CONCRETE COMPRESSIVE STRENGHT TEST REPORT NF EN

12390-3
CONTRACTOR Zerock CTR N° 108 30A100_RFI N°: 117 EXT MIX DESIGN
Production Line Shed; Electrical room / Paving;
PROJECT 1st Agri Hub PART OF STRUCTURE Footing / - TR16_D1-G1 ab B-D_2-4; Slab B-C_1-3; TRIAL MIX
- Longrin_F3-F2
POURING DATE 7/28/2023 ORIGIN OF CONCRETE Zerock Batching plant Loudima INFORMATION ✘

TEMPERATURE 27,1 / 30 °C SIZE OF SPECIMEN 16 x 32 cm DATE OF RECEIPT 8/1/2023

MIX DESIGN CODE 25-XC4-D25-S3-42.5N-SHR-S0/1


COMPOSITION OF CONCRETE CEMENT WATER SAND GRAVEL 1 GRAVEL 2 ADMIXTURE SLUMP TEST SPECIFIED

TYPE 42,5N - 0/1 5/12,5 16/25 ADMIX150 SLUMP TEST 0' 16,9 cm
THEORICAL (Kg/m3) 450 178.78 574 260 1018 4 SLUMP TEST 30'
PRATICAL - - - - - - SLUMP TEST 60'

COMPACTION Vibration CURING Water immersion

SPECIMEN AGE WEIGHT DENSITY LOAD COMPRESSIVE STRENGHT


CRUSHING DATE FAILURE
REFERENCE
(J) (Kg) (T/m3) (KN) MPa AVERAGE
AH367 28 8/25/2023 15.88 2.47 687.34 34.19 Correct
AH368 28 8/25/2023 15.76 2.45 696.05 34.62 31.93 Correct
AH369 28 8/25/2023 15.90 2.47 542.83 27.00 Correct

Remarks

Inspectors for : GEOLAB ENI CONGO ZEROCK


Name
Signature
Date
Roulé
Concassé

Correct
Incorrect