INFORMATION
ARC FLASH AND SHOCK HAZARD
!
NO PPE REQUIRED
ARC FLASH AND SHOCK HAZARD EVALUATION
Switchboard: EDB-79101 Protective device tag: T2N-160
Voltage: 0.208 kV Arcing current at busbar: 0.878 kA
Minimum working distance: 457.2 mm Boundary energy: 1.2 cal/cm²
Incident energy at min. working distance: 0.28 cal/cm² Limited approach*: 3.0 m/1.0 m
Arc flash protection boundary, PPE required within: 0.224 m Restricted approach: 0.3 m
MINIMUM PPE REQUIREMENTS**

*For exposed movable conductor / fixed circuit part ** For more information, see NFPA 70E standard.
Prepared on: 7/11/2023 WARNING: CHANGES IN EQUIPMENT SETTING ABB s.r.o., Nova Karolina Park, 28. rijna

ABB
Project no.: 0 OR SYSTEM CONFIGURATION WILL INVALIDATE 3348/65, 702 00 Ostrava, Czech Republic
PRESENTED CALCULATED VALUES AND PPE Tel.: +420733693847
Rev.: A REQUIREMENTS. E-mail: jan.veleba@cz.abb.com