IEC 62109-1
Safety of Power Converter for use in Photovoltaic Power Systems
Part 1: General requirements
Name of Testing Laboratory prepar- TÜV SÜD Certification and Testing (China) Co., Ltd. Guangzhou
ing the Report ............................... : Branch
5F, Communication Building, 163 Pingyun Rd, Huangpu Ave.
West, Guangzhou 510656, P. R. China
.......................... : EAST Group Co., Ltd.
Address ......................................... : No.6 Northern Industry Road, Songshan Lake Sci. & Tech. Indus-
try Park, 523808 DongGuan City, Guangdong Province,
PEOPLE'S REPUBLIC OF CHINA
Test specification:
Standard........................................ : IEC/EN 62109-1:2010
Test procedure.............................. : CE_LVD
Non-standard test method ........... : N/A
Test Report Form No. ................... : IEC62109_1B
Test Report Form(s) Originator.... : VDE Testing and Certification Institute
Master TRF .................................... : Dated 2016-04
Copyright © 2016 IEC System of Conformity Assessment Schemes for Electrotechnical Equipment
and Components (IECEE System). All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copy-
right owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the
reader's interpretation of the reproduced material due to its placement and context.
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB
Scheme procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and
appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
General disclaimer:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing CB Testing La-
boratory. The authenticity of this Test Report and its contents can be verified by contacting the NCB, respon-
sible for this Test Report.
TRF_IEC62109_1B
List of Attachments (including a total number of pages in each attachment):
This test report contains 2 parts listed in below table:
Item Description Pages
Part 1 IEC/EN 62109-1:2010 test report 103
Part 2 IEC/EN 62109-2:2011 test report 30
This test report shall be also used in conjunction with 12 pages of photo documentation.
Summary of testing:
All tests were carried out according to IEC 62109-1:2010. The text of IEC 62109-1:2010 was approved by
CENELEC as a European Standard without any modification.
Tests performed (name of test and test clause):
Clause Requirement
4.3 Thermal testing
4.4 Testing in single fault condition
4.5 Humidity preconditioning
4.6 Backfeed voltage protection
4.7 Electrical ratings tests
5.1.2 Durability of markings
6.3 Ingress protection
7.3 Protection against electric shock
7.4 Protection against energy hazards
7.5 Electrical tests related to shock hazard
8.5 Wall mounting
15 Software and firmware performing safety functions.
TRF_IEC62109_1B
Copy of marking plate:
The artwork below may be only a draft. The use of certification marks on a product must be authorized by
the respective NCBs that own these marks.
Below electric ratings and warnings are silk-screen on label and affixed side of enclosure.
TRF_IEC62109_1B
Test item particulars ..............................................:
Equipment mobility...................................................: movable hand-held stationary
fixed transportable for building-in
Connection to the mains ..........................................: pluggable equipment direct plug-in
permanent connection for building-in
Enviromental category.............................................: outdoor indoor indoor
unconditional conditional
Over voltage category Mains ...................................: OVC I OVC II OVC III OVC IV
Over voltage category PV........................................: OVC I OVC II OVC III OVC IV
Mains supply tolerance (%) .....................................: +/- 10%
Tested for power systems .......................................: TN system
IT testing, phase-phase voltage (V) .........................: N/A
Class of equipment .................................................: Class I Class II Class III
Not classified
Mass of equipment (kg) ...........................................: Net weight: 22.3 kg (Approx.)
Pollution degree ......................................................: PD II
IP protection class ...................................................: IP 20 (indoor use only)
Testing
Date of receipt of test item(s)................................... 2018-10-29
Dates tests performed ............................................. 2018-11-01 to 2019-03-18
Possible test case verdicts:
test case does not apply to the test object ........ N/A
test object does meet the requirement ............... Pass (P)
test object was not evaluated for the require- N/E
ment ..................................................................
test object does not meet the requirement ......... Fail (F)
General remarks:
"(see Attachment #)" refers to additional information appended to the report.
"(see appended table)" refers to a table appended to the report.
The tests results presented in this report relate only to the object tested.
This report shall not be reproduced except in full without the written approval of the testing laboratory.
Additional test data and/or information provided in the attachments to this report.
Throughout this report a comma / point is used as the decimal separator.
This TRF was modified by TUV SUD Guangzhou branch by adding Cl.4 and Annex A to J.
Abbreviations used in the report:
Basic insulation (BI); Supplementary insulation (SI); Double insulation (DI); Reinforced insulation (RI);
Functional insulation (FI); Single fault condition (SFC); Normal condition (NC); Mains overvoltage catego-
ry (OVC); Pollution degree (PD), CDF (Construction Data form)
-clause 4.2.5 of IECEE 02:
The application for obtaining a CB Test Certifi- Yes
cate includes more than one factory location and
Not applicable
a declaration from the Manufacturer stating that
the sample(s) submitted for evaluation is (are)
representative of the products from each factory
TRF_IEC62109_1B
has been provided ....................................................
When differences exist; they shall be identified in the General product information section.
Name and address of factory (ies) ........................ :
Factory name: EAST Group Co., Ltd.
Address: No.6 Northern Industry Road, Songshan Lake Sci. & Tech. Industry Park, 523808 DongGuan
City, Guangdong Province, PEOPLE'S REPUBLIC OF CHINA
General product information:
(1) The unit is non-isolated (transformerless) hybrid solar inverter, it is intended to be connected with
household generation systems with battery to store energy.
(2) The unit has four operating modes: grid-tied mode, anti-reflux mode, off-grid mode and bypass
mode. The difference between anti-reflux mode and grid-tied mode is that energy will not be deliv-
ered to the grid in anti-reflux mode.
(3) The unit has 4 connection terminals: PV input terminal, grid terminal, battery terminal and AC load
terminal. intended to use solar power, utility power and battery power to ensure continuous
power supply.
(4) The unit shall be used at specified ambient conditions. Indoor, conditioned, temperature range: 0 -
40 °C. Altitude: <1000 m, Auto-derating above 1000 m; Overvoltage category: III (Grid), II(PV);
Relative humidity range: 0 - 90 %.
(5) If certain functions are not permitted by local regulation, the function shall be disabled by hardware
or software setting (if applicable) by the manufacturer before putting into the market. For example,
Model differences:
N/A
Ratings:
Model EA5KHD
PV input rating
Max. input power 5500 W
Rated input voltage 360 Vd.c.
Max. input voltage 550 Vd.c.
MPPT voltage range 120 Vd.c. 530 Vd.c.
MPPT voltage range (full load) 250 Vd.c. 450 Vd.c.
TRF_IEC62109_1B
Max. input current 2 x 12 Ad.c.
PV short circuit current 2 x 15 Ad.c.
Battery input/output rating
Battery type Lithium or Lead-acid
Rated voltage (Lithium) 51.2 Vd.c.
Battery voltage range(Lithium) 46.4 Vd.c. - 57.6 Vd.c.
Rated voltage (Lead-acid) 48 Vd.c.
Battery voltage range(Lead-acid) 40 Vd.c. 58 Vd.c.
Max. charging power 2500 W
Max. charging current 50 Ad.c.
Max. discharging power 2500 W
Max. discharging current 50 Ad.c.
Grid input rating
Rated input voltage 230 Va.c.
Rated grid frequency 50 Hz
Max. input apparent power 2000 VA
Max. input active power 2000 W
Max. input current 8.7 Aa.c
Grid output rating
Max. output apparent power 5000 VA
Max. output active power 5000 W
Rated output voltage 230 Va.c.
Max. output current 21.7 Aa.c.
Rated output frequency 50 Hz
Power factor 0.9 leading - 0.9 lagging
AC load output rating
Max. output apparent power 2000 VA
Max. output active power 2000 W
Rated output voltage 230 Va.c.
Max. output current 8.7 Aa.c.
Rated output frequency 50 Hz
General
Operating temperature range 0 - 40 °C
Protective class I
Ingress protection IP20
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
a) mains selection devices shall be set to the cor- No mains selection devices. N/A
rect value unless otherwise noted in this standard;
b) Combinations of settings shall not be made if No combinations of settings N/A
c- devices
tions provided with the equipment.
4.2.2.11 Available short circuit current N/A
4.3 Thermal testing P
4.3.1 General P
4.3.2 Maximum temperature Tests of equipment rated for P
use in ambient temperatures
up to 40 °C
4.3.2.1 General P
Materials and components shall be selected so that P
under the most severe rated operating conditions,
the temperatures do not exceed the temperature
limits.
Conformity is verified by measuring temperatures P
under the conditions given in 4.2 for each rated op-
erating condition or mode of the PCE that could af-
fect the resulting temperatures.
The temperature limits specified below are total P
temperature limits (not temperature rise limits).
Tests of equipment rated for use in ambient tem- Maximum rated ambient tem- N/A
peratures up to 50°C may be conducted at any perature of the unit: 40 °C.
ambient temperature in the range given in 4.2.2.1,
(see appended table)
in which case the difference between the maximum
rated ambient temperature and the test ambient is
to be subtracted from or added to (as appropriate)
the measured temperatures for comparison to the
limits specified below.
PCE rated for use in ambient temperatures more N/A
than 50°C shall be tested at the maximum rated
ambient temperature +/- 5°C. the difference be-
tween the maximum rated ambient temperature
and the test ambient is to be subtracted from or
added to the measured temperatures for compari-
son to the limits specified.
PCE with different output ratings or with automatic N/A
derating for different ambient temperatures shall be
tested under as many conditions as are necessary
to record worst-case temperatures, including at
least the maximum ambient before derating, and
the maximum ambient with derating.
During thermal testing within NORMAL P
CONDITIONS protective devices shall not operate.
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
4.4.2.1 General P
The equipment shall be operated under the combi- P
nation of conditions in 4.2, which is least favourable
for the particular fault test being performed.
Fault conditions are to be applied only one at a P
time and shall be applied in turn in any convenient
order. Multiple simultaneous faults shall not be ap-
plied, but a subsequent fault may arise as a conse-
quence from an applied fault. Separate samples of
the EUT may be used for each separate fault test
applied, or the same sample may be used for many
tests if damage from previous fault tests has been
repaired or will not affect the results of further tests.
4.4.2.2 Duration of tests P
The equipment shall be operated until further P
change as a result of the applied fault is unlikely, as
determined by (for example) opening of a device
that removes the influence of the fault, stabilization
of temperatures, etc.
If a non-resettable, manual, or automatically reset- P
ting protective device or circuit operates in such a
way as to interrupt or mitigate the fault condition,
the test duration is as follows:
- automatic reset devices or circuits: allow the pro- P
tection to cycle on and off until no further change
as a result of the applied fault is likely, until the ul-
timate result is obtained, or until temperatures sta-
bilize
- manual reset devices or circuits: three cycles, with N/A
the device or circuit reset as soon as possible after
tripping
- non-resettable devices or circuits: one cycle N/A
4.4.3 Pass/fail criteria for testing under fault conditions P
4.4.3.1 Protection against shock hazard P
Compliance with requirements for protection P
against electric shock is checked after the applica-
tion of single faults as follows:
a) by making measurements to check that no ac- P
cessible DVC-A circuits have become shock-
hazardous using the steady state limits for DVC-A
in Table 6 and the short-term limits of 7.3.2.3, and
that such circuits remain separated from live parts
at voltages greater than DVC A with at least basic
insulation. Compliance is checked by the test of
7.5.2 (without humidity preconditioning) for basic
insulation; and
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
e) ventilation requirements; P
f) requirements for special services, for example No cooling liquid or other spe- N/A
cooling liquid; cial service
g) instructions and information relating to sound N/A
pressure level if required by 10.2.1;
h) where required by 14.8.1.3, instructions for the No such battery N/A
adequate ventilation of the room or location in
which PCE containing vented or valve-
regulated batteries is located, to prevent the
accumulation of hazardous gases;
i) tightening torque to be applied to wiring termi- P
nals;
j) values of backfeed short-circuit currents availa- P
ble from the PCE on input and output conduc-
tors under fault conditions, if those currents ex-
ceeds the max. rated current of the circuit, as
per 4.4.4.6;
k) for each input to the PCE, the max value of P
short-circuit current available from the source,
for which the PCE is designed; and
l) compatibility with RCD and RCM; N/A
m) instructions for protective earthing, including Provided in the installation P
the information required by 7.3.6.3.7 if a sec- manual.
ond protective earthing conductor is to be in-
stalled:
n) where required by 7.3.8, the installation instruc- N/A
tions shall include the following or equivalent
wording:
N/A
external protective earthing conductor. Where a
residual current-operated protective (RCD) or
monitoring (RCM) device is used for protection
in a case of direct or indirect contact, only an
RCD or RCM of Type B is allowed on the sup-
ply side of this prod
o) for PCE intended to charge batteries, the bat- P
tery nominal voltage rating, size, and type
p) PV array configuration information, such as rat- P
ings, whether the array is to be grounded or
floating, any external protection devices need-
ed, etc.
5.3.3 Information related to operation P
Instructions for use shall include any operating in- P
structions necessary to ensure safe operation, in-
cluding the following, as applicable:
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
7.3.4.2.1 General P
Parts of enclosures and barriers that provide pro- Secured by screws P
tection in accordance with these requirements shall
not be removable without the use of a tool (see
7.3.4.2.3).
Polymeric materials used to meet these require- P
ments shall also meet the requirements of 13.6
7.3.4.2.2 Access probe criteria P
Protection is considered to be achieved when the P
separation between the test probes and live parts,
when tested as described below, is as follows:
a) decisive voltage classification A, (DVC A) - the The communication interface P
probe may touch the live parts is considered as DVC A
b) decisive voltage classification B, (DVC B) - the The DVC B circuit is not ac- P
probe must not touch bare live parts cessible by probe
c) decisive voltage classification C, (DVC C) the The DVC C circuit is not ac- P
probe must have adequate clearance to live cessible by probe
parts, based on the clearance for Basic insula-
tion using the recurring peak working voltage
involved,
7.3.4.2.3 Access probe tests P
Compliance with 7.3.4.2.1 is checked by all of the P
following:
a) Inspection; and P
b) Tests with the test finger (Figure D.1) and test P
pin (Figure D.2) of 0E, the results of which shall
comply with the requirements of 7.3.4.2.1 a),
b), and c) as applicable. Probe tests are per-
formed on openings in the enclosures after re-
moval of parts that can be detached or opened
by an operator without the use of a tool, includ-
ing fuseholders, and with operator access
doors and covers open. It is permitted to leave
lamps in place for this test. Connectors that can
be separated by an operator without use of a
tool, shall also be tested during and after dis-
connection. Any movable parts are to be put in
the most unfavorable position.
The test finger and the test pin are applied as P
above, without appreciable force, in every pos-
sible position, except that floor-standing equip-
ment having a mass exceeding 40 kg is not tilt-
ed.
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
Voltages are measured from the protective earthing Measured from the farthest P
terminal to all parts whose protective bonding part of earthed metal enclo-
means are being considered. The impedance of the sure to the input earth terminal
protective earthing conductor is not included in the
measurement. However, if the protective earthing
conductor is supplied with the equipment, it is per-
mitted to include the conductor in the test circuit but
the measurement of the voltage drop is made only
from the main protective earthing terminal to the
accessible part required to be earthed.
On equipment where the protective earth Figure 11 used P
conncection to a subassembly or to a separate unit
is part of a cable that also supplies power to that
subassembly or unit, the resistance of the protec-
tive bonding conductor in that cable is not included
in the protective bond impedance measurements
for the subassembly or separate unit, as shown in
Figure 11. However, this option is only permitted if
the cab le is protected by a suitably rated protective
device that takes into account the size of the con-
ductor. Otherwise the impedance of the protective
bonding conductor between the separate units is to
be included, by measuring to the protective earth-
ing terminal where the power source enters the first
unit in the system, as shown in Figure 12.
7.3.6.3.3.1 Test current, duration, and acceptance criteria P
The test current, duration of the test and ac- P
ceptance criteria are as follows:
a) For PCE with an overcurrent protective device N/A
rating of 16 A or less, the test current is 200%
of the overcurrent protective device rating, but
not less than 32 A, applied for 120s. The im-
pedance of the protective bonding means dur-
ing and at the end of the test shall not exceed
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
7.3.7.2.3 Circuit other than mains circuit System voltage for PV is 550 P
Vd.c.
Clearance and solid insulation between circuit other
than the mains and their surroundings shall be de-
signed according to impulse voltage and recurring
peak voltage
7.3.7.2.4 Insulation between circuits Impulse voltage (4000 V) is P
calculated from table 12 for
a) For clearances and insulation, the require-
clearance before basic isola-
ments are determined by the circuit having
tion transformer for PV and AC
the higher impulse voltage;
mains side.
b) For creepages, r.m.s. working voltage
Impulse voltage (2500 V) is
across the insulation determines the re-
calculated from table 12 for
quirements.
clearance after basic isolation
transformer for battery side.
Working voltage (550 Vd.c.)
across insulation is used for
creepage.
7.3.7.3 Functional insulation P
For parts or circuit in OVC I, functional insulation
shall be designed according to the working voltage
across the insulation
For parts or circuit in OVC II, functional insulation
shall be designed according to the applicable im-
pulse voltage as determined by 7.3.7.1.4
7.3.7.4 Clearance distances P
7.3.7.4.1 Determination P
Table 13 defines the minimum clearance distances
required to provide functional, basic , or supplemen-
tary insulation
Clearance for use in altitudes above 2000 m shall be Not intended to use in altitudes N/A
calculated with correction factor according to Table above 2000 m.
A.2 of IEC 60664-1
For reinforced insulation, the value corresponding to P
the next higher impulse voltage, or 1.6 times the
temporary overvoltage, or 1.6 times the working
voltage shall be used, whichever results in the most
severe requirement
7.3.7.4.2 Electric field homogeneity Inhomogeneous electric field is N/A
considered for PCE
For homogeneous electric field and impulse voltage
is equal to or greater than 6000V for a circuit con-
nected directly to the mains or 4000V within a circuit,
the clearance may be reduced to the requirement by
Table F.2 Case B of IEC 60664-1. In this case, im-
pulse voltage test shall be performed on the clear-
ance
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
9.3.3 Protective devices provided or specified shall have External circuit breaker shall P
adequate breaking capacity to interrupt the maxi- be used for AC side.
mum short circuit current specified for the port to
which they are connected. If protection that is pro-
vided integral to the PCE for an input port is not
rated for the short-circuit current of the circuit in
which it is used, the installation instructions shall
specify that an upstream protective device, rated
for the prospective short-circuit current of that port,
shall be used to provide backup protection.
13 PHYSICAL REQUIREMENTS P
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
14 COMPONENTS P
14.1 General P
Where safety is involved, components shall be P
used in accordance with their specified RATINGS
unless a specific exception is made. They shall
conform to one of the following:
1. applicable safety requirements of a relevant P
IEC standard. Conformity with other require-
ments of the component standard is not re-
quired. If necessary for the application, compo-
nents shall be subjected to the test of this
standard, except that it is not necessary to car-
ry out identical or equivalent tests already per-
formed to check conformity with the component
standard;
2. the requirements of this standard and, where P
necessary for the application, any additional
applicable safety requirements of the relevant
IEC component standard;
3. if there is no relevant IEC standard, the re- P
quirements of this standard;
4. applicable safety requirements of a non-IEC P
standard which are at least as high as those of
the applicable IEC standard, provided that the
component has been approved to the non-IEC
standard by a recognized testing authority.
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
2h5
(7) 40 50% -- -- -- 230 10.8 2489 -- -- -- 51.2 54.0 2768
min
Remark:
(1) - (4) : Grid-Tied mode, PV to grid and battery;
(5) - (6) : Off-Grid mode, PV to load and battery;
(7) : Off-Grid mode, Battery to grid (house load).
Temperature (°C) of Measured temperature (°C) Permit-
part at: ted
No. (1) (2) (3) (4) (5) (6) (7)
(°C)
1 PV1 input terminal
44.0 44.3 41.9 41.9 42.8 41.2 40.2 105
block (internal)
2 PV1 input internal
46.3 46.4 43.2 42.9 44.3 42.9 40.3 105
wire
3 DC switch discon-
46.1 45.8 44.0 43.6 42.9 42.8 40.7 70
nector
4 Varistor R31 on PV-
44.8 44.8 41.9 41.8 42.7 43.6 40.2 105
inverter board
5 C21 on PV-inverter
45.7 45.7 42.8 42.7 43.5 44.8 40.5 105
board
6 L3 on PV-inverter
61.5 61.1 47.3 46.9 55.2 51.1 40.7 90
board
7 C35 on PV-inverter
52.6 52.2 47.6 47.2 47.9 46.3 41.2 125
board
8 CT1 on PV-inverter
50.1 49.7 46.8 46.9 46.1 46.2 41.8 85
board
9 Boost1 inductive coil 81.1 79.5 57.4 55.8 69.5 66.9 42.4 110
10 Boost1 inductive core 81.8 80.4 56.9 55.4 70.5 65.4 42.1 --
11 Boost1 IGBT Q7 on
64.7 64.5 50.3 50.5 58.8 54.1 42.3 130
PV-inverter board
12 D1 on PV-inverter
65.9 65.5 54.4 54.0 59.2 53.8 42.2 130
board
13 Insulation paper be-
tween Q7 and heat
60.2 59.8 49.0 48.8 54.6 53.4 41.9 150
sink on PV-inverter
board
14 C15 on PV-inverter
47.3 47.1 44.7 44.1 44.1 47.1 41.1 105
board
15 Q1 on PV-inverter
75.0 73.5 73.7 71.8 53.7 52.5 54.9 130
board
16 Q5 on PV-inverter
75.2 72.4 74.1 71.0 53.3 52.2 54.4 130
board
17 D3 on PV-inverter
72.9 70.1 72.1 68.9 52.9 51.9 53.3 130
board
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
18 C86 on PV-inverter
53.6 52.7 53.3 52.0 45.6 47.5 45.9 85
board
19 Fan1 (Under the pow-
45.1 44.9 44.5 44.1 42.7 44.3 42.3 70
er wire of Fan1)
20 Inverter inductive coil 90.0 81.2 90.0 80.4 50.3 49.6 51.9 110
21 Inverter inductive core 86.5 78.2 86.9 77.8 49.6 49.0 51.0 --
22 C118 on PV-inverter
45.9 45.4 46.3 46.7 41.6 43.3 42.0 105
board
23 CT4 on PV-inverter
51.2 50.4 51.1 49.9 45.0 45.5 45.8 105
board
24 L16 on PV-inverter
52.0 50.6 52.1 50.3 43.8 45.4 44.5 110
board
25 Relay RLY6 on PV-
56.8 55.3 56.6 55.1 41.9 43.7 48.5 60
inverter board
26 CT3 on PV-inverter
47.0 46.4 46.9 47.2 40.3 41.2 42.4 105
board
27 C79 on PV-inverter
42.9 42.9 42.9 42.4 39.7 39.8 40.8 110
board
28 Varistor R109 on PV-
44.4 44.1 44.3 43.5 39.7 40.1 41.0 125
inverter board
29 Fuse F1 on PV-
52.0 50.2 52.2 50.0 39.7 39.7 42.6 130
inverter board
30 Grid input internal
46.3 45.7 46.5 45.2 39.8 39.8 41.3 105
wire
31 Grid input terminal
43.9 43.6 43.9 43.2 39.8 39.6 40.6 105
block (internal)
32 CT5 on PV-inverter
43.5 43.6 43.4 43.4 47.7 47.8 42.1 110
board
33 L17 on PV-inverter
43.0 43.2 43.1 43.0 47.7 47.8 42.0 90
board
34 Grid Auxiliary Power
40.2 40.8 40.5 40.4 40.4 40.4 40.0 105
wire
35 L1 on DC-DC board 44.9 44.8 44.4 44.2 44.4 45.6 46.1 110
36 C291 on DC-DC
46.6 46.5 46.1 45.8 46.6 51.6 44.0 85
board
37 Q54 on DC-DC board 50.6 49.3 50.0 48.7 60.3 60.0 47.0 130
38 L29 on DC-DC board 49.7 48.3 49.4 48.9 64.6 66.9 52.0 110
39 C306 on DC-DC
54.0 51.7 53.3 51.0 70.8 70.0 54.3 105
board
40 T12 transformer coil
60.9 57.9 59.3 56.6 86.9 85.5 53.8 110
on DC-DC board
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
70 The top of unit 43.5 43.7 43.4 43.0 41.3 41.0 40.9 70
71 The mounting surfac-
46.8 46.6 45.6 46.1 42.4 43.3 41.3 90
es of unit
72 LCD 39.3 40.0 41.1 39.8 39.7 39.3 39.5 70
73 Test ambient temper-
39.3 39.6 41.0 39.2 39.7 39.4 39.5 Ref.
ature 1
Supplementary information:
40%
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
coverable.
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
coverable.
Below component single fault applied on DC-DC board
The fault applied during the unit op-
eration. After applied the fault, the
230 Va.c.,
15 R346 S-C 360 Vd.c. 5min unit shutdown immediately. ZD15,
5kW
C205, C246 and U15 were dam-
aged. No hazard. Unrecoverable.
The fault applied during the unit op-
eration. After applied the fault, the
Q49 (pin D 230 Va.c.,
16 S-C 360 Vd.c. 5min unit shutdown immediately. R301
to pin S) 5kW
and R300 were damaged. No haz-
ard. Unrecoverable.
The fault applied during the unit op-
230 Va.c., eration. After applied the fault, the
17 R300 S-C 360 Vd.c. 5min
5kW unit shutdown immediately. No
damage. No hazard. Recoverable.
The fault applied during the unit op-
eration. After applied the fault, the
U28 (pin 1 230 Va.c., unit shutdown immediately and LCD
18 S-C 360 Vd.c. 5min
to pin 3) 5kW
Recoverable.
The fault applied during the unit op-
U27 (pin 1 230 Va.c., eration. After applied the fault, the
19 S-C 360 Vd.c. 5min
to pin 2) 5kW unit shutdown immediately. No
damage. No hazard. Recoverable.
The fault applied during the unit op-
U27 (pin 3 230 Va.c., eration. After applied the fault, the
20 S-C 360 Vd.c. 5min
to pin 4) 5kW unit shutdown immediately. No
damage. No hazard. Recoverable.
The fault applied during the unit op-
230 Va.c., eration. After applied the fault, the
21 U27 (pin 1) O-C 360 Vd.c. 5min
5kW unit shutdown immediately. No
damage. No hazard. Recoverable.
The fault applied during the unit op-
PV: eration, the unit operated as normal
after applied the fault. When the unit
D88 (pin 1 360 Vd.c. 230 Va.c., shutdown and restarted, the unit
22 S-C 5min
to pin 3) Grid: 5kW / 2kW could restart. When the unit was at
bypass mode, the LCD blacked.
230 Va.c. R366 was damaged. No hazard.
Unrecoverable.
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
Recoverable.
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
Recoverable.
The fault applied during the unit op-
eration. After applied the fault, the
T3 (pin 11 to 230 Va.c., unit shutdown immediately and LCD
56 S-C 51.2 Vd.c. 5min
pin 19) 2.5kW OW
Recoverable.
Grid:
230 Va.c.,
The fault applied during the unit op-
5kW
T12 (pin 3 to eration. After applied the fault, the
57 S-C 360 Vd.c. 5min
pin 4) BAT: unit could not charge the battery. No
damage. No hazard. Recoverable.
51.2 Vd.c.
2.5kW
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
Grid:
230 Va.c.,
The fault applied during the unit op-
5kW
T12 (pin 4 to eration. After applied the fault, the
58 S-C 360 Vd.c. 5min
pin 5) BAT: unit could not charge the battery. No
damage. No hazard. Recoverable.
51.2 Vd.c.
2.5kW
Grid:
230 Va.c.,
The fault applied during the unit op-
5kW
T8 (pin N1 eration. After applied the fault, the
59 S-C 360 Vd.c. 5min
to pin N2) BAT: unit could not charge the battery. No
damage. No hazard. Recoverable.
51.2 Vd.c.
2.5kW
Grid:
230 Va.c.,
The fault applied during the unit op-
5kW
T8 (pin N4 eration. After applied the fault, the
60 S-C 360 Vd.c. 5min
to pin N5) BAT: unit could not charge the battery. No
damage. No hazard. Recoverable.
51.2 Vd.c.
2.5kW
Clause 4.4.4.7 Output overload
The fault applied during the unit op-
eration, After applied the fault, the
230 Va.c.,
61 AC output O-L 360 Vd.c. 5min unit operated as normal. The AC
5kW
output without overload function. No
damage. No hazard. Recoverable.
The fault applied during the unit op-
eration.
(1) When the unit overload 110%
lasted 10 mins, the LCD display
230 Va.c.,
62 Load output O-L 360 Vd.c. --
2kW (3) When the unit overload 150%
lasted 10 s, the LCD display
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
hazard. Recoverable.
The fault applied during the unit op-
eration. After applied the fault, the
Q39 (pin 1 230 Va.c., unit shutdown immediately and LCD
69 S-C 360 Vd.c. 5min
to pin 5) 5kW
hazard. Recoverable.
Clause 4.4.4.11 Reverse d.c. connections
The fault applied before the unit op-
eration. After applied the fault, the
230Va.c.,
70 R 360 Vd.c. 5min unit could not start and LCD display
- 5kW
age. No hazard. Recoverable.
The fault applied before the unit op-
eration. After applied the fault, the
230Va.c.,
71 R 51.2 Vd.c. 5min unit could not start and LCD display
- 2.5kW
damage. No hazard. Recoverable.
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
DVC C circuit to signal collection DC: 550 II (PV) 3.0 3.7 3.0 3.7
circuit (CT3) (BI) AC: 230 III (AC)
DVC C circuit to signal collection DC: 550 II (PV) 3.0 3.2 3.0 3.2
circuit (CT4) (BI) AC: 230 III (AC)
DVC C circuit to signal collection DC: 550 II (PV) 3.0 3.0 3.0 3.0
circuit CT5) (BI) AC: 230 III (AC)
DVC C circuit to signal collection DC: 550 II (PV) 3.0 3.3 3.0 3.3
circuit (PCB under RLY6) (BI) AC: 230 III (AC)
DVC C circuit to signal collection DC: 550 II (PV) 3.0 3.2 3.0 3.2
circuit (RLY7) (BI) AC: 230 III (AC)
DVC C circuit to signal collection DC: 550 II (PV) 3.0 3.6 3.0 3.6
circuit (RLY8) (BI) AC: 230 III (AC)
DVC C circuit to signal collection DC: 550 II (PV) 3.0 3.5 3.0 3.5
circuit (RLY9) (BI) AC: 230 III (AC)
DVC C circuit to signal collection DC: 550 II (PV) 3.0 5.4 3.0 5.4
circuit (RLY10) (BI) AC: 230 III (AC)
Between primary and secondary DC: 550 II (PV) 3.0 4.8(3.5 Inner 3.0 4.8(3.5 Inner
of T2 on the DC-DC board (BI) AC: 230 III (AC) layer) layer)
Between primary and secondary DC: 550 II (PV) 3.0 4.8(3.5 Inner 3.0 4.8(3.5 Inner
of T3 on the DC-DC board (BI) AC: 230 III (AC) layer) layer)
Between primary and secondary DC: 550 II (PV) 3.0 5.2(3.5 Inner 3.0 5.2(3.5 Inner
of T12 on the DC-DC board (BI) AC: 230 III (AC) layer) layer)
Between primary and secondary DC: 550 II (PV) 3.0 6.0 3.0 6.0
of T11 on the DC-DC board (BI) AC: 230 III (AC)
Between core and secondary of DC: 550 II (PV) 3.0 3.6 3.0 3.6
T11 on the DC-DC board (BI) AC: 230 III (AC)
Hazardous parts (R370\C249) to DC: 550 II (PV) 3.0 3.4 3.0 3.4
signal collection circuit track (BI) AC: 230 III (AC)
J33(DVC A circuit) to AC input DC: 550 5.5 5.9 5.5 5.9
II (PV)
connector on the DC-DC board
AC: 230 III (AC)
(J31) (RI)
Between primary and secondary DC: 550 3.0 6.0 3.0 6.0
II (PV)
(Pin 11-14) of T9 on the DC-DC
AC: 230 III (AC)
board (BI)
Between secondary (Pin 11-14) DC: 550 3.0 6.0 3.0 6.0
II (PV)
and secondary (Pin 8-9) of T9
AC: 230 III (AC)
on the DC-DC board (SI)
Between primary and secondary DC: 550 5.5 8.0 5.5 8.0
II (PV)
(Pin 8-9) of T9 on the DC-DC
AC: 230 III (AC)
board (RI)
Between core and secondary DC: 550 3.0 4.2 3.0 4.2
II (PV)
(Pin 11-14) of T9 on the DC-DC
AC: 230 III (AC)
board (BI)
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
Between core and secondary DC: 550 5.5 8.3 5.5 8.3
II (PV)
(Pin 8-9) of T9 on the DC-DC
AC: 230 III (AC)
board (RI)
Between primary and secondary DC: 550 II (PV) 3.0 7.4 3.0 7.4
of T8 on the DC-DC board (BI) AC: 230 III (AC)
Between primary and secondary DC: 550 II (PV) 3.0 6.2 3.0 6.2
of U25 on the DC-DC board (BI) AC: 230 III (AC)
Between primary and secondary DC: 550 II (PV) 3.0 6.2 3.0 6.2
of U26 on the DC-DC board (BI) AC: 230 III (AC)
Between primary and secondary DC: 550 II (PV) 3.0 6.2 3.0 6.2
of U27 on the DC-DC board (BI) AC: 230 III (AC)
SELV parts(TP4) to hazardous DC: 550 II (PV) 5.5 6.2 5.5 6.2
parts(C284) (RI) AC: 230 III (AC)
PCB track of SELV parts to haz- DC: 550 II (PV) 5.5 6.0 5.5 6.0
ardous parts (RI) AC: 230 III (AC)
PCB track of SELV parts to con- DC: 550 II (PV) 3.0 3.5 3.0 3.5
trol circuit parts (SI) AC: 230 III (AC)
Ground screw H2 to Hazardous DC: 550 II (PV) 3.0 6.6 3.0 6.6
parts on DC-DC board (BI) AC: 230 III (AC)
Ground screw H5 to Hazardous DC: 550 II (PV) 3.0 3.6 3.0 4.9
parts on DC-DC board (BI) AC: 230 III (AC)
Ground screw H7 to Hazardous DC: 550 II (PV) 3.0 6.3 3.0 6.3
parts on DC-DC board (BI) AC: 230 III (AC)
Ground screw H6 to Hazardous DC: 550 II (PV) 3.0 5.7 3.0 5.7
parts on DC-DC board (BI) AC: 230 III (AC)
Ground screw H14 to Hazardous DC: 550 II (PV) 3.0 6.8 3.0 6.8
parts on DC-DC board (BI) AC: 230 III (AC)
Ground screw H8 to Hazardous DC: 550 II (PV) 3.0 6.7 3.0 6.7
parts on DC-DC board (BI) AC: 230 III (AC)
Ground screw H6 to Hazardous DC: 550 II (PV) 3.0 5.3 3.0 5.3
parts on PV board (BI) AC: 230 III (AC)
Ground screw H9 to Hazardous DC: 550 II (PV) 3.0 3.1 3.0 3.1
parts on PV board (BI) AC: 230 III (AC)
Ground screw H10 to Hazardous DC: 550 II (PV) 3.0 3.6 3.0 3.6
parts on PV board (BI) AC: 230 III (AC)
Ground screw H7 to Hazardous DC: 550 II (PV) 3.0 3.1 3.0 3.1
parts on PV board (BI) AC: 230 III (AC)
Ground screw H2 to Hazardous DC: 550 II (PV) 3.0 3.1 3.0 3.1
parts on PV board (BI) AC: 230 III (AC)
Ground screw H1 to Hazardous DC: 550 II (PV) 3.0 3.4 3.0 3.4
parts on PV board (BI) AC: 230 III (AC)
Ground screw H8 to Hazardous DC: 550 II (PV) 3.0 3.2 3.0 3.2
parts on PV board (BI) AC: 230 III (AC)
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
Between primary and secondary DC: 550 II (PV) 5.5 5.9 5.5 5.9
of T2 on the display board (RI) AC: 230 III (AC)
Between primary and secondary DC: 550 II (PV) 5.5 6.3 5.5 6.3
of U21 on the display board (RI) AC: 230 III (AC)
Between primary and secondary DC: 550 3.0 3.1 3.0 3.1
II (PV)
of T1 on the IGBT driver board
AC: 230 III (AC)
(BI)
Between primary and secondary DC: 550 3.0 4.0 3.0 6.0
II (PV)
of U1 on the IGBT driver board
AC: 230 III (AC)
(BI)
Supplementary information:
(1) For AC mains circuit, nominal voltage is 230 V and overvoltage category is OVC III, impulse voltage
correspond to mains circuit is 4000 V;
(2) For PV circuit, system voltage is 550 V and overvoltage category is OVC II, impulse voltage corre-
spond to PV circuit is 2945 V;
(3) For battery circuit, is evaluated with basic insulation from AC mains and PV circuit, impulse voltage is
2500 V;
U r.m.s. required di di
distance through insulation di at/of: test voltage (V)
(V) (mm) (mm)
Plastic isolation sheet between upper enclosure 550Vd.c. 1500Vr.m.s. -- 0.25
and PCBA (BI)
230Va.c.
Plastic isolation sheet between PCBA and lower 550Vd.c. 1500Vr.m.s. -- 0.25
enclosure (BI)
230Va.c.
Insulation cover sheet on display (RI) 550Vd.c. 3000Vr.m.s. -- 0.50
230Va.c.
Two layers Insulation tape (RI) 550Vd.c. 3000Vr.m.s. -- Certified
230Va.c.
Supplementary information:
7.5 TABLE: electric strength measurements, impulse voltage test and partial dis- P
charge test
impulse with- partial discharge
test voltage
test voltage applied between: stand voltage extinction voltage result
(V)
(V) (V)
PV terminal and BAT terminal, relay
2120Vd.c. 4000Vpeak N/A Pass
contact short-circuit (BI)
PV terminal and metal enclosure (BI) 2120Vd.c. 4000Vpeak N/A Pass
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
10Ts;
Inductor (L16, Shenzhen Spitzer SPT- IEC 62109-1 Tested with
L7) Electronic Co., Ltd 42H6284-L N2
IEC 62109-2 appliance
10Ts;
Class B
WUXI JUFENG
COMPOUND LINE
- WIRE CO MW 30-C 180 °C UL 1446 E206882
LTD
TAI-I COPPER
SMEIW MW
- Alternative (GUANZHOU) CO 180 °C UL 1446 E85640
77-C
LTD
- Insulation DUPONT TEIJIN Melinex 0.075×8mm, VTM-2 UL 746
E93687
FILM FILM U S L P 238PV(a) 130 °C UL 94
JINGJIANG YAHUA
- MARGIN PRESSURE
WF* (c)(h) 4mm*0.3 ,130 °C UL 510A E165111
TAPE SENSITIVE GLUE
CO LTD
GUANGZHOU
POCHELY EPOXY, V-0, UL 746
- GLUE ELECTRONIC 5225A/B E204979
130 °C UL 94
MATERIAL CO LTD
KINGBOARD UL 746
- BOBBIN LAMINATES KB-6165 V-0, 130 °C E123995
HOLDINGS LTD UL 94
IEC 62109-1 Tested with
- Core DMEGC R10K
IEC 62109-2 appliance
XIAMEN HONGFA UL 60947-1 VDE
Relay (RLY3, 2A/30VDC
ELECTROACOUSTI HFD3 IEC/EN 40018867
RLY11) C CO LTD 0.5A/125VAC
61810-1 UL E133481
21Ts
High Frequency ShenZhen JiaMeiRui IEC 62109-1 Tested with
Transformer ELECTRONICS JBK-13E-259 20Ts
CO.,LTD IEC 62109-2 appliance
(T1)
21Ts
Class B
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
- Varnish KYOCERA
TVB2180T*(a) 155 °C UL 1446 UL E83702
CHEMICAL CORP
ELANTAS
ELECTRICAL
- Alternative V1630FS 130 °C UL 1446 UL E75225
INSULATION
ELANTAS PDG INC
SHENGYI
- PCB TECHNOLOGY CO FR-4 130 °C, V-0 UL 94 UL E109769
LTD
KINGBOARD
- Alternative LAMINATES FR-4 130 °C, V-0 UL 94 UL E123995
HOLDINGS LTD
PQ32/30 IEC 62109-1 Tested with
- Core DMEGC 34*30*30mm
DMR95 IEC 62109-2 appliance
X capacitor XIAMEN
630V, 47nF, -40 °C IEC 62109-1 Tested with
(C305, C306, FARATRONIC CO MMKP82
to 105 °C IEC 62109-2 appliance
C307, C308) LTD
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
200x 4P x 4Ts
N2: COPPER FOIL,
200x 4P x 4Ts
Class B
E I DUPONT DE UL 1694
- Bobbin NEMOURS & CO 410 220 °C, V-0 UL 94 E34739
INC UL 746A
EE55/55/21 IEC 62109-1 Tested with
- Core ANCI 58*42*9mm
ACP95 IEC 62109-2 appliance
TAI-I ELECTRIC
- Wire WIRE & CABLE CO UEWF 155 °C UL 1446 UL E85640
LTD
PACIFIC ELECTRIC
WIRE & CABLE
- Alternative UEF1/U@ 155 °C UL 1446 UL E201757
(SHENZHEN) CO
LTD
JINGJIANG YAHUA
PRESSURE
- Mylar tape PF-301 180 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
- Margin tape 3M COMPANY 44D(a) 130 °C UL 510A UL E17385
KYOCERA
- Varnish TVB2180T*(a) 155 °C UL 1446 UL E83702
CORPORATION
DONGGUAN
- Epoxy EATTO V-0, 130 °C UL 746C UL E218090
E-500 (XX)
ELECTRONIC
MATERIAL CO LTD
GREAT HOLDING
- Tube INDUSTRIAL CO TFL 200 °C, VW-1 UL 224 UL E156256
LTD
JEPULS 100Ts
Inductor (L13 TECHNOLOGY IEC 62109-1 Tested with
LC12-028
L26) (SHENZHEN) IEC 62109-2 appliance
1Ts
CO.,LTD
Class B
FR530(l)(+)(f1
E I DUPONT DE UL 94
),
- Bobbin NEMOURS & CO V-0, 155 °C UL E41938
FR530L(l)(+)(f UL 746A
INC
1)
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
20P x 2P x 8Ts
N2: COPPER FOIL,
25 x 30mm x
JEPULS 4Ts
Transformer TECHNOLOGY IEC 62109-1 Tested with
BCK5501-204 N3: COPPER FOIL,
(T3, T2) (SHENZHEN) IEC 62109-2 appliance
CO.,LTD
4Ts
20P x 2P x 8Ts
Class B
FR530(l)(+)(f1 UL 1694
E I DUPONT DE
),
- Bobbin NEMOURS & CO V-0, 155 °C UL 94 E41938
FR530L(l)(+)(f
INC UL 746A
1)
Ferrite, IEC 62109-1 Tested with
TDG HOLDING CO.,
- Core TP4 55mm*55mm*21m
LTD IEC 62109-2 appliance
m
FENG CHING
- Wire xUEW-2 130 °C UL 1446 UL E172395
METAL CORP
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
20P x 2P x 8Ts
N2: COPPER FOIL,
20P x 2P x 8Ts
Class B
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
27Ts
8Ts
4Ts
27Ts
Class B
IEC 62109-1 Tested with
- Core DMEGC EC29 DMR40 30*35*25mm
IEC 62109-2 appliance
UL 1694
CHANG CHUN
- Bobbin T375HF V-0, 150 °C UL 94 UL E59481
PLASTICS CO LTD
UL 746A
GREAT HOLDING
- Teflon Tube INDUSTRIAL CO TFL VW-1, 200 °C UL 224 UL E156256
LTD
TA YA ELECTRIC
- Wire WIRE & CABLE CO LZ-UEWB 130 °C, MW 75-C UL 1446 UL E84201
LTD
FENG CHING xUEW
- Alternative 130 °C, MW 75-C UL 1446 UL E172395
METAL CORP
ROSHOW xUEW@/130,
- Alternative TECHNOLOGY CO QA@-x/130 130 °C, MW 75-C UL 1446 UL E215691
LTD
TAI-I ELECTRIC UEW
- Alternative WIRE & CABLE CO 130 °C, MW 75-C UL 1446 UL E85640
LTD
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
48Ts
72Ts
SHENZHEN CLICK IEC 62109-1 Tested with
Transformer TECHNOLOGY EE25 8Ts
(T10) CO,.LTD IEC 62109-2 appliance
7Ts
48Ts
Class B
UL 1694
CHANG CHUN
- Bobbin T375HF V-0, 150 °C UL 94 UL E59481
PLASTICS CO LTD
UL 746A
28*20*25mm, IEC 62109-1 Tested with
- Core DMEGC EI25C DMR40
130 °C IEC 62109-2 appliance
GREAT HOLDING
- Tube INDUSTRIAL CO TFL VW-1, 200 °C UL 224 UL E156256
LTD
PACIFIC ELECTRIC
WIRE & CABLE
- Wire UEW/U@ 130 °C, MW 75-C UL 1446 UL E201757
(SHENZHEN) CO
LTD
TA YA ELECTRIC
- Alternative WIRE & CABLE CO LZ-UEWB 130 °C, MW 75-C UL 1446 UL E84201
LTD
TAI-I ELECTRIC UEW
- Alternative WIRE & CABLE CO 130 °C, MW 75-C UL 1446 UL E85640
LTD
ROSHOW xUEW@/130,
- Alternative TECHNOLOGY CO QA@-x/130 130 °C, MW 75-C UL 1446 UL E215691
LTD
FENG CHING xUEW
- Alternative 130 °C, MW 75-C UL 1446 UL E172395
METAL CORP
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
15Ts
90Ts
SHENZHEN CLICK IEC 62109-1 Tested with
Transformer TECHNOLOGY EI25 10Ts
(T11) CO,.LTD IEC 62109-2 appliance
10Ts
15Ts
Class B
UL 1694
CHANG CHUN
- Bobbin T375HF V-0, 150 °C UL 94 UL E59481
PLASTICS CO LTD
UL 746A
IEC 62109-1 Tested with
- Core Various Various 28.0x 6.5x23.5mm
IEC 62109-2 appliance
GREAT HOLDING
- Tube INDUSTRIAL CO TFL VW-1, 200 °C UL 224 UL E156256
LTD
PACIFIC ELECTRIC
WIRE & CABLE
- Wire UEW/U@ 130 °C, MW 75-C UL 1446 UL E201757
(SHENZHEN) CO
LTD
- Alternative TA YA ELECTRIC
WIRE & CABLE CO LZ-UEWB 130 °C, MW 75-C UL 1446 UL E84201
LTD
- Alternative TAI-I ELECTRIC UEW
WIRE & CABLE CO 130 °C MW 75-C UL 1446 UL E85640
LTD
- Alternative ROSHOW xUEW@/130,
TECHNOLOGY CO QA@-x/130 130 °C, MW 75-C UL 1446 UL E215691
LTD
- Alternative FENG CHING xUEW
130 °C, MW 75-C UL 1446 UL E172395
METAL CORP
JINGJIANG YAHUA
PRESSURE
- Tape CT (b)(g) 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict
TRF_IEC62109_1B
TEST REPORT
IEC 62109-2:2011
Safety of power converters for use in photovoltaic power systems
Part 2: Particular requirements for inverters
Address......................................... : No.6 Northern Industry Road, Songshan Lake Sci. & Tech.
Industry Park, 523808 DongGuan City, Guangdong Province,
PEOPLE'S REPUBLIC OF CHINA
Test specification:
Standard ....................................... : IEC/EN 62109-2:2011
Test procedure ............................. : CE_LVD
Non- N/A
Test Report Form No.................... : IEC62109_2B
Test Report Form(s) Originator ... : LCIE - Laboratoire Central des Industries Electriques
Master TRF ................................... : Dated 2016-08
Copyright © 2010 Worldwide System for Conformity Testing and Certification of Electrotechnical
Equipment and Components (IECEE), Geneva, Switzerland. All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copyright
owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the reader's
interpretation of the reproduced material due to its placement and context.
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the
CB Scheme procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory
and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
General disclaimer:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing CB Testing
Laboratory. The authenticity of this Test Report and its contents can be verified by contacting the NCB,
responsible for this Test Report.
TRF_IEC62109_2B
List of Attachments (including a total number of pages in each attachment):
This test report contains 2 parts listed in below table:
Item Description Pages
Part 1 IEC/EN 62109-1:2010 test report 103
Part 2 IEC/EN 62109-2:2011 test report 30
This test report shall be also used in conjunction with 12 pages of photo documentation.
Summary of testing:
All tests were carried out according to IEC 62109-2(ed.1). The text of IEC 62109-2(ed.1) was approved
by
CENELEC as a European Standard without any modification.
Clause Requirement
4.4.4.15 Fault-tolerance of protection for grid-interactive inverters
4.4.4.17 Cooling system failure Blanketing test
4.7.4.2 Steady state output voltage at nominal DC input
4.7.4.3 Steady state output voltage across the DC input range
4.7.4.4 Load step response of the output voltage at nominal DC input
4.7.4.5 Steady state output frequency
4.7.5.2 Sinusoidal output voltage waveform requirements
4.8.2.1 Array insulation resistance detection for inverters for ungrounded arrays
4.8.3.5 Protection by residual current monitoring
Address: No.6 Northern Industry Road, Songshan Lake Sci. & Tech. Industry Park, 523808 DongGuan City,
Guangdong Province, PEOPLE'S REPUBLIC OF CHINA
Model different:
N/A
Electrical Ratings:
See Report No.: 64.290.18.05995.01 part 1 of 2
IEC 62109-2
Clause Requirement Test Result Remark Verdict
- Transformer-less type. P
Where approach a) of 4.8.2.2 is used, the installation instructions for the inverter N/A
shall include all of the following:
a) the value of the total resistance between the N/A
PV circuit and ground integral to the
13 Physical requirements P
13.9 Fault indication P
Where this Part 2 requires the inverter to indicate a fault, both of the following P
shall be provided:
a) a visible or audible indication, integral to the P
inverter, and detectable from outside the
inverter, and
b) an electrical or electronic indication that can P
be remotely accessed and used.
The installation instructions shall include P
information regarding how to properly make
connections (where applicable) and use the
electrical or electronic means in b) above, in
accordance with 5.3.2.10.
IEC 62109-2
Clause Requirement Test Result Remark Verdict
No damage. No hazard.
Recoverable.
IEC 62109-2
Clause Requirement Test Result Remark Verdict
No damage. No hazard.
Recoverable.
The fault applied during the
unit operation. After applied
U9 (VCC to the fault, the unit shutdown
Short PV: 360Vd.c.
GEN) on control 5min -- -- immediately and LCD
circuit AC: 230Va.c.
board display alarmed " SYS CAN
. Q3 was damaged. No
hazard. Unrecoverable.
damage. No hazard.
Recoverable.
The fault applied during the unit
operation, the unit operated as
normal after applied the fault.
When the unit shutdown and
Short PV: 360Vd.c.
RLY6 5min -- -- restarted, the unit could not
circuit AC: 230Va.c.
restart and LCD display alarmed
damage. No hazard.
Recoverable.
The fault applied during the unit
operation, the unit operated as
normal after applied the fault.
When the unit shutdown and
Short PV: 360Vd.c.
RLY8 5min -- -- restarted, the unit could not
circuit AC: 230Va.c.
restart and LCD display alarmed
damage. No hazard.
Recoverable.
The fault applied during the unit
operation, the unit operated as
normal after applied the fault.
When the unit shutdown and
Short PV: 360Vd.c.
RLY10 5min -- -- restarted, the unit could not
circuit AC: 230Va.c.
restart and LCD display alarmed
damage. No hazard.
Recoverable.
Check that the relays fulfil the basic insulation or simple separation
Yes
based on the PV circuit working voltage.
Each active phase can be switched. (L and N) Yes
Supplementary information: The investor can disconnect from grid during a relay occurred a single failure.
IEC 62109-2
Clause Requirement Test Result Remark Verdict
Supplementary information:
IEC 62109-2
Clause Requirement Test Result Remark Verdict
Model EA5KHD
Model EA5KHD
4.8.2 TABLE: Array insulation resistance detection for inverters for ungrounded and P
functionally grounded arrays
4.8.2.1 Array insulation resistance detection for inverters for ungrounded arrays P
DC Voltage DC Voltage for Resistance between Required Insulation Result
below minimum inverter begin ground and PV input resistance
operating voltage operation terminal R = (VMAX PV / 30mA)
(V) (V)
PV+, (tracker 1)
The unit could not
operate and LCD display
115 150 16500 18333 INSU.TO
GROUND IMPE.
OCCUR
IEC 62109-2
Clause Requirement Test Result Remark Verdict
PV+, (tracker 2)
The unit could not
operate and LCD display
115 150 16500 18333 INSU.TO
GROUND IMPE.
OCCUR
PV-, (tracker 1)
The unit could not
operate and LCD display
115 150 16500 18333 INSU.TO
GROUND IMPE.
OCCUR
PV-, (tracker 2)
The unit could not
operate and LCD display
115 150 16500 18333 INSU.TO
GROUND IMPE.
OCCUR
Note:
For isolated inverters, shall indicate a fault in accordance with 13.9 (operation is allowed); the fault indication
shall be maintained until the array insulation resistance has recovered to a value higher than the limit above
For non-isolated inverters, or inverters with isolation not complying with the leakage current limits in the
minimum inverter isolation requirements in Table 30, shall indicate a fault in accordance with 13.9, and shall
not connect to the mains; the inverter may continue to make the measurement, may stop indicating a fault
and may connect to the mains if the array insulation resistance has recovered to a value higher than the limit
above.
It is not required to test all PV input terminals if analysis of the design indicates that one or more terminals
can be expected to have the same result, for example where multiple PV string inputs are in parallel.
Supplementary information:
1. The setting isolation resistor value is 20 k .
2. All above tests indicate a fault in accordance with clause 13.9