CONCRETE COMPRESSIVE STRENGHT TEST REPORT NF EN

12390-3
Number of Test Report 157
Project CONGO – BIOFUEL 1st AGRI HUB - INDUSTRIAL START-UP
Contractor ZEROCK CONSTRUCTION CONGO
Origin of Concrete Zerock Concrete Batching Plant in Loudima

Temperature 26,3 / 28,8 °C Size of specimen (16 x 32 cm) x 3


Pouring date 8/29/2023 Slump test at 0' 16,5 cm
Mix Design Code 25 - XC4 - D25 - S3 - 42.5N - SHR - S0/1
Composition Cement Water Sand Gravel 1 Gravel 2 Admixture
Type 42,5N - 0/1 5/12,5 16/25 Admix150
Quantity(Kg/m3) 450 178.78 574 260 1018 4
Part of Structure

2nd line Production / Bucket Elevator - BE9 ; Trench/ F31wall; TR16_D4-D5 wall

30A100_RFI_136 EXT
Number notification Date of receipt 9/4/2023

Density STRENGHT (Mpa)


Spec. Tag Age Crushing date Weight (Kg) Load (kN)
(T/m3) Unit Average
AH580 15.96 2.48 462.02 22.98
AH581 7 9/5/2023 15.96 2.48 457.54 22.76 23.01
AH582 15.92 2.48 468.38 23.30

Inspectors for : GEOLAB ENI CONGO ZEROCK

Name

Signature

Date

Number notification 30A100_RFI_173 EXT Date of receipt 9/4/2023

Density STRENGHT (Mpa)


Spec. Tag Age Crushing date Weight (Kg) Load (kN)
(T/m3) Unit Average
AH583
AH584 28 9/26/2023
AH585

Inspectors for : GEOLAB ENI CONGO ZEROCK

Name

Signature