed. has been opened.
Note - This screw controls the opening of Whenever the high pressure pump (6) is started
the solenoid valve diaphragm. up, the minimum pressure switch is enabled with
a delay preset on the timer (10 seconds). This
8) Check that the lever (V) beside the NC
delay is necessary to allow the pressure to
solenoid valve (7) has its pointer facing the
stabilize after the high pressure pump (6) has
letter "A".
started.
Note - The lever (V) must only be moved to
Note - If the pressure does not stabilize, the
letter "C" if the solenoid burns out,
high pressure pump is automatically
since in this position the solenoid
stopped.
valve is by-passed.
KEY
A) Pretreated water inlet: 1" steel L) PVC ball valve, ¾" (2B) Reject pressure gauge
collar M) PVC hose connection, ¾" (3) Regulation pin valve on working
B) Osmotized water outlet: ½" steel N) Reinforced polyethylene hose, ¾" pressure (by-pass pump)
collar (4) Adjustable range pressure switch
O) Pressure switch 0-3 bar with manual
C) Reject water outlet: ½” steel collar with maual re-activation
reset
or ¾” for models 2200, 2800 and (6) Motor pump kit
P) PVC ball valve, ¾"
3300 (7) Solenoid valve NC RO inlet
Q) PVC ball valve, ¾" (8) Regulation pin valve drain water
D) PVC ball valve, ¾” R) PVC ball valve, ¾" (9) Regulation pin valve recirculation
E) Pressure gauge 0-10 bar: S) PVC ball valve, ¾" water
pretreated water inlet
T) Drain (10) One way valve
F) Bronze pressure reducer ¾" (11) flow meter
U) Regulation screw for electrovalve
G) PVC check valve, ¾": for opening (12) skid
installation in the opposite direction V) Manual valve open/close (13) general switch (0-1) on the control
to the inlet water flow direction Z) Reinforced flexibel polietilene tube panel
H) Pressure gauge 0-10 bar: product dia ¾” (19) Three-pole switch with fuses +
(osmotized) water outlet W) 1” hose adapeter in PVC neutral + earth
I) Horizontal check valve in PVC, ¾": (1) Osmotic module
(for installation in the osmotized (2A) Pressure gauge in the outlet of
water flow direction) the pump
1) Adjust the pressure reducer (F) until the exceeds 13 bar for models up to
pressure value indicated by the pressure 1600, and 18 bar for models up to
gauge (E) is the same as the operating 3300, slowly open the needle valve
pressure value requested by the (9) on the recycling water line, until
customer. the pressure gauge (2A) shows a
Note - In no case must the water constant pressure of 13 bar or 18 bar
pressure be below 0.7 bar or over according to the model.
3 bar. Example:
2) Turn the main switch to "1" (ON). plant model Aqua-Cleer MFP/3 400
This provides two effects simultaneously: Product water
A) excitation of the solenoid valve (7) on (osmotized) : 8.3 l/m
the pretreated water inlet, and Reject water
illumination of the green "Start/Power" (drain) : 8.3 l/m
light;
Operating pressure : 13 bar
B) start-up, delayed by 30 seconds, of
6) Allow water to drain from the system until
the high pressure pump (5-6), and
all the sanitizing solution has been
illumination of the green "Pump Run"
completely eliminated, checking both the
light.
product (osmotized) water and the reject
3) Check that the motor runs in the direction water (drain).
of the arrow on the motor housing.
Note - If the motor runs in the opposite
direction, stop the plant by turning
SETTING THE FLOW RATES
the main switch to "0" (OFF) and
reverse two-phase wires on the In order to reduce the quantity of reject water,
terminal board of the motor (5). some of it may be recycled by setting the needle
valves (8-9) appropriately.
4) Set the tripping threshold of the pretreated
water low pressure switch (4) at a value of
1 bar (minimum).
Note - If the inlet water pressure is below RECOVERY RATE (RR)
the setting value, the plant stops The recovery rate represents the percentage of
automatically and the yellow low product water in relation to the flow rate of inlet
pressure warning light on the water entering the plant.
control panel illuminates.
5) With the plant in operation, make the quantity of product water (QP)
RR = x 100
following adjustments: quantity of inlet water (QI)
- Check that the needle valve (3) is
completely closed. Since the delivery rate of the plant feeding
- Regulate the needle valve (8) on the pumps vary depending on the operating
reject water line until the flow rate of pressure, it is more practical to calculate the real
water to the drain is the same as the inlet flow rate as the sum of the product water
product (osmotized) water flow rate. QP and of the drain water (QD).
CHECKS AND ADJUSTMENTS 1) Turn the main switch to "0" (stop) and check
that the green "Start/Power" light is off.
1) Ensure that the by-pass needle valve (3) is
set so that the pressure gauge (2A) reads a 2) Close the valve (Q) and open the valves
constant pressure of 14 or 18 bar. (P-L).
2) With the aid of a graduated bucket and a 3) Set the safety pressure switch with manual
watch, measure the flow rates of product reset (0) at 3 bar. This safety pressure
and reject water, which must be more or switch with manual reset is only tripped with
less the same. a service back-pressure of 3 bar, and shuts
3) Establish the recovery rate required (see down the plant completely. The possible
example below), and adjust the needle causes of this malfunction are:
valves (8-9) until the flow meter shows the
A) the valve (P) is closed
preset flow rate value.
Example: standard operating conditions. B) the check valve (G) is blocked in
Aqua-Cleer MFP/3 400 closed position and there is no request
(Recovery Rate 50% at pressure 14 bar). for water from the service.
4) Return the switch to "1" (ON) and press the
l/minute touch "Start/Power".
Rated flow rate of
= QP 8.3
product water THE PLANT IS NOW IN OPERATION.
Rated flow rate of
= QD 8.3
drain water
5) Check the pressure on the pressure gauge
Inlet water flow rate =QI = QP +QD 16.6 (2B) and the pressure indicated by the
pressure gauge (2A) on the control panel.
QP 8.3 The pressure difference indicates the
RR *= x 100 = x 100 = 50% membrane headloss.
QI 16.6
6) To stop and start the plant, use the
* Recovery Rate "Start/Power" switch on the control panel.
1) Prepare the quantity of sanitizing solution 10) Use the key to turn off the CLEAN switch.
required for the plant concerned in a Note - this reactivates the low pressure
container. switch (4).
2) Fit a plastic tube onto the hose connection 11) Leave the plant to stand for about two hours
of the PVC valve (S) and insert it into the before starting to flush the sanitizing
sanitizing solution container. solution out of the membrane.
3) Fit a plastic tube onto the hose connection Note - For temporary lay-offs, or for shut-
of the PVC valve (Q) and send it to the downs lasting more than 3-4 days,
drain (T). leave the sanitizing solution in the
4) Switch off the power supply to the plant by system. The membrane(s) must not
turning the switch on the control panel to "0" be flushed out until the plant is put
(OFF). back into operation.
5) Shut the PVC valves (D-R-P-L). The procedure is as follows:
6) Open the PVC valves (S-Q). 12) Close the PVC valve (S).
7) Turn the main switch on "1" position and 13) Open the PVC valve (D-R) allowing inlet of
activate the "cleaning" function by pushing pretreated water.
the related touch for 3-4 seconds. 14) Turn the main switch on the control panel to
Note - The use of the key on the "1" ON, press the "Start/Powr" touch and
CLEANING switch by-passes the allow water to flow from the PVC valve (Q)
low pressure switch (4), allowing the until all the sanitizing solution has been
motor-pump unit (5-6) to operate in eliminated.
direct suction regardless of the Note - Before putting the system into
pressure. and enabling the high service, analyze the product
pressure pump to draw in the (osmotized) and reject (drain) water
sterilizing solution at atmospheric using test to ensure that the water
pressure. does not contain any sanitizing
8) Check that the sanitiizing solution is flowing solution.
out of the PVC valve (Q) to the drain. 15) Turn the main switch to "0" (OFF).
9) CAUTION: switch off the power supply to 16) Shut the PVC valve (Q).
the plant using the switch on the control
17) Open the PVC valves (P-L).
panel before the container of sanitizing
solution is completely empty: 18) Turn the main switch to "1" (ON).
Note - The high pressure pump cannot 19) Check that the plant is working properly,
operate without water since the following the "Start-up Instructions" on page
teflon bushings would be damaged 14.
immediately.
THE PLANT HAS NOW BEEN SANITIZED AND
IS IN OPERATION.