Professional Documents
Culture Documents
more-about-arcfault-circuit-interrupters
more-about-arcfault-circuit-interrupters
Abstract: Since the Arc-Fault Circuit number of fires are occurring from electrical
Interrupter (AFCI) was commercially causes. [3, 4, 5, 6] Actual fire evidence indicates
introduced in 1998, questions have arisen that arcs are a cause of a significant number of
about how it detect arcs, whether it detects these electrical fires. [7, 8] As equipment is
series and parallel arcs, and what types of used, it may be subjected to physical damage or
AFCIs are available. Types other than the hot spots may occur from electrical or other
original branch/feeder AFCI are emerging. sources. In addition, those who are not skilled in
This paper is intended to provide an update electrical work do modifications. A common
regarding answers to those questions, initiation of arcing is arc tracking from an
following an earlier paper that introduced the exposed live part across organic insulation. The
basic functioning of the AFCI. [1] surface across which the arc travels becomes
carbonized or “pyrolyzed” and becomes fire fuel
Index Terms. Arc-fault circuit interrupter, as it becomes an electrical conductor.
arc-fault detection, AFCI.
Figure 1 shows a typical time-current
I. INTRODUCTION characteristic for a 20-ampere circuit breaker
used as overcurrent protection. Any element
According to 210.12 of the National Electrical such as the wire indicated above and to the right
Code (NEC), an AFCI is “a device intended to of the curve is protected. The circuit breaker
provide protection from the effects of arc faults opens the circuit prior to reaching those
by recognizing characteristics unique to arcing conditions. Therefore overcurrent protection
and by functioning to de-energize the circuit provides protection for arcing faults as well as
when an arc fault is detected.” [2] AFCIs are other faults or overcurrent conditions. However,
commercially available in ratings of 15 and 20 the circuit breaker does not open when
amperes, 120 V, ac, primarily for application in conditions of time and current are as shown in
residences. However, they are increasingly the regions marked 1 and 2 on the curve.
applied in commercial and industrial offices and
workrooms. Their purpose is to detect and This curve is intended to protect conductors from
disconnect uncontrolled arcing that could cause thermal damage. It is not intended to protect
fire. They are not helpful if they disconnect against the effects of arcing.
useful, normal energy, and the industry standard
comprehensively tests against unwanted
operation. 10000
10
techniques are applied in products that are being
produced today as well as newer products that 1
are currently being field tested.
0.1
0.01 2 1
II. SYSTEM PROTECTION
0.001
Each circuit today is provided with overcurrent 1 10 100 1000 10000
protection that detects overloads and short current (am peres)
circuits. When this overcurrent protection is
properly applied, it might seem that no other
form of circuit protection should be required. Figure 1 – Time-current characteristic for a 20 A
However, as pointed out in other publications, a circuit breaker
0 0
-20 -5
III. ARC MODES
-40 -10
Current
Hazardous or uncontrolled arcing occurs in three -60 -15
0.002
0.004
0.006
0.008
0.01
0.012
0.014
0.016
0.018
0.02
0.022
0.024
0.026
0.028
0
modes:
Time (sesonds)
• Line-to-neutral (L-N or parallel)
• Series
• Line-to ground (L-G)
Figure 2 – Generalized arc characteristics
The L-N arc is a short circuit and generally
occurs at higher levels that could cause fire
ignition rapidly. A series arc is in series with a In the parallel circuit case where influence of
load and therefore at lower levels than the L-N loads other than the conductors themselves is
1307
minimal on the current and voltage signal, these outputs a signal to cause the AFCI to open the
arc characteristics are relatively pronounced. circuit. In the next subsections, we will examine
However, as the attempt is made to distinguish arc occurrences in several load conditions to see
the arc where loads are in the circuit, other what the AFCI sees.
factors emerge. The next section will explore
several of those influences. B. Probabilistic Nature of the Arc
Arc Fault
Sensing &
Tripping Circuit
Line-to Series
ground arc
Normally arc
closed AFCI
contacts
Line
Supply
Neutral Load
Line-to-neutral
Sensing arc
transformer(s)
1308
C. Parallel Arc Figure 5 is exactly the same circuit, same type of
cable and same conditions as for Figure 4.
Figure 4 illustrates a parallel arc between line Notice the difference in characteristics. We see
and neutral conductors of a NM-B cable cut by a some characteristics pronounced in Figure 5:
metal blade. A short-circuit current of 75 A was • Reduced current
available at the cut point with a bolted fault • Rate of rise steeper than ideal
connected. • Shoulders
150
However, we do not see high frequency chatter
Arc current and the wave shape is quite different in the two
100
figures.
Peak current (Amperes)
50
0
The differences between Figures 4 and 5
0 0.01 0.02 0.03 0.04 0.05 illustrate the probabilistic nature of the arc and
-50
the fact that the detector must look for a
-100 combination of indicators to make a positive
Ideal current
-150
identification. With these L-N parallel arcs, the
Time (ms) characteristics are definite and recognizable,
even though quite variable from trial to trial and
from cycle to cycle.
Figure 4 – Current trace from a 75 A L-N arc
D. Series Arc
We can clearly see a number of arc
characteristics including: With the series arc we see lower current as well
• Reduced current amplitude from ideal as unusual waveshapes caused by the loads
• High frequency chatter themselves. To detect an arc when the arc is in
• Shoulders series with a load, it will be necessary to look for
• Rate of rise steeper than ideal in some cases changes as well as the characteristics themselves.
It is easiest to detect changes between normal
Notice that no two half cycle traces are the same and arcing current. However, the presence of the
and that the arc characteristics are more arc introduces changes from one half cycle to the
pronounced in some segments than others. Since next that also serve to distinguish arcing without
this arc was initiated by cutting the cable, there comparison with normal current. Some loads
was no “normal” current flow prior to the arc for have characteristics that look much like
comparison of changes. In other words, the characteristics of arcs. It is necessary in these
detector must recognize the arc characteristics cases to examine a number of half cycles in order
without a reference to “normal” current. Since to confirm that an arc is present with a high
the characteristics are definite in this case, the probability. We gain a glimpse of how that is
AFCI had no difficulty recognizing them and done as we look at current waveshapes in
opened the circuit after about 35 ms. Figures 6 through 9. Waveshapes of load current
with arcing in series are significantly different
150 from normal current waveshapes, but differences
Ideal current
100 may not be easily visible. They can be
Peak Current (Amperes)
1309
and current with arcing present. We see a
Even though current with and without an arc definite change in current amplitude from normal
present is similar, the characteristics of arcing to arcing current. Also, with arcing current, the
are readily distinguishable and the presence of duration of the current pulse varies. A high
the arc can be positively identified. frequency component is present, but not easily
seen in this figure. In order to distinguish arcing
20 Normal Arcing
15
positively with the dimmer in the circuit may
10
require a longer time for analysis than with more
Current (Amperes)
5
readily distinguishable loads.
0
-5 0 0.05 0.1 0.15 0.2
20 Normal Arcing
-10 15
-15
10
Current (Amperes)
-20
5
Time (Seconds)
0
-5 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16
-10
Figure 6 – Current trace from vacuum cleaner
-15
-20
Time (Seconds)
Personal computer
Figure 7 shows a personal computer. Again an Figure 8 – Current from 1000 W dimmer
arc is introduced after the device has been
operating, for comparison. The switch mode
power supply exhibits an unusual waveshape that Compressor
appears to have many of the characteristics of
arcing when no arcing is present. However, the The normal current and arcing current for the
genuine arcing is readily distinguishable from compressor seen in Figure 9 share many
normal current by several characteristics: characteristics that make it difficult to
• Significant change in amplitude from distinguish. As with the vacuum cleaner, high
normal frequency changes are not pronounced because
• Variable amplitude the inductance in the circuit filters them out to a
• Occasional absence of current pulse large degree. Also, notice that amplitude
• Heightened high frequency chatter variations exist in both normal and arcing
current. Distinguishable characteristics include:
25 Arcing • Amplitude variations
20
Normal • Shoulders present
15 • Change in rate of rise of current
Current (Amperes)
10
5 30 Arcing
0
Normal
20
-5 0 0.05 0.1 0.15 0.2
Current (Amperes)
-10 10
-15
0
-20
-0.05 0 0.05 0.1 0.15 0.2
Time (Seconds) -10
-20
-30
Figure 7 – Current from personal computer Time (Seconds)
1310
E. Microprocessor Decision Process for Arc these hot spots is to damage and pyrolyze
Signal Detection insulation, arc tracking and leakage is a frequent
result. The AFCI will detect such leakage and
The loads illustrated here represent those that are provides a degree of protection against this mode
among the most difficult to have in a circuit of electrical circuit damage.
while distinguishing the presence of an arc in
series. In each case, there are distinguishable The standard requirement is detection of L-G
characteristics, but it is necessary to look for arcing of 5 amperes or greater. The low 0.050 A
multiple characteristics. There is no single level of ground-fault detection identifies this
characteristic of the arc that is always present kind of fault in its early stages before it escalates
and measurable. From these illustrations, it to become a fire hazard.
should be clear that a systematic analysis is
possible to find the characteristics of arcing,
determine that multiple characteristics are VI. STANDARDS REQUIREMENTS
simultaneously present, and confirm that they
repeat. The analysis algorithm establishes Other works have identified the comprehensive
decision criteria that confirm the presence of an standards requirements for AFCIs, including
arc with a high probability. Although we have those that detect arcs in lower level circuits in
examined only current waveshapes for arcs in series with loads. [9, 10] The industry standard
series with loads, the analysis may also include is UL 1699, Standard for Safety for Arc-Fault
voltage characteristics. Circuit Interrupters. [11] UL 1699 includes three
extensive areas of testing for arc detection:
F. Ground Fault Detection • Arc detection, which is determination that
the device will detect arcing under several
In addition to arc signal detection and modes and a variety of current levels within
processing, present AFCIs employ ground-fault a specified time.
detection. That is, they detect the imbalance of • Unwanted operation in which avoidance of
current between that leaving the line terminal nuisance operation is tested with a wide
and that returning in the neutral conductor. If the variety of equipment including some of the
imbalance is greater than about 50 milliamperes, devices illustrated in Figures 6 to 9.
the device opens the circuit. • Operation inhibition in which the AFCI
must demonstrate that it will detect an arc
There are two key reasons for including ground- even when it is in series or parallel with
fault detection: equipment or appliances that tend to hide,
1. One form of arcing fault is the line-to- mask attenuate or disguise the arc.
ground fault. Regardless of whether this
stray current is arcing, it is unwanted since it Required detection levels are indicated in Table
is outside of the intended circuit and is 1 below.
detected at a low level. This is a very
definite method of detecting these L-G faults
including any arcing faults. VII. AFCI TYPES
2. Many arcing faults involve multiple modes
of arcing. For example L-N arc tracking There are three types of AFCI identified in UL
inside of a damaged lighting fixture may 1699: branch/feeder (B/F), outlet circuit (OC)
also include stray current to grounded metal. and combination (COMB). As we look at the
Detecting the stray current to ground and section above titled, “System protection” and
opening the circuit also clears the L-N fault. Figure 1, the B/F AFCI is targeted at region 1,
the OC AFCI is targeted at region 2 and the
There is a third reason for including ground-fault COMB AFCI combines the functions of the
detection that is really a corollary to reason 1 other two and targets both regions together.
above. Glowing connections, which are
extremely hot connection points arising from The definitions of these three devices from UL
loose connections, are frequently cited as the 1699 are as follows.
cause of damage to wiring devices and wire
insulation. The effects of these glowing Branch/Feeder AFCI – A device intended to be
connections can lead to fire. Since an effect of installed at the origin of a branch circuit or
1311
feeder, such as at a panelboard. It is intended to are nuances of difference between requirements
provide protection of the branch circuit wiring, for the two. However, the detection technology
feeder wiring, or both, against unwanted effects used for one would likely apply to the other with
of arcing. This device also provides limited minor differences, if any. The major difference
protection to branch circuit extension wiring. It between the two, as seen in the definitions, is the
may be a circuit-breaker type device or a device intended location in the circuit. The OC AFCI is
in its own enclosure mounted at or near a intended to be located at an outlet and would not
panelboard. protect an entire circuit from that location.
Outlet Circuit AFCI – A device intended to be
installed at a branch circuit outlet, such as at an
outlet box. It is intended to provide protection of
cord sets and power-supply cords connected to it VIII. CONCLUSION
(when provided with receptacle outlets) against
the unwanted effects of arcing. This device may This paper has:
provide feed-through protection of the cord sets • Clarified differences between higher current
and power-supply cords connected to L-N (parallel) arcs and lower current arcs
downstream receptacles. that are in series with a load
Combination AFCI – An AFCI that complies • Illustrated characteristics of an arc in current
with the requirements for both branch/feeder and and voltage signals as detected by the AFCI
outlet circuit AFCIs. It is intended to protect • Discussed the probabilistic nature of the
downstream branch circuit wiring and cord sets appearance of arc characteristics
and power-supply cords. • Shown that the AFCI detects several
characteristics simultaneously in order to
Table 1 below briefly compares the capabilities distinguish an arc from normal current with
of the three types of AFCI. a high probability
• Presented the various types of AFCI
The B/F AFCI was the first to be introduced
commercially and today (June 2003) it is the This information confirms that the AFCI is a
only AFCI commercially available. It detects the practical product in all three types presented. It
higher level arcs most likely to cause fire. It is detects arcs in all three modes, L-N, series and
also the device least likely to experience L-G. The differences in degree of detection
unwanted operation. However, several devices among the three types are seen in Table 1. This
have more recently been third party listed to UL information is intended to serve the reader in
1699 as COMB AFCIs. The manufacturers of applying AFCIs to achieve protection needed.
these devices have indicated that the COMB
AFCI is ready to be made commercially
available.
1312
IX. REFERENCES
1313