SCALE NTS
NOTES:
SERVICE METER
(EXTERIOR) 1. ALL ELECTRICAL INSTALLATION WORKS SHALL BE DONE IN ACCORDANCE WITH THESE PLANS AND SPECIFICATIONS,
APPLICABLE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE, RULES AND REGULATIONS OF
ELECTRIC UTILITY UTILITY THE LOCAL ENFORCING AUTHORITY AND THE REQUIREMENTS OF THE LOCAL POWER COMPANIES. THE ELECTRICAL WORK
KWH METER M SHALL BE UNDER THE IMMEDIATE SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER.
2. THE ELECTRICAL SYSTEM UTILIZATION VOLTAGE SHALL BE 230V, 1-PHASE, 3-WIRE, 60HZ.
230V SOURCE FROM 50kVA TRANSFORMER
DISTRIBUTION UTILITY 34.5kV/230V, 1-PHASE
3. LOW VOLTAGE BUILDING WIRING SHALL BE MADE OF COPPER AND THERMOPLASTIC INSULATED TYPE THW/THHN UNLESS
MCB-1 OTHERWISE INDICATED. THE MINIMUM SIZE FOR POWER AND LIGHTING SHALL BE 3.5sqmm.
250AT/250AF,
2P,230V 4. THE CONTRACTOR SHALL VERIFY AND ORIENT ACTUAL LOCATION OF INCOMING POWER FOR CONNECTION.
NEMA 3R
5. ALL SERVICE ENTRANCE EQUIPMENT, PANEL BOARDS, LIGHTING FIXTURES AND ALL NON-CURRENT CARRYING METAL
DRAWING FILE:C:\Users\Ian Carlos Ancheta\OneDrive - Miescor Infrastructure Development Corporation\Desktop\MIESCORv3.0\1. STANDARDS\1. SINGLE LINE DIAGRAM\1.2. SLD DESIGN VERSION
PARTS SHALL BE PROPERLY GROUNDED IN ACCORDANCE WITH THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL
CODE.
6. ALL 20-AMPERE CIRCUIT HOMERUNS TO PANEL BOARDS OF MORE THAN 30 METERS IN LENGTH SHALL BE 5.5 sqmm. UNLESS
SITE VICINITY
MCB-2 OTHERWISE SPECIFIED.
(INTERIOR)
250AT/250AF,
PROVIDE EXTENDED 2P,230V 7. ANY DISCREPANCY IN LOCATION AND RATINGS OF EQUIPMENT AND APPARATUS SHALL BE VERIFIED WITH THE
BUSBAR WITH LUGS NEMA 3R ENGINEER/OWNER OR ANY OF HIS REPRESENTATIVES AND CHANGES SHALL BE MADE ACCORDINGLY.
2-80mm² THHN +
1- 14mm² THHN (G) 8. ALL MATERIALS TO BE USED AND EQUIPMENT TO BE INSTALLED SHALL BE NEW AND MUST BE OF THE APPROVED TYPE FOR
IN 50mmØ IMC THE PARTICULAR LOCATION AND PURPOSE INTENDED.
ATS 10. ALL UNITS SHALL BE IN MILLIMETERS UNLESS OTHERWISE SPECIFIED IN THE DRAWING.
250A MOTORIZED
DITO-MCB
160AT/200AF,
TRANSFER WITH
MANUAL
Gs STAND-BY GENSET
37.5kVA, 1PH, 230V, .8pf
11. COORDINATE WITH ALL OTHER TRADES FOR PROPER PLACEMENT OF HANDHOLES AND SERVICE BOXES WITH RESPECT TO
OTHER UNDERGROUND/CONCEALED UTILITIES.
2P,230V CHANGEOVER
NEMA 3R SWITCH 12. ALL PANEL BOARDS SHALL BE INSTALLED GREATER THAN 1.6 METERS FROM TOP OF PANEL AND ABOVE FINISHED FLOOR
OPTION 1 LEVEL.
13. KINDLY REFER TO SITE DEVELOPMENT PLAN FOR THE ACTUAL NUMBER OF TELCO PROVIDER SERVED.
PROVIDE OPENING WITH LOCK FOR
80mm² MOBILE GENSET FEEDER 14. COLOR CODING OF WIRES AND CABLES ARE AS FOLLOWS:
MTS
250AT/250AF, A.SINGLE PHASE B. THREE PHASE
2P,230V LINE 1- BLACK LINE 1- BLACK
NEMA 3R LINE 2- RED/BLUE LINE 2- RED/BLUE
2-125mm² THHN + GROUND- GREEN LINE 3- YELLOW
1- 30mm² THHN (G) GROUND- GREEN
IN 50mmØ IMC
160AT, 2P 200AT, 2P
TO DITO TELCO
(OPTION 2) 1
MIDC
MIDC TELECOMMUNICATION TOWER
PROFESSIONAL ELECTRICAL ENGINEER STANDARD DRAWING
PLACE ISSUED: LONGITUDE: --- LATITUDE: --- DRAWN CHECKD APPRVD MIDC-###-E-0021 1