Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

RXTUG 22H

DC-DC converter
with regulated output voltage
RXTUG 22H

• Input voltage 24 - 250 V dc


• Output voltage selectable ±12, ±18 or ±24 V dc,
normally factory setting ±24 V dc
• Galvanically separated inputs and outputs
• Can be loaded with up to 20 W LED indicates
proper in service operation
• The output voltage is monitored and loss of voltage
alarmed by a built-in auxiliary relay
• Protected against wrong polarity on the input voltage
• Can be connected in parallel to receive redundant
voltage supply

Application
The RXTUG 22H is primarily intended for auxiliary voltage supply
of electronic circuits. It is suitable for use when moderate output
power is required, e.g. for the supply of protective relays or
automatic equipment. RXTUG 22H is directly replacing RXTUG 21H.

Design
The RXTUG 22H converts an incoming dc voltage to an ac
voltage which is subsequently transformed, rectified and
smoothed to another regulated and stabilized dc voltage. This
converter has a high degree of efficiency and it can be loaded
up to 20 W for 5 minutes and 15 W continuously. Unsymmetrical
load of plus and minus U2 (see Fig. 1) can be accepted
up to 100% of rated load. 01 RXTUG_22H

The input and output voltages of the converter are galvanically Using two parallel converters to receive redundant voltage
separated, which contributes to the suppression of any transients supplies, an external diode connection is needed for the secondary
occurring in the input voltage. The input is supplied with a voltage side, see Fig. 1. RTXE diodes acc. to 1MRK 513 019-BEN may be
polarizing protection to prevent damage in case of faulty connection. used. The RTXE diodes mount in the rear pockets of the terminal
The output voltage is monitored by a built-in auxiliary relay. bases and therefore do not add to the space requirements.
During normal operation a green LED at the front is lit. If the RTXC branch connectors acc. to 1MRK 513 003-BEN may be
output is short-circuited the converter drops out. When the used for making easy connections of the wiring from the RTXE´s.
short-circuit is removed, the converter restarts automatically. COMBIFLEX sockets are fitted to the wires from RTXE.
+116 126
+ U2 Table 2: Insulation tests (IEC 60255-27)
118 127
0
117 128
–U
2 Dielectric test
U<
Between voltage inputs
316 317 2,0 kV 50 Hz, 1 min
and outputs and to contact
318 circuits and ground

Impulse voltage test 5,0 kV, 1,2/50 μs, 0,5 J

+ 116 126
118 127
117 128
U< Table 3: Electromagnetic compatibility tests
316 317
318 Spark test (SS 436 15 03) 4-8 kV, class PL 4

1 MHz burst disturbance test


02 Parallel connection of two converters RXTUG_22H
2,5 kV, class III
(IEC 255-22-1)
Note: Terminal 117 has to be earthed
Fast transient test (IEC 255-22-4) 4 kV, class IV
Radiated electromagnetic field
10 V/m, 25-1000 MHz, class III
disturbance test (IEC 255-22-3)
Electromagnetic emission tests (EN
class A
50081-2)
Electrostatic discharge test
8 kV, class 4
Technical data (IEC 255-22-2)

Table 1: Energizing quantities,


rated values and limits + 116 126 + U
2
118 127 0
U1
117 128 –
U2
Nominal input voltage, U1 24-250 V dc U<

316 317
Nominal output voltage, U2 ±12 V dc, ±18 V dc, ±24 V dc (selectable)
318
Max. load 03 Terminal diagram
continuously 15 W
5 min 20 W
+20% to -20% of the input voltage, U1
Permitted variation in input voltage Ordering Specify:
• Type RXTUG 22H
Start time < 1,0 s
• Quantity
Current spike at connection ≤2A
• Ordering No. 1MRK 000 592-A
±10% at nominal input voltage Pout = 2-15
Max output voltage variation • U2 (if other than ±24 V dc)
W
Voltage ripple and transients at the
< 0,4 V p-p
output
Power dissipation at no load ≤ 1,7 W References

Maximum capacitive load ≤ 1000 μF COMBIFLEX connection and


1MRK 513 003-BEN
Permitted ambient temperature -20°C to +55 °C installation components

Hitachi Energy We reserve the right to make technical We reserve all rights in this document and in
Substation Automation Products changes or modify the contents of this the subject matter and illustrations contained
721 59 Västerås, Sweden document without prior notice. With regard therein. Any reproduction, disclosure to
Phone: +46 (0) 21 32 50 00 to purchase orders, the agreed particulars third parties or utilization of its contents – in
marketing-update@hitachienergy.com shall prevail. Hitachi Energy Ltd. does not whole or in parts – is forbidden without prior
© 2022 Hitachi Energy. All rights reserved. accept any responsibility whatsoever for written consent of Hitachi Energy Ltd.
potential errors or possible lack of information
www.hitachienergy.com/protection-control in this document. 1MRK 513 001-BEN Revision: C

You might also like