Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

M000-15

Rev. 06 - 04/2009

Aqua-Cleer

MFP/3
MFP/3 - 44

TECHNICAL MANUAL

Culligan reserves the right to change any technical or design specifications


CULLIGAN ITALIANA S.p.A. - Via Gandolfi, 6 - 40057 Cadriano di Granarolo E. BO (ITALY) –
Phone +39/0516017111 – fax +39/051765602
Quality System Certified according to UNI EN ISO 9001 Norm
This manual is intended for the Staff specifically appointed to install
and/or operate and/or repair the Culligan systems. Work by unauthorised
staff, or not in accordance with the instructions in the manual, will
relieve Culligan of all liability for the possible consequences.

SAFETY WARNINGS

 All handling, maintenance and repair of systems must be carried out by suitably trained staff.

 The room which is to house the systems, the accessory material and the consumable products must
comply with the safety, use and storage requirements envisaged by the regulations in force.

 The water produced by each device must be used for the specific purpose for which it was
intended. Culligan is not liable for the consequences of improper use of the water produced by its
equipment.

 All system malfunctions must be reported to the Culligan Service Centre immediately. Culligan is
not liable for the consequences of protracted use of a system on which malfunctions have
occurred.

 Where necessary, chemicals must be selected, dosed and handled by professional qualified staff,
in accordance with the Culligan instructions and the Safety Technical Information.

 The system must be disconnected from the electricity and water supplies during all maintenance or
repair operations.

 Waste or consumable materials from water treatment systems must be disposed of in accordance
with the regulations in force.
Aqua-Cleer
MFP/3
MFP/3 - 44

INDEX

- General Page 1
- Principles of Operation “ 3
- Flow Diagram ” 4
- Technical Specifications “ 7
- Installation Instruction ” 8
- Pre-assembling Instructions ” 8
- Electronical Connections ” 10
- Preparatory Instructions ” 13
- Start-up Instructions ” 15
- Sanitization ” 18
- Instructions for Sanitization with Pressurized
Distribution of Osmotized Water ” 19
- Trouble-Shooting Chart ” 20
Aqua-Cleer MFP/3
MFP/3 - 44
Models 400 - 800 - 1200 - 1600
2200 – 2800 - 3300
GENERAL

Aqua-Cleer MFP/3 plants are Reverse Osmosis The electronic control unit, complete with
(R.O.) plants specially designed to treat brackish control/monitoring display, receives and
water, or water considered unsuitable because displays all informative and alarm data.
of its excessive salt content for drinking and for What's more, the display can be used to
technological purposes. show other data useful for correct operation
of the system, such as:
Product and intake water conductivity, Saline
removal rate, Product and rejection water flow-
rate, System recovery ratio.
When a pressure of 13 or 18 bar according to
the model is applied to the water for treatment,
the passage through the osmotic membrane
removes 90-95% of salts (depending on the
nature of the salts themselves).
Since the membrane is able to "reject"
substances dissolved in ionic form, it is even
more effective in preventing the passage of
undissolved materials (colloids, bacteria, etc.) or
organic molecules larger in size than the ions.
However, it is important to remember that the
concentration of both these substances and the
dissolved salts increases strongly on the surface
of the membrane, and may give rise to
undesirable phenomena.
For example:
- the undissolved substances may deposit on
the surfaces of the membrane, clogging it and
thus reducing its efficiency.
- Some types of salts (particularly Calcium
salts) are only moderately soluble, so as the
concentration increases they may precipitate
and create a scale on the membrane, with
effects similar to those mentioned above.

M000-15 - Rev. 06 – 04/2009 Aqua-Cleer MFP/3 – MFP/3-44 1


These problems can be overcome by providing - Calcium sulphate, Calcium carbonate and
an adequate pretreatment of the water and by Silica: the limits indicated refer to the need to
ensuring proper plant management. prevent scaling precipitates.
In more general terms, with or without Normally, after chemical analysis of the
pretreatment, the water for treatment must have water, Culligan takes the limits into
the following main specifications (for the other consideration when designing the plant, and
parameters not considered here, it is supposed suggests any corrective pretreatment
that the water has the characteristics of drinking necessary (acidification and/or sequestration,
water). softening on resin, etc.).
Hydraulic pressure : - > 0.5 bar for mere
operation
- > 2 bar for project HYDRAULIC COMPONENTS
performances
- > than service All the hydraulic components used in Aqua-Cleer
pressure, in case of MFP/3 plants consist of corrosion-resistant
pressurized water materials suitable for use with products for
distribution human consumption, and are designed to
Outlet water pressure : 3 bar maximum withstand the envisaged operating conditions as
Temperature : 2-35°C (nominal follows:
temperature 20°C) - the elements upstream of the high pressure
Maximum salinity pump are resistant to a nominal pressure of 8
mod. from 400 to 1600 : 3000 mg/l (as TDS) bar (114 psi).
mod. from 2200 to 3300 : 1500 mg/l (as TDS) - The pipes are all of food grade, in various
SDI : 3 materials depending on the specific uses.
The materials used are:
pH : 71
- Rubber hoses with stainless steel
Active chlorine : absent (or < 0.1 ppm)
reinforcement
Calcium sulphate : concentration in reject
- PVC
water below the solubility
limit - AISI 316 stainless steel
Calcium Carbonate : Langelier index of reject - HT
water negative - The elements of the high pressure circuit
Silica : concentration in reject (membrane inlet and reject lines) withstand a
water below the solubility nominal pressure of 16 bar (228 psi) or 20
limit bar (285 psi) according to the model.
Note - with temperatures below or above the
specified limits, there may be irreversible
physical damage to the membranes PRETREATMENT AND PREFILTRATION
(because of frost or degradation of the
Because of the extreme variability of the
osmotic film).
characteristics of the water to be treated, Aqua-
The nominal temperature of 20°C is that taken Cleer MFP/3 plants do not include any standard
for the calculation of the forecast plant yield. pretreatment. Culligan will suggest the suitable
- The turbidity values requested may be system in each case on the basis of an accurate
reached by using adequate prefiltration if technical analysis.
necessary. With regard to turbidity and suspended solids,
- Active chlorine is normally added to water to apart from the possibility that other specific
disinfect it. The excess is then eliminated by filtration procedures may be necessary, it is
means of activated carbon or other considered that safety prefiltration on cartridge
procedures. filters (Filtr-Gard) capable of trapping particles
larger than 5 microns is needed in all cases to
protect the plant.

2 Aqua-Cleer MFP/3 – MFP/3-44 M000-15 - Rev. 06 – 04/2009


Principles of Operation
(see Figures Nos 1 - Flow Diagram)

Plug the unit in. The switch "0/1" must be on "1" If the overload cut-out is tripped and the pump-
position. motor unit cuts out, the red "Trip" lamp on the
The "Start/Power" touch will flash. control panel illuminates to indicate excessive
power absorption.
Press on the "Start/Power" touch. The
equipment will start the operation. The pump-motor cut-out for overload takes place
thanks to a signal given to the electronic control
In this condition the normally closed solenoid
panel by the thermic probe installed on the
valve (7) opens and the inlet water enters the
pump-motor unit.
plant. The pressure switch (4) checks its
pressure, and only if the preset values are Note: In case of overload it is possible to reset
reached it enables the automatic start-up of the the acoustic alarm.
motor-pump unit (5-6). Once the causes of the thermic cut-out
This prevents the pump from breaking because are eliminated, switch off the general
of lack of water and/or insufficient pressure. electronic board by turning to "0" position
When the pressure is low, the yellow "low the main switch. This will enable you to
pressure" lamp on the panel also illuminates. restore the "Overload" position.
- Once the motor-pump unit (5-6) has started
up, the water is pressurized and sent to the Standard MFP/3 model are the following:
osmotic membrane (or membranes, if the MFP - 400 = 1 membrane
pump supplies more than one).
On contact with the membrane, some of the MFP - 800 = 2 membranes, operating in
water passes through it and loses a large series
proportion of its salts (osmotized water), MFP - 1200 = 3 membranes, operating 2 in
while the remainer, with higher salt content, is parallel and 1 in series (double
rejected. stage with 3 membranes)
In order to reduce the quantity of reject water,
MFP - 1600= 4 membranes, operating 2 in
some of it can be recycled, with the regulating
parallel and 2 in series (double
valves (8-9) appropriately set on the basis of
stage with 4 membranes)
the information given by the flow meter (11).
When the pump is in operation, the green MFP - 2200 = 4 membranes, operating 2 in
"Pump Run" fixed lamp illuminates. parallel and 2 in series (double
- The pressure gauges (2A - 2B) allow stage with 4 membranes)
constant control of the pressures entering MFP - 2800 = 5 membranes, operating 2 in
and leaving the membrane, or regular checks parallel and 2 + 1 in series
on the pressure values can be used to (triple stage with 5
highlight any anomalies (such as scale and membranes)
deposits on the membrane itself).
MFP - 3300 = 6 membranes, operating 2 in
- The membranes used for Aqua-Cleer MFP/3 parallel and 2+2 in series
plants have a "spiral" configuration, and there (triple stage with 6
may be from 1 to 6 of them depending on the membranes)
model.
When more than one membrane is used, they
may be arranged in series, or in series-
parallel in order to optimize efficiency.

M000-15 - Rev. 06 – 04/2009 Aqua-Cleer MFP/3 – MFP/3-44 3


Figure No. 1 A FLOW DIAGRAM – Models 400-800-1200-1600

PLANT COMPONENTS
Note - The number of each point refers to the Note: both manometers allow the checking
flow diagrams in Figures Nos 1A – 1B. of the pressure loss across the osmotic
membranes, to optimize the setting and to
immediately detect an excessive pressure
1) Osmotic membranes: salt rejection from drop due to improper feed water
90% to 95%, 100% for substances with characteristics (Iron presence, high
molecular weight > 200 and 99% for bacteria turbidity, scaling agents, etc.). A prompt
and pyrogen. The membrane is housed into anomalous pressure reading permits to
a fiberglass vessel. The estimated life length intervene in order to avoid irreversible
of the membranes in normal working damages.
conditions is 24 months

3) Pump by-pass valve: for models up to


2A) Pump discharge pressure gauge: 0 – 350 1600, manufactured in stainless steel. It
psi scale (0 – 25 bar); (item 2A). allows the recirculation of a portion of the
discharged flow and subsequently the
2B) Reject pressure gauge: 0 – 350 psi scale adjustment of the working pressure. The
(0 – 25 bar); (item 2B). adjustment has to be carried out together
with valves 8 and 9.

4 Aqua-Cleer MFP/3 – MFP/3-44 M000-15 - Rev. 06 – 04/2009


Figure No. 1 B FLOW DIAGRAM – Models 2200-2800-2800-3300

4) Minimum pressure switch: adjustable 8) Reject valve: manufactured in stainless


down to 7 psi (0.5 bar), for equipment stop steel. It allows the adjustment of the reject
in case of feed water low pressure (item 4). flow and subsequently of the pressures.
Together with valves 3 and 9 it is also
5) Electric motor: vertical type, for continuous possible to regulate the recirculation flow
operation (IP55 class F); see Table No. 1 for (item 8)
further characteristics (item 5).
9) Reject recirculation valve: manufactured in
6) Pump: vertical, centrifugal type, all parts in stainless steel. It allows the adjustment of the
contact with water are manufactured in portion of the reject flow to be recirculated
stainless steel (item 6). and subsequently of the pressures. Together
with valves 3 and 8 it is possible to adjust the
7) Inlet electrovalve: low voltage, normally reject flow (item 9)
closed type (NC), manufactured in plastic
material. For closing of the feed when the 10) Reject recirculation check valve:
equipment is not in duty. In case of electrical manufactured with plastic material. It avoids
breakdowns the valve can be manually the backflow of the feed water into the
operated (see picture No.1 V) (item 7). recirculation line and the by-passing of the
osmotic membrane (item 10).

M000-15 - Rev. 06 – 04/2009 Aqua-Cleer MFP/3 – MFP/3-44 5


11) Recirculation flow-meter: manufactured acoustic signal will confirm the function
with plastic material, 0 – 1500 l/h scale. It and the "clean" led will flash. The mode
allows the checking of the recirculation flow. “cleaning” allows to by-pass the pressure
switch (4), and the motor-pump assembly
Furthermore: (5-6) will work in direct suction, with no
- Electronic Control Panel regard to the pressure. In order to
Airtight, in plastic. Components comply with disactivate this function press on the
quality standards. Control circuit at 24 "clean" touch; the related led will switch off
Volts; the side switch 0-1 acts as main and the "Start/Power" light will flash.
switch. Note: Check in person that the supply of
feed water NEVER fails during this
- ON/OFF switch (0-1) phase.
The green "Start/Power" lamp flashes and
the timer for plant start-up after opening of - Yellow "low pressure" lamp
the NC inlet solenoid valve which allows If illuminated, indicates that the plant feed
feed (raw) water to enter also starts. At this water pressure is below 2 bar (or the
point the "Start/Power" lamp illuminates pressure switch setting value), which
steadily. After 30" from the solenoid valve always causes the motor-pump unit to cut
opening, the pressure gauge reads the out unless the "cleaning" switch has been
pressure: if it is over 0.5 bar, the HP pump used.
starts, the "Pump-run" light illuminates and Note: During this forced operation, the
the pressure switch is cut out for 10 yellow "low pressure" lamp will
seconds. flash, with an acoustic signal. You
Note: The Motor-Pump unit (5-6) will may reset the acoustic alarm, by
automatically come into operation, as pushing the "reset" touch. The
soon as the feed (raw) water "low pressure" function will be
pressure reaches or exceeds 2 bar activated again once the pressure
(or the pressure value preset on the preset values are reached, after
pressure switch). HP pump start.
Note: Delays are pre-set and non
modifiables - Plant power supply
The power supply can only be turned on by
- Cleaning placing the main switch on "1". At the same
The operator may use the "Cleaning" time, the green "Start/Power" lamp will flash.
function only when the "Start/Power" light The pump will not be started unless the feed
is flashing. In order to activate this water pressure is satisfactory.
function press the "clean" touch for 3". An

6 Aqua-Cleer MFP/3 – MFP/3-44 M000-15 - Rev. 06 – 04/2009


Table No. 1 TECHNICAL SPECIFICATIONS

Nominal Flow
Rates Product Connections Dimensions
Max Max inlet
Model Inlet max (1)
Flow water
flow Max Shipping
Rate of pressure Electric
MFP/3 rates Max energy
MFP/3 Drain membran 3-ph + Freque Weight
min MFP/3 adsorbed consu Width Depth Heigh.
44 (2) e earth + ncy
MFP/3 44 power mpion.
neutral
(Imax)
l/h l/h l/h l/h Psi (bar) V Hz KW A mm mm mm kg
400 2000 500 450 1685 200 (14) 380 50 1.6 2.7 500 660 1550 115
800 2000 1000 900 1370 200 (14) 380 50 1.6 2.7 500 660 1550 140
1200 3600 1500 1350 2655 200 (14) 380 50 2.3 3.9 500 660 1550 170
1600 3600 2000 1800 2340 200 (14) 380 50 2.3 3.9 500 660 1550 190
2200 5500 2500 2350 3925 261 (18) 380 50 4.2 7.1 500 660 1800 220
2800 5500 3000 2850 3610 261 (18) 380 50 4.2 7.1 500 660 1800 250
3300 5500 3500 3350 3295 261 (18) 380 50 4.2 7.1 500 660 1800 280

1) Average values based on the following standard conditions: temperature 20°C, operating pressure 14 or 18
bar (200 or 261 psi), recovery ratio 75%; TDS 500 ppm as NaCl; product water pressure 0 bar; new
membranes.
2) Maximum values based on the following conditions: temperature 10°C, operating pressure 200 or 261 psi (14
or 18 bar), taking into consideration the models, rejet recirculation closed and old membranes.

Note - Minimum Pressure of Inlet Water: 2 bar.


WARNING: never exceed nominal flow rates if necessary, reduce feed pressure.

Installation Instructions

SHIPMENT

Aqua-Cleer MFP/3 desalinators are shipped in a 3) The room must have adequate lighting and
single package and mounted on a wooden ventilation, and must have a suitable drain.
support.

POSITIONING THE DESALINATOR


PLACE OF INSTALLATION 1) Take off the cardboard packaging and
1) The dimensions of the room in which the remove the plant from the wooden support.
desalinator is installed must also provide
space for any other equipment required for 2) Place the plant on a solid base, preferably in
pretreatment of the water. concrete.

2) The room must be easily accessible both for


installation of the equipment and to allow
troublefree maintenance and checks.

M000-15 - Rev. 06 – 04/2009 Aqua-Cleer MFP/3 – MFP/3-44 7


Pre-assembling Instructions
(see Figure No. 2)

WATER CONNECTIONS FOR DIRECT USE OF - a 1” pipeline for the unit feed, connected with
THE OSMOTIZED WATER "WITHOUT the potable water to be trated, equipped with a
STORAGE TANK" closing valve;
- a water drain, sized upon the max discharge
This special water connection has been flow-rate of the connected unit, as per Table N.
developed in particular for medical applications 1;
(e.g. Dialysis Centres) and makes the following - if possibile, a gravity drain should be provided
operations possible: in the floor, in order to preved flooding in the
equipment room during maintenance
operations, when the pipes must be
1) Supply of osmotized water at pre-set
disconnected.
pressure with automatic recycling of the
excess water produced.
1) Make the water connections as shown in
Figure No. 2 (pre-assembling instructions).
2) Easy sanitization or chemical flushing of the
osmotic membranes by manual operation of
the PVC valves. 2) Check that the desalinator water supply
pressure is not less than 0.5 bar.
3) The plant can be by-passed without water
stagnating along the water circuit during 3) Check that the back-pressure downstream of
normal operation. the desalinator does not exceed 3 bar.

4) Samples of raw water and product


(osmotized) water can be taken by means of
ACCESSORIES
the PVC valves.
On the unit feed the following elements should be
provided:
5) The plant stops automatically in case of
- a pre-treatment system, in consideration of the
incorrect operation (closing of PVC service
variabilità of the water to be treated;
outlet valve).
- Just bifore the unit, a pressare reducer, with a
regulation range 0-210 psi (0-15 bar), with a
gauge for pressare control;
On the same line, a passive level sensor or a
WATER CONNECTIONS pressare switch might be installed.
The equipment room should be provided with the On the theated water distribution line for the
following pipino connections, closet o the unit dialyzers, a redox-meter should be installed, with
location: a reading range 0-1000 millVolt.

8 Aqua-Cleer MFP/3 – MFP/3-44 M000-15 - Rev. 06 – 04/2009


Figure No. 2 PRE-ASSEMBLING INSTRUCTIONS WITH PRESSURIZED DISTRIBUTION OF
OSMOTIZED WATER

Key
A) Pretreated water inlet: 1" steel collar G) PVC check valve, ¾": for installation O) Pressure switch 0-3 bar with manual
B) Osmotized water outlet: ½" steel in the opposite direction to the inlet reset
collar water flow direction P) PVC ball valve, ¾"
C) Reject water outlet: ½” steel collar or H) Pressure gauge 0-10 bar: product Q) PVC ball valve, ¾"
¾” for models 2200, 2800 and 3300 (osmotized) water outlet R) PVC ball valve, ¾"
D) PVC ball valve, ½” or ¾” for models I) Horizontal check valve in PVC, ¾": S) PVC ball valve, ¾"
2200, 2800 and 3300 (for installation in the osmotized T) Drain
E) Pressure gauge 0-10 bar: pretreated water flow direction)
19) Three-pole switch with fuses +
water inlet L) PVC ball valve, ¾" neutral + earth
F) Bronze pressure reducer ¾" M) PVC hose connection, ¾"
N) Reinforced polyethylene hose, ¾"

M000-15 - Rev. 06 – 04/2009 Aqua-Cleer MFP/3 – MFP/3-44 9


ELECTRICAL CONNECTIONS
(see Figure No. 3)

1) Install a three-phase power supply line with EXT 3


suitably protected switch close to the plant. (inlet external contact) (flushing)
2) Interconnect the power supply line to the - The EXT 3 external contact acts by
control panel on the desalinator. closing the inlet solenoid valve and by
3) Check that no jumper exists between cutting out the pressure switch PS- (*)
terminals (5) and (6) (EXT 1). during the operation of the MFP/3.
4) Interconnect the safety pressure switch, if (*) Note - The pressure switch PS- is
any, with manual reset (0) to terminals Nos 5 cut out during all flushing
and 6 (EXT 1 contact). function (EXT 3). For
interconnection between
- The EXT 3 contact (terminals L and M) is
EXT 3 and the general
used for flushing function, if any.
control panel it is necessary
to bring a 4-pole cable to the
electronic panel of the
AVAILABLE CONTACTS IN THE MFP/3: 2 poles to the
TERMINAL BOARD (Detail 3) terminals EXT 3 - 21/22, 2
poles in paralles to the
EXT 1
cables of the pressure
(Remote unit control from product level
switch PS-, terminals 1-2.
switch or product pressure switch)
Should the flushing not be
- This optional control input requires an foreseen, make a jumper
external volt free contact to start and with the contact EXT 3.
stop the unit on demand.
Please Note: when connected to a
EXT 4
remote device it it NOT necessary to
- The contact EXT 4 is closed in case
operate the “Start” button on the control
of alarm (overload, low pressure).
panel facia. Pressing of the “Start”
The contact is: NA-C-NC (clean
button will override the remote input
contact), terminals 9-10-11.
signal (EXT 1) and will not
automatically stop the unit on high level
or high pressure.
5) The flexibility of this electronic panel allows it
EXT 2 to operate with following feed:
(Outlet external contact) (feeder) - 230V - 50-60 Hz - Single Phase
- It is a clean outlet contact, in order to - 230V - 50-60 Hz - Three-Phase
show when the MFP/3 pump is - 400V - 50-60 Hz - Three-Phase
operating (may be used for control of a
- For the right connection of the unit with three-
dosing pump, or other devices,
phase power, please refer to the details of
Terminal 12-13).
Figure No. 4 and to the wiring diagram of
Note - During the clean function the Figure No. 3.
outlet contact EXT 2 is not
activated.

10 Aqua-Cleer MFP/3 – MFP/3-44 M000-15 - Rev. 06 – 04/2009


Figure No. 3 WIRING DIAGRAM

M000-15 - Rev. 06 – 04/2009 Aqua-Cleer MFP/3 – MFP/3-44 11


In this case (three-phase connection) the detail 2 Note - Before the connection with the HP pump-
connections remain unchanged, and it is necessary motor unit please check the operating
to move the jumper as shown in detail 1. power.
- For the right connection of the unit with single - Please check also that the fuses 1,2,3 are
phase power, please refer to the wiring properly sized in relation with power, phases
diagram of Figure No. 3. number, and pump-motor power (see Figure
No. 3) is the one shown in the table below.

FUSE TABLE (in relation with voltage and power)

MFP/3 230/50 Voltage 3-ph 380/50 Voltage 3-ph 230/50 Voltage 1-ph

MFP/3 44 Pump Pump Pump


Fuse Q.ty Fuse Q.ty Fuse Q.ty
Model kW kW kW
400 1,5 8A 3 1,5 4A 3 1,5 10A 2
800 1,5 8A 3 1,5 4A 3 1,5 10A 2
1200 2,2 10A 3 2,2 6A 3 2,2 16A 2
1600 2,2 10A 3 2,2 6A 3 2,2 16A 2
2200 4 10A 3
2800 4 10A 3
3300 4 10A 3

Figure No. 4

Key
INDICATOR TYPE COLOUR FUNCTION
OVERLOAD Lamp red Thermical Cut-out
CLEAN Touch yellow Sanitization Start
LOW PRESS Lamp yellow Inlet Low Pressure
RESET Touch -- Acustic Alarm Switch-off
PUMP RUN Lamp green HP Pump in Operation
START/POWER Touch green Unit Start-up

12 Aqua-Cleer MFP/3 – MFP/3-44 M000-15 - Rev. 06 – 04/2009


Preparatory Instructions
(see Figure No. 5)

When the plant is put into operation for the first 9) Open the valve (D) on the pretreated water
time, it is essential to fill the water circuit and inlet line.
flush out the membranes to remove the 10) Check on the pressure gauge (E) that the
disinfectant solution they contain (Aldehyde, inlet water pressure is between 0.7 and 3
Bisulphites or other substances). bar.
During this operation it is vital that the 11) Turn the switch (13) to "1" (ON).
osmotized water should be sent directly to
Note - The green "Start/Power" light (14)
the drain.
on the control panel illuminates and
at the same time the NC solenoid
valve (7) on the pretreated water
FILLING THE WATER CIRCUIT inlet is activated, allowing the water
to fill both the water circuit and the
high pressure pump (6).
1) Check that the valves (D-L) on the
This operation can be considered complete
pretreated water inlet line and on the
when water has been flowing from the valve
osmotized water line are closed.
(S) for a few minutes.
2) Open the valve (R) and check that the valve
12) Turn the main switch (13) back to "0" (OFF)
(S) is closed.
and check that the green "Start/Power" light
3) Fit the plastic pipe into the hose-connection (14) has switched off.
of the valve (Q) and connect it to the drain.
4) Open the valve (Q) and check that the valve
(P) is closed.
PRESET DELAYS
5) Completely open the needle valve (8) on the
reject water line (drain) and close the
needle valves (3-9). Whenever the plant is started up the high
6) Ensure that the power master switch (19) on pressure pump (6) comes into operation with the
the power supply line is turned off. delay preset (30 seconds).
7) Check that the white screw (U) called "Off This delay is necessary to allow the hydraulic
Limit Stop" on the head of the NC solenoid circuit to pressurize after the solenoid valve (7)
valve (7) is completely unscrewed. has been opened.
Note - This screw controls the opening of Whenever the high pressure pump (6) is started
the solenoid valve diaphragm. up, the minimum pressure switch is enabled with
a delay preset on the timer (10 seconds). This
8) Check that the lever (V) beside the NC
delay is necessary to allow the pressure to
solenoid valve (7) has its pointer facing the
stabilize after the high pressure pump (6) has
letter "A".
started.
Note - The lever (V) must only be moved to
Note - If the pressure does not stabilize, the
letter "C" if the solenoid burns out,
high pressure pump is automatically
since in this position the solenoid
stopped.
valve is by-passed.

M000-15 - Rev. 06 – 04/2009 Aqua-Cleer MFP/3 – MFP/3-44 13


Figura No. 5 DIAGRAM SHOWING INSTRUCTIONS FOR START-UP WITH PRESSURIZED
DISTRIBUTION OF OSMOTIZED WATER

KEY
A) Pretreated water inlet: 1" steel L) PVC ball valve, ¾" (2B) Reject pressure gauge
collar M) PVC hose connection, ¾" (3) Regulation pin valve on working
B) Osmotized water outlet: ½" steel N) Reinforced polyethylene hose, ¾" pressure (by-pass pump)
collar (4) Adjustable range pressure switch
O) Pressure switch 0-3 bar with manual
C) Reject water outlet: ½” steel collar with maual re-activation
reset
or ¾” for models 2200, 2800 and (6) Motor pump kit
P) PVC ball valve, ¾"
3300 (7) Solenoid valve NC RO inlet
Q) PVC ball valve, ¾" (8) Regulation pin valve drain water
D) PVC ball valve, ¾” R) PVC ball valve, ¾" (9) Regulation pin valve recirculation
E) Pressure gauge 0-10 bar: S) PVC ball valve, ¾" water
pretreated water inlet
T) Drain (10) One way valve
F) Bronze pressure reducer ¾" (11) flow meter
U) Regulation screw for electrovalve
G) PVC check valve, ¾": for opening (12) skid
installation in the opposite direction V) Manual valve open/close (13) general switch (0-1) on the control
to the inlet water flow direction Z) Reinforced flexibel polietilene tube panel
H) Pressure gauge 0-10 bar: product dia ¾” (19) Three-pole switch with fuses +
(osmotized) water outlet W) 1” hose adapeter in PVC neutral + earth
I) Horizontal check valve in PVC, ¾": (1) Osmotic module
(for installation in the osmotized (2A) Pressure gauge in the outlet of
water flow direction) the pump

14 Aqua-Cleer MFP/3 – MFP/3-44 M000-15 - Rev. 06 – 04/2009


Start-up Instructions
(see Figure No. 5)

1) Adjust the pressure reducer (F) until the exceeds 13 bar for models up to
pressure value indicated by the pressure 1600, and 18 bar for models up to
gauge (E) is the same as the operating 3300, slowly open the needle valve
pressure value requested by the (9) on the recycling water line, until
customer. the pressure gauge (2A) shows a
Note - In no case must the water constant pressure of 13 bar or 18 bar
pressure be below 0.7 bar or over according to the model.
3 bar. Example:
2) Turn the main switch to "1" (ON). plant model Aqua-Cleer MFP/3 400
This provides two effects simultaneously: Product water
A) excitation of the solenoid valve (7) on (osmotized) : 8.3 l/m
the pretreated water inlet, and Reject water
illumination of the green "Start/Power" (drain) : 8.3 l/m
light;
Operating pressure : 13 bar
B) start-up, delayed by 30 seconds, of
6) Allow water to drain from the system until
the high pressure pump (5-6), and
all the sanitizing solution has been
illumination of the green "Pump Run"
completely eliminated, checking both the
light.
product (osmotized) water and the reject
3) Check that the motor runs in the direction water (drain).
of the arrow on the motor housing.
Note - If the motor runs in the opposite
direction, stop the plant by turning
SETTING THE FLOW RATES
the main switch to "0" (OFF) and
reverse two-phase wires on the In order to reduce the quantity of reject water,
terminal board of the motor (5). some of it may be recycled by setting the needle
valves (8-9) appropriately.
4) Set the tripping threshold of the pretreated
water low pressure switch (4) at a value of
1 bar (minimum).
Note - If the inlet water pressure is below RECOVERY RATE (RR)
the setting value, the plant stops The recovery rate represents the percentage of
automatically and the yellow low product water in relation to the flow rate of inlet
pressure warning light on the water entering the plant.
control panel illuminates.
5) With the plant in operation, make the quantity of product water (QP)
RR = x 100
following adjustments: quantity of inlet water (QI)
- Check that the needle valve (3) is
completely closed. Since the delivery rate of the plant feeding
- Regulate the needle valve (8) on the pumps vary depending on the operating
reject water line until the flow rate of pressure, it is more practical to calculate the real
water to the drain is the same as the inlet flow rate as the sum of the product water
product (osmotized) water flow rate. QP and of the drain water (QD).

- Check the operating pressure on the QI = QP+ QD


pressure gauge (2A) and, if the pressure

M000-15 - Rev. 06 – 04/2009 Aqua-Cleer MFP/3 – MFP/3-44 15


INCREASING THE RECOVERY RATE Therefore, if the recovery rate of the MFP/3 400
In order to reduce the quantity of water going to plant is to be increased to 65%, the needle valve
the drain, some of it may be recycled. must be set so that:
In this way the Recovery Rate may be increased 8.3
Q Drain = x (100 - 65) = 4.5 l/minute
by about 50% up to 75% maximum. 65
Once the necessary adjustments have been
made, proceed as follows:

CHECKS AND ADJUSTMENTS 1) Turn the main switch to "0" (stop) and check
that the green "Start/Power" light is off.
1) Ensure that the by-pass needle valve (3) is
set so that the pressure gauge (2A) reads a 2) Close the valve (Q) and open the valves
constant pressure of 14 or 18 bar. (P-L).
2) With the aid of a graduated bucket and a 3) Set the safety pressure switch with manual
watch, measure the flow rates of product reset (0) at 3 bar. This safety pressure
and reject water, which must be more or switch with manual reset is only tripped with
less the same. a service back-pressure of 3 bar, and shuts
3) Establish the recovery rate required (see down the plant completely. The possible
example below), and adjust the needle causes of this malfunction are:
valves (8-9) until the flow meter shows the
A) the valve (P) is closed
preset flow rate value.
Example: standard operating conditions. B) the check valve (G) is blocked in
Aqua-Cleer MFP/3 400 closed position and there is no request
(Recovery Rate 50% at pressure 14 bar). for water from the service.
4) Return the switch to "1" (ON) and press the
l/minute touch "Start/Power".
Rated flow rate of
= QP 8.3
product water THE PLANT IS NOW IN OPERATION.
Rated flow rate of
= QD 8.3
drain water
5) Check the pressure on the pressure gauge
Inlet water flow rate =QI = QP +QD 16.6 (2B) and the pressure indicated by the
pressure gauge (2A) on the control panel.
QP 8.3 The pressure difference indicates the
RR *= x 100 = x 100 = 50% membrane headloss.
QI 16.6
6) To stop and start the plant, use the
* Recovery Rate "Start/Power" switch on the control panel.

CALCULATING THE REJECT WATER FLOW


OPERATING CHECK ON SAFETY PRESSURE
RATE TO OBTAIN AN INCREASE IN RR
SWITCH WITH MANUAL RESET (0).
To increase the recovery rate, a proportion of the
1) With the plant in operation close the valve
drain water is recycled as described above.
(P).
This means that the plant's real drain flow rate
Note - The plant must stop operation
becomes:
immediately.
2) Reopen the valve (P) and reactivate the
Q Product pressure switch.
Q Drain = (x 100 - RR)
Recovery Rate

16 Aqua-Cleer MFP/3 – MFP/3-44 M000-15 - Rev. 06 – 04/2009


BY-PASSING THE DESALINATOR PRODUCT CORRECTION FACTOR IN
If the desalination plant has to be by-passed for RELATION TO TEMPERATURE
more than 3-4 days the membrane(s) must first
be sanitized (see sanitization section). Then Inlet Water Temperature Correction Factor
proceed as follows: 10°C 0.63
1) turn the switch on the control panel to "0" 11°C 0.67
(off) and disconnect the power supply using 12°C 0.71
the main switch outside the system. 13°C 0.74
2) Close the pretreated water inlet valves 14°C 0.77
(D-R). 15°C 0.81
16°C 0.86
3) Eliminate the hydraulic pressure from the
17°C 0.89
lines by opening the valves (S-P-Q) for a
few seconds. 18°C 0.93
19°C 0.96
4) Disconnect one end of the reinforced PVC
20°C 1*
hoses (N) and interconnect the end of the
21°C 1.04
pretreated water inlet hose to the connection
(M) to by-pass the horizontal check valve (G). 22°C 1.07
23°C 1.11
5) Open the valve (D).
24°C 1.14
25°C 1.18
THE PLANT HAS NOW BEEN BY-PASSED. 26°C 1.23
27°C 1.26
CAUTION: when the desalinator is put back into 28°C 1.31
operation, follow the "Preparatory 29°C 1.36
Instructions" for initial start-up of the 30°C 1.40
plant, on page 14. * Nominal Capacity at 20°C

M000-15 - Rev. 06 – 04/2009 Aqua-Cleer MFP/3 – MFP/3-44 17


Sanitization

GENERAL DESCRIPTION A) Whenever the plant is to be out of service


The sanitization of reverse osmosis plants is an for periods exceeding 3-4 days.
essential operation to prevent the proliferation of B) When the osmotized water is contaminated
microorganisms (bacteria, algae, fungi, etc.). by bacteria.
The proliferation of bacteria in the membranes is C) Whenever the membranes are replaced, in
harmful for the following reasons: order to sanitize the entire water circuit of
the plant.
1) some bacteria have scale-forming
properties: one typical example are ferro- D) Systematically every 6 months.
bacteria, which precipitate in the form of E) Whenever the membranes are flushed with
Iron hydroxide (Iron in solution in the water). an organic agent.
2) If the inlet water is seriously polluted, the Note - For certain medical applications of
proliferation of bacteria may clog one or the osmotized water, sanitization
more of the membranes (algae). may be required more frequently,
3) The proliferation of certain forms of bacteria but this must be decided by the
may occur on the permeable side of the Health Authority.
membrane and thus threaten the
bacteriological quality of the product
(osmotized) water.
PREPARING THE SANITIZATION SOLUTION
This is done using a concentration of Peracetic
acid, Glutaraldehyde, Formaldehide at the
SANITIZATION FREQUENCY concentration admissable for the R.O.
The frequency with which plants must be membranes, and in accordance with the
sanitized depends on the quality of the inlet Directives in force.
water and the required quality of the product After the sanitization, qualified personnel must
water. check, by means of appropriate test-kits, that
When plants are installed in hospitals or there is no traces of sanitizing solution in the
laboratories, this operation is advisable at least unit.
twice a month. However, since bacteria tend to
proliferate when in a stagnant environment,
sanitized is essential in the following cases:

18 Aqua-Cleer MFP/3 – MFP/3-44 M000-15 - Rev. 06 – 04/2009


Instructions for Sanitization with Pressurized Distribution of
Osmotized Water
(see Figure No. 5)

1) Prepare the quantity of sanitizing solution 10) Use the key to turn off the CLEAN switch.
required for the plant concerned in a Note - this reactivates the low pressure
container. switch (4).
2) Fit a plastic tube onto the hose connection 11) Leave the plant to stand for about two hours
of the PVC valve (S) and insert it into the before starting to flush the sanitizing
sanitizing solution container. solution out of the membrane.
3) Fit a plastic tube onto the hose connection Note - For temporary lay-offs, or for shut-
of the PVC valve (Q) and send it to the downs lasting more than 3-4 days,
drain (T). leave the sanitizing solution in the
4) Switch off the power supply to the plant by system. The membrane(s) must not
turning the switch on the control panel to "0" be flushed out until the plant is put
(OFF). back into operation.
5) Shut the PVC valves (D-R-P-L). The procedure is as follows:
6) Open the PVC valves (S-Q). 12) Close the PVC valve (S).
7) Turn the main switch on "1" position and 13) Open the PVC valve (D-R) allowing inlet of
activate the "cleaning" function by pushing pretreated water.
the related touch for 3-4 seconds. 14) Turn the main switch on the control panel to
Note - The use of the key on the "1" ON, press the "Start/Powr" touch and
CLEANING switch by-passes the allow water to flow from the PVC valve (Q)
low pressure switch (4), allowing the until all the sanitizing solution has been
motor-pump unit (5-6) to operate in eliminated.
direct suction regardless of the Note - Before putting the system into
pressure. and enabling the high service, analyze the product
pressure pump to draw in the (osmotized) and reject (drain) water
sterilizing solution at atmospheric using test to ensure that the water
pressure. does not contain any sanitizing
8) Check that the sanitiizing solution is flowing solution.
out of the PVC valve (Q) to the drain. 15) Turn the main switch to "0" (OFF).
9) CAUTION: switch off the power supply to 16) Shut the PVC valve (Q).
the plant using the switch on the control
17) Open the PVC valves (P-L).
panel before the container of sanitizing
solution is completely empty: 18) Turn the main switch to "1" (ON).

Note - The high pressure pump cannot 19) Check that the plant is working properly,
operate without water since the following the "Start-up Instructions" on page
teflon bushings would be damaged 14.
immediately.
THE PLANT HAS NOW BEEN SANITIZED AND
IS IN OPERATION.

M000-15 - Rev. 06 – 04/2009 Aqua-Cleer MFP/3 – MFP/3-44 19


Trouble-Shooting Chart
(see Figures Nos 1 "Flow Diagram" and Figure No. 3 "Wiring Diagram")

Problem Remedy Cause


1) Plant receiving power, main A) Power supply socket 380 V a) Check and eliminate the
switch on control panel 50 Hz + neutral + earth not cause.
turned on and green receiving power.
"START/POWER" lights off.
B) The fuses (F4-F5) b) Check and replace after
protecting the control circuit identifying the cause.
have blown.
2) Switch "Start/Power" turned A) The fuses (F1-F2-F3) a) Replace the fuses and check
on, red lamp "Overload" protecting the control circuit for the cause.
illuminated, and pump- have blown.
motor unit (5-6) does not
work.
3) Unit out of operation for low A) Water pressure inadequate. a) Open the manual PVC valves
pressure. Yellow lamp illuminated. (D-R).
B) Low pressure switch (4) b) Check operation of the
incorrectly set. pressure switch.
C) Solenoid valve (7) not c) Check operation of the
working. solenoid valve.

D) Filtr-Gard cartridges dirty. d) Check the state of the Filtr-


Gard cartridges and replace if
necessary.
4) Insufficient pump pressure. A) The needle valves (3-8-9) a) Check and adjust or replace if
which regulate the high necessary.
pressure pump (5-6) are
faulty or badly set.
B) Osmotic membrane(s) b) Check and replace only if
is/are faulty. beyond recovery.
C) Motor running in wrong c) Reverse two phases on the
direction. motor terminal board.
5) Poor quality product A) See point 3). a) See point 3).
(desalinated) water. B) the chemico-physical b) Check the quality of the raw
characteristics of the inlet water.
water have changed. c) Modify the chemical
pretreatment.
d) Modify the reject water
recovery percentage.
6) Product water flow rate A) See point 3). a) See point 3).
insufficient. B) Inlet water temperature b) Increase the temperature of
too cold. the inlet water to 20°C (if
possible).

20 Aqua-Cleer MFP/3 – MFP/3-44 M000-15 - Rev. 06 – 04/2009

You might also like