RELAIS TEMPO Carlo Gavazzi

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Timers

Star Delta
Types DAC01, PAC01
• Time range (Star): 0.1 to 600 s
• Time range (Star to Delta): 50 to 130 ms
• Knob selection of star time range
• Knob adjustable time setting
• Automatic start
• Repeatability: ≤ 0.2%
• Output: 8 A SPDT relay with neutral centre position
• For mounting on DIN-rail in accordance with DIN/EN
50 022
• 22.5 mm Euronorm housing or 36 mm Plug-in module
housing
• LED indication for relay status and power supply ON
DAC01 PAC01

Product Description Ordering key DAC 01 C M24


Star-delta control relay with ing on Housing
two adjustable time ranges: DIN-rail (DAC 01) on Plug-in Function
Star function (0.1 to 600 s) (PAC01). Type
and star to delta function Item number
(50 to 130 ms). For mount- Output
Power Supply

Type Selection
Mounting Output Housing Supply: 24 VDC and 24 to 240 VAC Supply: 380 to 415 VAC

For DIN-rail 1 x SPDT D - 22.5 mm DAC 01 C M24 DAC 01 C M40


Plug-in P - Housing PAC 01 C M24 PAC 01 C M40

Time Specifications Output Specifications


Time ranges (star) Output SPDT relay with neutral
Knob selectable 0.1 to 1 s centre position
1 to 10 s Rated insulation voltage 250 VAC (RMS)
6 to 60 s
60 to 600s Contact Ratings (AgSnO2) µ
Resistive loads AC 1 8 A @ 250 VAC
Star to delta delay 50 to 130 ms DC 12 5 A @ 24 VDC
Neutral centre position between star and delta Small inductive loads AC 15 2.5 A @ 250 VAC
position DC 13 2.5 A @ 24 VDC
Setting accuracy ≤ 5% Mechanical life ≥ 30 x 106 operations
Repeatability ≤ 0.2% Electrical life ≥ 105 operations
Time variation (at 8 A, 250 V, cos ϕ = 1)
Within rated power supply ≤ 0.05% Operating frequency < 7200 operations/h
Within ambient temperature ≤ 0.2%
Dielectric strength
Reset Dielectric voltage 2 kVAC (RMS)
Time and relay Power supply interruption Rated impulse withstand
≥ 200 ms voltage 4 kV (1.2/50µs)

Specifications are subject to change without notice (15.03.01) 1

Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com


DAC 01

Supply Specifications General Specifications


Power supply Overvoltage cat. III Power ON delay ≤ 100 ms
Rated operational voltage (IEC 60664, IEC 60038) Power OFF delay ≤ 100 ms
through terminals:
A1 and A2 (DAC01) Indication for
2, 10 (PAC01) 24 VDC 10%15% Power supply status LED, green
M24 24 to 240 VAC +10% -15% Output status LED, yellow (flashing when
45 to 65 Hz timing)
M40: 380 to 415 VAC ± 15% Environment (EN 60529)
45 to 65 Hz Degree of protection IP 20
Voltage interruption ≤ 40 ms Pollution degree 3 (DAC01) ,2 (PAC01)
(IEC 60664)
Rated operational power 1.5 W Operating temperature -20 to 60 °C, R.H. < 95%
Storage temperature -30 to 80 °C, R.H. < 95%
Weight 100 g
Time Setting Screw terminals DAC01
Tightening torque Max 0.5 Nm according to
Upper knob: Lower knob: IEC 60947
Setting of star time range Star to delta time setting (50 CE Marking Yes
to 130 ms) EMC Electromagnetic Compatibility
Centre knob: Immunity According to EN 50082-2
Star time setting on relative Emission According to EN 50082-1
scale: 1 to 10% with respect
to the chosen range. Timer Specifications According to EN 68812-1

Mode of Operation
The output relay is normally At the end of the set time 50 to 130 ms), the relay rupted for more than 200 ms
in the neutral centre position. period, the relay returns to switches in delta position before the star time period
When the power supply is the neutral centre position (pin 18 or 3) and does not has expired, the relay does
applied, the relay switches to and the set delay between release until the power sup- not operate and the time cir-
star position (pin 16 or 4) star and delta position starts. ply is interrupted for at least cuit is set to zero. The relay
and the star period starts. At the end of the star to 200 ms. is ready for a new time peri-
delta delay (adjustable from If the power supply is inter- od.

Wiring Diagrams
DAC01 PAC01

Operation Diagram

2 Specifications are subject to change without notice (15.03.01)

Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com

You might also like