Control Valve Sizing Liquid Rev 3.5b
Control Valve Sizing Liquid Rev 3.5b
Qf= 746.20
0.7
0.6
0.3
0.0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Flow units are gpm
Relative Travel, h
Installed Gain
4
3.5
Neles RE
3 inch
3 PV123
Gain, d(Q/Qmax)/dh
2.5
Qmax = maximum
1.5
design flow = 550
1
Qmin = minimum
design flow = 80
0.5
0
0.0 0.1 0.2 0.3 0.4Q/Qmax
0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 Flow units are gpm
Typical FL values based on the Cv reported on Line 15 of the Valve Sizing tab For initial calculations (before
for TURBULENT FLOW and the valve size entered in D12 of the Valve Sizing tab. the Cv is known), consider usin
the FL values listed below.
Flow 80 213 423 550 Minimum
Valve type Liquid pressure recovery factor. FL Flow
Typical FL values based on the Cv reported on Line 26 of the Valve Sizing tab
for NON-TURBULENT FLOW and the valve size entered in D12 of the Valve Sizing tab.
Segment ball
Butterfly
Full ball
For initial calculations (before
the Cv is known), consider using DESCRIPTION OF VARIABLE
the FL values listed below. CALCULATED IN COLUMN "O"
Maximum
Flow Valve Cv/Valve size squared (Turbulent flow)
0.92 The value of "Cv_over_d_Sq_T" is taken from the Valve Sizing tab (S, T, U, V 628)
where Kv has been converted to Cv if the worksheet has been
0.88 configured for Kv and valve size in mm has been converted
to inch if the worksheet has been configured for mm.
0.78
Valve Cv/Valve size squared (NonTurbulent flow)
0.72
The value of "Cv_over_d_Sq_NT" is calculated from the Non-turb flow coef. on
0.58 Line 26 of the Valve Sizing tab converted to Cv if the worksheet has been configure
for Kv and Valve size in D12 of the Valve Sizing tab is converted to inch
0.67 if the worksheet has been configured for valve size in mm.
Intermediate calculations
Conversion from Pounds per hour to Gallons per minute (gpm) Case 1 Case 2
Conversion from Kilograms per hour to cubic meters per hour (m3/h)
Data input
Final results
ss flow entered in the blue
Intermediate Calculations
Case 3 Case 4
Density based on Specific Gravity on the Valve Sizing Tab
211575 275099 lbm/ft3 RHO_lb 62.37 62.37 62.37 62.37
423.00 550.00 kg/m3 RHO_kg 999.1 999.1 999.1 999.1
95977 124793
96.063 124.905