CONCRETE COMPRESSIVE STRENGHT TEST REPORT NF EN

12390-3
Number of Test Report 228
Project CONGO – BIOFUEL 1st AGRI HUB - INDUSTRIAL START-UP
Contractor ZEROCK CONSTRUCTION CONGO
Origin of Concrete Zerock Concrete Batching Plant in Loudima

Temperature 29.7 / 28.6 °C Size of specimen (16 x 32 cm) x 3


Pouring date 12/3/2023 Slump test at 0' 14.5 cm
Mix Design Code 25 - XC4 - D25 - S3 - 42.5N - SHR - S0/1
Composition Cement Water Sand Gravel 1 Gravel 2 Admixture
Type 42,5N - 0/1 5/12,5 16/25 Admix150
Quantity(Kg/m3) 450 178.78 574 260 1018 4
Part of Structure

2nd line Production / Paving / Paving_F32L-F31; Paving_F31-F12; Paving_TR16-F27

30A100_RFI_299 EXT
Number notification Date of receipt 12/6/2023
30A100_RFI_340 EXT
Curing by Density Strength (Mpa)
Spec. Tag Crushing date Weight (Kg) Load (kN)
days (T/m3) Unit Average
AH1195 15.86 2.47 382.97 19.05
AH1196 7 12/10/2023 15.76 2.45 402.91 20.04 19.15
AH1197 15.92 2.48 369.46 18.38
AH1198 15.76 2.45 500.16 24.88
AH1199 28 12/31/2023 15.78 2.45 336.74 16.75 18.45
AH1200 15.76 2.45 275.90 13.72

Number notification 30A100_RFI_391 EXT Date of receipt 1/27/2024

Density STRENGHT (Mpa)


Spec. Tag Age Crushing date Weight (Kg) Load (kN)
(T/m3) Unit Average
AH1201
AH1202 57 1/29/2024
AH1203

Inspectors for : GEOLAB ENI CONGO ZEROCK