Method Statement for Irrigation System
This Method Statement for Irrigation System defines the general procedure implemented
for the installation of the irrigation systems as per project specifications, and installation
details drawings.
1- 1” Remote-control Valve method of statement
a. The remote-control valve assembly shall incorporate the following components
starting from No. 1 in the inlet side to No. 9 in the outlet side:
1. PE compression male adaptor 32 mm x 1”.
2. Bronze gate valve 1” FTHD.
3. Hex nipple brass or stainless-steel 1”.
4. Union brass or stainless-steel 1” FTHD.
5. Y pattern disc filter 1” MTHD.
6. Solenoid valve (ICV-101G-B) with on-top pressure regulator (Accu Sync)
7. Hex nipple brass or stainless-steel 1”.
8. Union brass or stainless-steel 1” FTHD.
9. PE compression male adaptor 32 mm x 1”.
b. The remote-control valve assembly shall be placed inside a HDPE rectangular valve
box- series 1320.
The HDPE rectangular valve box is placed on a concrete base ensuring to bring the top
of the valve box 20 mm higher than the finish grade.
A cavity with the dimensions of 300 mm depth, 285 mm width, and 450 mm length
should be created inside the concrete base.
Both the HDPE rectangular valve box from the outer side and the cavity from inner
side shall be wrapped with a Geo-textile fabric semi-permeable membrane.
A layer of 100 mm of ¾” crushed gravel shall be placed inside the cavity above the
Geo-textile fabric semi-permeable membrane.
c. The remote-control valve assembly shall have an identification Tag fixed on the wheel
of the bronze gate valve.
d. Each remote-control valve assembly shall have one single station
decoder (ICD-100) linked from one side the coil of the solenoid valve and to the
decoder twisted cable from the other.
The connection between the wires of the single station decoder and that of the
decoder twisted cable and of the coil shall be done using 3M DBRY/6 waterproof wire
connectors.
The copper non-insulated wire shall be inserted in the soil to ensure an electrical surge
protection.
The riser from the irrigation main line to which the remote-control valve assembly is
connected shall be 63 mm sized down to 50 mm prior to the inlet side of the remote-
control valve assembly. All the PE fittings unless noted shall be of the butt-weld type.
2- 1 1/2” Remote-control Valve method of statement
a. The remote-control valve assembly shall incorporate the following components
starting from No. 1 in the inlet side to No. 9 in the outlet side:
1. PE compression male adaptor 50 mm x 1 1/2”.
2. Bronze gate valve 1 1/2” FTHD.
3. Hex nipple brass or stainless-steel 1 1/2”.
4. Union brass or stainless-steel 1 1/2” FTHD.
5. Y pattern disc filter 1 1/2” MTHD.
6. Solenoid valve (ICV-151G-B) with on-top pressure regulator (Accu Sync)
7. Hex nipple brass or stainless-steel 1 1/2”.
8. Union brass or stainless-steel 1 1/2” FTHD.
9. PE compression male adaptor 50 mm x 1 1/2”.
b. The remote-control valve assembly shall be placed inside a HDPE rectangular valve
box- series 1320.
The HDPE rectangular valve box is placed on a concrete base ensuring to bring the top
of the valve box 20 mm higher than the finish grade.
A cavity with the dimensions of 300 mm depth, 285 mm width, and 450 mm length
should be created inside the concrete base.
Both the HDPE rectangular valve box from the outer side and the cavity from inner
side shall be wrapped with a Geo-textile fabric semi-permeable membrane.
A layer of 100 mm of ¾” crushed gravel shall be placed inside the cavity above the
Geo-textile fabric semi-permeable membrane.
c. The remote-control valve assembly shall have an identification Tag fixed on the wheel
of the bronze gate valve.
d. Each remote-control valve assembly shall have one single station decoder (ICD-100)
linked from one side the coil of the solenoid valve and to the decoder twisted cable
from the other.
The connection between the wires of the single station decoder and that of the
decoder twisted cable and of the coil shall be done using 3M DBRY/6 waterproof wire
connectors.
The copper non-insulated wire shall be inserted in the soil to ensure an electrical surge
protection.
The riser from the irrigation main line to which the remote-control
valve assembly is connected shall be 63 mm sized down to 50 mm prior to the inlet
side of the remote-control valve assembly. All the PE fittings unless noted shall be of
the butt-weld type.
3- 2” Remote-control Valve method of statement
a. The remote-control valve assembly shall incorporate the following components
starting from No. 1 in the inlet side to No. 9 in the outlet side:
10. PE compression male adaptor 63 mm x 2”.
11. Bronze gate valve 2” FTHD.
12. Hex nipple brass or stainless-steel 2”.
13. Union brass or stainless-steel 2” FTHD.
14. Y pattern disc filter 2” MTHD.
15. Solenoid valve (ICV-201G-B) with on-top pressure regulator (Accu Sync)
16. Hex nipple brass or stainless-steel 1 1/2”.
17. Union brass or stainless-steel 2” FTHD.
18. PE compression male adaptor 63 mm x 2”.
b. The remote-control valve assembly shall be placed inside a HDPE rectangular valve
box- series 1324.
The HDPE rectangular valve box is placed on a concrete base ensuring to bring the top
of the valve box 20 mm higher than the finish grade.
A cavity with the dimensions of 300 mm depth, 420 mm width, and 635 mm length
should be created inside the concrete base.
Both the HDPE rectangular valve box from the outer side and the cavity from inner
side shall be wrapped with a Geo-textile fabric semi-permeable membrane.
A layer of 100 mm of ¾” crushed gravel shall be placed inside the cavity above the
Geo-textile fabric semi-permeable membrane.
c. The remote-control valve assembly shall have an identification Tag fixed on the wheel
of the bronze gate valve.
d. Each remote-control valve assembly shall have one single station decoder (ICD-100)
linked from one side the coil of the solenoid valve and to the decoder twisted cable
from the other.
The connection between the wires of the single station decoder and that of the
decoder twisted cable and of the coil shall be done using 3M DBRY/6 waterproof wire
connectors.
The copper non-insulated wire shall be inserted in the soil to
ensure an electrical surge protection.
The riser from the irrigation main line to which the remote-control valve assembly is
connected shall be 63 mm sized down to 50 mm prior to the inlet side of the remote-
control valve assembly. All the PE fittings unless noted shall be of the butt-weld type.
4- Quick coupling valve method of statement
a. The quick coupling valve assembly shall incorporate the following components
starting from No. 1 in the inlet side to No. 4 in the outlet side:
1. PE compression male adaptor 25 mm x 3/4”.
2. Bronze gate valve 3/4” FTHD.
3. Hex nipple brass or stainless-steel 3/4”.
4. Quick coupling valve (HQ-33DLRC).
b. The quick coupling valve assembly shall be placed inside a HDPE round valve box-
series 910.
The HDPE round valve box is placed on a concrete base ensuring to bring the top of
the valve box 20 mm higher than the finish grade.
A cavity with the dimensions of 200 mm depth, 260 mm width, and 260 mm length
should be created inside the concrete base.
Both the HDPE round valve box from the outer side and the cavity from inner side shall
be wrapped with a Geo-textile fabric semi-permeable membrane.
A layer of 300 mm of ¾” crushed gravel shall be placed inside the cavity above the
Geo-textile fabric semi-permeable membrane.
c. The quick coupling valve assembly shall be fixed using a stiffener, galvanized steel bar
800 mm length with stainless-steel hose clamps for support.
The riser from the irrigation main line to which the quick coupling valve assembly is connected
shall be 50 mm sized down to 25 mm prior to the inlet side of the quick coupling valve
assembly. All the PE fittings unless noted shall be of the butt-weld type.
5- Quick coupling valve method of statement
a. The quick coupling valve assembly shall incorporate the following components
starting from No. 1 in the inlet side to No. 4 in the outlet side:
5. PE compression male adaptor 32 mm x 31”.
6. Bronze gate valve 1” FTHD.
7. Hex nipple brass or stainless-steel 1”.
8. Quick coupling valve (HQ-44RC).
b. The quick coupling valve assembly shall be placed inside a HDPE round valve box-
series 910.
The HDPE round valve box is placed on a concrete base ensuring to bring the top of
the valve box 20 mm higher than the finish grade.
A cavity with the dimensions of 200 mm depth, 260 mm width, and 260 mm length
should be created inside the concrete base.
Both the HDPE round valve box from the outer side and the cavity from inner side shall
be wrapped with a Geo-textile fabric semi-permeable membrane.
A layer of 300 mm of ¾” crushed gravel shall be placed inside the cavity above the
Geo-textile fabric semi-permeable membrane.
c. The quick coupling valve assembly shall be fixed using a stiffener, galvanized steel bar
800 mm length with stainless-steel hose clamps for support.
The riser from the irrigation main line to which the quick coupling valve assembly is
connected shall be 50 mm sized down to 25 mm prior to the inlet side of the quick
coupling valve assembly. All the PE fittings unless noted shall be of the butt-weld type.
6- Air/vacuum release valve method of statement
a. The double acting Air/vacuum release valve assembly shall incorporate the following
components starting from No. 1 in the inlet side to No. 4 in the outlet side:
1. PE compression male adaptor 63 mm x 2”.
2. Bronze gate valve 2” FTHD.
3. Hex nipple brass or stainless-steel 2”.
4. 2” double acting air/vacuum release valve (D-040).
b. The double acting Air/vacuum release valve assembly shall be placed inside a HDPE
round valve box- series 910.
The HDPE round valve box is placed on a concrete base ensuring to bring the top of
the valve box 20 mm higher than the finish grade.
A cavity with the dimensions of 200 mm depth, 260 mm width, and 260 mm length
should be created inside the concrete base.
Both the HDPE round valve box from the outer side and the cavity from inner side shall
be wrapped with a Geo-textile fabric semi-permeable membrane.
A layer of 300 mm of ¾” crushed gravel shall be placed inside the cavity above the
Geo-textile fabric semi-permeable membrane.
The riser from the irrigation main line to which the double acting Air/vacuum release
valve assembly is connected shall be 63 mm. All the PE fittings unless noted shall be
of the butt-weld type.
7- Isolation valve method of statement
a. Isolation Valves should be protected from damage during transportation, loading, and
handling.
b. Lifting by means of any lifting device should only be done using the flange holes, lifting
eyes, or appropriate straps. Never suspend the valve in a handwheel, gearbox, or
actuator.
c. Before installation, a visual check must be performed. Special attention should be paid
to checking the system, valve seat area, flanges, and coating. Look for defects, bent or
out-of-place parts, dents, scratches, and other damages. Actions should be taken to repair
or replace the valves if any defects are detected.
d. Bolts must be tightening in a criss/cross pattern. Actions should be taken to ensure even
pressure on the gasket surface.
The Washing out Valve assembly shall incorporate the following components:
1. Gate valve, flanged, ductile or cast iron.
2. Flanged adaptor, ductile or cast iron.
3. Main line pipe, HDPE 16 bars.
4. Valve box, circular, Model 910.
5. Square ring base, Concrete 400×400×100 mm.
6. Pipe as support, PVC Class 3, 10mm (4”), Cut length to suit depth of valve.
7. Support base concrete to suit depth of valve.
8. T-Key, Epoxy-coated steel.
9. Anti-Corrosion PE tape.
10. Identification tag.
9- Root zone watering system method of statement
a. The root zone watering system (RZWS2450-LB) will be used as the application devices
on the trees. Each tree will be provided with 2 Nos.
The RZWS2450-LB is a full system incorporate one PCB-50 (0.5 GPM) pressure
compensating bubbler ready with ½” swing joint.
The 2 Nos. of RZWS2450-LB will be installed at 25 cm on opposite sides from the tree
trunk.
b. Each of the RZWS2450-LB will be installed as per the following steps:
1. Create a round cavity with the dimensions of 610 mm depth by 120 mm diameter.
2. Wrap the mesh tube of the RZWS2450-LB with Geo-textile fabric semi-permeable
membrane (sleeve).
3. Connect the spiral barb elbow of the RZWS2450-LB with the lateral line passing
nearby through the saddle (xx mm x ½”)
4. Insert the Wrapped mesh tube of the RZWS2450-LB into the round cavity ensuring
the top of the RZWS2450-LB will be flush with the finish level.
5. Fill the gap between the wrapped RZWS2450-LB and cavity wall with ¾” crushed
gravel layer.
6. Make sure to have the wrapped mesh tube of the RZWS2450-LB is placed correctly
and do not have empty spaces between the sleeve and the soil.
7. Open the cap of the RZWS2450-LB and start fill the tube of the RZWS2450-LB with
¾” crushed gravel till the bottom of the internal spiral barb elbow.
8. Close the cap to its position.