Effective April 2022

Time Current Curves TC01200002E Supersedes March 2018

Series C F-frame circuit breaker


time current curves
Contents
Description Page
Catalog Number Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Digitrip 310+ Electronic Trip Unit


Types FDE, HFDE, FDCE
Long Delay (LD) and Short Delay (SD) with Flat Response and Override
(225A) (LSI, LSIG) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC01203015E . . . . . . . . 6
Long Delay Response and Short Delay with I2t Response Curve and Override
(225A) (LS, LSG) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC01203016E . . . . . . . . 7
Ground Fault Response Curve (LSG, LSIG) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC01203017E . . . . . . . 8

Digitrip 210+ Electronic Trip Unit


Types FDE, HFDE, FDCE
Long Delay (LD) and Short Delay (SD) with Flat Response and Override
(100A, 225A) (LSI) (Profiles J, K, R, S) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC012001EN . . . . . . . . 9
(100A, 225A) (LSI) (Profiles M, N) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC012002EN . . . . . . . 10
(100A, 225A) (LSI) (Profiles P, Q) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC012003EN . . . . . . . 11
Long Delay (LD) and Short Delay (SD) with I2t Response Curve and Override
(100A, 225A) (LSI) (Profiles L, O) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC012004EN . . . . . . . 12
Long Delay (LD), Instantaneous, and Override
(100A, 150A) (LI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC012005EN . . . . . . . 13
(225A) (LI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC012006EN . . . . . . . 14

Single-pole thermal-magnetic trip units


Series C types EHD, FD, and HFD 15A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-4423-88A . . . . . . . 15
Series C types EHD, FD, and HFD 20A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-4424-88A . . . . . . . 16
Series C types EHD, FD, and HFD 25A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-4425-88A . . . . . . . 17
Series C types EHD, FD, and HFD 30A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-4426-88A . . . . . . . 18
Series C types EHD, FD, and HFD 35A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-4427-88A . . . . . . . 19
Series C types EHD, FD, and HFD 40A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-4428-88A . . . . . . . 20
Series C types EHD, FD, and HFD 45A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-4429-88A . . . . . . . 21
Series C types EHD, FD, and HFD 50A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-4430-88A . . . . . . . 22
Series C types EHD, FD, and HFD 60A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-4431-88A . . . . . . . 23
Series C types EHD, FD, and HFD 70A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-4432-88A . . . . . . . 24
Series C types EHD, FD, and HFD 80A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-4433-88A . . . . . . . 25
Series C types EHD, FD, and HFD 90A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-4434-88A . . . . . . . 26
Series C types EHD, FD, and HFD 100A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-4435-88A . . . . . . . 27
Series C types FD and HFD 110A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-4436-88A . . . . . . . 28
Series C types FD and HFD 125A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-4437-88A . . . . . . . 29
Series C types FD and HFD 150A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-4438-88A . . . . . . . 30
Contents (continued)
Two-, three-, and four-pole thermal-magnetic trip units Page
Series C types ED, EHD, FDB, FD, FDC, and HFD 15A 2, 3 & 4 pole . . . . . . . . . . . . . . . . . . TC012036 . . . . . . . 31
Series C types ED, EHD, FDB, FD, FDC, and HFD 20A 2, 3 & 4 pole . . . . . . . . . . . . . . . . . . TC012037 . . . . . . . 32
Series C types ED, EHD, FDB, FD, FDC, and HFD 25A 2, 3 & 4 pole . . . . . . . . . . . . . . . . . . TC012038 . . . . . . . 33
Series C types ED, EHD, FDB, FD, FDC, and HFD 30A 2, 3 & 4 pole . . . . . . . . . . . . . . . . . . TC012039 . . . . . . . 34
Series C types ED, EHD, FDB, FD, FDC, and HFD 35A 2, 3 & 4 pole . . . . . . . . . . . . . . . . . . TC012040 . . . . . . . 35
Series C types ED, EHD, FDB, FD, FDC, and HFD 40A 2, 3 & 4 pole . . . . . . . . . . . . . . . . . . TC012041 . . . . . . . 36
Series C types ED, EHD, FDB, FD, FDC, and HFD 45A 2, 3 & 4 pole . . . . . . . . . . . . . . . . . . TC012042 . . . . . . . 37
Series C types ED, EHD, FDB, FD, FDC, and HFD 50A 2, 3 & 4 pole . . . . . . . . . . . . . . . . . . TC012043 . . . . . . . 38
Series C types ED, EHD, FDB, FD, FDC, and HFD 60A 2, 3 & 4 pole . . . . . . . . . . . . . . . . . . TC012044 . . . . . . . 39
Series C types ED, EHD, FDB, FD, FDC, and HFD 70A 2, 3 & 4 pole . . . . . . . . . . . . . . . . . . TC012045 . . . . . . . 40
Series C types ED, EHD, FDB, FD, FDC, and HFD 80A 2, 3 & 4 pole . . . . . . . . . . . . . . . . . . TC012046 . . . . . . . 41
Series C types ED, EHD, FDB, FD, FDC, and HFD 90A 2, 3 & 4 pole . . . . . . . . . . . . . . . . . . TC012047 . . . . . . . 42
Series C types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 100A 2, 3 & 4 pole . TC012029EN . . . . . . 43
Series C types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 110A 2, 3, & 4 pole . TC012030EN . . . . . . 44
Series C types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 125A 2, 3, & 4 pole . TC012031EN . . . . . . 45
Series C types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 150A 2, 3, & 4 pole . TC012032EN . . . . . . 46
Series C types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 175A 2, 3, & 4 pole . TC012033EN . . . . . . 47
Series C types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 200A 2, 3, & 4 pole . TC012034EN . . . . . . 48
Series C types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 225A 2, 3, & 4 pole . TC012035EN . . . . . . 49
Series C type FDC - 240V let-through current 150A................................... April 2022........ 50
Series C type FDC - 240V let-through energy 150A. .................................. April 2022........ 51
Series C type FDC - 240V let-through current 225A. .................................. April 2022........ 52
Series C type FDC - 240V let-through energy 225A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . April 2022. . . . . . . . 53
Series C type FDC - 480V let through current 150A. .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . April 2022........ 54
Series C type FDC - 480V let through energy 150A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . April 2022........ 55
Series C type FDC - 480V let-through current 225A. .................................. April 2022........ 56
Series C type FDC - 480V let through energy 225A. .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . April 2022........ 57
Series C type FDC - 600V let-through current 150A. .................................. April 2022........ 58
Series C type FDC - 600V let-through energy 150A. .................................. April 2022........ 59
Series C type FDC - 600V let-through current 225A. ................................. April 2022........ 60
Series C type FDC - 600V let-through energy 225A. .................................. April 2022........ 61

Note:
Time/current characteristic curves for Series C® F-frame circuit breakers—voltages shown in curve headings are
maximum at which the breaker may be applied. Interrupting capacity of individual breaker is tabulated on each curve.

Time Current Curves are engineering reference documents for application and coordination purposes only.
For field testing molded case circuit breakers, refer to NEMA AB 4 guidelines.

2 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

Revision notes
Note: Unless noted below, all curves remain unchanged from their prior revision.

Revision Curve number Page Date


Changed FDCE, 600V interruption rating from 35 to 25 TC01203015 6 05-24-17

Deleted curves: SC-4146-87B, SC-4147-87B, SC-4148-87B, SC-4149-87B, See revision note. 43-48, 61-65 05-24-17
SC-6970-98, SC-5805-94A, SC-5528-93A, SC-5529-93A, SC-5530-93A, (old page #’s)
SC-5531-93A, SC-6871-98.
Added 7 new curves, combining FDC data with all other frame data. New curve See revision note. 43-49 05-24-17
#’s are: TC012029EN, TC012030EN, TC012031EN, TC012032EN, TC012033EN, (new page #’s)
TC012034EN, TC012035EN.
Added 3 new curves, demonstrating let-through current at 240V, 480V and 600V. AD-29-166A 62-64 05-24-17
AD-29-166B (new page #’s)
AD-29-166C
Corrected maximum single pole trip time curves 110A, 125A. TC012030EN 44-45 04-01-18
TC012031EN
Deleted curves: SC-5516-93A, SC-5517-93A, SC-5518-93A, SC-5519-93A, 04-01-18
SC-5520-93A, SC-5521-93A, SC-5522-93A, SC-5523-93A, SC-5524-93A,
SC-5525-93A, SC-5526-93A, SC-5527-93A.
Added 12 new curves, combining FDC data with all other frame data. See revision note. 31-42 04-01-18
New curve #’s are: TC012036EN , TC012037EN, TC012038EN, TC012039EN,
TC012040EN, TC012041EN, TC012042EN, TC012043EN, TC012044EN, TC012045EN,
TC012046EN, TC012047EN.
Added 12 new FDC Current Limiting curves. 50--61 04-14-22
Removed JDC, KDC, and LDC Current Limiting curves (AD-29-166).

EATON www.eaton.com 3
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

Catalog Number Selection


This information is presented only as an aid to understanding catalog numbers.
It is not to be used to build catalog numbers for circuit breakers or trip units.

Table 1. F-Frame Circuit Breakers with 310+ Electronic Trip Unit Technology

FDE 3 225 32 W

Circuit Breaker Suffix Suffix


Type Number of ZG = Zone W = Without terminals
Poles Trip Trip Unit selective L = Line and load terminals
FDE = 35 kAIC
3 = 3 poles Amperes 33 = LS interlocking Blank = Load side terminals only
HFDE = 65 kAIC
80 32 = LSI Blank = No option
FDCE = 100 kAIC
160 35 = LSG
225 36 = LSIG

Table 2. F-Frame Circuit Breakers with 210+ Electronic Trip Unit Technology

HFDE 3 100 21 L

Performance Suffix
@ 480 Vac Number of W = Without Terminals
FDE = 35 kAIC Poles Trip Unit L = Line and Load Terminals
Amperes
HFDE = 65 kAIC 3 = 3 poles 21 = LI Blank = Load Side Terminals Only
100 22 = LSI
150
225

Table3. F-Frame Circuit Breakers with Thermal-Magnetic Trip Unit Technology

FDC 3 100 L

Circuit Breaker Suffix


Type Number of Trip Amperes E = 100% protected (four-pole only) neutral pole
EHD Poles 070 EH = 50% protected (four-pole only)
010
FDB 1 = 1 pole 015 080 K = High magnetic molded case switch
FD 2 = 2 poles 020 090 L = Line and load terminals
HFD 3 = 3 poles 025 100 S = Stainless steel terminals
FDC 4 = 4 poles 030 110 V = 50 °C calibration
035 125 W = Without terminals
040 150 Y = Line terminals only
045 175 (FD, HFD, FDC, two-, three-, four-pole only) Z = Aluminum terminals (≤100 amperes)
050 200 (FD, HFD, FDC, two-, three-, four-pole only) Blank = Load side terminals only
060 225 (FD, HFD, FDC, two-, three-, four-pole only)

EDC 3 200 L

Circuit Breaker Suffix


Type Number of Trip L = Line and load terminals
EDB Poles Amperes W = Without terminals
EDS 2 = 2 poles 100 Y = Line terminals only
ED 3 = 3 poles 125 Z = Aluminum terminals (100 amperes)
EDH 150 Blank = Load side terminals only
EDC 175
200
225

4 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

LS LSG LSI LSIG

Figure 1. Digitrip 310+ Nameplates

LI LSI

Figure 2. Digitrip 210+ Nameplates

EATON www.eaton.com 5
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

Current in Multiples of (lr)


Digitrip 310+ Circuit Breaker Time/Current Curves (Phase Current)
.5 .7 1 2 3 4 5 7 10 20 30
10000
Series C F-Frame Circuit Breakers
2 HOURS

9000
8000
7000 Catalog Types: FDE, HFDE, FDCE
6000 FDE Circuit breaker time/current curves (phase current)
Trip Unit Types: 32 (LSI), 36 (LSIG)
5000
1.15 Types FDE,
Available FDCE, HFDE
Sensors circuit160A,
(In): 80A, breakers
225A I r In 80A 160A 225A
1 HOUR

4000
Long Delay (LD) and Short Delay (SD) with A
Flat Response
15A 60A 100A
3000 ( In) :
Available sensors B 20A 70A 110A
(Ir) / (In80A
) 80A 160A 225A C 30A 80A 125A
2000 160A D 40A 90A 150A
A 225A 15A 60A 100A E 50A 100A 160A
B 20A 70A 110A F 60A 125A 175A
C 30A 80A 125A G 70A 150A 200A
D 40A 90A 150A H 80A 160A 225A
1000
900 E 50A 100A 160A
800
F
Interrupting 60AHz
ratings—50/60 125A 175A
700 Maximum total
600 G
Breaker Symmetrical 70A 150A
RMS amperes (kA) UL/CSA 200A
clearing time typeH
500 240 V 80A 480 V 160A600V 225A
400
FDE 65 35 18
Interrupting
HFDE 100 Rating—50/60
65 Hz 25
FDCE 200 100 35
300 Symmetrical RMS amperes (kAS) UL/CSA
Breaker Type
Notes: 240V 480V 600V
200
1.FDE
Curve accuracy applies from –20C65to +55C ambient.
35 Temperatures 18
above +85C cause an over-
temperature
HFDE protection trip. For possible
100 continuous65ampere dertaing25for ambient above 40C,
refer to Eaton.
FDCE 200 100 25
Available long delay time:
2. Application frequency is 50/60 Hz.
100 2,4,7,10,12,15,20,24 sec.
90 Shown @ 6x Ir Notes:
80 3. There is a memory effect that can act to shorten the long delay. The memory effect comes into play
2,4,7,15,24 seconds 1. Curve accuracy applies from –20C to +55C ambient. Temperatures above +85C cause an overtemperature
1 MINUTE

70 if a current above the long delay pick up value exists for a time and then is cleared by the tripping of
+0 / –30% protection trip. For possible continuous ampere derating for ambient above 40C, refer to Eaton.
a down stream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker
60
to tripin shorter time than normal. The amount of time delay reduction is inverse to the amount of
50 2. that
time Application frequency
has elapsed since theisprevious
50/60 Hz.
overload. Approximately five minutes is required between
40 overloads tocompletely reset memory.
3. There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current
4.
Theabove the long
right portion delay
of the pickis up
curve value exists
determined for
by the a time and
interrupting thenofisthe
rating cleared
circuit by the tripping
breaker. of a down stream device
.
30
or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than
24 The left portion of the curve of
is shown as a multiple of the long delay
normal. The amount time delay reduction is inverse to setting.
the amount of time that has elapsed since the previous
20 (long delay pick Approximately
overload. up = 115% of In ).five
Range is 110%–120%.
minutes is required between overloads to completely reset memory.
.
15
6. Total clearing times shown include the response times of the trip unit, the breaker opening, and the
4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
interruption of the current.
Minimum total
10 7.5.
TheThe leftdelay
short portion
pick of
up the curve
has nine is shown as a multiple
settings/positions, of
the long delay setting.
2–8, 10, 12.
clearing time (long delay pick up = 115% of In ). Range is 110%–120%.
9
8
7 .
7
8. For high fault current levels an additional fixed instantaneous hardware override is provided
6. Total clearing times shown 9) include
at 12x (Inthe
) andresponse times ofi. the trip unit, the breaker
TIME IN SECONDS

(corresponding to SDPU position designated as 12I Instantaneous tolerance is +/–20%.


6 opening, and the interruption of the current.
9. For LD response and SD with flat response (this curve): TC01203015E

.
5
7. The short delay pick up has nine settings/positions, 2–8, 10, 12.
4 4 10. For LD response and SD with I 2 T response curve, see: TC01203016E

3
12 8. For high fault current levels an additional fixed instantaneous hardware override is provided (corresponding to
11. For ground fault delay response curve, see: TC01203017E
SDPU position 9) at 12x (In) and designated as 12Ii. Instantaneous tolerance is +/–20%.

2 . 2
12. Digitrip RMS 310+ trip units are suitable for functional field testing with test kit Cat. No. MTST120V.
9.
For Fortesting
field LD response and SD
using primary with flat
injection response
methods, (this
follow NEMA curve): TC01203015E.
publication AB 4-2003.

10. For LD response and SD with I2T response curve, see: TC01203016E.
2 4
11. For ground fault delay response
1 curve, see: TC01203017E.
1 1
.9 .9
.8 3
6 12. Digitrip RMS 310+ trip units are suitable for functional field testing with test kit Cat. No. MTS120V.
.8 For field
.7 testing using primary injection methods, follow NEMA publication AB-4-2003. .7
8
.6 .6
5
.5 Fixed Instantaneous .5
Instantaneous
.4 Override override(see Note 8) .4

.3 300 ms .3
TIME IN SECONDS

(P,Q,R)
Available short delay 0.1
.2 pick up settings .2
2 – 8,10, 12 x Ir 5%
(See Note 7) 7
Application determines
end of curve
120 ms
.1 (M,N,O) .1
.09 .09
.08 .08
.07 600V .07
.06 10 .06
.05
Inst. 480V
.05
(J,K,L) 0.01
.04 .04
12 Ii
.03 Interrupting .03

Rating 240V
.02 Determines .02

End of Curve

.01 0.001 .01


.5 .7 1 2 3 4 5 7 10 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 100
1000 10000 100000
Current in Multiples of (lr) Current in Multiples of (lin
Current r) Amps

Figure 3. Types FDE, HFDE, and FDCE 225A—Long/Short Delay—Curve Number TC01203015E

6 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

Current in Multiples of (lr) Digitrip 310+ Circuit Breaker Time/Current Curves (Phase Current)
Series C F-Frame Circuit Breakers
.5 .7 1 2 3 4 5 7 10 20 30
10000
9000 Catalog Types: FDE, HFDE, FDCE
2 HOURS

8000
7000 Trip Unit Types: 32 (LS), 5 (LSG)
6000 FDE Circuit breaker time/current curves (phase current)
Available Sensors (In): 80A, 160A, 225A
5000
1.15 Types
Long FDE,
Delay FDCE, HFDE
Response circuit
(Ir) and breakers
Short Ir
Delay with I nI2T Response
80A 160A 225A
Curve
4000 2
1 HOUR

Long delay (LD) and short delay (SD) with I T response


(Ir) / (In) A 15A 60A 100A
3000
80A 160A 225A B 20A 70A 10A
Available sensors
(In): C 30A 80A 125A
A 15A 60A 100A
80A D 40A 90A 150A
2000
B 160A
20A 70A 110A E 50A 100A 160A
C 225A 30A 80A 125A F 60A 125A 175A
G 70A 150A 200A
D 40A 90A 150A H 80A 160A 225A
EInterrupting ratings—50/60
50A Hz 100A 160A
1000 F Breaker 60A
Symmetrical RMS 125A
amperes (kA) UL/CSA 175A
900 type 240 V 70A
800
G 480V 150A 600 V 200A
700
Maximum total HFDE 65 80A 35 160A 18 225A
600 clearing time HFDE 100 65 25
500 Interrupting
FDCE Rating
200 100 35
UL/CSA rms Sym. kA, 50/60 Hz
400 Notes:
Breaker Type 240V 480V 600V
300 1. Curve accuracy applies from –20C to +55C ambient. Temperatures above +85C cause an over-
FDE 65 35 18
temperature protection trip. For possible continuous ampere derating for ambient above 40C, refer
HFDE
to Eaton. 100 65 25
200 FDCE 200 100 25
2. Application frequency is 50/60 Hz.
Notes:
if a current above the long delay pick up value exists for a time and then is cleared by the tripping of a
Available long delay time:
down stream
1. Curve device
accuracy or thefrom
applies circuit–20C
breaker itself. Aambient.
to +55C subsequent overload willabove
Temperatures cause the circuit
+85C breaker
cause to trip
an overtemperature
100 2,4,7,10,12,15,20,24 sec.
90 in shorter time
protection trip.than
Fornormal.
possibleThecontinuous
amount of time
amperedelayderating
reductionfor
is inverse
ambient to above
the amount
40C,ofrefer
timeto
that
Eaton.
Shown @ 6 x Ir
80
2,4,7,15,24 seconds
1 MINUTE

70 completely reset memory.


+0 / –30% 2. Application frequency is 50/60 Hz.
60
4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
50 3. There is a memory effect that can act to shorten the long delay. The memory effect comes into
40
play if aleft
5. The current
portionabove
of the the
curvelong delay pick
is shown as a up valueofexists
multiple for delay
the long a timesetting
and then is cleared by the
tripping
(Long delayof apick
downup =stream
115% Iof
r
device or110%–120%.
). Range the
is circuit breaker itself. A subsequent overload will cause the
circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse
.
30
to6. the amount
Total clearingof timeshown
times that has elapsed
include since the
the response previous
times overload.
of the trip unit, theApproximately five
breaker opening, andminutes
the is
24 interruption
required of the current.
between overloads to completely reset memory.
20

.
7. The short delay pick up has nine settings/positions: 2–8, 10, 12.
4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
15
2
8. Short
5. The delay I Tofband
left portion the has a tolerance
curve is shownof as
+/–15%.
a multiple of the long delay setting.
Minimum total (long delay pick up = 115% of Ir ). Range is 110%–120%.
10 2
clearing time 9. Breakpoint back to FLAT response occurs @
Ir 8x for upper line of the I T curve.
9
8
7 . 7
6. Total clearing times shown include the response times of the trip unit, the breaker
opening, and the interruption of the current.
(corresponding to SDPU position nine) at (12x
In) +/–20%.is
and designatedIias 12 . Instant aneous tolerance
TIME IN SECONDS

6
7. The short delay pick up has nine settings/positions, 2–8, 10, 12.
.
5

8. Short delay I2T band has a tolerance of +/–15%.


4 4
2
3 12. For LD response and SD with I T response (this curve):
TC01203016E
9. Breakpoint back to FLAT response occurs @ 8x Ir for upper line of the I2T curve.

2
3 . 2
13. For ground fault delay response curve, see: TC01203017E
10. For high fault current levels an additional fixed instantaneous hardware override is provided (corresponding
to SDPU position nine) at 12x (In) and designated as Ii. Instantaneous tolerance is +/–20%.

2 11. For LD response and SD with flat response curve, see: TC01203015E.
4
1
1 12. For LD response and SD with I2T response (this curve): TC01203016E. 1
.9 .9
.8 .8
.7 5 13. For ground fault delay response curve, see: TC01203017E. .7
.6 .6
.5 14. Digitrip RMS 310+ trip units are suitable for functional field testing with test kit Cat. No .5
MTST120V. For field testing using primary injection methods, follow NEMA publication AB 4-2003.
.4 7 .4
12
.3 .3
TIME IN SECONDS

8 Available short delay


.2 pick up settings 0.1 .2
6
2– 8,10, 12 x Ir 5% InstantaneousFixed Instantaneous
(see Note 7) override(see Note 10)
2
I T short delay Override
(see Note 8)

.1 .1
.09 10 .09
.08
.07
.06
. Application determines
end of curve 600V
.08
.07
.06
67ms
.05 .05
0.01 480V
.04 .04

.03 .03
Interrupting
See Note 9 12 Ii
Rating 240V
.02 .02
Determines
End of Curve

.01 .01
.5 .7 1 2 3 4 5 7 10 20 30 40 50 70 100 0.001
2 3 4 5 7 10 20 30 40 50 70 100
1000 10000 100000
Current in Multiples of (lr) of (lr) in Amps
Current in Multiples Current

Figure 4. Types FDE, HFDE, and FDCE 225A—Long Short Delay and I2T—Curve Number TC01203016E

EATON www.eaton.com 7
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

.1 .2 .3 .4 .5 .7 1.0 2.0
10000
9000
8000
7000
6000
Digitrip 310+ Circuit breaker time/current curves (ground current)
5000
Series C F-Frame Circuit Breakers
4000
Catalog Types: FDE, HFDE, FDCE, industrail circuit breakers
3000
Ground fault delay response

2000

1000
900
800
700
600
500

400

300

200

100
90
80
1 MINUTE

70
60
LSG
50

40

30

20
TIME IN SE C ONDS

10
9
8
7
6 Ground fault pickup settings
5
(tolerance 10%)

.2X
.4X LSIG
.6X 1X
1
.9 .3X
Switch
.8
Setting tSD tGF (Ir) / (In) 80A 160A 225A
.7
.8X
.6 J Inst. Inst. A 15A 60A 100A
.5 K Inst. 120 20A 70A 110A
B
.4 L Inst. 300 C 30A 80A 125A
M 120 Inst. D 40A 90A 150A
.3 120 120
N E 50A 100A 160A
300ms
(L,O,R) O 120 300 F 60A 125A 175A
.2 P 300 Inst. G 70A 150A 200A
Q 300 120 H 80A 160A 225A
R 300 300

.1 120ms Notes:
.09 (K,N,Q)
.08
.07 1. Curve accuracy applies from –20C to +55C ambient. Temperatures above +85C cause an
.06 overtemperature protection trip. For possible continuous ampere derating for ambient above 40C,
refer to Eaton.
.05
Inst.
.04
(J,M,P)
2. Application frequency is 50/60 Hz.

.03 3. Trip units are suitable for functional field testing with test kit style # 70C1056G52.

4. For LD response and SD with flat response curve, see: TC01203015E.


.02

5. For LD response and SD with I2T response curve, see: TC01203016E.

4. For ground fault delay response (this curve): TC01203017E.


.01
.1 .2 .3 .4 .5 .7 1.0 2.0

Ground current in multiple of ( In )

Figure 5. Types FDE, HFDE, and FDCE 225A—LSIG—Curve Number TC01203017E

8 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

10000 Digitrip 210+ Circuit Breaker Time/Current Curves (Phase Current)


Series C F-frame circuit breakers (100A and 225A)
Catalog Types: FDE, HFDE Profiles: J, K, R, S
Trip Unit Types: 22 (LSI)

Interrupting Rating
UL/CSA rms Sym. kA, 50/60 Hz
Long Delay Pickup Breaker Type 240Vac 480Vac 600Vac 250Vdc
@ 115%r I ± 5% FDE 65 35 18 —
HFDE 100 65 25 —

1000
Rated Amperes
SD Profile Isd (X lr) tsd(ms)
Ir 100A 225A
J 2 150
Maximum total A 40A 100A
K 2 300
clearingtime B 50A 110A
L 2 I2t
C 60A 125A
M 4 Inst
D 70A 150A
N 4 150
E 80A 175A
O 4 I2t
F 90A 200A
P 6 Inst
G 100A 225A
Q 6 300
R 10 150
100 S 10 300

Long Delay Notes:


Minimum @ 6× Ir +0%/-30%
Commit Time 1 Curve accuracy applies from -20C to +55C. Temperatures above +105C cause an
overtemperature protection trip.

2 There is a memory effect that can act to shorten the long delay. Approximately five
minutes is required between overloads to completely reset this thermal memory.
Time in Seconds

3 Total clearing times shown include the response times of the trip unit, the breaker
opening, and the interruption of the current.

4 Short delay pickups settings in multiples of Ir ± 10%. Short delay time accuracy
10 +0ms/-30ms

5 For high fault current levels an additional fixed instantaneous hardware override is
provided at 2500A ±10%.
10x
2x

1 1

Fixed Instantaneous
300 ms Override
0.1
150 ms

0.1
600V
0.01 480V

Interrupting
Rating 240V
Determines
End of Curve
0.01 0.001
1 10 1000 100 10000 100000
Current in Multiples of I r Current in Amps

Figure 6. Digitrip 210+ Trip Units (100 & 225A), Long Delay and Short Delay with Flat Response and Override (LSI, Profiles K, J, S, R)
Curve Number TD012001EN, June 2015

EATON www.eaton.com 9
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

10000 Digitrip 210+ Circuit Breaker Time/Current Curves (Phase Current)


Series C F-frame circuit breakers (100A and 225A)
Catalog Types: FDE, HFDE Profiles: M, N
Trip Unit Types: 22 (LSI)
Long Delay Pickup
Interrupting Rating
@ 115%r I ± 5% UL/CSA rms Sym. kA, 50/60 Hz
Breaker Type 240Vac 480Vac 600Vac 250Vdc
FDE 65 35 18 —
HFDE 100 65 25 —

1000
Rated Amperes
SD Profile Isd (X lr) tsd(ms)
Ir 100A 225A
J 2 150
Maximum total A 40A 100A
K 2 300
B 50A 110A
clearing time L 2 I2t
C 60A 125A
M 4 Inst
D 70A 150A
N 4 150
E 80A 175A
O 4 I2t
F 90A 200A
P 6 Inst
G 100A 225A
Q 6 300
R 10 150
100 Long Delay
S 10 300
@ 6× Ir +0%/-30%
Notes:
Minimum 1 Curve accuracy applies from -20C to +55C. Temperatures above +105C cause an
Commit Time overtemperature protection trip.

2 There is a memory effect that can act to shorten the long delay. Approximately five
Time in Seconds

minutes is required between overloads to completely reset this thermal memory.

3 Total clearing times shown include the response times of the trip unit, the breaker
opening, and the interruption of the current.

4 Short delay pickups settings in multiples of Ir ± 10%. Short delay time accuracy
10 +0ms/-30ms

5 For high fault current levels an additional fixed instantaneous hardware override is
provided at 2500A ±10%.
4x

1 1

0.1 Fixed Instantaneous


150 ms Override

0.1
600V
50 ms 0.01 480V

Interrupting
Rating 240V
Determines
End of Curve
0.01 0.001
1 10 1000 100 10000 100000
Current in Multiples of I r Current in Amps

Figure 7. Digitrip 210+ Trip Units (100 & 225A), Long Delay and Short Delay with Flat Response and Override (LSI, Profiles N, M)
Curve Number TD012002EN, June 2015

10 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

Digitrip 210+ Circuit Breaker Time/Current Curves (Phase Current)


10000
Series C F-frame circuit breakers (100A and 225A)
Catalog Types: FDE, HFDE Profiles: P, Q
Trip Unit Types: 22 (LSI)

Interrupting Rating
UL/CSA rms Sym. kA, 50/60 Hz
Long Delay Pickup Breaker Type 240Vac 480Vac 600Vac 250Vdc
@ 115%r I ± 5% FDE 65 35 18 —
HFDE 100 65 25 —

1000
Rated Amperes
SD Profile Isd (X lr) tsd(ms)
Ir 100A 225A
J 2 150
A 40A 100A
K 2 300
B 50A 110A
L 2 I2t
Maximum total C 60A 125A
M 4 Inst
D 70A 150A
clearing time E 80A 175A
N 4 150
O 4 I2t
F 90A 200A
P 6 Inst
G 100A 225A
Q 6 300
R 10 150
100 S 10 300

Long Delay Notes:


@ 6× Ir +0%/-30%
1 Curve accuracy applies from -20C to +55C. Temperatures above +105C cause an
Minimum overtemperature protection trip.
Commit Time 2 There is a memory effect that can act to shorten the long delay. Approximately five
minutes is required between overloads to completely reset this thermal memory.
Time in Seconds

3 Total clearing times shown include the response times of the trip unit, the breaker
opening, and the interruption of the current.

4 Short delay pickups settings in multiples of Ir ± 10%. Short delay time accuracy
+0ms/-30ms
10
5 For high fault current levels an additional fixed instantaneous hardware override is
provided at 2500A ±10%.
6x

1 1

300 ms

0.1
Fixed Instantaneous
Override
0.1
600V
50 ms 0.01 480V

Interrupting
Rating 240V
Determines
End of Curve
0.01 0.001
1 10 1000 100 10000 100000
Current in Multiples of I r
Current in Amps

Figure 8. Digitrip 210+ Trip Units (100 & 225A), Long Delay and Short Delay with Flat Response and Override (LSI, Profiles Q, P)
Curve Number TD012003EN, June 2015

EATON www.eaton.com 11
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

10000 Digitrip 210+ Circuit Breaker Time/Current Curves (Phase Current)


Series C F-frame circuit breakers (100A and 225A)
Catalog Types: FDE, HFDE Profiles: L, O
Trip Unit Types: 22 (LSI)

Interrupting Rating
UL/CSA rms Sym. kA, 50/60 Hz
Long Delay Pickup Breaker Type 240Vac 480Vac 600Vac 250Vdc
@ 115%r I ± 5% FDE 65 35 18 —
HFDE 100 65 25 —

1000
Rated Amperes
SD Profile Isd (X lr) tsd(ms)
Ir 100A 225A
J 2 150
Maximum total A 40A 100A
K 2 300
B 50A 110A
clearing time C 60A 125A
L 2 I2t
M 4 Inst
D 70A 150A
N 4 150
E 80A 175A
O 4 I2t
F 90A 200A
P 6 Inst
G 100A 225A
Q 6 300
R 10 150
100 S 10 300

Long Delay Notes:


@ 6× Ir +0%/-30%
1 Curve accuracy applies from -20C to +55C. Temperatures above +105C cause an
Minimum overtemperature protection trip.
Commit Time 2 There is a memory effect that can act to shorten the long delay. Approximately five
Time in Seconds

minutes is required between overloads to completely reset this thermal memory.

3 Total clearing times shown include the response times of the trip unit, the breaker
opening, and the interruption of the current.

4 Short delay pickups settings in multiples of Ir ± 10%. Short delay time accuracy
10 +0ms/-30ms

5 For high fault current levels an additional fixed instantaneous hardware override is
provided at 2500A ±10%.
2x

4x

1 1

0.1
Fixed Instantaneous
Override
0.1
600V
0.01 480V
I2T Short Delay
Interrupting
Rating 240V
Determines
End of Curve
0.01 0.001
1 10 1000 100 10000 100000
Current in Multiples of Ir Current in Amps

Figure 9. Digitrip 210+ Trip Units (100 & 225A), Long Delay and Short Delay with I2t Response and Override (LSI, Profiles L, O)
Curve Number TD012004EN, June 2015

12 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

Digitrip 210+ Circuit Breaker Time/Current Curves (Phase Current)


Series C F-frame circuit breakers (100A and 225A)
10000
Catalog Types: FDE, HFDE
Trip Unit Types: 21 (LI)

Interrupting Rating
UL/CSA rms Sym. kA, 50/60 Hz
Breaker Type 240Vac 480Vac 600Vac 250Vdc
FDE 65 35 18 —
Long Delay Pickup
HFDE 100 65 25 —
@ 115%r I ± 5%

100A 150A
1000 Setting li(xln) Level Setting li(xln) Level
J 2 200A J 2 300A
K 2.5 250A K 2.5 375A
L 3 300A L 3 450A
M 3.5 350A M 3.5 525A
N 4 400A N 4 600A
O 5 500A O 5 750A
P 6 600A P 6 900A
Q 8 800A Q 8 1200A
R 10 1000A R 10 1500A
S 12 1200A S 12 1800A
Override 2500A Override 2500A
100
Rated Amperes
Long Delay
Ir 100A 150A
@ 6× Ir +0%/-30%
A 40A 70A
B 50A 80A
C 60A 90A
Time in Seconds

2× D 70A 100A
E 80A 110A
F 90A 125A
G 100A 150A
2.5x
10 Notes:

1 Curve accuracy applies from -20C to +55C. Temperatures above +105C cause an
3× overtemperature protection trip.

2 There is a thermal memory effect that can act to shorten the long delay. The amount
of time delay reduction is inversely proportional to the amount of time that has
3.5x elapsed since the previous overload. Approximately five minutes is required
between overloads to completely reset this thermal memory effect.

3 Total clearing times shown include the response times of the trip unit, the breaker
opening, and the interruption of the current.

4 For high fault current levels an additional fixed instantaneous hardware override is
provided at 2400A ±20% (corresponding to 11xlr 225A frame, 16xlr for 150A frame,
1 and1 24xlr for 100A frame).

Instantaneous
Pickup ± 10%

8× 0.1 Fixed Instantaneous


Override

0.1 10×

600V
12×
0.01 480V

Interrupting
Rating 240V
Determines
End of Curve
0.01 0.001
1 10 1000 100 10000 100000
Current in Multiples of I n Current in Amps

Figure 10. Digitrip 210+ Trip Units (100 & 150A), Long Delay, Instantaneous Pickups and Override (LI)
Curve Number TD012005EN, June 2015

EATON www.eaton.com 13
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

Digitrip 210+ Circuit Breaker Time/Current Curves (Phase Current)


10000 Series C F-frame circuit breakers (225A)
Catalog Types: FDE, HFDE
Trip Unit Types: 21 (LSI)

Interrupting Rating
UL/CSA rms Sym. kA, 50/60 Hz
Breaker Type 240Vac 480Vac 600Vac 250Vdc
Long Delay Pickup FDE 65 35 18 —
@ 115%r I ± 5% HFDE 100 65 25 —

1000 Rated Amperes


Ir 100A 225A Setting li(xln) Level
A 40A 100A J 2 450A
B 50A 110A K 2.5 565A
C 60A 125A L 3 675A
D 70A 150A M 3.5 790A
E 80A 175A N 4 900A
F 90A 200A O 5 1125A
G 100A 225A P 6 1350A
Q 8 1800A
R 10 2250A
100 S
Override
Override 2500A
2500A
Notes:
Long Delay
@ 6× Ir +0%/-30% 1 Curve accuracy applies from -20C to +55C. Temperatures above +105C cause an
overtemperature protection trip.

2 There is a thermal memory effect that can act to shorten the long delay. The amount
2× of time delay reduction is inversely proportional to the amount of time that has
elapsed since the previous overload. Approximately five minutes is required
Time in Seconds

between overloads to completely reset this thermal memory effect.

3 Total clearing times shown include the response times of the trip unit, the breaker
2.5× opening, and the interruption of the current.
10 4 For high fault current levels an additional fixed instantaneous hardware override is
provided at 2400A ±20% (corresponding to 11xlr 225A frame, 16xlr for 150A frame,
3× and 24xlr for 100A frame).

3.5×

1 1

Instantaneous
Pickup ±10%

8× 0.1
Fixed Instantaneous
Override
0.1 10×

600V
0.01 480V

Interrupting
Rating 240V
Determines
End of Curve
0.01 0.001
1 10 1000 100 10000 100000
Current in Multiples of In Current in Amps

Figure 11. Digitrip 210+ Trip Units (225A), Long Delay, Instantaneous Pickups and Override (LI)
Curve Number TD012006EN, June 2015

14 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

CURRENT IN AMPERES
15A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000

2 HOURS
2 HOURS
5,000 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

Series C F-frame circuit breakers


3,000 3,000
Catalog Types: EHD, FD and HFD circuit breakers, single-pole.
2,000 For application and coordination purposes only. Based on 40°C 2,000
ambient,
cold start.
Connected with four (4) feet of rated wire (60°C up to 100A, 75°C above 125A) per
terminal. Tested in open air.
1,000 1,000
Maximum Vac: 277 at 50/60 Hz
Maximum Vdc: 125

500 Breaker rating 500

Continuous amperes Instantaneous trip, amperes


300 300
15A See curve

200 Interrupting Rating (UL/CSA Listed) 200

Symmetrical RMS amperes (kA) DC Amps


Breaker Type 277V 125V
100 Maximum single- EHD 14 10100
pole trip times
at 25°C 1 FD 35 10

1 MINUTE
1 MINUTE

HFD 65 10
50 50
Notes:

30 1 Single-pole test data at 25°C based on NEMA procedures (AB304-2003) for verifying
performance of molded case circuit breakers.
20 20

10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 .02

Maximum interrupting time


.01 .01

Interrupting
.005 rating .005
determines
end of curve
.003 .003

.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 12. Single Pole, Series C, Types EHD, FD, and HFD 15A—Curve Number SC-4423-88A

EATON www.eaton.com 15
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

CURRENT IN AMPERES
20A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000

2 HOURS
2 HOURS

5,000 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

Series C F-frame circuit breakers


3,000 3,000
Catalog Types: EHD, FD and HFD circuit breakers, single-pole.
2,000 For application and coordination purposes only. Based on 40°C ambient,
2,000 cold start.
Connected with four (4) feet of rated wire (60°C up to 100A, 75°C above 125A) per
terminal. Tested in open air.

1,000 Maximum Vac: 277 at 50/60 Hz 1,000


Maximum Vdc: 125

Breaker rating
500 500
Continuous amperes Instantaneous trip, amperes

300
20A See curve 300

Interrupting Rating (UL/CSA Listed)


200 200
Symmetrical RMS amperes (kA) DC Amps
Breaker Type 277V 125V
EHD 14 10
100 Maximum single- FD 35 10 100
pole trip times
at 25°C 1 HFD 65 10

1 MINUTE
1 MINUTE

Notes:
50 50

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
performance of molded case circuit breakers.
30 30

20 20

Minimum Maximum
10 10

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 .02

Maximum
interrupting
.01 time .01

Interrupting
.005 rating .005
determines
end of curve
.003 .003

.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 13. Single Pole, Series C, Types EHD, FD, and HFD 20A—Curve Number SC-4424-88A

16 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

CURRENT IN AMPERES
25A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000

2 HOURS
2 HOURS
5,000 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

Series C F-frame circuit breakers


3,000 3,000
Catalog Types: EHD, FD and HFD circuit breakers, single-pole.
2,000 For application and coordination purposes only. Based on 40°C ambient,
2,000 cold start.
Connected with four (4) feet of rated wire (60°C up to 100A, 75°C above 125A) per
terminal. Tested in open air.

1,000 Maximum Vac: 277 at 50/60 Hz 1,000


Maximum Vdc: 125

Breaker rating
500 500
Continuous amperes Instantaneous trip, amperes

300
25A See curve 300

Interrupting Rating (UL/CSA Listed)


200 200
Symmetrical RMS amperes (kA) DC Amps
Breaker Type 277V 125V
EHD 14 10
100 Maximum single- FD 100
pole t rip ti mes 35 10
at 25°C 1 HFD 65 10

1 MINUTE
1 MINUTE

Notes:
50 50

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
performance of molded case circuit breakers.
30 30

20 20

10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 .02

Maximum interrupting time


.01 .01

.005 .005
Interrupting
rating
.003 determines .003
end of curve
.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 14. Single Pole, Series C, Types EHD, FD, and HFD 25A—Curve No. SC-4425-88A

EATON www.eaton.com 17
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

CURRENT IN AMPERES
30A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000

2 HOURS
2 HOURS

5,000 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

Series C F-frame circuit breakers


3,000 3,000
Catalog Types: EHD, FD and HFD circuit breakers, single-pole.
2,000 For application and coordination purposes only. Based on 40°C ambient,
2,000 cold start.
Connected with four (4) feet of rated wire (60°C up to 100A, 75°C above 125A) per
terminal. Tested in open air.

1,000 Maximum Vac: 277 at 50/60 Hz 1,000


Maximum Vdc: 125

Breaker rating
500 500
Continuous amperes Instantaneous trip, amperes

30A See curve 300


300

Interrupting Rating (UL/CSA Listed)


200
Symmetrical RMS amperes (kA) DC 200
Amps
Breaker Type 277V 125V
Maximum single- EHD 14 10
100 pole trip times FD 35 10 100
at 25°C 1
HFD 65 10

1 MINUTE
1 MINUTE

Notes:
50 50

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
performance of molded case circuit breakers.
30 30

20 20

10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 .02

Maximum interrupting time


.01 .01

.005 .005
Interrupting
rating
.003 determines .003
end of curve
.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 15. Single Pole, Series C, Types EHD, FD, and HFD 30A—Curve Number SC-4426-88A

18 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

CURRENT IN AMPERES
35A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000

2 HOURS
2 HOURS
Catalog types EHD, FD and HFD circuit breakers, single-pole.
5,000 Circuit
Forbreaker time/current
application and curves
coordination purposes only. 5,000

1 HOUR
1 HOUR

Based on 40˚C ambient, cold start. Connected with four (4) feet of
Seriesrated wire (60˚C up to 100A, 75˚C above 125A) per terminal.
C F-frame
Tested in open air.
circuit breakers
3,000 3,000
Catalog Types: EHD, FD and HFD circuit breakers, single-pole.
Maximum Vac : 277 at 50/60 Hz
Maximum Vdc : 125
2,000 For application and coordination purposes only. Based on 40°C ambient,
2,000 cold start.
Connected with
Breaker four (4) feet of rated wire (60°C up to 100A, 75°C above 125A) per
rating
Continuous
terminal. Tested in open air.
amperes Instantaneous trip, amperes
35A See curve
1,000 Maximum Vac: 277 at 50/60 Hz 1,000
Maximum Vdc: 125
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (kA ) DC amps
type 277V 125V
Breaker rating
EHD 14 10
500 500
Continuous
FD amperes
35 Instantaneous trip, amperes
10
HFD 65 10
35A
Single-pole test data at 25˚C See curve
based on NEMA procedures
300 300
(AB 4-2003
circuit
Interrupting Rating (UL/CSA Listed)
200
Symmetrical RMS amperes (kA) DC 200
Amps
Breaker Type 277V 125V
Maximum single- EHD 14 10
100 pole trip times FD 35 10 100
at 25°C 1
HFD 65 10

1 MINUTE
1 MINUTE

Notes:
50 50

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
performance of molded case circuit breakers.
30 30

20 20

10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 .02

Maximum
interrupting
.01 time .01

.005 .005
Interrupting
rating
.003 determines .003
end of curve
.002 .002

.001 .001
10000
7000

5 6 7 8 9 10 20 40 50 60 70 8090
1000

2000

3000

4000
5000
6000

8000
9000
500

30
700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 16. Single Pole, Series C, Types EHD, FD, and HFD 35A—Curve Number SC-4427-88A

EATON www.eaton.com 19
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

CURRENT IN AMPERES
40A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
Circuit breaker time/current curves

2 HOURS
2 HOURS

®
Series C F-frame circuit breakers
Catalog types EHD, FD and HFD circuit breakers, single-pole.
5,000 For application and coordination purposes only. 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

Based on 40˚C ambient, cold start. Connected with four (4) feet of
Seriesrated wire (60˚C up to 100A, 75˚C above 125A) per terminal.
C F-frame
Tested in open air. circuit breakers
3,000 3,000
Catalog Types:
Maximum EHD,
Vac: FD
277 and HFD
at 50/60 Hz circuit breakers, single-pole.
Maximum Vdc: 125
2,000 For application and coordination purposes only. Based on 40°C ambient,2,000 cold start.
Breaker
Connected rating
with four (4) feet of rated wire (60°C up to 100A, 75°C above 125A) per
Continuous
terminal. Tested
amperes
in open air. Instantaneous trip, amperes
40A See curve
1,000 Maximum Vac: 277 at 50/60 Hz 1,000
Interrupting
Maximum Vdc: 125rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (kA ) DC amps
type 277V 125V
Breaker rating
EHD 14 10
500 500
FD
Continuous 35
amperes Instantaneous 10
trip, amperes
HFD 65 10
40A See curve
Single-pole test data at 25˚C based on NEMA procedures
300 300
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Interrupting Rating (UL/CSA Listed)
200
Symmetrical RMS amperes (kA) DC 200
Amps
Breaker Type 277V 125V
Maximum single- EHD 14 10
100 pole trip times FD 35 10 100
at 25°C 1
HFD 65 10

1 MINUTE
1 MINUTE

Notes:
50 50

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
performance of molded case circuit breakers.
30 30

20 20

10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 .02

Maximum interrupting time


.01 .01

.005 .005
Interrupting
rating
.003 determines .003
end of curve
.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 17. Single Pole, Series C, Types EHD, FD, and HFD 40A—Curve Number SC-4428-88A
20 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

CURRENT IN AMPERES
45A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
Circuit breaker time/current curves

2 HOURS
2 HOURS
Series C ® F-frame circuit breakers
Catalog types EHD, FD and HFD circuit breakers, single-pole.
5,000 For application and coordination purposes only. 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

Based on 40˚C ambient, cold start. Connected with four (4) feet of
rated wire (60˚C up to 100A, 75˚C above 125A) per terminal.
Series C F-frame circuit breakers
Tested in open air.
3,000 3,000
Catalog Types:
Maximum Vac EHD,
: 277 atFD and
50/60 HzHFD circuit breakers, single-pole.
Maximum Vdc : 125
2,000 For application and coordination purposes only. Based on 40°C ambient,
2,000 cold start.
Connected
Breaker with
ratingfour (4) feet of rated wire (60°C up to 100A, 75°C above 125A) per
Continuous
terminal. Tested in open air.
amperes Instantaneous trip, amperes
45A See curve
1,000 Maximum Vac: 277 at 50/60 Hz 1,000
Maximum 125 (UL/CSA listed)
Vdc:rating
Interrupting
Breaker Symmetrical Rms amperes (kA ) DC amps
type 277V 125V
Breaker rating
EHD 14 10
500 500
Continuous
FD 35amperes Instantaneous trip,10
amperes
HFD 65 10
45A Seeoncurve
Single-pole test data at 25˚C based NEMA procedures
300 300
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Interrupting Rating (UL/CSA Listed)
200 200Amps
Symmetrical RMS amperes (kA) DC
Breaker Type 277V 125V
Maximum single- EHD 14 10
100 pole trip times FD 35 10100
at 25°C 1 HFD 65 10

1 MINUTE
1 MINUTE

Notes:
50 50
1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
performance of molded case circuit breakers.
30 30

20 20

10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 .02

Maximum interrupting time


.01 .01

.005 .005
Interrupting
rating
.003 determines .003
end of curve
.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 18. Single Pole, Series C, Types EHD, FD, and HFD 45A—Curve No. SC-4429-88A

EATON www.eaton.com 21
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

CURRENT IN AMPERES
50A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000

2 HOURS
Circuit breaker time/current curves
2 HOURS

®
Series C F-frame circuit breakers
Catalog types EHD, FD and HFD circuit breakers, single-pole.
5,000 For application and coordination purposes only. 5,000
Circuit breaker time/current
start. Connectedcurves

1 HOUR
1 HOUR

Based on 40˚C ambient, cold with four (4) feet of


rated wire (60˚C up to 100A, 75˚C above 125A) per terminal.
Series C F-frame
Tested in open air. circuit breakers
3,000 3,000
Catalog Types:
Maximum Vac: 277 EHD,
at 50/60FD
Hz and HFD circuit breakers, single-pole.
Maximum Vdc: 125
2,000 For application and coordination purposes only. Based on 40°C 2,000ambient, cold start.
Breaker rating
Connected with four (4) feet of rated wire (60°C up to 100A, 75°C above 125A) per
Continuous
terminal.
amperes Tested in open air. Instantaneous trip, amperes
50A See curve
1,000 Maximum Vac: 277 at 50/60 Hz 1,000
Interrupting rating (UL/CSA listed)
Maximum Vdc: 125
Breaker Symmetrical Rms amperes (kA ) DC amps
type 277V 125V
Breaker14rating
EHD 10
500 500
FD 35
Continuous
HFD 65
amperes Instantaneous 10
trip, amperes
10

300 50A See curve


Single-pole test data at 25˚C based on NEMA procedures
300
(AB 4-2003) for verifying performance of molded case
circuit breakers.

200
Interrupting Rating (UL/CSA Listed)
200
Symmetrical RMS amperes (kA) DC Amps
Breaker Type 277V 125V
Maximum single- EHD 14 10
100 pole trip times FD
100
at 25°C 1 35 10
HFD 65 10

1 MINUTE
1 MINUTE

50
Notes: 50

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
30 performance of molded case circuit breakers. 30

20 20

10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 .02

Maximum interrupting time


.01 .01

.005 .005
Interrupting
rating
.003 determines .003
end of curve
.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 19. Single Pole, Series C, Types EHD, FD, and HFD 50A—Curve Number SC-4430-88A

22 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

CURRENT IN AMPERES
60A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
Circuit breaker time/current curves

2 HOURS
2 HOURS
®
Series C F-frame circuit breakers
Catalog types EHD, FD and HFD circuit breakers, single-pole.
5,000 For application and coordination purposes only. 5,000
Circuit
on 40˚Cbreaker time/current curves

1 HOUR
1 HOUR

Based ambient, cold start. Connected with four (4) feet of


rated wire (60˚C up to 100A, 75˚C above 125A) per terminal.
Series
Tested in openCair.
F-frame circuit breakers
3,000 3,000
Catalog
Maximum Types:
Vac: 277 at EHD, FD
50/60 Hz and HFD circuit breakers, single-pole.
Maximum Vdc: 125
2,000 For application and coordination purposes only. Based on 40°C
2,000 ambient, cold start.
Breaker rating with four (4) feet of rated wire (60°C
Connected up to 100A, 75°C above 125A) per
Continuous
terminal. Tested in openInstantaneous
amperes
air. trip, amperes
60A See curve
1,000 Maximum Vac: 277 at 50/60 Hz 1,000
Maximum
Interrupting Vdc:
rating 125 listed)
(UL/CSA
Breaker Symmetrical Rms amperes (kA ) DC amps
type 277V 125V
Breaker rating
EHD 14 10
500 500
FD Continuous
35 amperes Instantaneous
10trip, amperes
HFD 65 10
60A
Single-pole See procedures
test data at 25˚C based on NEMA curve
300 300
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Interrupting Rating (UL/CSA Listed)
200
Symmetrical RMS amperes (kA) 200 DC Amps
Breaker Type 277V 125V
Maximum single- EHD 14 10
100 pole trip times FD 35 100 10
at 25°C 1 HFD 65 10

1 MINUTE
1 MINUTE

Notes:
50 50
1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
performance of molded case circuit breakers.
30 30

20 20

10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 .02

Maximum interrupting time


.01 .01

.005 .005
Interrupting
rating
.003 determines .003
end of curve
.002 .002

.001 .001
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

5 6 7 8 9 10 20 30 40 50 60 70 8090

CURRENT IN AMPERES

Figure 20. Single Pole, Series C, Types EHD, FD, and HFD 60A—Curve Number SC-4431-88A

EATON www.eaton.com 23
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

CURRENT IN AMPERES
70A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000

2 HOURS
2 HOURS

Circuit breaker time/current curves


Series C ® F-frame circuit breakers
Catalog types EHD, FD and HFD circuit breakers, single-pole.
5,000 For application and coordination purposes only. 5,000
Circuit breaker
ambient, time/current curves

1 HOUR
1 HOUR

Based on 40˚C cold start. Connected with four (4) feet of


rated wire (60˚C up to 100A, 75˚C above 125A) per terminal.
Series C F-frame
Tested in open air. circuit breakers
3,000 3,000
Catalog
Maximum Types:
Vac: 277EHD, FDHzand HFD circuit breakers, single-pole.
at 50/60
Maximum Vdc: 125
2,000 For application and coordination purposes only. Based on 40°C ambient, cold start.
2,000
Breaker rating
Connected with four (4) feet of rated wire (60°C up to 100A, 75°C above 125A) per
Continuous
terminal.
amperes
Tested in open air.
Instantaneous trip, amperes
70A See curve
1,000 Maximum Vac: 277 at 50/60 Hz 1,000
Interrupting Vdc:
Maximum rating 125
(UL/CSA listed)
Breaker Symmetrical Rms amperes (kA ) DC amps
type 277V 125V
Breaker rating
EHD 14 10 500
500
FD 35
Continuous amperes 10
Instantaneous trip, amperes
HFD 65 10

300
70A
Single-pole test data at 25˚C based onSee curve
NEMA procedures
300
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Interrupting Rating (UL/CSA Listed)
200 200
Symmetrical RMS amperes (kA) DC Amps
Maximum single- Breaker Type 277V 125V
pole trip times
at 25°C 1 EHD 14 10
100 FD 100
35 10
HFD 65 10

1 MINUTE
1 MINUTE

Notes:
50 50

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
performance of molded case circuit breakers.
30 30

20 20

10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 .02
Maximum
interrupting
time
.01 .01

.005 .005
Interrupting
rating
.003 determines .003
end of curve
.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 21. Single Pole, Series C, Types EHD, FD, and HFD 70A—Curve Number SC-4432-88A

24 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

CURRENT IN AMPERES
80A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
Circuit breaker time/current curves

2 HOURS
2 HOURS
Series C ® F-frame circuit breakers
Catalog types EHD, FD and HFD circuit breakers, single-pole.
5,000 For application and coordination purposes only. 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

Based on 40˚C ambient, cold start. Connected with four (4) feet of
rated wire (60˚C up to 100A, 75˚C above 125A) per terminal.
Series
Tested C air.
in open F-frame circuit breakers
3,000 3,000
Catalog
Maximum Types:
Vac: 277 atEHD, FD
50/60 Hz and HFD circuit breakers, single-pole.
Maximum Vdc: 125
2,000 For application and coordination purposes only. Based on 40°C
2,000 ambient, cold start.
Breaker rating with four (4) feet of rated wire (60°C
Connected up to 100A, 75°C above 125A) per
Continuous
terminal. Tested in openInstantaneous
amperes
air. trip, amperes
80A See curve
1,000 Maximum Vac: 277 at 50/60 Hz 1,000
Interrupting
Maximum rating
Vdc:(UL/CSA
125 listed)
Breaker Symmetrical Rms amperes (kA ) DC amps
type 277V 125V
Breaker rating
EHD 14 10
500 500
FDContinuous
35 amperes Instantaneous10trip, amperes
HFD 65 10
80A See procedures
Single-pole test data at 25˚C based on NEMA curve
300 300
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Interrupting Rating (UL/CSA Listed)
200
Symmetrical RMS amperes (kA) 200 DC Amps
Maximum single- Breaker Type 277V 125V
pole trip times
at 25°C 1 EHD 14 10
100 FD 35 100 10
HFD 65 10

1 MINUTE
1 MINUTE

Notes:
50 50

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
performance of molded case circuit breakers.
30 30

20 20

10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 .02

Maximum
interrupting
time
.01 .01

.005 .005
Interrupting
rating
.003 determines .003
end of curve
.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 22. Single Pole, Series C, Types EHD, FD, and HFD 80A—Curve Number SC-4433-88A

EATON www.eaton.com 25
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

CURRENT IN AMPERES
90A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000

2 HOURS
2 HOURS

Circuit breaker time/current curves


®
Series C F-frame circuit breakers
Catalog types EHD, FD and HFD circuit breakers, single-pole.
5,000 For application and coordination purposes only. 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

Based on 40˚C ambient, cold start. Connected with four (4) feet of
rated wire (60˚C up to 100A, 75˚C above 125A) per terminal.
Series
Tested C air.
in open F-frame circuit breakers
3,000 3,000
Catalog
Maximum Types:
Vac: 277 atEHD,
50/60 FD
Hz and HFD circuit breakers, single-pole.
Maximum Vdc: 125
2,000 For application and coordination purposes only. Based on 40°C
2,000ambient, cold start.
Breaker rating with four (4) feet of rated wire (60°C
Connected up to 100A, 75°C above 125A) per
Continuous
terminal. Tested in open Instantaneous
amperes
air. trip, amperes
90A See curve
1,000 Maximum Vac: 277 at 50/60 Hz 1,000
Interrupting
Maximum rating
Vdc: (UL/CSA
125 listed)
Breaker Symmetrical Rms amperes (kA ) DC amps
type 277V 125V
Breaker rating
500 EHD 14 10 500
FDContinuous
35 amperes Instantaneous10trip, amperes
HFD 65 10
90A See curve
Single-pole test data at 25˚C based on NEMA procedures
300
300 (AB 4-2003) for verifying performance of molded case circuit
breakers.
Interrupting Rating (UL/CSA Listed)
200
Symmetrical RMS amperes (kA) 200 DC Amps
Maximum single- Breaker Type 277V 125V
pole trip times
at 25°C 1 EHD 14 10
100 FD 35 100 10
HFD 65 10

1 MINUTE
1 MINUTE

Notes:
50 50

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
performance of molded case circuit breakers.
30 30

20 20

10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 .02

Maximum
interrupting
time
.01 .01

.005 .005
Interrupting
rating
.003 determines .003
end of curve
.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 23. Single Pole, Series C, Types EHD, FD, and HFD 90A—Curve Number SC-4434-88A

26 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

CURRENT IN AMPERES
100A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
Circuit breaker time/current curves

2 HOURS
2 HOURS
®
Series C F-frame circuit breakers
Catalog types EHD, FD and HFD circuit breakers, single-pole.
5,000 For application and coordination purposes only. 5,000
Circuit breaker coldtime/current curves

1 HOUR
1 HOUR

Based on 40˚C ambient, start. Connected with four (4) feet of


rated wire (60˚C up to 100A, 75˚C above 125A) per terminal.
Series
Tested in openC air.F-frame circuit breakers
3,000 3,000
Catalog
Maximum Vac:Types: EHD,HzFD
277 at 50/60 and HFD circuit breakers, single-pole.
Maximum Vdc: 125
2,000 For application and coordination purposes only. Based on2,000
40°C ambient, cold start.
Breaker rating with four (4) feet of rated wire (60°C
Connected up to 100A, 75°C above 125A) per
Continuous
terminal. Tested in open
amperes air.
Instantaneous trip, amperes
100A See curve
1,000 Maximum Vac: 277 at 50/60 Hz 1,000
Interrupting
Maximum rating (UL/CSA
Vdc: 125 listed)
Breaker Symmetrical Rms amperes (kA ) DC amps
type 277V 125V
Breaker rating
EHD 14 10
500 500
FD 35 10
Continuous amperes Instantaneous trip, amperes
HFD 65 10

300
100A
Single-pole Seeprocedures
test data at 25˚C based on NEMA curve 300
(AB 4-2003) for verifying performance of molded case
circuit breakers.
Interrupting Rating (UL/CSA Listed)
200 200
Symmetrical RMS amperes (kA) DC Amps
Maximum single-
pole trip times Breaker Type 277V 125V
at 25°C 1 EHD 14 10
100 100
FD 35 10
HFD 65 10

1 MINUTE
1 MINUTE

Notes: 50
50

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
30
performance of molded case circuit breakers.
30

20 20

10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 .02

Maximum
interrupting
time
.01 .01

.005 .005
Interrupting
rating
.003 determines .003
end of curve
.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 24. Single Pole, Series C, Types EHD, FD, and HFD 100A—Curve Number SC-4435-88A

EATON www.eaton.com 27
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

CURRENT IN AMPERES
110A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000

2 HOURS
2 HOURS

®
F-frame circuit breakers
Circuit breaker time/current curves
5,000 Series C F-frame circuit breakers 5,000

1 HOUR
1 HOUR

Catalog Types: EHD, FD and HFD circuit breakers, single-pole.


3,000 For application and coordination purposes only. Based on 40°C 3,000
ambient, cold start.
Connected with277 at 50/60 Hz
four
125
(4) feet of rated wire (60°C up to 100A, 75°C above 125A) per
2,000 terminal. Tested in open air. 2,000

Maximum Vac: 277 at 50/60 Hz


Maximum Vdc: 125
1,000 1,000
Breaker rating
DC amps
Continuous amperes Instantaneous 125V
trip, amperes
10
500 500
110A See curve 10

300 Interrupting Rating (UL/CSA Listed) 300


Symmetrical RMS amperes (kA) DC Amps
200 Breaker Type 277V 125V 200
FD 35 10
HFD 65 10
100 Notes: 100

1 MINUTE
1 MINUTE

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
performance of molded case circuit breakers.
50 50

30 30

20 Maximum single- 20
pole trip times
at 25°C 1

10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 .02

Maximum
interrupting
time
.01 .01

.005 .005
Interrupting
rating
.003 determines .003
end of curve
.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 25. Single Pole, Series C, Types FD and HFD 110A—Curve Number SC-4436-88A

28 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

CURRENT IN AMPERES
125A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000

2 HOURS
2 HOURS
®
F-frame circuit breakers

5,000 For application and coordination purposes only. 5,000


Circuit breaker time/current curves

1 HOUR
1 HOUR

Based on 40˚C ambient, cold start. Connected with four (4) feet of
rated wire (60˚C up to 100A, 75˚C above 125A) per terminal.
Series
TestedC F-frame
in open air. circuit breakers
3,000 3,000
Catalog Types:
Maximum Vac: FD and
277 at HFD
50/60 Hz circuit breakers, single-pole.
Maximum Vdc: 125
2,000 For application and coordination purposes only. Based on 40°C ambient,
2,000 cold start.
Breaker rating
Connected with four (4) feet of rated wire (60°C up to 100A, 75°C above 125A) per
Continuous
terminal. Tested
amperes in open air. Instantaneous trip, amperes
125A See curve
1,000 Maximum Vac: 277 at 50/60 Hz 1,000
Interrupting rating (UL/CSA listed)
Maximum Vdc: 125
Breaker Symmetrical Rms amperes (kA ) DC amps
type 277V 125V
Breaker rating
FD 35 10
500 500
HFD 65 10
Continuous amperes Instantaneous trip, amperes
Single-pole test data at 25˚C based on NEMA procedures
300
125A See of
(AB 4-2003) for verifying performance curve
molded case 300
circuit breakers.

Interrupting Rating (UL/CSA Listed)


200 200
Symmetrical RMS amperes (kA) DC Amps
Breaker Type 277V 125V
FD 35 10
100 100
HFD 65 10
Notes:

1 MINUTE
1 MINUTE

50 1 Single-pole test data at 25°C based on NEMA procedures (AB


50 4-2003) for verifying
performance of molded case circuit breakers.

30 30

20 20

Maximum single-
pole trip times
at 25°C 1
10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 .02

Maximum
interrupting
time
.01 .01

.005 .005
Interrupting
rating
.003 determines .003
end of curve
.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 26. Single Pole, Series C, Types FD and HFD 125A—Curve Number SC-4437-88A

EATON www.eaton.com 29
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

CURRENT IN AMPERES
150A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000

2 HOURS
2 HOURS

Circuit breaker time/current curves


Series C ® F-frame circuit breakers
Catalog types FD and HFD circuit breakers, single-pole.
5,000 For application and time/current
coordination purposes only. 5,000
Circuit breaker curves

1 HOUR
1 HOUR

Based on 40˚C ambient, cold start. Connected with four (4) feet of
rated wire (60˚C up to 100A, 75˚C above 125A) per terminal.
Series C F-frame circuit breakers
Tested in open air.
3,000 3,000
Catalog Types: FD and HFD circuit breakers, single-pole.
Maximum Vac: 277 at 50/60 Hz
Maximum Vdc: 125
2,000 For application and coordination purposes only. Based on 40°C ambient,
2,000 cold start.
Connected with four (4) feet of rated wire (60°C up to 100A, 75°C above 125A) per
Breaker rating
Continuous
terminal. Tested in open air.
amperes Instantaneous trip, amperes
150A See curve
1,000 Maximum Vac: 277 at 50/60 Hz 1,000
Maximum 125 (UL/CSA listed)
Vdc:rating
Interrupting
Breaker Symmetrical Rms amperes (kA ) DC amps
type 277V 125V
Breaker rating
FD 35 10
500 500
Continuous
HFD 65amperes Instantaneous trip,10amperes
Single-pole test data at 25˚C based on NEMA procedures
150A See curve
(AB 4-2003) for verifying performance of molded case
300 300
circuit breakers.
Interrupting Rating (UL/CSA Listed)
200 200Amps
Symmetrical RMS amperes (kA) DC
Breaker Type 277V 125V
FD 35 10
100 HFD 65 10100

Notes:

1 MINUTE
1 MINUTE

50 1 Single-pole test data at 25°C based on NEMA procedures (AB504-2003) for verifying
performance of molded case circuit breakers.

30 30

20 20

Maximum single-
pole trip times
10 at 25°C 1 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 .02

Maximum
interrupting
time
.01 .01

.005 .005
Interrupting
rating
.003 determines .003
end of curve
.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 27. Single Pole, Series C, Types FD and HFD 150A—Curve Number SC-4438-88A

30 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

ED, EHD, FDB FD, HFD, FDC 15A 2, 3 & 4 pole


AB DE-ION Circuit Breakers—two-, three-, and four-poles

10000.00

Circuit Breaker time/current curv es

Series C F-Frame Circuit Breakers


Catalog Types: ED, EHD, FDB, FD, HFD, FDC
for two, three and four pole breakers

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
Connected with four (4) feet of rated wire (60/75° C) per terminal
with all poles wired in series. Tested in open air.
1000.00 Instantaneous tripping is single pole.

Maximum Vac: 600V at 50/60Hz


Maximum Vdc: 250V

Maximum Single Pole Trip Breaker Rating


Times at 25 C Continuous Amps Instantaneous trip amperes

15A See curve


May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc 125 Vdc
100.00 ED 65 -- -- -- 10
EHD 18 14 -- 10 --
FDB 18 14 14 10 --
FD 65 35 18 10 --
HFD 100 65 25 22 --
FDC 200 100 35 22 --
Time in Seconds

Maximum
Tolerance
10.00
Minimum
Tolerance

1.00

0.10
interruption rating and
application determines
end of curve

240V 480V 600V

0.01
10 100 1000 10000 100000 1000000

Current in Amperes

Figure 28. Types ED, EHD, FDB, FD, FDC, and HFD 15A 2, 3 & 4 pole—Curve Number TC012036EN

EATON www.eaton.com 31
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame
ED, EHD, FDB FD, HFD, FDC 20A 2, 3 & 4 pole

10000.00

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Catalog Types: ED, EHD, FDB, FD, HFD, FDC
for two, three and four pole breakers

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
Connected with four (4) feet of rated wire (60/75°C) per terminal with
1000.00 all poles wired in series. Tested in open air.
Instantaneous tripping is single pole.

Maximum Vac: 600V at 50/60Hz


Maximum Vdc: 250V
Maximum Single Pole Trip
Breaker Rating
Times at 25°C Continuous Amps Instantaneous trip amperes

20A See curve


May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


Breaker Symmetrical RMS amperes (kA)
100.00 Type 240 Vac 480Vac 600 Vac 250 Vdc 125 Vdc
ED 65 -- -- -- 10
EHD 18 14 -- 10 --
FDB 18 14 14 10 --
FD 65 35 18 10 --
HFD 100 65 25 22 --
FDC 200 100 35 22 --
Time in Seconds

Maximum
Tolerance
10.00
Minimum
Tolerance

1.00

0.10
interruption rating and
application determines
end of curve

240V 480V 600V

0.01
10 100 1000 10000 100000 1000000
Current in Amperes

Figure 29. Types ED, EHD, FDB, FD, FDC, and HFD 20A 2, 3 & 4 pole—Curve Number TC012037EN

Eaton Corporation January 2012


32 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022
ED, EHD, FDB FD, HFD, FDC 25A 2, 3 & 4 pole

10000.00

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Catalog Types: ED, EHD, FDB, FD, HFD, FDC
for two, three and four pole breakers

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
Connected with four (4) feet of rated wire (60/75°C) per terminal with
1000.00 all poles wired in series. Tested in open air.
Instantaneous tripping is single pole.

Maximum Vac: 600V at 50/60Hz


Maximum Vdc: 250V
Maximum Single Pole Trip
Times at 25°C
Breaker Rating
Continuous Amps Instantaneous trip amperes

25A See curve


May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


100.00 Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc 125 Vdc
ED 65 -- -- -- 10
EHD 18 14 -- 10 --
FDB 18 14 14 10 --
FD 65 35 18 10 --
HFD 100 65 25 22 --
FDC 200 100 35 22 --
Time in Seconds

Maximum
Tolerance
10.00
Minimum
Tolerance

1.00

0.10
interruption rating and
application determines
end of curve

240V 480V 600V

0.01
10 100 1000 10000 100000 1000000
Current in Amperes

Figure 30. Types ED, EHD, FDB, FD, FDC, and HFD 25A 2, 3 & 4 pole—Curve Number TC012038EN

Eaton Corporation January 2012


EATON www.eaton.com 33
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame
ED, EDH, EHD, FDB FD, HFD, FDC 30A 2, 3 & 4 pole

10000.00

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Catalog Types: ED, EHD,FDB, FD, HFD, FDC
for two, three and four pole breakers

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
Connected with four (4) feet of rated wire (60/75°C) per terminal with
1000.00 all poles wired in series. Tested in open air.
Instantaneous tripping is single pole.

Maximum Vac: 600V at 50/60Hz


Maximum Vdc: 250V
Maximum Single Pole Trip
Times at 25°C
Breaker Rating
Continuous Amps Instantaneous trip amperes

30A See curve


May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


100.00 Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc 125 Vdc
ED 65 -- -- -- 10
EHD 18 14 -- 10 --
FDB 18 14 14 10 --
FD 65 35 18 10 --
HFD 100 65 25 22 --
FDC 200 100 35 22 --
Time in Seconds

Maximum
Tolerance
10.00
Minimum
Tolerance

1.00

0.10
interruption rating and
application determines
end of curve

240V 480V 600V

0.01
10 100 1000 10000 100000 1000000
Current in Amperes

Figure 31. Types ED, EHD, FDB, FD, FDC, and HFD 30A 2, 3 & 4 pole—Curve Number TC012039EN

Eaton Corporation January 2012


34 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022
ED, EHD, FDB FD, HFD, FDC 35A 2, 3 & 4 pole

10000.00

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Catalog Types: ED, EHD, FDB, FD, HFD, FDC
for two, three and four pole breakers

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
Connected with four (4) feet of rated wire (60/75°C) per terminal with
1000.00 all poles wired in series. Tested in open air.
Instantaneous tripping is single pole.

Maximum Vac: 600V at 50/60Hz


Maximum Single Pole Trip Maximum Vdc: 250V
Times at 25°C
Breaker Rating
Continuous Amps Instantaneous trip amperes

35A See curve


May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


100.00 Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc 125 Vdc
ED 65 -- -- -- 10
EHD 18 14 -- 10 --
FDB 18 14 14 10 --
FD 65 35 18 10 --
HFD 100 65 25 22 --
FDC 200 100 35 22 --
Time in Seconds

Maximum
Tolerance
10.00
Minimum
Tolerance

1.00

0.10
interruption rating and
application determines
end of curve

240V 480V 600V

0.01
10 100 1000 10000 100000 1000000
Current in Amperes

Figure 32. Types ED, EHD, FDB, FD, FDC, and HFD 35A 2, 3 & 4 pole—Curve Number TC012040EN

Eaton Corporation January 2012


EATON www.eaton.com 35
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame
ED, EHD, FDB FD, HFD, FDC 40A 2, 3 & 4 pole

10000.00

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Catalog Types: ED, EHD, FDB, FD, HFD, FDC
for two, three and four pole breakers

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
Connected with four (4) feet of rated wire (60/75°C) per terminal with
1000.00 all poles wired in series. Tested in open air.
Instantaneous tripping is single pole.

Maximum Vac: 600V at 50/60Hz


Maximum Single Pole Trip Maximum Vdc: 250V
Times at 25°C
Breaker Rating
Continuous Amps Instantaneous trip amperes

40A See curve


May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


100.00 Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc 125 Vdc
ED 65 -- -- -- 10
EHD 18 14 -- 10 --
FDB 18 14 14 10 --
FD 65 35 18 10 --
HFD 100 65 25 22 --
FDC 200 100 35 22 --
Time in Seconds

Maximum
Tolerance
10.00
Minimum
Tolerance

1.00

0.10
interruption rating and
application determines
end of curve

240V 480V 600V

0.01
10 100 1000 10000 100000 1000000
Current in Amperes

Figure 33. Types ED, EHD, FDB, FD, FDC, and HFD 40A 2, 3 & 4 pole—Curve Number TC012041EN

Eaton Corporation January 2012


36 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022
ED, EHD, FDB FD, HFD, FDC 45A 2, 3 & 4 pole

10000.00

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Catalog Types: ED, EHD, FDB, FD, HFD, FDC
for two, three and four pole breakers

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
Connected with four (4) feet of rated wire (60/75°C) per terminal with
1000.00 all poles wired in series. Tested in open air.
Instantaneous tripping is single pole.

Maximum Vac: 600V at 50/60Hz


Maximum Vdc: 250V
Maximum Single Pole Trip
Times at 25°C
Breaker Rating
Continuous Amps Instantaneous trip amperes

45A See curve


May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


100.00 Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc 125 Vdc
ED 65 -- -- -- 10
EHD 18 14 -- 10 --
FDB 18 14 14 10 --
FD 65 35 18 10 --
HFD 100 65 25 22 --
FDC 200 100 35 22 --
Time in Seconds

Maximum
Tolerance
10.00
Minimum
Tolerance

1.00

0.10
interruption rating and
application determines
end of curve

240V 480V 600V

0.01
10 100 1000 10000 100000 1000000
Current in Amperes

Figure 34. Types ED, EHD, FDB, FD, FDC, and HFD 45A 2, 3 & 4 pole—Curve Number TC012042EN

Eaton Corporation January 2012


EATON www.eaton.com 37
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame
ED, EHD, FDB FD, HFD, FDC 50A 2, 3 & 4 pole

10000.00

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Catalog Types: ED, EHD, FDB, FD, HFD, FDC
for two, three and four pole breakers

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
Connected with four (4) feet of rated wire (60/75°C) per terminal with
1000.00 all poles wired in series. Tested in open air.
Maximum Single Pole Trip Instantaneous tripping is single pole.
Times at 25°C
Maximum Vac: 600V at 50/60Hz
Maximum Vdc: 250V

Breaker Rating
Continuous Amps Instantaneous trip amperes

50A See curve


May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


100.00 Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc 125 Vdc
ED 65 -- -- -- 10
EHD 18 14 -- 10 --
FDB 18 14 14 10 --
FD 65 35 18 10 --
HFD 100 65 25 22 --
FDC 200 100 35 22 --
Time in Seconds

Maximum
Tolerance
10.00
Minimum
Tolerance

1.00

0.10
interruption rating and
application determines
end of curve

240V 480V 600V

0.01
10 100 1000 10000 100000 1000000
Current in Amperes

Figure 35. Types ED, EHD, FDB, FD, FDC, and HFD 50A 2, 3 & 4 pole—Curve Number TC012043EN

Eaton Corporation January 2012


38 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022
ED, EHD, FDB FD, HFD, FDC 60A 2, 3 & 4 pole

10000.00

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Catalog Types: ED, EHD, FDB, FD, HFD, FDC
for two, three and four pole breakers

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
Connected with four (4) feet of rated wire (60/75°C) per terminal with
1000.00 all poles wired in series. Tested in open air.
Maximum Single Pole Trip Instantaneous tripping is single pole.
Times at 25°C
Maximum Vac: 600V at 50/60Hz
Maximum Vdc: 250V

Breaker Rating
Continuous Amps Instantaneous trip amperes

60A See curve


May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


100.00 Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc 125 Vdc
ED 65 -- -- -- 10
EHD 18 14 -- 10 --
FDB 18 14 14 10 --
FD 65 35 18 10 --
HFD 100 65 25 22 --
FDC 200 100 35 22 --
Time in Seconds

Maximum
Tolerance
10.00
Minimum
Tolerance

1.00

0.10
interruption rating and
application determines
end of curve

240V 480V 600V

0.01
10 100 1000 10000 100000 1000000
Current in Amperes

Figure 36. Types ED, EHD, FDB, FD, FDC, and HFD 60A 2, 3 & 4 pole—Curve Number TC012044EN
Eaton Corporation January 2012
EATON www.eaton.com 39
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame
ED, EHD, FDB FD, HFD, FDC 70A 2, 3 & 4 pole

10000.00

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Catalog Types: ED, EHD, FDB, FD, HFD, FDC
for two, three and four pole breakers

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
Connected with four (4) feet of rated wire (60/75°C) per terminal with
1000.00 all poles wired in series. Tested in open air.
Maximum Single Pole Trip Instantaneous tripping is single pole.
Times at 25°C
Maximum Vac: 600V at 50/60Hz
Maximum Vdc: 250V

Breaker Rating
Continuous Amps Instantaneous trip amperes

70A See curve


May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


100.00 Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc 125 Vdc
ED 65 -- -- -- 10
EHD 18 14 -- 10 --
FDB 18 14 14 10 --
FD 65 35 18 10 --
HFD 100 65 25 22 --
FDC 200 100 35 22 --
Time in Seconds

Maximum
Tolerance
10.00
Minimum
Tolerance

1.00

0.10
interruption rating and
application determines
end of curve

240V 480V 600V

0.01
10 100 1000 10000 100000 1000000
Current in Amperes

Figure 37. Types ED, EHD, FDB, FD, FDC, and HFD 70A 2, 3 & 4 pole—Curve Number TC012045EN
Eaton Corporation January 2012
40 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022
ED, EHD, FDB FD, HFD, FDC 80A 2, 3 & 4 pole

10000.00

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Catalog Types: ED, EHD, FDB, FD, HFD, FDC
for two, three and four pole breakers

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
Connected with four (4) feet of rated wire (60/75°C) per terminal with
1000.00 all poles wired in series. Tested in open air.
Instantaneous tripping is single pole.
Maximum Single Pole Trip
Maximum Vac: 600V at 50/60Hz
Times at 25°C Maximum Vdc: 250V

Breaker Rating
Continuous Amps Instantaneous trip amperes

80A See curve


May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


100.00 Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc 125 Vdc
ED 65 -- -- -- 10
EHD 18 14 -- 10 --
FDB 18 14 14 10 --
FD 65 35 18 10 --
HFD 100 65 25 22 --
FDC 200 100 35 22 --
Time in Seconds

Maximum
Tolerance
10.00
Minimum
Tolerance

1.00

0.10
interruption rating and
application determines
end of curve

240V 480V 600V

0.01
10 100 1000 10000 100000 1000000
Current in Amperes

Figure 38. Types ED, EHD, FDB, FD, FDC, and HFD 80A 2, 3 & 4 pole—Curve Number TC012046EN

Eaton Corporation January 2012


EATON www.eaton.com 41
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame
ED, EHD, FDB FD, HFD, FDC 90A 2, 3 & 4 pole

10000.00

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Catalog Types: ED, EHD, FDB, FD, HFD, FDC
for two, three and four pole breakers

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
Connected with four (4) feet of rated wire (60/75°C) per terminal with
1000.00 all poles wired in series. Tested in open air.
Instantaneous tripping is single pole.
Maximum Single Pole Trip
Maximum Vac: 600V at 50/60Hz
Times at 25°C Maximum Vdc: 250V

Breaker Rating
Continuous Amps Instantaneous trip amperes

90A See curve


May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


100.00 Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc 125 Vdc
ED 65 -- -- -- 10
EHD 18 14 -- 10 --
FDB 18 14 14 10 --
FD 65 35 18 10 --
HFD 100 65 25 22 --
FDC 200 100 35 22 --
Time in Seconds

Maximum
Tolerance
10.00
Minimum
Tolerance

1.00

0.10
interruption rating and
application determines
end of curve

240V 480V 600V

0.01
10 100 1000 10000 100000 1000000
Current in Amperes

Figure 39. Types ED, EHD, FDB, FD, FDC, and HFD 90A 2, 3 & 4 pole—Curve Number TC012047EN
Eaton Corporation January 2012
42 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022
ED, EDB, EDS, EDH, EDC, EHD, FDB FD, HFD, FDC 100A 2, 3 & 4 pole

10000.00

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Catalog Types: ED, EDB, EDS, EDH, EDC, EHD,
FDB, FD D, HFD,, FDC
for two, three and four pole breakers

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
1000.00 Connected with four (4) feet of rated wire (60/75°C) per terminal
Maximum Single Pole Trip with all poles wired in series. Tested in open air.
Instantaneous tripping is single pole.
Times at 25°C
Maximum Vac: 600V at 50/60Hz
Maximum Vdc: 250V

Breaker Rating
Continuous Amps Instantaneous trip amperes

100A see curve


May be 42% higher for dc voltages

100.00 Interruption Ratings (UL/CSA listed)


Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc 125 Vdc
ED 65 -- -- -- 10
EDB 22 -- -- -- 10
EDS 42 -- -- -- 10
EDH 100 -- -- -- 10
EDC 200 -- -- -- 10
EHD 18 14 -- 10 --
Time in Seconds

Maximum FDB 18 14 14 10 --
Minimum FD 65 35 18 10 --
Tolerance Tolerance
10.00 HFD 100 65 25 22 --
FCD 200 100 35 22 --

1.00

0.10

interruption rating and


application determines
end of curve

240V 480V 600V

0.01
10 100 1000 10000 100000 1000000
Current in Amperes

Figure 40. Types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 100A 2, 3 & 4 pole—Curve Number TC012029EN

EATON www.eaton.com 43
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

Figure 41. Types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 110A 2, 3, & 4 pole—Curve Number TC012030EN

44 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

Figure 42. Types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 125A 2, 3, & 4 pole—Curve Number TC012031EN

EATON www.eaton.com 45
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame
ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD FDC 150A 2, 3 & 4 pole

10000.000

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Catalog Types: ED, EDB, EDS, EDH, EDC, EHD,
FDB, FD,, HFD,, FDC
for two, three and four pole breakers
Maximum Single Pole Trip For application and coordination purposes only.
Times at 25°C Based on cold start at rated ambient temperature.
1000.000 Connected with four (4) feet of rated wire (60/75 °C) per terminal
with all poles wired in series. Tested in open air.
Instantaneous tripping is single pole.

Maximum Vac: 600V at 50/60Hz


Maximum Vdc: 250V

Breaker Rating
Continuous Amps Instantaneous trip amperes
150A see curve
May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


100.000 Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc 125 Vdc
ED 65 -- -- -- 10
EDB 22 -- -- -- 10
EDS 42 -- -- -- 10
EDH 100 -- -- -- 10
EDC 200 -- -- -- 10
EHD 18 14 -- 10 --
FDB 18 14 14 10 --
Time in Seconds

FD 65 35 18 10 --
HFD 100 65 25 22 --
FDC 200 100 35 22 --
10.000

Minimum Maximum
Tolerance Tolerance

1.000

0.100
interruption rating and
application determines
end of curve

240V 480V 600V

0.010
10 100 1000 10000 100000 1000000
Current in Amperes

Figure 43. Types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 150A 2, 3, & 4 pole—Curve Number TC012032EN

46 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

ED, EDB, EDS, EDH, EDC, EHD, FDB FD, HFD, FDC 175A 2, 3 & 4 pole

10000.000

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Maximum Single Pole Trip Catalog Types: ED, EDB, EDS, EDH, EDC, EHD,
Times at 25°C FDB, FD,, HFD,,FDC
for two, three and four pole breakers

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
1000.000 Connected with four (4) feet of rated wire (60/75°C) per terminal
with all poles wired in series. Tested in open air.
Instantaneous tripping is single pole.

Maximum Vac: 600V at 50/60Hz


Maximum Vdc: 250V

Breaker Rating
Continuous Amps Instantaneous trip amperes

175A See curve


May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


100.000
Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc 125 Vdc
ED 65 -- -- -- 10
EDB 22 -- -- -- 10
EDS 42 -- -- -- 10
EDH 100 -- -- -- 10
Maximum EDC 200 -- -- -- 10
Tolerance EHD 18 14 -- 10 --
Time in Seconds

FDB 18 14 14 10 --
FD 65 35 18 10 --
Minimum HFD 100 65 25 22 --
10.000 FDC 200 100 35 22 --
Tolerance

1.000

0.100
interruption rating and
application determines
end of curve

240V 480V 600V

0.010
10 100 1000 10000 100000 1000000
Current in Amperes

Figure 44. Types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 175A 2, 3 & 4 pole—Curve Number TC012033EN
Eaton Corporation January 2012
EATON www.eaton.com 47
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame
ED, EDB, EDS, EDH, EDC, EHD, FDB FD, HFD, FDC 200A 2, 3 & 4 pole

10000.000

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Maximum Single Pole Trip Catalog Types: ED, EDB, EDS, EDH, EDC, EHD,
Times at 25°C FDB, FD,, HFD,,FDC
for two, three and four pole breakers

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
1000.000 Connected with four (4) feet of rated wire (60/75°C) per terminal
with all poles wired in series. Tested in open air.
Instantaneous tripping is single pole.

Maximum Vac: 600V at 50/60Hz


Maximum Vdc: 250V

Breaker Rating
Continuous Amps Instantaneous trip amperes

200A See curve


May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


100.000
Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc 125 Vdc
ED 65 -- -- -- 10
EDB 22 -- -- -- 10
EDS 42 -- -- -- 10
EDH 100 -- -- -- 10
Maximum
EDC 200 -- -- -- 10
Tolerance EHD 18 14 -- 10 --
Time in Seconds

FDB 18 14 14 10 --
FD 65 35 18 10 --
Minimum HFD 100 65 25 22 --
10.000 FDC 200 100 35 22 --
Tolerance

1.000

0.100
interruption rating and
application determines
end of curve

240V 480V 600V

0.010
10 100 1000 10000 100000 1000000
Current in Amperes

Figure 45. Types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 200A 2, 3, & 4 pole—Curve Number TC012034EN
Eaton Corporation January 2012
48 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

ED, EDB, EDS, EDH, EDC, EHD, FDB FD, HFD, FDC 225A 2, 3 & 4 pole

10000.000

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Maximum Single Pole Trip Catalog Types: ED, EDB, EDS, EDH, EDC, EHD,
Times at 25°C FDB, FD,, HFD,, FDC
for two, three and four pole breakers

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
1000.000 Connected with four (4) feet of rated wire (60/75°C) per terminal
with all poles wired in series. Tested in open air.
Instantaneous tripping is single pole.

Maximum Vac: 600V at 50/60Hz


Maximum Vdc: 250V

Breaker Rating
Continuous Amps Instantaneous trip amperes

225A See curve


May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


100.000
Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc 125 Vdc
ED 65 -- -- -- 10
EDB 22 -- -- -- 10
EDS 42 -- -- -- 10
Maximum EDH 100 -- -- -- 10
Tolerance EDC 200 -- -- -- 10
EHD 18 14 -- 10 --
Time in Seconds

FDB 18 14 14 10 --
FD 65 35 18 10 --
Minimum HFD 100 65 25 22 --
10.000 FDC 200 100 35 22 --
Tolerance

1.000

0.100
interruption rating and
application determines
end of curve

240V 480V 600V

0.010
10 100 1000 10000 100000 1000000
Current in Amperes

Figure 46. Types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 225A 2, 3, & 4 pole—Curve Number TC012035EN

EATON www.eaton.com 49
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

FDC 150A 240V


Peak Let Through Current
100

240V
Peak Let -Through Current, kA

10

1
1 10 100 1000
Available Short Circuit Current, kA rms

Figure 47. Series C type FDC - 240V let-through current 150A. April 2022.

Eaton Corporation September 2017 Rev. 1

50 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

FDC 150A 240V


Peak Let Through Energy
10000000
Peak Let -Through Energy I2t, A2sec

1000000
240V

100000

10000
1 10 100 1000
Available Short Circuit Current, kA rms

Figure 48. Series C type FDC - 240V let-through energy 150A. April 2022.

Eaton Corporation September 2017 Rev. 1

EATON www.eaton.com 51
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

FDC 225A 240V


Peak Let Through Current
100

240V
Peak Let -Through Current, kA

10

1
1 10 100 1000
Available Short Circuit Current, kA rms
Figure 49. Series C type FDC - 240V let-through current 225A. April 2022

Eaton Corporation September 2017 Rev. 1

52 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

FDC 225A 240V


Peak Let Through Energy
10000000
Peak Let -Through Energy I2t, A2sec

1000000
240V

100000

10000
1 10 100 1000
Available Short Circuit Current, kA rms

Figure 50. Series C type FDC - 240V let-through energy 225A. April 2022

Eaton Corporation September 2017 Rev. 1

EATON www.eaton.com 53
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

FDC 150A 480V


Peak Let Through Current
100

480V
Peak Let -Through Current, kA

10

1
1 10 100 1000
Available Short Circuit Current, kA rms

Figure 51. Series C type FDC 480V let through current 150A. April 2022

Eaton Corporation September 2017 Rev. 1

54 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

FDC 150A 480V


Peak Let Through Energy
10000000
Peak Let -Through Energy I2t, A2sec

480V

1000000

100000
1 10 100 1000
Available Short Circuit Current, kA rms

Figure 52. Series C type FDC - 480V let through energy 150A. April 2022

Eaton Corporation September 2017 Rev. 1

EATON www.eaton.com 55
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

FDC 225A 480V


Peak Let Through Current
100

480V
Peak Let -Through Current, kA

10

1
1 10 100 1000
Available Short Circuit Current, kA rms
Figure 53. Series C type FDC - 480V let-through current 225A. April 2022

Eaton Corporation September 2017 Rev. 1

56 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

FDC 225A 480V


Peak Let Through Energy
10000000
Peak Let -Through Energy I2t, A2sec

480V

1000000

100000
1 10 100 1000
Available Short Circuit Current, kA rms

Figure 54. Series C type FDC - 480V let through energy 225A. April 2022

Eaton Corporation September 2017 Rev. 1

EATON www.eaton.com 57
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

FDC 150A 600V


Peak Let Through Current
100

600V
Peak Let -Through Current, kA

10

1
1 10 100
Available Short Circuit Current, kA rms

Figure 55. Series C type FDC - 600V let-through current 150A. April 2022

Eaton Corporation September 2017 Rev. 1

58 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

FDC 150A 600V


Peak Let Through Energy
10000000

600V
Peak Let-Through Energy I2t, A2 sec

1000000

100000
1 10 100
Available Short Circuit Current, kA rms

Figure 56 Series C type FDC - 600V let-through energy 150A. April 2022

Eaton Corporation September 2017 Rev. 1

EATON www.eaton.com 59
Time Current Curves TC01200002E Series C
Effective April 2022 F-Frame

FDC 225A 600V


Peak Let Through Current
100

600V
Peak Let -Through Current, kA

10

1
1 10 100
Available Short Circuit Current, kA rms

Figure 57. Series C type FDC - 600V let-through current 225A. April 2022

Eaton Corporation September 2017 Rev. 1

60 EATON www.eaton.com
Series C Time Current Curves TC01200002E
F-Frame Effective April 2022

FDC 225A 600V


Peak Let Through Energy
10000000

600V
Peak Let-Through Energy I2t, A2 sec

1000000

100000
1 10 100
Available Short Circuit Current, kA rms

Figure 58. Series C type FDC - 600V let-through energy 225A. April 2022

Eaton Corporation September 2017 Rev. 1

EATON www.eaton.com 61
Time Current Curves TC01200002E Series C F-frame circuit breaker
Effective April 2022 time current curves