This handbook is aimed at installers of medium-voltage un-
derground cable accessories, focused on cable preparation
and correct usage concerning recommended tools. Comple-
mentary information of cable accessories, tubing technology
and cable construction is also included.
Table of Contents
3
Installers play a key
role in the reliability of
underground distribution
networks.
Medium-voltage cable accessories
Cable joint
A cable joint is used to connect two ca-
bles together.
Termination
A cable termination is used at the end of
the line to permanently connect a cable
to the terminal of a piece of equipment.
5
Heat-shrink technology
6
Cold-shrink and hybrid technology
The reliability of several com- Cold-shrink accessories are the solution Ensto manufactures medium-voltage
ponents integrated into one in places where hot work is not possible cold-shrink and hybrid joints, termina-
or permits are difficult to obtain. A sili- tions (for indoor and outdoor use) and
body and shorter installation cone body with integrated components screened separable connectors.
times are the main advantages is molded and then pre-expanded on a
of cold-shrink and hybrid tech- spiral or tube, ready to be installed with- Why silicone?
out using any flame. > Great molding performance
nologies. > Resistant to environmental stress,
Hybrid accessories include silicone such as UV radiation, heat, moisture,
bodies with heat-shrink outer sealing oil and ozone.
tubes, an alternative that combines > Inorganic material that doesn’t absorb
the advantages of both cold and heat- dirt and humidity, therefore insulation
shrink technologies. properties remain excellent.
7
Cable preparation
In most cases, faults that oc- The cable preparation process is criti- Insulation material
cur in cable accessories are cal. The accessory emulates the struc- The insulation material most widely
ture of the cable, layer by layer, and used in modern underground polymer-
the result of errors in cable provides a safe and reliable transition ic insulated cables are cross-linked poly-
preparation. when jointing with another cable or ethylene (XLPE) and ethylene propylene
terminating the cable at the end of the rubber (EPR).
line.
At the core of an underground cable,
Polymeric insulated extruded cables the conductor screen, the insulation
Cables with extruded polymeric insu- and the insulation screen are co-extrud-
lation have a very consistent structure ed. Installers must carefully prepare the
among different models and manufac- insulation and the screen, because the
turers. The main differences from the in- electrical behavior is controlled by these
staller perspective are the types of insu- parts of the cable and their equivalent
lation screen and the different methods or corresponding part in the accessory
and tools for correct handling. kit.
8
Basic construction of an extruded cable
1 2 3 4 5
1 3 5
9
Outer sheath and metallic screen
The metallic screen defines The outer sheath provides protection Materials and features
what tool can be used for re- to the cable. It insulates the metallic The outer sheath must be fire retard-
screen from the ground and protects ant and protect the cable from the en-
moving the outer sheath. from corrosion and humidity. vironment (animals and weather). PVC
and PE are widely used for their me-
The metallic screen keeps the field con- chanical strength and fire retardant
tained within the cable, contributes to properties, but corrosive and toxic
waterproofing (in the case of aluminum fumes are released if the burning point
laminate) and allows partial circulation is reached.
of short-circuit currents.
Halogen-free, fire-retardant materials
Always clean the
Also, relevant information about the are not as mechanically strong as PVC
outer sheath
cable is marked or printed on the out- or PE but reduce the spread of fire and
before removal.
er sheath, i.e., cable type, nominal fumes harmful to personnel and equip-
voltage, cross section, manufacturer, ment in case of fire.
phase marking, etc.
The metallic screen is made of aluminum
Function of the outer sheath or copper. The two most typical screens
> Insulation and corrosion protection in extruded cables are aluminum lami-
for the metallic screen nate and copper wires. The aluminum
> Reduction of the contribution of cables laminate is removed with the outer
to fire propagation sheath and extended with a grounding
> Mechanical protection grater or braid. Copper wires are treated
> Information about the cable independently and terminated or jointed
by a lug or connector.
10
Outer sheath removal
Multifunction tool for outer sheath and insulation removal Scan QR code for video
demonstration or click here.
11
Outer sheath removal
Universal cable stripper with fast locking system Scan QR code for video
demonstration or click here.
12
Outer sheath removal
Complementary tools
Ensto ST285 for outer sheath longitudinal cut. The tool splits
the MV cable outer sheath and aluminum laminate for a dis-
tance of 40 mm. Application ø is 16-60 mm.
13
Outer sheath removal
Plier for outer sheath Scan QR code for video
demonstration or click here.
14
Outer sheath removal
Waterproofing Scan QR code for video
demonstration or click here.
Instructions
> Grind the cutback of the cable outer
sheath according to installation instruc-
tions. Grinding should be performed
parallel to the cut of the cable (1).
> Clean the cable outer sheath after
grinding to ensure correct adhesion
of the sealing mastic and the glue un- 2
der the outer sealing tube (2).
Always clean
the outer sheath
before removal
and after
grinding it.
15
Outer sheath removal
Hot opening
16
Insulation screen
Insulation screen is also known Bonded insulation screen Strippable insulation screen
as the semi-conductive layer. Consists of a black cross-linked com- Also known as “easy strip”. Not ful-
pound that requires rotating stripping ly bonded to the insulation and must
It prevents concentration of tools for removal. To avoid dangerous be strippable by hand. Rotating tools
electrical field at the interface concentrations of electric field, avoid with adjustable depth length are rec-
between the insulation and sharp edges in the edge of the semi- ommended for its removal. The use
conductive layer. Grinding the insula- of unguarded knives is forbidden due
the metallic screen. It can be tion is recommended after removing a to the risk of damaging the insulation
bonded or strippable. When bonded insulation screen. and causing discharges. Cables with
terminating or jointing a me- strippable insulation screen require no
grinding of the insulation after screen
dium-voltage cable, part of the removal.
insulation screen must be re-
moved.
17
Insulation screen removal
Bonded semiconductor stripper Scan QR code for video
demonstration or click here.
18
Insulation screen removal
Peelable non-vulcanized semiconductor stripper Scan QR code for video
demonstration or click here.
19
Additional comments on
the insulation screen
20
Insulation
The insulation thickness is de- Extrusion The conductor screen is removed to-
fined by the rated voltage of Plastic polymeric insulated cables are gether with the insulation. When in
three-layer extruded: place, it ensures a good contact and
the cable. Cross-linked poly- > Conductor screen: Semi-conductive, fills any voids between the conductors
ethylene (XLPE) and ethylene between the conductors and the in- and the insulation, while diminishing
propylene rubber (EPR) are sulation material. the concentration of field at the surface
> Insulation: High resistivity of the conductors.
common insulation materials. > Insulation screen: Semi-conductive, > Save the bags of the tubes, joint or
between the insulation material and termination bodies to cover the insu-
the metallic screen. lation and use them after screen re-
moval and before grinding as protec-
Treating the insulation tion for the insulation or the silicone
After removing the insulation screen, body parts.
part of the insulation is removed for con- > When cleaning the insulation, always
necting a lug or connector. The remaining begin from the external side and con-
peeled insulation must have a smooth tinue up to the screen. Never do the
surface and may require grinding, de- opposite, otherwise conductive par-
pending of the tool used and the skill of ticles or dirt could be dragged to the
the installer. When jointing two cables, it insulation and cause discharge.
is recommended to chamfer the edge of
the insulation.
21
Insulation removal
Multifunction tool for outer sheath and insulation removal Scan QR code for video
demonstration or click here.
22
Insulation removal
23
Installation grease is
applied to the insulation to
set the silicone bodies and
to help positioning them.
Additional comments on the insulation
Grinding, polishing and cleaning Scan QR code for video
demonstration or click here.
Cleaning
Thoroughly clean the insulation, always
toward the insulation screen. Never
use the same side of a cleaning tissue
twice. The insulation must be clean of
conductive particles and dirt.
25
Conductors
Classification
examples
(1) Class 2 circular
aluminum stranded
(2) Class 2 sector
copper stranded
1 2
26
Conductors
Cable lugs and connectors Scan QR code for video
demonstration or click here.
Cable lugs are used when ter- Clamp device When installing a lug or a connector
minating a cable. Connectors Ensto ST251 is used to hold the lug or > Pay attention to the shape and cross
connector while tightening the bolts. Es- section of the conductors. Put the
are used when jointing two pecially suitable for underground shear centering ring on if needed.
cables. head bolt connectors with diameters > Brush the conductors just before in-
from 14 to 40 mm. Suitable for work on stalling a lug or connector.
live parts with voltages up to 1000 V AC > Use the clamp device ST251 to hold
and 1500 V DC. Insulated in compliance the lug or connector.
with EN60900/IEC900 standards. > Perform the pre-tightening and tight-
ening sequences, from the outer
bolts to the inner ones. Scan the QR
code for a video demonstration.
> Wrap the insulation with a plastic
or fabric before breaking the shear
head bolts.
> Clean the insulation thoroughly and
Scan QR code for
remove the conductive particles and
bolt tightening
dirt.
sequence of the > If there is a ground connector for exter-
connector.
nal grounding wires, do not connect it
close to the joint bodies.
27
Brushing lowers the
probability of additional
heating of the lug or the
connector by lowering
the resistance at the
connection point.
Transition joints and paper-insulated cables
Transition joints are used to Cellulose paper is not a good insulation Handling old paper cables
connect paper insulated cables material by itself, but the high dielectric Paper-insulated cables do not require
strength of the mineral oil used to im- special tools, but they do require more
to polymeric insulated cables. pregnate the paper provides a satisfac- skill from the installer. Follow these
tory insulation level in low, medium- and recommendations when handling old
high-voltage applications. paper cables:
> Manipulate the cable with care be-
Before polymeric insulated cables be- cause the armor may have been cor-
came a worldwide trend during the roded, leaving the cable with no me-
1980s, different types of paper-insulat- chanical protection.
ed cables were installed by utilities and > Bend the phases very carefully.
industries. This is why paper cables are Cracking the paper insulation will re-
still in service in many distribution net- sult in failure during operation.
works and installers are required to > Perform the installation until the end
know how to work with them. after removing the lead or aluminum
sheath to prevent moisture from be-
Installing transition joints from oil- ing absorbed by the cable.
impregnated paper cables on polymeric > Wear gloves while manipulating the
insulated cables is the most typical task lead sheath.
some installers may ever perform in the
field, therefore, it is important to be fa-
miliar with the types of paper cables
and how to handle them.
29
Parts of a paper insulated cable
Outer sheath / Serving coat from each phase, but the vector sum is other hand it has a limited short circuit
Paper-insulated cables typically have always close to zero, resulting in very capacity, it is made of an expensive ma-
a polymeric outer sheath or bitumen- small induced currents in the armor. In terial and because of its toxicity, its use
impregnated hessian tape as the most single-core cables, non-magnetic alu- is being restricted. A lead sheath can be
external layer. For optimal removal of minum is used to prevent this from hap- removed with a knife or with a Plier for
bitumen-impregnated serving coats, it pening. In this procedure, the armor medium-voltage cable outer sheath.
is sufficient to apply enough heat and is laid over the bedding, which is typi-
then proceed to remove it by hand. cally made of wrapped layers of paper Belt insulation, belt screen and
A constant force spring, PVC tape or and bitumen hessian tape. The bedding fillers
screw clip can be used to have a fixed serves as a surface for the armor and The belt insulation and fillers are typi-
and straight cut at the desired length. protection for the sheath underneath cally made of paper, impregnated with a
If the outer sheath is made of PVC or and the laid-up cores. mass-impregnated non-draining (MIND)
MDPE, refer to the Plier for medium- compound. The belt screen is made of
voltage cable outer sheath. For correct removal of armor and bed- carbon paper tapes.
ding, use a constant force spring to keep
Armor and bedding the armor in place and a hacksaw to cut Insulation screen and insulation
The armor provides mechanical pro- the armor. Once the outer sheath is ex- The impregnated paper tapes are heli-
tection against crushing forces and can posed, heat up the bitumen with a me- cally lapped around the conductors up
also be used as a neutral conductor to- dium flame and then use wax help to re- to the thickness defined by the voltage
gether with the cable sheath. There are move the bitumen from the sheath and level. In belted cables, there is no insu-
three ways to armor cables: clean it. lation screen at all, but in type H and
> STA: Steel tape armor, used in multi- HSL, it is made of carbon paper tapes
core cables (magnetic) Sheath and a copper tape or aluminum foil.
> SWA: Steel wire armor, used in multi- In most cases, an extruded sheath of
core cables (magnetic) lead or lead alloy is applied to protect
> AWA: Aluminum wire armor, used in the paper insulation, but aluminum is
single-core cables (non-magnetic) also used. Connected to the armor, it
The reason behind using magnetic or provides a path for fault and leakage
non-magnetic armoring is related to current. The main advantages of an ex-
overheating. In three-core cables, the truded lead sheath are waterproofing
current flowing induces a magnetic field and corrosion resistance, but on the
30
Types of medium-voltage paper-insulated cables
Belted
Conductor
Unscreened phases
The unscreened phases are laid up and insulated to with-
stand full line-to-line voltage.
31
Types of medium-voltage paper-insulated cables
Type H
Filler
32
Types of medium-voltage paper-insulated cables
Type HSL
Filler
Bedding Conductor
33
Preparation before the installation
Ensto ST277
cable joint stand
locking mechanism
keeps cable ends
in place during
cable preparation
and makes jointing
easier.
35
Installation errors
Example of mistakes that cause faults in cable accessories
Sharp bolt
Shear head bolts break when the right
torque is achieved. Always use the cor-
rect tools for tightening the bolts and
never try to break the bolts using other
methods. Sharp edges or other shape
irregularities will cause the accessory to
fail. This is not a problem when install-
ing Ensto step-less screw connectors.
Once the screw breaks, a semi-conduc-
tive cover is placed on top of it.
36
Tubes shrank asymmetrically
Flame must be in constant movement
and applied symmetrically all around
the heat-shrink tubes.
37
Installation errors
Example of mistakes that cause faults in cable accessories
Treeing marks
Discharge occurs in air gaps on untreated
insulation. The damage of this discharge
is progressive and eventually causes the
accessory to fail.
38
Ensto Pro
and Installer Certification
Ensto Pro is a technical training concept happen in the field or in virtual. Also, we 6000 units yearly – zero installation
targeted to Enstos’ customers, part- are ready to teach about a host of top- faults
ners and our own personnel. The aim ics as customer needs and wishes dic- The Finnish DSO Enerke has already
is to support sales and create loyal cus- tate. We also arrange, or are involved in, certificated of all their installers. The
tomer relations by sharing knowledge. sessions attended by professionals from original certificates were valid for five
We wish to learn from customer experi- various institutions, such as cable man- years and in 2020 it was time to re-cer-
ences and truly understand customers’ ufacturers and energy-market authori- tify. Enerke sees certification very im-
requirements, thereby becoming able ties. By offering all the necessary infor- portant and certification is in place to
to develop our products to best meet mation in one session, we save time and make sure that everyone can produce
those precise needs. energy. We care about your success. top quality.
Ensto Pro training is unique: Ensto Installer Certification Enerke terminates yearly 2000 units of
> Local service in the local language. Installer Certification means a screen- 3-phase cables resulting to 6000 termi-
> Customized trainings. ing test for the installation of Ensto’s nations. In normal year there has been
> Consistent and engaging training low and medium voltage underground not a single fault. Enerke believes in
methods and presentations. cable accessories, which aims at the Ensto as a partner that helps in many
> Easy-going and easily approachable correct installation. The starting point is ways to achieve the high quality and re-
professionals. the need for network companies to re- liability criteria they have set for them-
> Emphasis on two-way learning. duce failure interruptions due to instal- selves.
lation errors, which is a global problem.
Customer benefits from Ensto Pro Ask more of Ensto Pro training and
training: Installer Certification has many benefits Installer Certification from sales.
> Time, cost, and energy savings. for the DSO’s, contractors and installers.
> Fewer installation errors. > Correctly installed solutions and longer
> Confidence and motivation. lifespan.
> The opportunity to have an influence. > Reliability to the network.
> New perspectives. > Time and cost savings – avoiding elec-
trical outages.
Variety of Training Types > Motivated professionals.
Our customer training ranges from small > Professional know-how.
installation sessions to large lecture- > Extended warranty.
type events. Installation trainings can > Certified quality.
39
Cable tools
Our selection includes peeling tools for the insulation,
insulation screen and sheath of medium voltage cables.
ST270.10 6438100330309 Insulation removal insert 10kV 120 mm² for ST261
ST271.10 6438100330316 Insulation removal insert 10kV 150 mm² for ST261
ST272.10 6438100330323 Insulation removal insert 10kV 185 mm² for ST261
ST273.10 6438100330330 Insulation removal insert 10kV 240 mm² for ST261
ST270 6438100316136 Insulation removal insert 20kV 120 mm² for ST261
ST271 6438100316143 Insulation removal insert 20kV 150 mm² for ST261
ST272 6438100316150 Insulation removal insert 20kV 185 mm² for ST261
ST273 6438100316167 Insulation removal insert 20kV 240 mm² for ST261
40
Cable tools
Cable stands
Product code GTIN Description
Additional tools
Product code GTIN Description
ST259 6438100312367 Wedge for spreading the outer sheath and aluminium laminate
ST286 6438100320287 Tool for spreading the outer sheath and aluminium laminate
41