R O T A R Y
A D D R E S S I N G
Intelligent Manual
Pull Stations
FX-270, FX-278
Device Addressing T
L ITF
Use a screwdriver to adjust the two rotary switches on the front of L IF
Glass rod
the module. Set the TENS rotary switch (0 through 12) for the 10s release lever
digit and the ONES rotary switch for the 0 through 9 digit.
5 6 7 89 3
4 5
6
4
3 10 2 7 Screw
2 11 1 8
1 0 12 0 9
Example: Insert
device screwdriver
address 21, sethere
TENS rotary switch to 2 FX-278 Double Action Pull Station
and set the ONES rotary switch to 1. Compatible
electrical
Refer to the Specifications Table for available address numbers. box
Wiring
Back
Toggle plate
switch Glass rod
( )
To next OPEN
device ( )
Screw
Key-latch
From ( ) cover release
previous
device
[1]
[1] Refer to the control panel technical reference manual for wiring
specifications
2. All wiring is power-limited and supervised
Ordering Information
Catalog
Number Description Ship Wt. lbs (kg)
FX-270 Single Action Fire Pull Station, Kidde Addressable
1 (0.5)
FX-278 Double Action Fire Pull Station, Kidde Addressable
Warning Caution
These pull stations will not operate without electrical power. As fires
Wire in accordance with NFPA 72 and CAN/ULC-S524. Be sure to
frequently cause power interruption, you should discuss further
observe the polarity of the wires as shown in the diagram.
safeguards with your local fire protection specialist.