CONCRETE COMPRESSIVE STRENGHT TEST REPORT NF EN 12390-

3
CONTRACTOR Zerock CTR N° 121 30A100_RFI N°: 131 EXT MIX DESIGN

2nd line Production / Bucket Elevator - BE2;


PROJECT 1st Agri Hub PART OF STRUCTURE Bucket Elevator - BE8; Seed Cleaner Bag Filter A / F14 TRIAL MIX
base; F16base; F24base; F31base; F12 base

POURING DATE 8/25/2023 ORIGIN OF CONCRETE Zerock Batching plant Loudima INFORMATION ✘

TEMPERATURE 26,2 / 30,6 °C SIZE OF SPECIMEN 16 x 32 cm DATE OF RECEIPT 8/30/2023

MIX DESIGN CODE 25-XC4-D25-S3-42.5N-SHR-S0/1


COMPOSITION OF CONCRETE CEMENT WATER SAND GRAVEL 1 GRAVEL 2 ADMIXTURE SLUMP TEST SPECIFIED

TYPE 42,5N - 0/1 5/12,5 16/25 ADMIX150 SLUMP TEST 0' 13,9 cm
THEORICAL (Kg/m3) 450 178.78 574 260 1018 4 SLUMP TEST 30'

COMPACTION Vibration CURING Water immersion

SPECIMEN AGE WEIGHT DENSITY LOAD COMPRESSIVE STRENGHT


CRUSHING DATE FAILURE
REFERENCE
(J) (Kg) (T/m3) (KN) MPa AVERAGE
AH553 7 9/1/2023 15.72 2.44 499.89 24.86 Correct
AH554 7 9/1/2023 16.04 2.49 445.21 22.14 23.58 Correct
AH555 7 9/1/2023 15.76 2.45 477.25 23.74 Correct

Remarks

Inspectors for : GEOLAB ENI CONGO ZEROCK


Name
Signature
Date
Roulé
Concassé

Correct