TEST REPORT

IEC 62109-1
Safety of Power Converter for use in Photovoltaic Power Systems
Part 1: General requirements

Report Number. ............................ : 64.290.18.05995.01 part 1 of 2


Date of issue .......................... : 2019-04-08
Total number of pages ................. : 103 pages

Name of Testing Laboratory prepar- TÜV SÜD Certification and Testing (China) Co., Ltd. Guangzhou
ing the Report ............................... : Branch
5F, Communication Building, 163 Pingyun Rd, Huangpu Ave.
West, Guangzhou 510656, P. R. China
.......................... : EAST Group Co., Ltd.
Address ......................................... : No.6 Northern Industry Road, Songshan Lake Sci. & Tech. Indus-
try Park, 523808 DongGuan City, Guangdong Province,
PEOPLE'S REPUBLIC OF CHINA
Test specification:
Standard........................................ : IEC/EN 62109-1:2010
Test procedure.............................. : CE_LVD
Non-standard test method ........... : N/A
Test Report Form No. ................... : IEC62109_1B
Test Report Form(s) Originator.... : VDE Testing and Certification Institute
Master TRF .................................... : Dated 2016-04
Copyright © 2016 IEC System of Conformity Assessment Schemes for Electrotechnical Equipment
and Components (IECEE System). All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copy-
right owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the
reader's interpretation of the reproduced material due to its placement and context.

If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB
Scheme procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and
appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
General disclaimer:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing CB Testing La-
boratory. The authenticity of this Test Report and its contents can be verified by contacting the NCB, respon-
sible for this Test Report.

TRF_IEC62109_1B
List of Attachments (including a total number of pages in each attachment):
This test report contains 2 parts listed in below table:
Item Description Pages
Part 1 IEC/EN 62109-1:2010 test report 103
Part 2 IEC/EN 62109-2:2011 test report 30
This test report shall be also used in conjunction with 12 pages of photo documentation.

Summary of testing:
All tests were carried out according to IEC 62109-1:2010. The text of IEC 62109-1:2010 was approved by
CENELEC as a European Standard without any modification.
Tests performed (name of test and test clause):
Clause Requirement
4.3 Thermal testing
4.4 Testing in single fault condition
4.5 Humidity preconditioning
4.6 Backfeed voltage protection
4.7 Electrical ratings tests
5.1.2 Durability of markings
6.3 Ingress protection
7.3 Protection against electric shock
7.4 Protection against energy hazards
7.5 Electrical tests related to shock hazard
8.5 Wall mounting
15 Software and firmware performing safety functions.

TRF_IEC62109_1B
Copy of marking plate:
The artwork below may be only a draft. The use of certification marks on a product must be authorized by
the respective NCBs that own these marks.
Below electric ratings and warnings are silk-screen on label and affixed side of enclosure.

TRF_IEC62109_1B
Test item particulars ..............................................:
Equipment mobility...................................................: movable hand-held stationary
fixed transportable for building-in
Connection to the mains ..........................................: pluggable equipment direct plug-in
permanent connection for building-in
Enviromental category.............................................: outdoor indoor indoor
unconditional conditional
Over voltage category Mains ...................................: OVC I OVC II OVC III OVC IV
Over voltage category PV........................................: OVC I OVC II OVC III OVC IV
Mains supply tolerance (%) .....................................: +/- 10%
Tested for power systems .......................................: TN system
IT testing, phase-phase voltage (V) .........................: N/A
Class of equipment .................................................: Class I Class II Class III
Not classified
Mass of equipment (kg) ...........................................: Net weight: 22.3 kg (Approx.)
Pollution degree ......................................................: PD II
IP protection class ...................................................: IP 20 (indoor use only)
Testing
Date of receipt of test item(s)................................... 2018-10-29
Dates tests performed ............................................. 2018-11-01 to 2019-03-18
Possible test case verdicts:
test case does not apply to the test object ........ N/A
test object does meet the requirement ............... Pass (P)
test object was not evaluated for the require- N/E
ment ..................................................................
test object does not meet the requirement ......... Fail (F)
General remarks:
"(see Attachment #)" refers to additional information appended to the report.
"(see appended table)" refers to a table appended to the report.
The tests results presented in this report relate only to the object tested.
This report shall not be reproduced except in full without the written approval of the testing laboratory.
Additional test data and/or information provided in the attachments to this report.
Throughout this report a comma / point is used as the decimal separator.
This TRF was modified by TUV SUD Guangzhou branch by adding Cl.4 and Annex A to J.
Abbreviations used in the report:
Basic insulation (BI); Supplementary insulation (SI); Double insulation (DI); Reinforced insulation (RI);
Functional insulation (FI); Single fault condition (SFC); Normal condition (NC); Mains overvoltage catego-
ry (OVC); Pollution degree (PD), CDF (Construction Data form)
-clause 4.2.5 of IECEE 02:
The application for obtaining a CB Test Certifi- Yes
cate includes more than one factory location and
Not applicable
a declaration from the Manufacturer stating that
the sample(s) submitted for evaluation is (are)
representative of the products from each factory
TRF_IEC62109_1B
has been provided ....................................................
When differences exist; they shall be identified in the General product information section.
Name and address of factory (ies) ........................ :
Factory name: EAST Group Co., Ltd.
Address: No.6 Northern Industry Road, Songshan Lake Sci. & Tech. Industry Park, 523808 DongGuan
City, Guangdong Province, PEOPLE'S REPUBLIC OF CHINA
General product information:
(1) The unit is non-isolated (transformerless) hybrid solar inverter, it is intended to be connected with
household generation systems with battery to store energy.
(2) The unit has four operating modes: grid-tied mode, anti-reflux mode, off-grid mode and bypass
mode. The difference between anti-reflux mode and grid-tied mode is that energy will not be deliv-
ered to the grid in anti-reflux mode.
(3) The unit has 4 connection terminals: PV input terminal, grid terminal, battery terminal and AC load
terminal. intended to use solar power, utility power and battery power to ensure continuous
power supply.
(4) The unit shall be used at specified ambient conditions. Indoor, conditioned, temperature range: 0 -
40 °C. Altitude: <1000 m, Auto-derating above 1000 m; Overvoltage category: III (Grid), II(PV);
Relative humidity range: 0 - 90 %.
(5) If certain functions are not permitted by local regulation, the function shall be disabled by hardware
or software setting (if applicable) by the manufacturer before putting into the market. For example,

reimbursement in some nations.


(6) Low voltage electrical installations shall comply with national and local regulation. Only qualified
electricians are allowed to install and maintain the converter.
(7) In order to protect the PCE, user and installer, external DC and AC circuit breaker shall be
equipped at the end-use application.
(8) The unit provides four disconnection relays, two for line conductor and another two for neutral
conductor.
(9) Basic insulation is provided between PV input / AC output circuit and battery circuit, additional
protection of battery terminal is necessary in the installation.
(10) Firmware version: Inverter master: V4.09, display screen: V7.2F.

Model differences:
N/A
Ratings:
Model EA5KHD
PV input rating
Max. input power 5500 W
Rated input voltage 360 Vd.c.
Max. input voltage 550 Vd.c.
MPPT voltage range 120 Vd.c. 530 Vd.c.
MPPT voltage range (full load) 250 Vd.c. 450 Vd.c.

TRF_IEC62109_1B
Max. input current 2 x 12 Ad.c.
PV short circuit current 2 x 15 Ad.c.
Battery input/output rating
Battery type Lithium or Lead-acid
Rated voltage (Lithium) 51.2 Vd.c.
Battery voltage range(Lithium) 46.4 Vd.c. - 57.6 Vd.c.
Rated voltage (Lead-acid) 48 Vd.c.
Battery voltage range(Lead-acid) 40 Vd.c. 58 Vd.c.
Max. charging power 2500 W
Max. charging current 50 Ad.c.
Max. discharging power 2500 W
Max. discharging current 50 Ad.c.
Grid input rating
Rated input voltage 230 Va.c.
Rated grid frequency 50 Hz
Max. input apparent power 2000 VA
Max. input active power 2000 W
Max. input current 8.7 Aa.c
Grid output rating
Max. output apparent power 5000 VA
Max. output active power 5000 W
Rated output voltage 230 Va.c.
Max. output current 21.7 Aa.c.
Rated output frequency 50 Hz
Power factor 0.9 leading - 0.9 lagging
AC load output rating
Max. output apparent power 2000 VA
Max. output active power 2000 W
Rated output voltage 230 Va.c.
Max. output current 8.7 Aa.c.
Rated output frequency 50 Hz
General
Operating temperature range 0 - 40 °C
Protective class I
Ingress protection IP20

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

4 General testing requirements P


4.1 General P
4.2 General conditions for testing P
4.2.1 Sequence of tests P
4.2.2 Reference test conditions P
4.2.2.1 Environmental conditions P
Unless otherwise specified, the following ambient P
environmental conditions shall exist in the test loca-
tion:
a) temperature of 15 °C to 40 °C
b) a relative humidity of not more than 75 %
and not less than 5%
c) an air pressure of 75 kPa to 106 kPa.
d) no frost, dew, percolating water, rain, solar radia-
tion, etc.
4.2.2.2 State of equipment P
4.2.2.3 Position of equipment The equipment were installed P
in accordance with the manu-

configuration that results in the


worst-case test conditions.
4.2.2.4 Accessories No accessories or operator in- N/A
terchangeable parts
4.2.2.5 Covers and removable parts No such covers and remova- N/A
ble parts.
4.2.2.6 Main supply 230 Va.c. (90% to 110% toler- P
ance), 50Hz, TN system con-
sidered.
4.2.2.7 Supply ports other than the mains DC input P
4.2.2.7.1 Photovoltaic supply sources PV input P
4.2.2.7.2 Battery inputs External battery pack can P
connect to the unit.
4.2.2.8 Conditions of loading for output ports P
4.2.2.9 Earthing terminals Protective conductor terminal P
was connected to earth. No
functional earth terminal.
4.2.2.10 Controls P
Controls which the operator can adjust shall be set Control is set to max. AC out- P
to any position except that put power. But it is not intend-
ed for user

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

a) mains selection devices shall be set to the cor- No mains selection devices. N/A
rect value unless otherwise noted in this standard;
b) Combinations of settings shall not be made if No combinations of settings N/A
c- devices
tions provided with the equipment.
4.2.2.11 Available short circuit current N/A
4.3 Thermal testing P
4.3.1 General P
4.3.2 Maximum temperature Tests of equipment rated for P
use in ambient temperatures
up to 40 °C
4.3.2.1 General P
Materials and components shall be selected so that P
under the most severe rated operating conditions,
the temperatures do not exceed the temperature
limits.
Conformity is verified by measuring temperatures P
under the conditions given in 4.2 for each rated op-
erating condition or mode of the PCE that could af-
fect the resulting temperatures.
The temperature limits specified below are total P
temperature limits (not temperature rise limits).
Tests of equipment rated for use in ambient tem- Maximum rated ambient tem- N/A
peratures up to 50°C may be conducted at any perature of the unit: 40 °C.
ambient temperature in the range given in 4.2.2.1,
(see appended table)
in which case the difference between the maximum
rated ambient temperature and the test ambient is
to be subtracted from or added to (as appropriate)
the measured temperatures for comparison to the
limits specified below.
PCE rated for use in ambient temperatures more N/A
than 50°C shall be tested at the maximum rated
ambient temperature +/- 5°C. the difference be-
tween the maximum rated ambient temperature
and the test ambient is to be subtracted from or
added to the measured temperatures for compari-
son to the limits specified.
PCE with different output ratings or with automatic N/A
derating for different ambient temperatures shall be
tested under as many conditions as are necessary
to record worst-case temperatures, including at
least the maximum ambient before derating, and
the maximum ambient with derating.
During thermal testing within NORMAL P
CONDITIONS protective devices shall not operate.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Temperatures are to be measured by thermocou- Method of thermocouples is P


ples, except that for coils the change of resistance used, including transformers,
method may be used. inductors, and other coils. Mul-
tiple embedded thermocou-
ples, where the thermocouples
are attached during winding of
the part, are more likely to
record hot-spot temperatures.
Limits: P
- for coils and their insulation systems, the tem-
perature limits in Table 1 apply.
- for other components the measured temperatures (see appended table) P
shall not exceed the lower of:
- the applicable IEC component standards P
- c P
operating temperature
- if neither of the above exists, temperature limits P
are given in Table 2.
4.3.2.2 Touch temperatures P
The maximum temperature for accessible parts of P
the PCE shall be in compliance with table 3
It is permitted that accessible parts that are re- P
quired to get hot as part of their intended function
(for example heatsinks) may have temperatures up
to 100 °C, if the parts are marked with the hot sur-
face marking of symbol 14 of Annex C. For prod-
ucts only for use in a closed electrical operating ar-
ea the 100 °C limit does not apply.
4.3.2.3 Temperature limits for mounting surfaces P
In order to protect against long-term degradation of P
building materials, surfaces of the PCE that will be
in contact with the mounting surface shall not ex-
ceed a maximum total temperature of 90 °C.
4.4 Testing in single fault condition P
4.4.1 General P
Testing in single fault conditions is done to deter- P
mine that no hazards result from reasonably ex-
pected fault conditions that may arise in normal
service or from reasonably expected misuse.
Fault testing shall be done unless it can be conclu- P
sively demonstrated that no hazards could arise
from a particular fault condition, or unless alterna-
tive methods of checking conformity are specified
in this standard in place of fault testing.
4.4.2 Test conditions and duration for testing under fault P
conditions
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

4.4.2.1 General P
The equipment shall be operated under the combi- P
nation of conditions in 4.2, which is least favourable
for the particular fault test being performed.
Fault conditions are to be applied only one at a P
time and shall be applied in turn in any convenient
order. Multiple simultaneous faults shall not be ap-
plied, but a subsequent fault may arise as a conse-
quence from an applied fault. Separate samples of
the EUT may be used for each separate fault test
applied, or the same sample may be used for many
tests if damage from previous fault tests has been
repaired or will not affect the results of further tests.
4.4.2.2 Duration of tests P
The equipment shall be operated until further P
change as a result of the applied fault is unlikely, as
determined by (for example) opening of a device
that removes the influence of the fault, stabilization
of temperatures, etc.
If a non-resettable, manual, or automatically reset- P
ting protective device or circuit operates in such a
way as to interrupt or mitigate the fault condition,
the test duration is as follows:
- automatic reset devices or circuits: allow the pro- P
tection to cycle on and off until no further change
as a result of the applied fault is likely, until the ul-
timate result is obtained, or until temperatures sta-
bilize
- manual reset devices or circuits: three cycles, with N/A
the device or circuit reset as soon as possible after
tripping
- non-resettable devices or circuits: one cycle N/A
4.4.3 Pass/fail criteria for testing under fault conditions P
4.4.3.1 Protection against shock hazard P
Compliance with requirements for protection P
against electric shock is checked after the applica-
tion of single faults as follows:
a) by making measurements to check that no ac- P
cessible DVC-A circuits have become shock-
hazardous using the steady state limits for DVC-A
in Table 6 and the short-term limits of 7.3.2.3, and
that such circuits remain separated from live parts
at voltages greater than DVC A with at least basic
insulation. Compliance is checked by the test of
7.5.2 (without humidity preconditioning) for basic
insulation; and

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

b) by performing a dielectric strength test as per P


7.5.2 (without humidity preconditioning) in the fol-
lowing cases:
i) on reinforced or double Insulation, using the test P
level for Basic insulation, and
ii) on basic insulation in Protective Class I equip- P
ment, using the test level for Basic insulation, un-
less it can be determined that the fault did not re-
sult in any damage to the protective earthing con-
ductor or terminal, or to protective bonding means;
and
c) by inspection to ensure a fuse connected be- P
tween the protective earthing terminal and the pro-
tective earthing conductor in the test setup has not
opened; the fuse shall be rated 3A non-time-delay
(for equipment rated for use on circuits protected
by overcurrent protection rated 30A or less) or 30A
to 35A non-time-delay(for equipment rated for use
on circuits protected by overcurrent protection rated
more than 30A); the enclosure is not to be contact-
ing earth in any other location during the testing;
and
d) by inspection of the enclosure to ensure that no P
damage has resulted that allows access to parts
that are hazardous live.
4.4.3.2 Protection against the spread of fire P
Compliance with requirements for protection P
against the spread of fire is checked by placing the
equipment on white tissue-paper covering a soft-
wood surface and covering the equipment with
cheesecloth or surgical cotton during the fault test-
ing. As an alternative, the cheesecloth or surgical
cotton may be placed only over the openings of
large equipment.
There shall be no emission of molten metal, burn- P
ing insulation, or flaming or glowing particles from
the fire enclosure, and there shall be no charring,
glowing, or flaming of the tissue paper, cheese-
cloth, or glowing or flaming of surgical cotton.
4.4.3.3 Protection against other hazards P
Conformity with requirements for protection against P
other HAZARDS after application of the fault tests
is checked as specified elsewhere in this standard.
4.4.3.4 Protection against parts expulsion hazards P

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Failure of any component within the PCE shall not P


release parts outside the PCE enclosure with suffi-
cient energy to lead to a hazard, for example, ex-
pulsion of material into an area occupied by per-
sonnel.
4.4.4 Single Fault conditions to be applied P
4.4.4.1 Component fault tests (see appended table) P
The following faults are simulated: P
a) Short circuit or open circuit of relevant compo- P
nents
b) Short circuit or open circuit of any components P
or insulation where failure could adversely affect
supplementary insulation or reinforced insulation.
c) In addition, where required by Method 2 of 9.1.1, P
components that could result in a fire hazard are to
be overloaded unless they comply with the re-
quirements of 9.1.3
4.4.4.2 Equipment or parts for short-term or intermittent Not for short-term or intermit- N/A
operation tent operation
Components such as motors, relays, other elec- No components normally op- N/A
tromagnetic devices and heaters, which are nor- erated only intermittently
mally operated only intermittently, shall be operated
continuously if continuous operation could occur in
a single fault conditions.
4.4.4.3 Motors P
Motors shall be stopped while fully energized or DC fans are tested. P
prevented from starting, whichever is less favoura-
ble.
4.4.4.4 Transformer short circuit tests (see appended table) P
The output windings of transformers shall be short- P
circuited one at a time. A transformer damaged
during one test may be repaired or replaced before
the next test.
4.4.4.5 Output short circuit P

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Testing is required to be performed on all combina- (1) Grid output P


tions of terminals for the port under consideration,
(2) Battery output
two at a time, including neutral and earth terminals,
and one test with all current-carrying terminals of (3) Load output
the port shorted together at once.
Above three combinations of
output terminals are tested
one a time.
The AC output short-circuit
current is 319Apeak impulse
(0.7ms, duration) when single
fault (1) was applied.
The battery output short-circuit
current is 950Apeak impulse
(2.2ms, duration) when single
fault (2) was applied.
The load output short-circuit
current is 45.8Apeak impulse
(164.5ms, duration) when sin-
gle fault (3) was applied.
the short-circuit currents are to be recorded and if P
they exceed the maximum rated current of the cir-
cuit, the maximum measured current shall be pro-
vided in the installation manual for the purpose of
coordination of overcurrent protection of the exter-
nal circuit conductors.
4.4.4.6 Backfeed current test P
For equipment intended to be connected simulta- DC (PV and battery) and AC P
neously to more than one source of supply, each consider as source of supply.
input of the PCE shall be tested one at a time, to
determine if hazardous conditions can result from
current from one source of supply flowing into the
wiring for another source under fault conditions.
With the PCE operating under normal conditions, a P
short circuit shall be applied at the field wiring ter-
minals of the circuit under consideration, with all in-
tended other sources connected to the PCE
through the over current protective devices (if any)
intended to be present in the installation.
the short-circuit currents are to be recorded and if The AC input short-circuit cur- P
they exceed the maximum rated current for the rent is 94Apeak impulse
port, the maximum measured current shall be pro- (0.09ms).
vided in the installation manual for the purpose of
The battery input short-circuit
coordination of overcurrent protection of the exter-
current is 1048Apeak impulse
nal circuit conductors
(2.0ms).
The PV input short-circuit cur-
rent is 85.8Apeak impulse
(0.25ms).
4.4.4.7 Output overload P

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Each output of the PCE, and each section of a P


tapped output, shall be overloaded in turn, one at a
time. The other windings are loaded or not loaded,
whichever load condition of normal use is less fa-
vorable. Overloading is carried out by connecting a
variable resistor across the winding. The resistor is
adjusted as quickly as possible and readjusted, if
necessary, after 1 min to maintain the applicable
overload. No further readjustments are then permit-
ted.
If over-current protection is provided by a current- N/A
sensitive device or circuit, the overload test current
is the maximum current which the over-current pro-
tection device is just capable of passing for 1 h. If
this value cannot be derived from the specification,
it is to be established by test. Before the test, the
device is made inoperative or replaced by a link
with negligible impedance.
For equipment in which the output voltage is de- P
signed to collapse when a specified overload cur-
rent is reached, the overload is slowly increased to
the point of maximum output power before the point
which causes the output voltage to collapse.
In all other cases, the loading is the maximum P
power output obtainable from the output.
4.4.4.8 Cooling system failure P
4.4.4.9 Heating devices No heating devices used N/A
In equipment incorporating heating devices, the fol- N/A
lowing faults shall be applied one at a time:
a) timers which limit the heating period shall be
overridden to energize the heating circuit continu-
ously;
b) temperature control devices or circuits shall have
single fault conditions applied such that control
over the heater is lost. Over-temperature protection
devices meeting the requirements of 14.3 are left
operational during the test.
4.4.4.10 Safety interlock No safety interlock N/A
4.4.4.11 Reverse d.c. connections (see appended table) P
4.4.4.12 Voltage selector mismatch No voltage selector N/A
4.4.4.13 Mis-wiring with incorrect phase sequence or polari- (see appended table) P
ty
4.4.4.14 PWB short-circuit test P
4.5 Humidity preconditioning P
4.5.1 General P
4.5.2 Conditions P
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Relative humidity (%), temperature (°C) 92.5% RH., 40 °C, 48 h P


4.6 Voltage Backfeed protection P
4.6.1 Backfeed tests under normal conditions The PV input terminal is not P
accessible to people after in-
stallation. The discharge time
after disconnection from DC
and AC sources is tested in Cl.
7.3.9.2.
For service access, the unit
was marked with discharge
time
4.6.2 Backfeed tests under single-fault condtions P
4.6.3 Compliance with backfeed tests P
The PCE is compliant with the requirements if dur- P
ing the tests in 4.6.1 and 4.6.2 no hazardous volt-
age or energy is present on the PCE terminals for
the source under test.
Measurements are taken 15 s or 1 s after the
source is de-energized or disconnected, as follows:
- 15 s for sources that are connected by fixed wir- P
ing
- 1 s for sources that are cord-connected or use N/A
connectors that can be opened without the use of a
tool
4.7 Electrical ratings tests P
4.7.1 Input ratings (see appended table) P
4.7.1.1 Measurement requirements for DC input ports P
4.7.2 Output ratings P

5 MARKING AND DOCUMENTATION P


5.1 Marking P
5.1.1 General P
Equipment shall bear markings as specified in 5.1 Label are marked on the PCE P
and 5.2 and graphic symbol is ex-
plained in user manual
Graphic symbols may be used and shall be in ac- P
cordance with Annex C or IEC 60417 as applicable.
Graphic symbols shall be explained in the docu- P
mentation provided with the PCE.
5.1.2 Durability of markings P

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Markings required by this clause to be located on P


the PCE shall remain clear and legible under condi-
tions of NORMAL USE and resist the effects of
cleaning agents specified by the manufacturer
5.1.3 Identification P
The equipment shall, as a minimum, be permanent- P
ly marked with:
a) the name or trade mark of the manufacturer or Trade mark P
supplier
b) model number, name or other means to identify Model number P
the equipment
c) a serial number, code or other marking allowing See marking label P
identification of manufacturing location and the
manufacturing batch or date within a three
month time period.
5.1.4 Equipment ratings See below P
Unless otherwise specified in another part of IEC Special requirement as per P
62109, the following ratings, as applicable shall be IEC 62109-2.
marked on the equipment:
input voltage, type of voltage (a.c. or d.c.), fre- Refer to the marking label P
quency, and max. continuous current for each
input
output voltage, type of voltage (a.c. or d.c.), Refer to the marking label P
frequency, max. continuous current, and for
a.c. outputs, either the power or power factor
for each output
the ingress protection (IP) rating as in 6.3 be- IP20 P
low
5.1.5 Fuse identification P
Marking shall be located adjacent to each fuse or N/A
fuseholder, or on the fuseholder, or in another loca-
tion provided that it is obvious to which fuse the
marking applies, giving the fuse current rating and
where fuses of different voltage rating value could
be fitted, the fuse voltage rating.
Where fuses with special fusing characteristics N/A
such as time delay or breaking capacity are neces-
sary, the type shall also be indicated
For fuses not located in operator access areas and P
for soldered-in fuses located in operator access ar-
eas, it is permitted to provide an unambiguous
cross-reference (for example, F1, F2, etc.) to the
servicing instructions which shall contain the rele-
vant information.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

5.1.6 Terminals, Connections, and Controls PV input, grid connection, load P


connection, battery connection
and communication interface
If necessary for safety, an indication shall be given Symbol 9 are marked on the P
of the purpose of Terminals, connectors, controls, PCE and user manual indicate
and indicators, and their various positions, includ- the installation and safety of
ing any connections for coolant fluids such as water connection of connector, con-
and drainage. The symbols in Annex C may be trol and indicator.
used, and where there is insufficient space, symbol
9 of Annex C may be used.
Push-buttons and actuators of emergency stop de- No emergency stop N/A
vices, and indicator lamps used only to indicate a
warning of danger or the need for urgent action
shall be coloured red.
A multiple-voltage unit shall be marked to indicate No setting is accessible to us- N/A
the particular voltage for which it is set when er
shipped from the factory. The marking is allowed to
be in the form of a paper tag or any other nonper-
manent material.
A unit with d.c. terminals shall be plainly marked See below P
indicating the polarity of the connections, with:
- The PV input and battery ter- P
minals for each module and
whole unit are silk-screen with
- for
negative
a pictorial representation illustrating the proper Not provided N/A
polarity where the correct polarity can be un-
ambiguously determined from the representa-
tion
5.1.6.1 Protective Conductor Terminals P
The means of connection for the protective earthing The PE terminal is connected N/A
conductor shall be marked with: via AC output cable
symbol 7 of Annex C; or P
N/A
the colour coding green-yellow. P
5.1.7 Switches and circuit-breakers P
The on and off-positions of switches and circuits P
breakers shall be clearly marked. If a push-button
switch is used as the power switch, symbols 10 and
16 of Annex C may be used to indicate the on-
position, or symbols 11 and 17 to indicate the off-
position, with the pair of symbols (10 and 16, or 11
and 17) close together.
5.1.8 Class Equipment Class I N/A

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Equipment using Class protective means N/A


throughout shall be marked with symbol 12 of An-
nex C. Equipment which is only partially protected
by DOUBLE INSULATION or REINFORCED
INSULATION shall not bear symbol 12 of Table
Annex C.
Where such equipment has provision for the con- N/A
nection of an earthing conductor for functional rea-
sons (see 7.3.6.4) it shall be marked with symbol 6
of Annex C
5.1.9 Terminal boxes for External Connections No such terminal boxes. N/A
Where required by note 1 of Table 2 as a result of N/A
high temperatures of terminals or parts in the wiring
compartment, there shall be a marking, visible be-
side the terminal before connection, of either:
a) the minimum temperature Rating and size of N/A
the cable to be connected to the TERMINALS;
or
b) a marking to warn the installer to consult the in- N/A
stallation instruction. Symbol 9 of Table D-1 is
an acceptable marking
5.2 Warning markings P
5.2.1 Visibility and legibility requirements for warning P
markings
Warning markings shall be legible, and shall have P
minimum dimensions as follows:
Printed symbols shall be at least 2.75 mm high P
Printed text characters shall be at least 1.5 mm P
high and shall contrast in colour with the back-
ground
Symbols or text that are moulded, stamped or N/A
engraved in a material shall have a character
height of at least 2,0 mm, and if not contrasting
in colour from the background, shall have a
depht or raised height of at least 0,5 mm.
If it is necessary to refer to the instruction manual The manual provide necessary P
to preserve the protection afforded by the equip- information for the warning
ment, the equipment shall be marked with symbol 9 marking.
of Annex C
Symbol 9 of Annex C is not required to be used ad- P
jacent to symbols that are explained in the manual
5.2.2 Content for warning markings P
5.2.2.1 Ungrounded heatsinks and similar parts Ungrounded heatsink P

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

An ungrounded heat sink or other part that may be Symbol 13 marked on P


mistaken for a grounded part and involves a risk of heatsink
electric shock in accordance with 7.3 shall be
marked with symbol 13 of Annex C, or equivalent.
The marking may be on or adjacent to the heatsink
and shall be clearly visible when the PCE is disas-
sembled to the extent that a risk of contact with the
heatsink exists.
5.2.2.2 Hot Surfaces N/A
A part of the PCE that exceeds the temperature N/A
limits specified in 4.3.2 shall be marked with sym-
bol 14 of Annex C or equivalent.
5.2.2.3 Coolant Coolant is not used N/A
A unit containing coolant that exceeds 70 °C shall N/A
be legibly marked externally where readily visible
after installation with symbol 15 of Annex C. The
documentation shall provide a warning regarding
the risk of burns from hot coolant, and either:
a) statement that coolant system servicing is to be N/A
done only by SERVICE PERSONNEL, or
b) instructions for safe venting, draining, or other- N/A
wise working on the cooling system, if these
operations can be performed without
OPERATOR access to HAZARDS internal to
the equipment
5.2.2.4 Stored energy P
Where required by 7.3.9.2 or 7.4.2 the PCE shall Symbol 21 is marked on PCE P
be marked with Symbol 21 of Annex C and the time
to discharge capacitors to safe voltage and energy
levels shall accompany the symbol.
5.2.2.5 Motor guarding P
Where required by 8.2 a marking shall be provided It is not accessible by finger. P
where it is visible to service personnel before re-
moval of a guard, warning of the hazard and giving
instructions for safe servicing (for example discon-
nection of the source before removing the guard).
5.2.3 Sonic hazard markings and instructions No sonic hazard N/A
If required by 10.2.1 a PCE shall: N/A
a) be marked to warn the operator of the sonic N/A
pressure hazard; or

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

b) be provided with installation instructions that N/A


specify how the installer can ensure that the
sound pressure level from equipment at its
point of use after installation, will not reach a
value, which could cause a hazard. These in-
structions shall include the measured sound
pressure level, and shall identify readily availa-
ble and practicable protective materials or
measures which may be used.
5.2.4 Equipment with multiple sources of supply PV array, battery and AC P
mains.
A PCE with connections for multiple energy Symbol 13 provided on PCE P
sources shall be marked with symbol 13 of Annex
C and the manual shall contain the information re-
quired in 5.3.4.
The symbol shall be located on the outside of the P
unit or shall be prominently visible behind any cov-
er giving access to hazardous parts.
5.2.5 Excessive touch current N/A
Where required by 7.3.6.3.7 the PCE shall be N/A
marked with symbol 15 of Annex C. See also 5.3.2
for information to be provided in the installation
manual.
5.3 Documentation P
5.3.1 General P
The documentation provided with the PCE shall P
provide the information needed for the safe opera-
tion, installation, and (where applicable) mainte-
nance of the equipment. The documentation shall
include the items required in 5.3.2 through 5.3.4,
and the following:
a) explanations of equipment makings, including P
symbols used
b) location and function of terminals and controls P
c) all ratings or specifications that are necessary P
to safely install and operate the PCE, including
the following environmental ratings along with
an explanation of their meaning and any result-
ing installation requirements:
ENVIRONMENTAL CATEGORY as per 6.1 Indoor P
WET LOCATIONS classification fort he in- Suitable for dry location P
tended external environment as per 6.1
POLLUTION DEGREE classification for the 2 P
intended external environment as per 6.2
INGRESS PROTECTION rating as per 6.3 IP20 P

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Ambient temperature and relative humidity Max. 40 °C and 90%RH P


ratings
MAXIMUM altitude rating Up to 2000 m P
OVERVOLTAGE CATEGORY assigned to OVC II (PV), OVC III (Mains) P
each input and output port as per
7.3.7.1.2, accompanied by guidance re-
garding how to ensure that the installation
complies with the required overvoltage cat-
egories;
d) a warning that when the photovoltaic array is P
exposed to light, it supplies a d.c. voltage to the
PCE
5.3.1.1 Language English provide P
Instructions related to safety shall be in a language For other country language, N/A
that is acceptable in the country where the equip- further evaluation is needed.
ment is to be installed.
5.3.1.2 Format P
In general, the documentation must be provided in Printed form provided and is to P
printed form and is to be delivered with the equip- be delivered with equipment
ment.
For equipment which requires the use of a comput- P
er for both installation and operation, documenta-
tion may be provided in electronic format without
accompanying printed format.
5.3.2 Information related to installation P
The documentation shall include installation and P
where applicable, specific commissioning instruc-
tions and, if necessary for safety, warnings against
hazards which could arise during installation or
commissioning of the equipment. The information
provided shall include:
a) assembly, location, and mounting require- P
ments:
b) ratings and means of connection to each P
source of supply and any requirements related
to wiring and external controls, colour coding of
leads, disconnection means, or overcurrent
protection needed, including instructions that
the installation position shall not prevent access
to the disconnection means;
c) ratings and means of connection of any outputs P
from the PCE, and any requirements related to
wiring and externals controls, colour coding of
leads, or overcurrent protection needed;
d) explanation of the pin-out of connectors for ex- P
ternal connections, unless the connector is
used for a standard purpose (e.g. RS 232)
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

e) ventilation requirements; P
f) requirements for special services, for example No cooling liquid or other spe- N/A
cooling liquid; cial service
g) instructions and information relating to sound N/A
pressure level if required by 10.2.1;
h) where required by 14.8.1.3, instructions for the No such battery N/A
adequate ventilation of the room or location in
which PCE containing vented or valve-
regulated batteries is located, to prevent the
accumulation of hazardous gases;
i) tightening torque to be applied to wiring termi- P
nals;
j) values of backfeed short-circuit currents availa- P
ble from the PCE on input and output conduc-
tors under fault conditions, if those currents ex-
ceeds the max. rated current of the circuit, as
per 4.4.4.6;
k) for each input to the PCE, the max value of P
short-circuit current available from the source,
for which the PCE is designed; and
l) compatibility with RCD and RCM; N/A
m) instructions for protective earthing, including Provided in the installation P
the information required by 7.3.6.3.7 if a sec- manual.
ond protective earthing conductor is to be in-
stalled:
n) where required by 7.3.8, the installation instruc- N/A
tions shall include the following or equivalent
wording:
N/A
external protective earthing conductor. Where a
residual current-operated protective (RCD) or
monitoring (RCM) device is used for protection
in a case of direct or indirect contact, only an
RCD or RCM of Type B is allowed on the sup-
ply side of this prod
o) for PCE intended to charge batteries, the bat- P
tery nominal voltage rating, size, and type
p) PV array configuration information, such as rat- P
ings, whether the array is to be grounded or
floating, any external protection devices need-
ed, etc.
5.3.3 Information related to operation P
Instructions for use shall include any operating in- P
structions necessary to ensure safe operation, in-
cluding the following, as applicable:

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Instructions for adjustment of controls including P


the effects of adjustment;
Instructions for interconnection to accessories P
and other equipment, including indication of
suitable accessories, detachable parts and any
special materials;
Warnings regarding the risk of burns from sur- P
faces permitted to exceed the temperature lim-
its of 4.3.2 and required operator actions to re-
duce the risk; and
Instructions, that if the equipment is used in a P
manner not specified by the manufacturer, the
protection provided by the equipment may be
impaired.
5.3.4 Information related to maintenance P
Maintenance instructions shall include the follow- P
ing:
Intervals and instructions for any preventive P
maintenance that is required to maintain safety
(for example air filter replacement or periodic
re-tightening of terminals);
Instructions for accessing operator access are- P
as, if any are present, including a warning not
to enter other areas of the equipment;
Part numbers and instructions for obtaining any No replaceable parts N/A
required operator replaceable parts;
Instructions for safe cleaning (if recommended) P
Where there is more than one source of supply P
energizing the PCE, information shall be pro-
vided in the manual to indicate which discon-
nect device or devices are required to be oper-
ated in order to completely isolate the equip-
ment.
5.3.4.1 Battery maintenance No energy storage battery in- N/A
side
Where required by 14.8.5, the documentation shall N/A
include the applicable items from the following list
of instructions regarding maintenance of batteries:
Servicing of batteries should be performed or N/A
supervised by personnel knowledgeable about
batteries and the required precautions
When replacing batteries, replace with the N/A
same type and number of batteries or battery
packs

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

General instructions regarding removal and in- N/A


stallation of batteries
CAUTION: Do not dispose of batteries in a fire. N/A
The batteries may explode.
CAUTION: Do not open or damage batteries. N/A
Released electrolyte is harmful to the skin and
eyes. It may be toxic.
CAUTION: A battery can present a risk of elec- N/A
trical shock and high short-circuit current. The
following precautions should be observed when
working on batteries:
a) Remove watches, rings, or other metal objects. N/A
b) Use tools with insulated handles. N/A
c) Wear rubber gloves and boots. N/A
d) Do not lay tools or metal parts on top of batter- N/A
ies
e) Disconnect charging source prior to connecting N/A
or disconnecting battery terminals
f) Determine if battery is inadvertently grounded. N/A
If inadvertently grounded, remove source from
ground. Contact with any part of a grounded
battery can result in electrical shock. The likeli-
hood of such shock can be reduced if such
grounds are removed during installation and
maintenance (applicable to equipment and re-
mote battery supplies not having a grounded
supply circuit).

6 ENVIRONMENTAL REQUIREMENTS AND CONDITIONS P


The manufacturer shall rate the PCE for the follow- P
ing environmental conditions:
ENVIRONMENTAL CATEGORY, as in 6.1 be- Indoor use P
low
Suitability for WET LOCATIONS or not Suitability for dry locations P
POLLUTION DEGREE rating in 6.2 below PD2 P
INGRESS PROTECTION (IP) rating, as in 6.3 IP20 P
below
Ultraviolet (UV) exposure rating, as in 6.4 be- Indoor use N/A
low
Ambient temperature and relative humidity rat- P
ings, as in 6.5 below
6.1 Environmental categories and minimum environmental conditions P
6.1.1 Outdoor N/A
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

6.1.2 Indoor, unconditioned N/A


6.1.3 Indoor, conditioned P
6.2 Pollution degree PD2 P
6.3 Ingress Protection IP20 P
6.4 UV exposure N/A
6.5 Temperature and humidity Max. 40 °C and 90%RH P

7 PROTECTION AGAINST ELECTRIC SHOCK AND ENERGY HAZARDS P


7.1 General P
7.2 Fault conditions Normal and single fault condi- P
tion are considered
7.3 Protection against electric shock P
7.3.1 General In the PCE the earthed metal P
enclosure is evaluated by
means of basic insulation from
DVC C circuit.
DVC A circuit and unearthed
accessible parts are evaluated
by means of double insulation
or reinforce insulation from
DVC C.
DVC C: The PV input and
mains output.
DVC A: the communication in-
terface.
7.3.2 Decisive voltage classification P
7.3.2.1 Use of decisive voltage class (DVC) Working voltage and protec- P
tive measures are considered.
7.3.2.2 Limits of DVC (according table 6) P
7.3.2.3 Short-terms limits of accessible voltages under fault P
conditions
7.3.2.4 Requirements for protection (according table 7) Single fault condition is con- P
sidered. Accessible earthed
conductive parts are separat-
ed from DVC-C circuits by
basic insulation. Accessible
unearthed conductive parts
separated from DVC C circuit
by double insulation.
7.3.2.5 Connection to PELV and SELV circuits The external signal communi- P
cation interface are considered
as SELV
7.3.2.6 Working voltage and DVC P
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

7.3.2.6.1 General Transients and voltage P


fluctuations are disregarded.
And worst case normal
operating condition is
considered
7.3.2.6.2 AC working voltage (see Figure 2) 230 Vr.m.s considered P
7.3.2.6.3 DC working voltage (see Figure 3) Max. DC open voltage: 550 V P
7.3.2.6.4 Pulsating working voltage (see Figure 4) N/A
7.3.3 protective separation See description in Cl. 7.3.1 P
Protective separation shall be achieved by: P
double or reinforced insulation, or P
protective screening, i.e. by a conductive P
screen connected to earth by protective bond-
ing in the PCE, or connected to the protective
earth conductor itself, whereby the screen is
separated from live parts by at least basic insu-
lation, or
protective impedance comprising limitation of P
current per 7.3.5.3 and of discharged energy
per 7.3.5.4, or
limitation of voltage according to 7.3.5.4. N/A
The protective separation shall be fully and effec- P
tively maintained under all conditions of intended
use of the PCE
7.3.4 Protection against direct contact P
7.3.4.1 General P
Protection against direct contact is employed to Enclosure provided P
prevent persons from touching live parts that do not
meet the requirements of 7.3.5 and shall be provid-
ed by one or more of the measure given in 7.3.4.2
(enclosures and barriers) and 7.3.4.3 (insulation).
Open type sub-assemblies and devices do not re- End use product N/A
quire protective measures against direct contact
but the instruction provided with the equipment
must indicate that such measures must be provided
in the end equipment or in the installation.
Product intended for installation in CLOSED No use under this condition N/A
ELECTRICAL OPERATING AREAS, (see 3.9)
need not have protective measures against direct
contact, except as required by 7.3.4.2.4.
7.3.4.2 Protection by means of enclosures and barriers P
The following requirements apply where protection Enclosure provided to prevent P
against contact with live parts is provided by enclo- access to inside live parts
sures or barriers, not by insulation in accordance
with 7.3.4.3.
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

7.3.4.2.1 General P
Parts of enclosures and barriers that provide pro- Secured by screws P
tection in accordance with these requirements shall
not be removable without the use of a tool (see
7.3.4.2.3).
Polymeric materials used to meet these require- P
ments shall also meet the requirements of 13.6
7.3.4.2.2 Access probe criteria P
Protection is considered to be achieved when the P
separation between the test probes and live parts,
when tested as described below, is as follows:
a) decisive voltage classification A, (DVC A) - the The communication interface P
probe may touch the live parts is considered as DVC A
b) decisive voltage classification B, (DVC B) - the The DVC B circuit is not ac- P
probe must not touch bare live parts cessible by probe
c) decisive voltage classification C, (DVC C) the The DVC C circuit is not ac- P
probe must have adequate clearance to live cessible by probe
parts, based on the clearance for Basic insula-
tion using the recurring peak working voltage
involved,
7.3.4.2.3 Access probe tests P
Compliance with 7.3.4.2.1 is checked by all of the P
following:
a) Inspection; and P
b) Tests with the test finger (Figure D.1) and test P
pin (Figure D.2) of 0E, the results of which shall
comply with the requirements of 7.3.4.2.1 a),
b), and c) as applicable. Probe tests are per-
formed on openings in the enclosures after re-
moval of parts that can be detached or opened
by an operator without the use of a tool, includ-
ing fuseholders, and with operator access
doors and covers open. It is permitted to leave
lamps in place for this test. Connectors that can
be separated by an operator without use of a
tool, shall also be tested during and after dis-
connection. Any movable parts are to be put in
the most unfavorable position.
The test finger and the test pin are applied as P
above, without appreciable force, in every pos-
sible position, except that floor-standing equip-
ment having a mass exceeding 40 kg is not tilt-
ed.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Equipment intended for building-in or rack N/A


mounting, or for incorporation in larger equip-
ment, is tested with access to the equipment
limited according to the method of mounting de-
tailed in the installation instructions.
c) Openings preventing the entry of the jointed air-intakes for cooling fans. P
test finger ( Figure E-1 of 0E) during test b)
above, are further tested by means of straight
unjointed test finger (Figure E-3 of 0E), applied
with a force of 30 N. If the unjointed finger en-
ters, the test with the jointed finger is repeated
except that the finger is applied using any nec-
essary force up to 30 N.
d) In addition to a) c) above, top surfaces of en- N/A
closure shall be tested with the IP3X probe of
IEC 60529. The test probe shall not penetrate
the top surface of the enclosure when probed
from the vertical direction ±5 ° only.
7.3.4.2.4 Service access areas 16.1 s@60 V bus after dis- P
connecting DC side.
Inside PCE are not intentional-
ly touched with energized
parts when installation and
maintenance. Symbol 21 of
Annex C are marked on PCE
and explained in user manual.
7.3.4.3 Protection by means of insulation of live parts The earthed enclosure is with P
basic insulation from the live
parts inside
Where the requirements of 7.3.4.2 are not met, live P
parts shall be provided with insulation if:
their working voltage is greater than the maxi- P
mum limit of decisive voltage class A, or
for a DVC A or B circuit, protective separation P
from adjacent circuit of DVC C is not provided

7.3.5 Protection in case of direct contact The communication interface P


are direct contact and evaluat-
ed with double insulation from
live parts
7.3.5.1 General P
Protection in case of direct contact is required to P
ensure that contact with live parts does not produce
a shock hazard.
The protection against direct contact according to Considered P
7.3.4 is not required if the circuit contacted is sepa-
rated from other circuits according to 7.3.2.3, and:

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

is of decisive voltage class A and complies with The communication interface P


7.3.5.2, or is DVC A and double insula-
tion from the live parts by
means of isolation transformer
with isolation power supply
and opto-coupler
is provided with protective impedance accord- At least four resistors (total re- P
ing to 7.3.5.3, or sistance >2.4
voltage sampling.
is limited in voltage according to 7.3.5.4 N/A
In addition to the measures as given in 7.3.5.2 to Considered P
7.3.5.4, it shall be ensured that in the event of error
or polarity reversal of connectors no voltages that
exceed DVC A can be connected into a circuit with
protective separation. This applies for example to
plug-in-sub-assemblies or other plug-in devices
which can be plugged-in without the use of a tool
(key) or which are accessible without the use of a
tool.
Conformity is checked by visual inspection and trial P
insertion.
7.3.5.2 Protection using decisive voltage class A The communication interface P
is DVC A and double insula-
tion from the live parts by
means of isolation transformer
with isolation power supply
and opto-coupler
7.3.5.3 Protection by means of protective impedance At least five resistors (total re- P
sistance > 5
Circuits and conductive parts do not require protec- P
tion against direct contact if any connection to cir-
cuits of DVC-B or DVC-C is through protective im-
pedance, and the accessible circuit or part is oth-
erwise provided with protective separation from cir-
cuits of DVC-B or DVC-C according 7.3.3.
7.3.5.3.1 Limitation of current through protective impedance P
The current available through protective impedance P
to earth and between simultaneously accessible
parts, measured at the accessible live parts, shall
not exceed a value of 3,5 mA a.c. or 10 mA d.c.
under normal and single-fault conditions.
7.3.5.3.2 Limitation of discharging energy through protective P
impedance

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

The discharging energy available between simulta- P


neously accessible parts protected by protective
impedance shall not exceed the charging voltage
and capacitance limits given in Table 9, which ap-
plies to both wet and dry locations, under normal
and single fault conditions. Refer to figure 8.
7.3.5.4 Protection by means of limited voltages No such design N/A
That portion of a circuit that has its voltage reduced N/A
to DVC-A by a voltage divider that complies with
the following requirements, and that is otherwise
provided with protective separation from circuits of
DVC-B or DVC-C according to 7.3.3, does not re-
quire protection against direct contact.
The voltage divider shall be designed so that under N/A
normal and single fault conditions, including faults
in the voltage division circuit, the voltage across the
output of the voltage divider does not exceed the
limit for DVC-A.
This type of protection shall not be used in case of N/A
protective class II or unearthed circuits, because it
relies on protective earth being connected.
7.3.6 Protection against indirect contact P
7.3.6.1 General P
Protection against indirect contact is required to P
prevent shock- hazardous current being accessible
from conductive parts during an insulation failure.
This protection shall comply with the requirements
for protective class I (basic insulation plus protec-
tive earthing), class II (double or reinforced insula-
tion) or class III (limitation of voltages)
That part of a PCE meets the requirements of The earthed metal enclosure P
7.3.6.2 and 7.3.6.3 is defined as protective class I meet this requirement
That part of a PCE meets the requirements of The communication interface P
7.3.6.4 is defined as protective class II. is double insulated from live
parts inside.
That part of PCE which meets the requirements of N/A
decisive voltage class A and in which no hazardous
voltages are derived, is defined as protective class
III. No shock hazard is present in such circuits.
Where protection against indirect contact is de- The manual require the PCE P
pendent on means provided during installation, the must be securely earthed
installation instructions shall provide details of the
required means and shall indicate the associated
hazards.
7.3.6.2 Insulation between live parts and accessible con- See Cl. 7.3.7.4 and Cl. 7.3.7.5 P
ductive parts

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Accessible conductive parts of equipment shall be P


separated from live parts by insulation meeting the
requirements of Table 7 or by clearances as speci-
fied in 7.3.7.4 and creepages as specified in 7.3.7.5
7.3.6.3 Protective class I Protective bonding and earthing P
7.3.6.3.1 General P
Equipment of protective class I shall be provided P
with protective earthing, and with protective bond-
ing to ensure electrical contact between accessible
conductive parts and the means of connection for
the external protective earthing conductor, except
bonding is not required for:
a) accessible conductive parts that are protected N/A
by one of the measures in 7.3.5.2 to 7.3.5.4, or
b) accessible conductive parts are separated from P
live parts of DVC-B or -C using double or rein-
forced insulation.
7.3.6.3.2 Requirements for protective bonding P
Electrical contact with the means of connection of The PCE provide internal and P
the external protective earthing conductor shall be external optional earthing
achieved by one or more of the following means: screws for protective earthing.
a) through direct metallic contact; P
b) through other conductive parts which are not N/A
removed when the PCE or sub-units are used
as intended ;
c) through a dedicated protective bonding conduc- P
tor;
d) through other metallic components of the PCE N/A
Where direct metallic contact is used and one or P
both of the parts involved is painted or coated, the
paint or coating shall be removed in the area of
contact, or reliably penetrated, to ensure metal to
metal contact.
For moving or removable parts, hinges or sliding No such design N/A
contacts designed and maintained to have a low
resistance are examples of acceptable means if
they comply with the requirements of 7.3.6.3.3.
Metal ducts of flexible or rigid construction and me- No such design N/A
tallic sheaths shall not be used as protective bond-
ing conductors, unless the device or material has
been investigated as suitable for protective bonding
purposes.
7.3.6.3.3 Rating of protective bonding P

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Protective bonding shall withstand the highest P


thermal and dynamic stresses that can occur to the
PCE item(s) concerned when they are subjected to
a fault connecting live parts to accessible conduc-
tive parts.
The protective bonding shall remain effective for as
long as a fault to the accessible conductive parts
persists or until an upstream protective device re-
moves power from the part.
Protective bonding shall meet following require- P
ments:
a) For PCE with an overcurrent protective device N/A
rating of 16 A or less, the impedance of the
protective bonding means shall not exceed 0,1
elow.
b) For PCE with an overcurrent protective device P
rating of more than 16 A, the voltage drop in
the protective bonding test shall not exceed
2,5 V during or at the end of the test below.
As alternative to a) and b) the protective bonding P
may designed according to the requirements for the
external protective earthing conductor in 7.3.6.3.5,
in which case no testing is required.
The impedance of protective bonding means shall P
be checked by passing a test current through the
bond for a period of time as specified below. The
test current is based on the rating of the overcur-
rent protection for the equipment or part of the
equipment under consideration, as follows:
a) For pluggable equipment type A, the overcur- N/A
rent protective device is that provided external
to the equipment (for example, in the building
wiring, in the mains plug or in an equipment
rack);
b) For pluggable equipment type B and fixed Fixed equipment P
equipment, the maximum rating of the overcur-
rent protective device specified in the equip-
ment installation instructions to be provided ex-
ternal to the equipment;
c) For a circuit or part of the equipment for which N/A
an overcurrent protective device is provided as
part of the equipment, the rating of the provid-
ed overcurrent device.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Voltages are measured from the protective earthing Measured from the farthest P
terminal to all parts whose protective bonding part of earthed metal enclo-
means are being considered. The impedance of the sure to the input earth terminal
protective earthing conductor is not included in the
measurement. However, if the protective earthing
conductor is supplied with the equipment, it is per-
mitted to include the conductor in the test circuit but
the measurement of the voltage drop is made only
from the main protective earthing terminal to the
accessible part required to be earthed.
On equipment where the protective earth Figure 11 used P
conncection to a subassembly or to a separate unit
is part of a cable that also supplies power to that
subassembly or unit, the resistance of the protec-
tive bonding conductor in that cable is not included
in the protective bond impedance measurements
for the subassembly or separate unit, as shown in
Figure 11. However, this option is only permitted if
the cab le is protected by a suitably rated protective
device that takes into account the size of the con-
ductor. Otherwise the impedance of the protective
bonding conductor between the separate units is to
be included, by measuring to the protective earth-
ing terminal where the power source enters the first
unit in the system, as shown in Figure 12.
7.3.6.3.3.1 Test current, duration, and acceptance criteria P
The test current, duration of the test and ac- P
ceptance criteria are as follows:
a) For PCE with an overcurrent protective device N/A
rating of 16 A or less, the test current is 200%
of the overcurrent protective device rating, but
not less than 32 A, applied for 120s. The im-
pedance of the protective bonding means dur-
ing and at the end of the test shall not exceed

b) For PCE with an overcurrent protective device 0.25 V P


rating of more than 16 A, the test current is
200% of the overcurrent protective device rat-
ing and the duration of the test is as shown in
Table 10 below. The voltage drop in the protec-
tive bonding means, during and at the end of
the test, shall not exceed 2,5 V.
c) During and after the test, there shall be no P
melting, loosening, or other damage that would
impair the effectiveness of the protective bond-
ing means.
The test current is derived from an a.c or d.c supply DC supply P
source, the output of which is not earthed.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

As an alternative to Table 10, where the time- P


current characteristic of the overcurrent protective
device that limits the fault current in the protective
bonding means is known because the device is ei-
ther provided in the equipment or fully specified in
the installation instructions, the test duration may
s time-current
characteristic. The tests are conducted for a dura-
tion corresponding to the 200% current value on
the time-current characteristic.
7.3.6.3.4 Protective bonding impedance (routine test) N/A
If the continuity of the protective bonding is Declared by Manufacturer and N/A
achieved at any point by a single means only (for working instruction checked
example a single conductor or single fastener), or if during factory inspection
the PCE is assembled at the installation location,
then the impedance of the protective bonding shall
also be tested as a routine test.
The test shall be as in 7.3.6.3.3, except for the fol-
lowing:
the test current may be reduced to any conven- N/A
ient value greater than 10 A sufficient to allow
measurement or calculation of the impedance
of the protective bonding means:
the test duration may be reduced to no less N/A
than 2 s
For equipment subject to the type test in N/A
7.3.6.3.3.1a), the impedance during the routine test

For equipment subject to the type test in N/A


7.3.6.3.3.1b) the impedance during the routine test
shall not exceed 2,5 V divided by the test current
required by 7.3.6.3.3.1b).
7.3.6.3.5 External protective earthing conductor N/A
A protective earthing conductor shall be connected N/A
at all times when power is supplied to PCE of pro-
tective class I. Unless local wiring regulations state
otherwise, the protective earthing conductor cross-
sectional area shall be determined from Table 11 or
by calculation according to IEC 60364-5-54.
If the external protective earthing conductor is rout- N/A
ed through a plug and socket or similar means of
disconnection, it shall not be possible to disconnect
it unless power is simultaneously removed from the
part to be protected.
The cross-sectional area of every external protec- External protective earthing N/A
tive earthing conductor which does not form part of conductor is integrated with
the supply cable or cable enclosure shall, in any output cable
case, be not less than:

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

2,5 mm² if mechanical protection is provided; N/A


4 mm² if mechanical protection is not provided. N/A
For cord-connected equipment, provisions shall be N/A
made so that the external protective earthing con-
ductor in the cord shall, in the case of failure of the
strain-relief mechanism, be the last conductor to be
interrupted.
7.3.6.3.6 Means of connection for the external protective P
earthing conductor
7.3.6.3.6.1 General P
The means of connection for the external protective Integrated within output cable P
earthing conductor shall be located near the termi-
nals for the respective live conductors. The means
of connections shall be corrosion-resistant and
shall be suitable for the connection of cables ac-
cording to 7.3.6.3.5.
The means of connection for the protective earthing
conductor shall not be used as a part of the me-
chanical assembly of the equipment or for other
connections.
A separate means of connection shall be provided
for each external protective earthing conductor.
Connection and bonding points shall be so de-
signed that their current-carrying capacity is not
impaired by mechanical, chemical, or electrochem-
ical influences. Where enclosures and/or conduc-
tors of aluminium or aluminium alloys are used,
particular attention should be given to the problems
of electrolytic corrosion.
The means of connection for the protective earthing P
conductor shall be permanently marked with:
symbol 7 of Annex C; or P
the colour coding green-yellow P
Marking shall not be done on easily changeable N/A
parts such as screws.
7.3.6.3.7 Touch current in case of failure of the protective P
earthing conductor
The requirements of this sub-clause shall be satis- The measured touch current is P
fied to maintain safety in case of damage to or dis- 1.5 mA.
connection of the protective earthing conductor.
For pluggable equipment type A, the touch current N/A
measured in accordance with 7.5.4 shall not ex-
ceed 3,5 mA a.c. or mA d.c.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

For all other PCE, one or more of the following N/A


measure shall be applied, unless the touch current
measured in accordance with 7.5.4 using the test
network of IEC 60990 test figure 4 shall not exceed
3,5 mA a.c. or 10 mA d.c.
a) Permanently connected wiring, and: N/A
a cross-section of the protective earthing N/A
conductor of at least 10 mm² Cu or 16 mm²
Al; or
automatic disconnection of the supply in N/A
case of discontinuity of the protective
earthing conductor; or
provision of an additional terminal for a N/A
second protective earthing conductor of the
same cross-sectional area as the original
protective earthing conductor and installa-
tion instruction requiring a second protec-
tive earthing conductor to be installed or
b) Connection with an industrial connector accord- N/A
ing to IEC 60309 and a minimum protective
earthing conductor cross-section of 2,5 mm² as
part of a multi-conductor power cable. Ade-
quate strain relief shall be provided.
In addition, the caution symbol 15 of Annex C N/A
shall be fixed to the product and the installation
manual shall provide details of the protective
earthing measures required in the installation
as required in 5.3.2.
When it is intended and allowed to connect two N/A
or more PCEs in parallel using one common
PE conductor, the above touch current re-
quirements apply to the maximum number of
the PCEs to be connected in parallel, unless
one of the measures in a)
or b) above is used. The maximum number of N/A
parallel PCEs is used in the testing and has to
be stated in the installation manual.
7.3.6.4 Protective Class II Double or Reinforced Insula- Communication interface is P
tion evaluated with double insula-
tion from live part inside.
Comply with clause 7.3.4.3
Equipment or parts of equipment designed for pro- N/A
tective class II shall have insulation between live
parts and accessible surfaces in accordance with
7.3.4.3. The following requirements also apply:

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

equipment designed to protective class II shall N/A


not have means of connection for the external
protective earthing conductor. However this
does not apply if the external protective earth-
ing conductor is passed through the equipment
to equipment series-connected beyond it. In the
latter event, the external protective earthing
conductor and its means for connection shall
be insulated with basic insulation from the ac-
cessible surface of the equipment and from cir-
cuits that employ protective separation, extra-
low voltage, protective impedance and limited
discharging energy, according to 7.3.5. This
basic insulation shall correspond to the rated
voltage of the series-connected equipment;
metal-encased equipment of protective class II N/A
may have provision on its enclosure for the
connection of an equipotential bonding conduc-
tor;
equipment of protective class II may have pro- N/A
vision for the connection of an earthing conduc-
tor for functional reasons or for damping of
overvoltages; it shall, however, be insulated as
though it is a live part;
equipment employing protective class II shall N/A
be marked according to 5.1.8.
7.3.7 Insulation Including Clearance and Creepage Dis- P
tance
7.3.7.1 General P
This subclause gives minimum requirements for in- P
sulation, based on the principles of IEC 60664.
Manufacturing tolerances shall be taken into ac- P
count during measurement of creepage, clearance,
and insulation distance in the PCE.
Insulation shall be selected after consideration of P
the following influences:
pollution degree PD2 P
overvoltage category PV (OVC II), Mains (OVC III) P
supply earthing system TN considered. P
insulation voltage PV input: max. 550 Vd.c. and P
Mains: 230 Va.c.
location of insulation See table 7.3.7.4 and 7.3.7.5 P
for detail
type of insulation See table 7.3.7.4 and 7.3.7.5 P
for detail

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Compliance of insulation, creepage distances, and P


clearance distances, shall be verified by measure-
ment or visual inspection, and the tests of 7.5.
7.3.7.1.3 Supply earthing systems P
Three basic types of earthing system are described Inverter is intended to installed P
in IEC 60364-1. They are: in TN system.
TN system: has one point directly earthed, the P
accessible conductive parts of the installation
being connected to that point by protective
conductors. Three types of TN systems, TN-C,
TN-S and TN-C-S, are defined according to the
arrangement of the neutral and protective con-
ductor.
TT system: has one point directly earthed, the N/A
accessible conductive parts of the installation
being connected to earth electrodes electrically
independent of the earth electrodes of the
power system;
IT sytem: has all live parts isolated from earth N/A
or one point connected to earth through an im-
pedance, the accessible conductive parts of the
installation being earthed independently or col-
lectively to the earthing system.
7.3.7.1.4 Insulation voltages See table 7.3.7.4 and 7.3.7.5 P
for detail
Table 12 makes use of the circuit system voltage P
and overvoltage category to define the impulse
withstand voltage and the temporary overvoltage.
7.3.7.2 Insulation between a circuit and its surroundings P
7.3.7.2.1 General 230Va.c., OVC III (4000 V im- P
pulse voltage, 1500 Vrms tem-
Basic, supplementary and reinforced insulation be-
porary overvoltage) for the AC
tween a circuit and its surroundings shall be de-
mains output;
signed according to:
550 Vd.c. system voltage, OVC
Impulse voltage;
II (4000 V impulse voltage, no
temporary overvoltage; temporary overvoltage for the
PV input;
working voltage of the circuit;
No insulation between PV and
AC mains output.
Basic insulation between PV/
AC mains and battery terminal.
7.3.7.2.2 Circuit connected directly to the mains System voltage for mains is P
300 Vrms according to table
Clearance and solid insulation between circuit con-
12. 4000 V impulse voltage
nected directly to the mains and their surroundings
gives the most severe re-
shall be designed according to the impulse voltage,
quirement
temporary overvoltage, or working voltage, whichev-
er gives the most severe requirement
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

7.3.7.2.3 Circuit other than mains circuit System voltage for PV is 550 P
Vd.c.
Clearance and solid insulation between circuit other
than the mains and their surroundings shall be de-
signed according to impulse voltage and recurring
peak voltage
7.3.7.2.4 Insulation between circuits Impulse voltage (4000 V) is P
calculated from table 12 for
a) For clearances and insulation, the require-
clearance before basic isola-
ments are determined by the circuit having
tion transformer for PV and AC
the higher impulse voltage;
mains side.
b) For creepages, r.m.s. working voltage
Impulse voltage (2500 V) is
across the insulation determines the re-
calculated from table 12 for
quirements.
clearance after basic isolation
transformer for battery side.
Working voltage (550 Vd.c.)
across insulation is used for
creepage.
7.3.7.3 Functional insulation P
For parts or circuit in OVC I, functional insulation
shall be designed according to the working voltage
across the insulation
For parts or circuit in OVC II, functional insulation
shall be designed according to the applicable im-
pulse voltage as determined by 7.3.7.1.4
7.3.7.4 Clearance distances P
7.3.7.4.1 Determination P
Table 13 defines the minimum clearance distances
required to provide functional, basic , or supplemen-
tary insulation
Clearance for use in altitudes above 2000 m shall be Not intended to use in altitudes N/A
calculated with correction factor according to Table above 2000 m.
A.2 of IEC 60664-1
For reinforced insulation, the value corresponding to P
the next higher impulse voltage, or 1.6 times the
temporary overvoltage, or 1.6 times the working
voltage shall be used, whichever results in the most
severe requirement
7.3.7.4.2 Electric field homogeneity Inhomogeneous electric field is N/A
considered for PCE
For homogeneous electric field and impulse voltage
is equal to or greater than 6000V for a circuit con-
nected directly to the mains or 4000V within a circuit,
the clearance may be reduced to the requirement by
Table F.2 Case B of IEC 60664-1. In this case, im-
pulse voltage test shall be performed on the clear-
ance

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

7.3.7.4.3 Clearance to conductive enclosures P


Clearance shall be measured following the defor-
mation test of 13.7 for conductive enclosures
7.3.7.5 Creeage distances P
7.3.7.5.1 General PV Maximum 550 Vd.c. system P
voltage is used for the RMS
Creepage distances shall be large enough to pre-
voltage across insulation
vent long-term degradation of the surface of solid in-
sulators.
For reinforced insulation, the value is doubled.
If less than clearance, it shall be increased to that
clearance
7.3.7.5.2 Voltage r.m.s. value of working voltage is used. In- P
terpolation is permitted
7.3.7.5.3 Materials P
7.3.7.6 Coating N/A
7.3.7.7 PWB spacings for functional insulation PWB rated V-0 and has a min- P
imum CTI of 175, short-circuit
test are considered
7.3.7.8 Solid insulation P
7.3.7.8.1 General Insulation tape, sheet, optical P
Isolator, isolation power supply
Material for solid insulation shall be able to withstand
and transformer.
mechanical, electrical, thermal and climatic stresses
in normal use and ageing during the expected life-
time. Compliance is evaluated by test and inspec-
tion.
7.3.7.8.2 Requirements for electrical withstand capability of P
solid insulation
7.3.7.8.2.1 Basic and supplementary, reinforced, and double in- P
sulation. Solid insulation shall withstand the impulse
voltage test 7.5.1 and voltage test 7.5.2.
In addition, if recurring peak working voltage across N/A
the insulation is greater than 700 V and voltage
stress on insulation is greater than 1kV/mm, double
and reinforced insulation shall withstand the partial
discharge test according to 7.5.3
7.3.7.8.2.2 Functional insulation N/A
7.3.7.8.3 Thin sheet or tape material P
7.3.7.8.3.1 General P
Insulation of thin sheet or tape less than 0,7 mm is
subject to this requirement
7.3.7.8.3.2 Material thickness not less than 0,2 mm P

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Basic or supplementary insulation shall consist of Communication transformer P


at least one layer of material, and shall meet the with isolation power supply
impulse and a.c. or d.c. voltage test requirements consider as double insulation.
of 7.3.7.8.2.1 for basic or supplementary insulation.
Double insulation shall consist of at least two layers P
of material. Each layer shall meet the impulse and
a.c. or d.c. voltage test requirements of 7.3.7.8.2.1
for basic insulation, and the partial discharge re-
quirements of 7.3.7.8.2.1. The two or more layers
together shall meet the impulse and a.c. or d.c.
voltage test requirements of 7.3.7.8.2.1 for double
insulation.
Reinforced insulation shall consist of a single layer Insulation sheet cover on dis- P
of material, which will meet the impulse, a.c. or d.c. play consider as reinforced in-
voltage, and partial discharge test requirements sulation.
7.3.7.8.2.1 for reinforced insulation.
7.3.7.8.3.3 Material thickness less than 0,2 mm P
Basic or supplementary insulation shall consist of P
at least one layer of material, and shall meet the
impulse and a.c. or d.c. voltage test requirements
of 7.3.7.8.2.1 for basic or supplementary insulation.
Double insulation shall consist of at least three lay- P
ers of material. Each layer shall meet the impulse
and a.c. or d.c. voltage test requirements of
7.3.7.8.2.1 for basic insulation any two layers to-
gether shall meet the impulse, a.c. or d.c. voltage,
and partial discharge test requirements of
7.3.7.8.2.1 for double insulation.
Reinforced insulation consisting of a single layer of N/A
material less than 0,2 mm thick is not permitted.
7.3.7.8.3.4 Compliance P
Component, sub-assembly, or material is checked
by applicable tests 7.5.1 to 7.5.3 according to
7.3.7.8.
7.3.7.8.4 Printed wiring boards (PWBs) P
7.3.7.8.4.1 General P
Insulation between conductor layers in double-
sided single-layer PWBs, multi-layer PWBs and
metal core PWBs, shall meet the requirements for
solid insulation in 7.3.7.8.
For the inner layers of multi-layer PWBs, the insula- P
tion between adjacent tracks on the same layer
shall be treated as either:
a creepage distance for pollution degree 1 and a P
clearance as in air (see Annex A, figure A.13); or
as solid insulation, in which case it shall meet the N/A
requirements of 7.3.7.8.
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

7.3.7.8.4.2 Use of coating materials N/A


A coating material used to provide a microenviron- N/A
ment or to provide functional, basic, supplementary
and reinforced insulation shall meet the requirement
as specified below.
Type 1 protection (as defined in IEC 60664-3) im- N/A
proves the microenvironment (Pollution Degree) of
the parts under protection. The clearance and
creepage distance of Table 13 and Table 14 for pol-
lution degree 1 apply under the protection. Between
two conductive parts, it is a requirement that one or
both conductive parts, together with all the spacing
between them, are covered by the protection.
Type 2 protection is considered to be similar to solid N/A
insulation. Under the protection, the requirements for
solid insulation specified in 7.3.7.8 are applicable
and spacings shall not be less than those specified
in Table 1 of IEC 60664-3. The requirements for
clearance and creepage in Table 13 and Table 14
do not apply. Between two conductive parts, it is a
requirement that both conductive parts, together with
the spacing between them, are covered by the pro-
tection so that no airgap exists between the protec-
tive material, the conductive parts and the printed
wiring boards.
The coating material used to provide Type 1 and N/A
Type 2 protection shall be designed to withstand the
stresses anticipated to occur during the expected
lifetime of the PCE.
Compliance is checked by a type test on representa- N/A
tive conducted according to IEC 60664-3
Clause 5.
For the Cold test (5.7.1), a temperature of 25 °C N/A
shall be used, and for the rapid change of tempera-
ture test (5.7.3): 25 °C to +125 °C, except that if the
temperature rating of the PCE is lower than 25 °C,
the low temperature limit for the test is reduced to
the rating of the PCE.
7.3.7.8.5 Wound components P
Varnish or enamel insulation of wires shall not be Varnish are not considered as P
used for basic, supplementary, double or reinforced insulation and voltage test per-
insulation. formed as routine test. See al-
so Cl.7.3.7.8.1 to Cl.7.3.7.8.2
Wound components shall meet the requirements of N/A
7.3.7.8.1 and 7.3.7.8.2.
The component itself shall pass the requirements P
given in 7.3.7.8.1 and 7.3.7.8.2. If the component
has reinforced or double insulation, the voltage test
in 7.5.2 shall be performed as a routine test.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

7.3.7.8.6 Potting materials N/A


A potting material may be used to provide solid in- Potting materials used in boost N/A
sulation or to act as a coating to protect against inductor and inverting inductor
pollution. If used as solid insulation, it shall comply are not intended to provide sol-
with the requirements of 7.3.7.8.1 and 7.3.7.8.2. If id insulation or to act a coating
used to protect against pollution, the requirements to protect against pollution.
for Type 1 protection in 7.3.7.8.4.2 apply.
7.3.7.9 Insulation requirements above 30 kHz P
Where voltages across insulation have fundamen- P
tal frequencies greater than 30 kHz, further consid-
erations apply. Requirements for this are provided
in IEC 60664-4, and the more severe of these and
the requirements of 7.3.7.1 to 7.3.7.8 shall be ap-
plied.
Annex G contains flow-charts for the determination P
of clearance and creepage distances under these
circumstances. For convenience, Tables 1 and 2 of
IEC 60664-4 are also included in Annex G.
7.3.8 Residual Current-operated protective (RCD) or Internal RCM is used accord- P
monitoring (RCM) device compatibility. ing to IEC 62109-2 test.
RCD and RCM are used to provide protection N/A
against insulation faults in some domestic and in-
dustrial installations, additional to that provided by
the installed equipment.
7.3.9 Protection against shock hazard due to stored en- P
ergy
7.3.9.1 Operator access area Accessible communication in- P
terface is DVC A
In the case of plugs, connectors, or similar devices P
that can be disconnected without the use of a tool,
the withdrawal of which results in the exposure of
conductors (e.g. pins), the discharge time to reduce
the voltage to DVC A (see 7.3.2.2) or, for capaci-
tors, to a stored charge level below the limits speci-
fied in 7.3.5.3.2, shall not exceed 1 s.
7.3.9.2 Service access areas P
Capacitors and other energy storage devices locat- P
ed behind panels that are removable for servicing,
installation, or disconnection shall present no risk of
electric shock or energy hazard from stored charge
after disconnection of the PCE.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Capacitors within a PCE shall be discharged to a 16.1s@60 V bus after discon- P


voltage less than DVC A (see 7.3.2.2), or an ener- necting DC side.
gy level below the limits specified in 7.3.5.3.2, with-
Inside capacitor discharge to
in 10 s after the removal of power from the PCE. If
DVC A and no energy hazard
this requirement is not achievable for functional or
level within 60 seconds.
other reasons, the warning symbol 21 of Annex C
and an indication of the discharge time shall be
placed in a clearly visible position on the enclosure,
the capacitor protective barrier, or at a point close
to the capacitor(s) concerned (depending on the
construction) (see 5.2.2.4).
For energy storage devices (such as batteries or ul- Warning symbol 21 of Annex P
tra capacitors) the intended function of which is to C is marked on PCE
maintain charge even with the PCE off and discon-
nected from external sources, a barrier or insulation
shall be provided so that unintentional contact with
hazardous live parts is prevented. The warning
symbol 21 of Annex C shall be placed in a clearly
visible position on or adjacent to the barrier or insu-
lation, where it will be seen before removal of the
barrier or insulation.
7.4 Protection against energy hazards P
7.4.1 Determination of hazardous energy level P
A hazardous energy level is considered to exist if Condition b is considered P
a) The voltage is 2 V or more, and power availa- N/A
ble after 60 s exceeds 240 VA.
b) The stored energy in a capacitor is at a voltage. See below Cl.7.4.3 P
U of 2 V or more, and the stored energy. E,
C=470 µF x 5=2350 µF
calculated from the following equation, exceeds
20J: U=130.5 Vpeak@20 J
E = 0,5 CU²
7.4.2 Operator Access Areas No energized parts accessible P
by user
Equipment shall be so designed that there is no P
risk of energy hazard in operator access areas from
accessible circuits.
7.4.3 Services Access Areas P
Energy storage devices located behind panels that P
are removable for servicing, installation or discon-
nection shall present no risk of electric energy haz-
ard from charge stored after disconnection of the
PCE.
Energy storage devices within a PCE shall be dis- Warning symbol 21 of Annex P
charged to an energy level less than 20 J, as in C is marked
7.4.1, within 10 s after the removal
7.5 Electrical tests related to shock hazard P
7.5.1 Impulse voltage test (type test) P

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

7.5.2 Voltage test (dielectric strength test) (type test) P


7.5.3 Partial discharge test (type test or sample test) N/A
7.5.4 Touch current measurement (type test) P
The touch current shall be measured if required by Measured touch current is 1.5 P
7.3.6.3.7 and shall not be greater than 3.5 mA a.c. mA. See clause 7.3.6.3.7
or 10 mA d.c. or special measures of protection as
given in 7.3.6.3.7 are required.
For type tests on PCE for which wet locations re- P
quirements apply according to 6.1, the humidity
pre-conditioning of 4.5 shall be performed immedi-
ately prior to the touch current test.
7.5.5 Equipment with multiple sources of supply N/A

8 PROTECTION AGAINST MECHANICAL HAZARDS P


8.1 General P
Operation shall not lead to a mechanical HAZARD P
in NORMAL CONDITION or SINGLE FAULT
CONDITION.
Edges, projections, corners, openings, guards,
handles and the like, that are accessible to the op-
erator shall be smooth and rounded so as not to
cause injury during normal use of the equipment.
Conformity is checked as specified in 8.2 to 8.6. P
8.2 Moving parts P
Moving parts shall not be able to crush, cut or is protected by P
pierce parts of the body of an OPERATOR likely to barriers.
contact them, nor severely pinch the OPERATOR's
skin. Hazardous moving parts of equipment, that is
moving parts which have the potential to cause in-
jury, shall be so arranged, enclosed or guarded as
to provide adequate protection against the risk of
personal injury.
8.2.1 Protection of service persons P
Protection shall be provided such that unintentional The fans stopped operating P
contact with hazardous moving parts is unlikely during servicing.
during servicing operations. If a guard over a haz-
ardous moving part may need to be removed for
servicing, the marking of symbol 15 of Table D-1
shall be applied on or near the guard.
8.3 Stability N/A
Equipment and assemblies of equipment not se- Wall mounted N/A
cured to the building structure before operation
shall be physically stable in NORMAL USE.
8.4 Provisions for lifting and carrying P

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

If carrying handles or grips are fitted to, or supplied P


with, the equipment, they shall be capable of with-
standing a force of four times the weight of the
equipment.
Equipment or parts having a mass of 18 kg or more About 22.3 kg(net weight) P
shall be provided with a means for lifting and carry-
ing or directions shall be given in the manufactur-
er s documentation.
8.5 Wall mounting P
Mounting brackets on equipment intended to be It is intended to be mounted P
mounted on a wall or ceiling shall withstand a force on concrete wall
of four times the weight of the equipment.
8.6 Expelled parts N/A
Equipment shall contain or limit the energy of parts N/A
that could cause a HAZARD if expelled in the event
of a fault.

9 PROTECTION AGAINST FIRE HAZARDS P


9.1 Resistance to fire P
This subclause specifies requirements intended to Components are witnessed at P
reduce the risk of ignition and the spread of flame, normal condition and abnor-
both within the equipment and to the outside, by mal tests are verified
the appropriate use of materials and components
and by suitable construction.
9.1.1 Reducing the risk of ignition and spread of flame P
For equipment or a portion of equipment, there are Method 1 used P
two alternative methods of providing protection
against ignition and spread of flame that could af-
fect materials, wiring, wound components and elec-
tronic components such as integrated circuits, tran-
sistors, thyristors, diodes, resistors and capacitors.
9.1.2 Conditions for a fire enclosure P
A FIRE ENCLOSURE is required for equipment or P
parts of equipment for which Method 2 is not fully
applied and complied with.
9.1.2.1 Parts requiring a fire enclosure P
Except where Method 2 is used, or as permitted in P
9.1.2.2, the following are considered to have a risk
of ignition and, therefore, require a FIRE
ENCLOSURE:
components in PRIMARY CIRCUITS P
components in SECONDARY CIRCUITS sup- P
plied by power sources which exceed the limits
for a LIMITED POWER SOURCE as specified
in 9.2;

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

components in SECONDARY CIRCUITS sup- N/A


plied by a LIMITED POWER SOURCE as
specified in 9.2, but not mounted on a material
of FLAMMABILITY CLASS V-1;
components within a power supply unit or as- P
sembly having a limited power output comply-
ing with the criteria for a LIMITED POWER
SOURCE as specified in 9.2, including overcur-
rent protective devices, limiting impedances,
regulating networks and wiring, up to the point
where the LIMITED POWER SOURCE output
criteria are met;
components having unenclosed arcing parts, Certified relay with fire enclo- N/A
such as open switch and relay contacts and sure
commutators, in a circuit at HAZARDOUS
VOLTAGE or at a HAZARDOUS ENERGY
LEVEL; and
insulated wiring, except as permitte in 9.1.2.2. PVC wire N/A
9.1.2.2 Parts not requiring a fire enclosure Fire enclosure used N/A
9.1.3 Materials requirements for protection against fire P
hazard
9.1.3.1 General P
ENCLOSURES, components and other parts shall P
be so constructed, or shall make use of such mate-
rials, that the propagation of fire is limited.
9.1.3.2 Materials for fire enclosures P
If an enclosure material is not classified as speci- 1. V-0 PCB as part of fire P
fied below, a test may be performed on the final enclosure.
enclosure or part of the enclosure, in which case 2. V-0 barrier used.
the material shall additionally be subjected to peri-
3. LPS for display circuit.
odic SAMPLE testing.
9.1.3.3 Materials for components and other parts inside fire At least V-1 material used in- P
enclosures side fire enclosure, PCB rated
V-0 and internal wire rated
VW-1
9.1.3.4 Materials for air filter assemblies N/A
9.1.4 Openings in fire enclosures P
9.1.4.1 General N/A
For equipment that is intended to be used or in- The equipment is intended to N/A
stalled in more than one orientation as specified in be used one orientation
the product documentation, the following require-
ments apply in each orientation.
These requirements are in addition to those in the N/A
following sections:
7.3.4, Protection against direct contact; N/A

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

7.4, Protection against energy hazards; N/A


13.5, Openings in enclosures N/A
9.1.4.2 Side openings treated as bottom openings N/A
9.1.4.3 Openings in the bottom of a fire enclosure P
The bottom of a FIRE ENCLOSURE or individual Metal bottom screens with P
barriers, shall provide protection against emission mesh opening less than 2mm.
of flaming or molten material under all internal
parts, including partially enclosed components or
assemblies, for which Method 2 of 9.1.1 has not
been fully applied and complied with.
9.1.4.4 Equipment for use in a CLOSED ELECTRICAL Not intend use at this area N/A
OPERATING AREA
The requirements of 9.1.4.3 do not apply to FIXED N/A
EQUIPMENT intended only for use in a CLOSED
ELECTRICAL OPERATING AREA and to be
mounted on a concrete floor or other non-
combustible surface. Such equipment shall be
marked as follows:
WARNING: FIRE HAZARD SUITABLE FOR N/A
MOUNTING ON CONCRETE OR OTHER NON-
COMBUSTIBLE SURFACE ONLY
9.1.4.5 Doors or covers in fire enclosures No door or cover operated by N/A
user.
9.1.4.6 Additional requirements for openings in transporta- N/A
ble equipment
9.2 LIMITED POWER SOURCES N/A
9.2.1 General N/A
9.2.2 Limited power source tests N/A
9.3 Short-circuit and overcurrent protection P
9.3.1 General P
The PCE shall not present a hazard, under short- P
circuit or overcurrent conditions at any port, includ-
ing phase-to-phase, phase-to-earth and phase-to-
neutral, and adequate information shall be provided
to allow proper selection of external wiring and ex-
ternal protective devices.
9.3.2 Protection against short-circuits and overcurrents P
shall be provided for all input circuits, and for output
circuits that do not comply with the requirements for
limited power sources in 9.2, except for circuits in
which no overcurrent hazard is presented by short-
circuits and overloads.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

9.3.3 Protective devices provided or specified shall have External circuit breaker shall P
adequate breaking capacity to interrupt the maxi- be used for AC side.
mum short circuit current specified for the port to
which they are connected. If protection that is pro-
vided integral to the PCE for an input port is not
rated for the short-circuit current of the circuit in
which it is used, the installation instructions shall
specify that an upstream protective device, rated
for the prospective short-circuit current of that port,
shall be used to provide backup protection.

10 PROTECTION AGAINST SONIC PRESSURE HAZARDS N/A


10.1 General N/A
The equipment shall provide protection against the N/A
effect of sonic pressure. Conformity tests are car-
ried out if the equipment is likely to cause such
HAZARDS.
10.2 Sonic pressure and Sound level N/A
10.2.1 Hazardous Noise Levels N/A

11 PROTECTION AGAINST LIQUID HAZARDS N/A


11.1 Liquid Containment, Pressure and Leakage No liquid containment system N/A
The liquid containment system components shall N/A
be compatible with the liquid to be used.
There shall be no leakage of liquid onto live parts N/A
as a result of:
a) Normal operation, including condensation; N/A
b) Servicing of the equipment; or N/A
c) Inadvertent loosening or detachment of hoses N/A
or other cooling system parts over time.
11.2 Fluid pressure and leakage N/A
11.2.1 Maximum pressure N/A
11.2.2 Leakage from parts N/A
11.2.3 Overpressure safety device N/A
11.3 Oil and grease N/A

12 CHEMICAL HAZARDS N/A


12.1 General N/A

13 PHYSICAL REQUIREMENTS P

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

13.1 Handles and manual controls P


Handles, knobs, grips, levers and the like shall be P
reliably fixed so that they will not work loose in
normal use, if this might result in a hazard. Sealing
compounds and the like, other than selfhardening
resins, shall not be used to prevent loosening. If
handles, knobs and the like are used to indicate the
position of switches or similar components, it shall
not be possible to fix them in a wrong position if this
might result in hazard.
13.1.1 Adjustable controls N/A
13.2 Securing of parts P
13.3 Provisions for external connections P
13.3.1 General P
13.3.2 Connection to an a.c. Mains supply AC connector P
13.3.2.1 General P
For safe and reliable connection to a MAINS sup- P
ply, equipment shall be provided with one of the fol-
lowing:
terminals or leads or a non-detachable power permanent connection to the P
supply cord for permanent connection to the supply.
supply; or
a non-detachable power supply cord for con- N/A
nection to the supply by means of a plug
an appliance inlet for connection of a detacha- N/A
ble power supply cord; or
a mains plug that is part of direct plug-in N/A
equipment as in 13.3.8
13.3.2.2 Permanently connected equipment P
13.3.2.3 Appliance inlets N/A
13.3.2.4 Power supply cord N/A
13.3.2.5 Cord anchorages and strain relief N/A
For equipment with a non-detachable power supply N/A
cord, a cord anchorage shall be supplied such that:
the connecting points of the cord conductors N/A
are relieved from strain; and
the outer covering of the cord is protected from N/A
abrasion.
13.3.2.6 Protection against mechanical damage P
13.3.3 Wiring terminals for connection of external conduc- P
tors
13.3.3.1 Wiring terminals P

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

13.3.3.2 Screw terminals P


13.3.3.3 Wiring terminal sizes P
13.3.3.4 Wiring terminal design P
13.3.3.5 Grouping of wiring terminals P
13.3.3.6 Stranded wire N/A
13.3.4 Supply wiring space N/A
13.3.5 Wire bending space for wires 10 mm² and greater N/A
13.3.6 Disconnection from supply sources Installation manual instruct the P
disconnect device shall be
provided before connecting
AC mains, PV array and bat-
tery.
13.3.7 Connectors, plugs and sockets No such connectors, plugs N/A
and sockets employed
13.3.8 Direct plug-in equipment N/A
13.4 Internal wiring and connections P
13.4.1 General P
13.4.2 Routing Internal wire is routed to avoid P
sharp edge and overheat
13.4.3 Colour coding Green-yellow wire used as P
protective bonding only
13.4.4 Splices and connections P
13.4.5 Interconnections between parts of the PCE No such interconnections N/A
13.5 Openings in enclosures P
13.5.1 Top and side openings P
Openings in the top and sides of ENCLOSURES P
shall be so located or constructed that it is unlikely
that objects will enter the openings and create haz-
ards by contacting bare conductive parts.
13.6 Polymeric Materials P
13.6.1 General P
13.6.1.1 Thermal index or capability P
13.6.2 Polymers serving as enclosures or barriers pre- Polymers serving as barriers P
venting access to hazards preventing access to hazards
13.6.2.1 Stress relief test P
13.6.3 Polymers serving as solid insulation N/A
13.6.3.1 Resistance to arcing Arcing parts are enclosed in- N/A
side certified relay
13.6.4 UV resistance N/A

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Polymeric parts of an OUTDOOR ENCLOSURE N/A


required for compliance with this standard shall be
sufficiently resistance to degradation by ultra-violet
(UV) radiation
13.7 Mechanical resistance to deflection, impact, or drop P
13.7.1 General P
13.7.2 250-N deflection test for metal enclosures P
13.7.3 7-J impact test for polymeric enclosures P
13.7.4 Drop test N/A
13.8 Thickness requirements for metal enclosures P
13.8.1 General P
13.8.2 Cast metal N/A
13.8.3 Sheet metal P

14 COMPONENTS P
14.1 General P
Where safety is involved, components shall be P
used in accordance with their specified RATINGS
unless a specific exception is made. They shall
conform to one of the following:
1. applicable safety requirements of a relevant P
IEC standard. Conformity with other require-
ments of the component standard is not re-
quired. If necessary for the application, compo-
nents shall be subjected to the test of this
standard, except that it is not necessary to car-
ry out identical or equivalent tests already per-
formed to check conformity with the component
standard;
2. the requirements of this standard and, where P
necessary for the application, any additional
applicable safety requirements of the relevant
IEC component standard;
3. if there is no relevant IEC standard, the re- P
quirements of this standard;
4. applicable safety requirements of a non-IEC P
standard which are at least as high as those of
the applicable IEC standard, provided that the
component has been approved to the non-IEC
standard by a recognized testing authority.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Components such as optocouplers, capacitors, P


transformers, and relays connected across basic,
supplemental, reinforced, or double insulation shall
comply with the requirements applicable for the
grade of insulation being bridged, and if not previ-
ously certified to the applicable component safety
standard shall be subjected to the voltage test of
7.5.2 as routine test.
14.2 Motor Over temperature Protection N/A
Motors which, when stopped or prevented from N/A
starting (see 4.4.4.3), would present an electric
shock HAZARD, a temperature HAZARD, or a fire
HAZARD, shall be protected by an over-
temperature or thermal protection device meeting
the requirements of 14.3.
14.3 Overtemperature protection devices N/A
14.4 Fuse holders N/A
14.5 MAINS voltage selecting devices N/A
14.6 Printed circuit boards P
Printed circuit boards shall be made of material V-0 P
with a flammability classification of V-1 of IEC
60707 or better.
This requirement does not apply to thin-film flexible N/A
printed circuit boards that contain only circuits
powered from limited power sources meeting the
requirements of 9.2.
Conformity of the flammability RATING is checked N/A
by inspection of data on the materials. Alternatively,
conformity is checked by performing the V-1 tests
specified in IEC 60707 on three samples of the rel-
evant parts.
14.7 Circuits or components used as transient overvoltage limiting devices N/A
If control of transient overvoltage is employed in the N/A
equipment, any overvoltage limiting component or
circuit shall be tested with the applicable impulse
withstand voltage of Table 7-10 using the test
method from 7.5.1 except 10 positive and 10 nega-
tive impulses are to be applied and may be spaced
up to 1 min apart.
14.8 Batteries N/A
Equipment containing batteries shall be designed No battery used. N/A
to reduce the risk of fire, explosion and chemical
leaks under normal conditions and after a single
fault in the equipment including a fault in circuitry
within the equipment battery pack.
14.8.1 Battery Enclosure Ventilation N/A

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

14.8.1.1 Ventilation requirements N/A


14.8.1.2 Ventilation testing N/A
14.8.1.3 Ventilation instructions N/A
14.8.2 Battery Mounting N/A
Compliance is verified by the application of the N/A
force to the battery s mounting surface. The test
force is to be increased gradually so as to reach
the required value in 5 to 10 s, and is to be main-
tained at that value for 1 min. A nonmetallic rack or
tray shall be tested at the highest normal condition
operating temperature.
14.8.3 Electrolyte spillage N/A
Battery trays and cabinets shall have an electro- N/A
lyte-resistant coating.
The ENCLOSURE or compartment housing a N/A
VENTED BATTERY shall be constructed so that
spillage or leakage of the electrolyte from one bat-
tery will be contained within the ENCLOSURE and
be prevented from:
a) reaching the PCE outer surfaces that can be N/A
contacted by the USER
b) contaminating adjacent electrical components N/A
or materials; and
c) bridging required electrical distances N/A
14.8.4 Battery Connections N/A
Reverse battery connection of the terminals shall N/A
be prevented if reverse connection could result in a
hazard within the meaning of this Standard
14.8.5 Battery maintenance instructions N/A
The information and instructions listed in 5.3.4.1 N/A
shall be included in the operator manual for equip-
ment in which battery maintenance is performed by
the operator, or in the service manual if battery
maintenance is to be performed by service person-
nel only.
14.8.6 Battery accessibility and maintainability N/A
Battery terminals and connectors shall be accessi- N/A
ble for maintenance with the correct TOOLS. Bat-
teries with liquid electrolyte, requiring maintained
shall be so located that the battery cell caps are
accessible for electrolyte tests and readjusting of
electrolyte levels.
15 Software and firmware performing safety functions P

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Annex A Measurement of clearances and creepage distanc- P


es (see 7.3.7.4 and 7.3.7.5)

Annex B Programmable Equipment P


B.1 Software or firmware that perform safety critical P
functions
B.1.1 Firmware or software that performs a critical safety P
function/s, the failure of which can result in a risk of
fire, electric shock or other hazard as specified by
this standard, shall be evaluated by one of the fol-
lowing means.
a) All software or firmware limits or controls shall be P
disabled before the test to evaluate the hardware
circuitry during the abnormal test condition related
to the safety function.
b) Protective controls employing software or firm- N/A
ware to perform their function(s), shall be so con-
structed that they comply with IEC 60730-1 Annex
H to address the risks identified in B.2.1.
B.2 Evaluation of controls employing software P

Annex C Symbols to be used in equipment markings P

Annex D Test Probes for Determining Access P


Annex E RCDs N/A
Annex F Altitude correction for clearances N/A

Annex G Clearance and creepage distance determination for P


frequencies greater than 30 kHz

Annex H Measuring Instrument for Touch Current Measure- P


ments
H.1 Measuring instrument P
H.2 Alternative measuring instrument N/A

Annex I Examples of Protection, Insulation, and Overvolt- P


age Category Requirements for PCE

Annex J Ultraviolet light conditioning test N/A

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

4.7 #1 TABLE: mains supply electrical data in normal condition P


Model PV Grid
U (V) d.c. I (A)d.c. P (kW) d.c. U (V) a.c. I (A) a.c. P (kW) a.c.
EA5KHD 120.4 25.02 3.012 208.1 13.49 2.798
249.9 19.00 4.749 208.8 21.49 4.480
359.1 13.16 4.725 208.8 21.49 4.480
449.6 10.48 4.711 208.8 21.51 4.481
529.0 8.92 4.718 208.8 21.53 4.487
120.7 24.94 3.010 231.2 11.69 2.699
249.8 20.96 5.235 231.3 21.46 4.958
359.0 14.51 5.208 231.3 21.46 4.959
450.0 11.54 5.192 231.3 21.47 4.959
530.0 9.81 5.198 231.3 21.49 4.961
120.8 24.91 3.010 254.1 10.73 2.724
249.8 20.88 5.216 254.2 19.51 4.954
360.0 14.41 5.188 254.2 19.52 4.955
449.0 11.52 5.171 254.0 19.50 4.957
530.0 9.78 5.181 254.2 19.56 4.961
Remark: Grid-Tied mode, PV to grid, no load.

4.7 #2 TABLE: mains supply electrical data in normal condition P


Model PV Grid Load
U (V) I (A)d.c. P (kW) U (V) I (A) a.c. P (kW) U (V) I (A) a.c. P (kW)
d.c. d.c. a.c. a.c. a.c. a.c.
EA5KHD 120.1 25.09 3.013 207.5 3.91 0.792 207.4 9.68 2.008
250.0 18.97 4.742 208.0 11.82 2.448 208.1 9.70 2.018
360.2 13.10 4.718 208.0 11.82 2.449 208.1 9.70 2.018
449.8 10.45 4.699 208.0 11.82 2.448 208.1 9.70 2.018
529.6 8.88 4.703 208.0 11.83 2.449 208.1 9.69 2.017
120.4 25.02 3.011 230.7 3.05 0.696 230.6 8.78 2.025
249.9 20.95 5.234 231.1 12.65 2.913 231.3 8.81 2.037
360.1 14.46 5.208 231.1 12.65 2.915 231.3 8.81 2.037
449.1 11.56 5.190 231.1 12.66 2.915 231.3 8.80 2.036
530.0 9.76 5.170 231.1 12.67 2.916 231.3 8.80 2.036

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

120.6 25.02 3.017 253.7 2.80 0.704 253.7 7.95 2.016


249.9 20.87 5.214 254.1 11.57 2.931 254.3 7.95 2.021
360.1 14.40 5.187 254.1 11.58 2.932 254.3 7.95 2.021
449.1 11.50 5.167 254.1 11.58 2.931 254.3 7.95 2.020
530.0 9.75 5.166 254.1 11.59 2.933 254.3 7.95 2.020
Remark: Grid-Tied mode, PV to grid and load.

4.7 #3 TABLE: mains supply electrical data in normal condition P


Model PV Load
U (V) d.c. I (A)d.c. P (kW) d.c. U (V) a.c. I (A) a.c. P (kW) a.c.
EA5KHD 119.5 18.10 2.162 230.2 8.79 2.024
249.7 8.41 2.101 230.2 8.66 1.994
359.6 5.88 2.113 230.2 8.76 2.016
449.6 4.68 2.106 230.3 8.76 2.017
529.6 3.99 2.112 230.4 8.76 2.018
Remark: Off-Grid mode, PV to load.

4.7 #4 TABLE: mains supply electrical data in normal condition P


Model PV Battery
U (V) d.c. I (A)d.c. P (kW) d.c. U (V) d.c. I (A)d.c. P (kW) d.c.
EA5KHD 119.9 23.52 2.819 56.3 45.53 2.561
251.1 11.21 2.815 56.3 45.60 2.566
360.0 7.79 2.805 56.3 45.61 2.566
448.6 6.25 2.803 56.2 45.65 2.568
528.5 5.22 2.757 56.2 45.71 2.569
Remark: Off-Grid mode, PV to Battery.

4.7 #5 TABLE: mains supply electrical data in normal condition P


Model Battery Load
U (V) d.c. I (A)d.c. P (kW) d.c. U (V) a.c. I (A) a.c. P (kW) a.c.
EA5KHD 49.8 43.71 2.176 230.2 8.78 2.021
Remark: Off-Grid mode, Battery to load.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

4.7 #6 TABLE: mains supply electrical data in normal condition P


Model Battery Grid
U (V) d.c. I (A)d.c. P (kW) d.c. U (V) a.c. I (A) a.c. P (kW) a.c.
EA5KHD 50.2 53.24 2.672 230.7 10.72 2.473
Remark: Battery to Grid(House load).

4.7 #7 TABLE: mains supply electrical data in normal condition P


Model PV Load Battery
U (V) I (A)d.c. P (kW) U (V) I (A) a.c. P (kW) U (V) I (A)d.c. P (kW)
d.c. d.c. a.c. a.c. d.c. d.c.
EA5KHD 119.6 25.54 3.054 230.3 8.76 2.016 56.4 15.16 0.855
250.9 19.47 4.885 230.2 8.75 2.015 56.3 45.75 2.574
360.2 14.02 4.794 230.2 8.75 2.015 56.3 45.68 2.560
451.0 10.77 4.859 230.3 8.76 2.018 56.2 45.35 2.550
528.4 9.17 4.844 230.3 8.76 2.017 56.3 45.37 2.554
Remark: PV to load and battery.

4.7 #8 TABLE: mains supply electrical data in normal condition P


Model PV Grid Battery
U (V) I (A)d.c. P (kW) U (V) I (A) a.c. P (kW) U (V) I (A)d.c. P (kW)
d.c. d.c. a.c. a.c. d.c. d.c.
EA5KHD 120.9 24.99 3.020 207.4 0.98 0.203 56.2 45.45 2.556
249.7 21.84 5.456 207.6 12.95 2.682 56.2 45.55 2.562
360.0 15.22 5.480 207.7 13.21 2.737 56.3 45.53 2.561
451.4 12.13 5.476 207.7 13.25 2.745 56.2 45.56 2.562
529.3 10.37 5.486 207.7 13.35 2.766 56.2 45.56 2.562
121.3 24.95 3.025 230.4 1.04 0.239 56.2 45.56 2.563
249.7 21.93 5.477 230.6 11.36 2.612 56.2 45.55 2.562
359.9 15.18 5.464 230.6 11.44 2.630 56.2 45.57 2.563
451.3 12.13 5.473 230.6 11.40 2.621 56.2 45.57 2.563
528.9 10.34 5.468 230.6 11.54 2.651 56.2 45.58 2.563
120.8 24.95 3.013 253.0 0.87 0.205 56.2 45.57 2.563
248.7 22.01 5.475 253.6 10.31 2.607 56.2 45.59 2.563
360.0 15.22 5.477 253.6 10.35 2.617 56.2 45.58 2.563
450.3 12.21 5.497 253.6 10.47 2.625 56.2 45.59 2.562

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

530.4 10.36 5.496 253.6 10.48 2.649 56.2 45.61 2.564


Remark: PV to grid and battery.

4.7 #9 TABLE: mains supply electrical data in normal condition P


Model Grid Load
U (V) a.c. I (A) a.c. P (kW) a.c. U (V) a.c. I (A) a.c. P (kW) a.c.
EA5KHD 229.7 8.96 2.056 229.1 8.84 2.025
Remark: Grid to load.

4.7 #10 TABLE: mains supply electrical data in normal condition P


Model PV Battery Load
U (V) I (A)d.c. P (kW) U (V) I (A)d.c. P (kW) U (V) I (A) a.c. P (kW)
d.c. d.c. d.c. d.c. a.c. a.c.
EA5KHD 122.2 8.07 0.986 50.9 23.41 1.192 230.2 8.77 2.019
249.7 3.98 0.995 48.5 23.68 1.148 230.2 8.76 2.016
360.8 2.76 0.997 48.5 23.47 1.138 230.2 8.76 2.016
399.2 2.33 0.929 51.9 23.53 1.221 230.2 8.75 2.015
444.5 2.46 1.096 57.1 18.14 1.036 230.3 8.76 2.018
Remark: PV and battery to load.

4.3 Thermal testing (by thermocouples) P


Model EA5KHD
No. Ambient Humidity Test PV Grid Load Battery
(RH)
(°C) time V A V A V A V A
W W W W
d.c. d.c. a.c. a.c. a.c. a.c. d.c. d.c.
2h59
(1) 40 50% 250 22.0 5494 207 21.6 4481 -- -- -- 55.8 11.6 649
min
3h4
(2) 40 50% 249 22.0 5493 253 19.7 4990 -- -- -- 56.0 3.9 220
min
2h16
(3) 40 50% 450 12.2 5484 207 21.6 4482 -- -- -- 55.9 12.5 698
min
3h38
(4) 40 50% 450 12.2 5489 254 19.6 4970 -- -- -- 56.1 4.3 242
min
2h31
(5) 40 50% 250 19.9 4982 -- -- -- 230 8.9 2046 55.9 44.6 2497
min
3h7
(6) 40 50% 450 10.9 4903 -- -- -- 230 8.9 2044 55.9 44.7 2496
min

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

2h5
(7) 40 50% -- -- -- 230 10.8 2489 -- -- -- 51.2 54.0 2768
min
Remark:
(1) - (4) : Grid-Tied mode, PV to grid and battery;
(5) - (6) : Off-Grid mode, PV to load and battery;
(7) : Off-Grid mode, Battery to grid (house load).
Temperature (°C) of Measured temperature (°C) Permit-
part at: ted
No. (1) (2) (3) (4) (5) (6) (7)
(°C)
1 PV1 input terminal
44.0 44.3 41.9 41.9 42.8 41.2 40.2 105
block (internal)
2 PV1 input internal
46.3 46.4 43.2 42.9 44.3 42.9 40.3 105
wire
3 DC switch discon-
46.1 45.8 44.0 43.6 42.9 42.8 40.7 70
nector
4 Varistor R31 on PV-
44.8 44.8 41.9 41.8 42.7 43.6 40.2 105
inverter board
5 C21 on PV-inverter
45.7 45.7 42.8 42.7 43.5 44.8 40.5 105
board
6 L3 on PV-inverter
61.5 61.1 47.3 46.9 55.2 51.1 40.7 90
board
7 C35 on PV-inverter
52.6 52.2 47.6 47.2 47.9 46.3 41.2 125
board
8 CT1 on PV-inverter
50.1 49.7 46.8 46.9 46.1 46.2 41.8 85
board
9 Boost1 inductive coil 81.1 79.5 57.4 55.8 69.5 66.9 42.4 110
10 Boost1 inductive core 81.8 80.4 56.9 55.4 70.5 65.4 42.1 --
11 Boost1 IGBT Q7 on
64.7 64.5 50.3 50.5 58.8 54.1 42.3 130
PV-inverter board
12 D1 on PV-inverter
65.9 65.5 54.4 54.0 59.2 53.8 42.2 130
board
13 Insulation paper be-
tween Q7 and heat
60.2 59.8 49.0 48.8 54.6 53.4 41.9 150
sink on PV-inverter
board
14 C15 on PV-inverter
47.3 47.1 44.7 44.1 44.1 47.1 41.1 105
board
15 Q1 on PV-inverter
75.0 73.5 73.7 71.8 53.7 52.5 54.9 130
board
16 Q5 on PV-inverter
75.2 72.4 74.1 71.0 53.3 52.2 54.4 130
board
17 D3 on PV-inverter
72.9 70.1 72.1 68.9 52.9 51.9 53.3 130
board
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

18 C86 on PV-inverter
53.6 52.7 53.3 52.0 45.6 47.5 45.9 85
board
19 Fan1 (Under the pow-
45.1 44.9 44.5 44.1 42.7 44.3 42.3 70
er wire of Fan1)
20 Inverter inductive coil 90.0 81.2 90.0 80.4 50.3 49.6 51.9 110
21 Inverter inductive core 86.5 78.2 86.9 77.8 49.6 49.0 51.0 --
22 C118 on PV-inverter
45.9 45.4 46.3 46.7 41.6 43.3 42.0 105
board
23 CT4 on PV-inverter
51.2 50.4 51.1 49.9 45.0 45.5 45.8 105
board
24 L16 on PV-inverter
52.0 50.6 52.1 50.3 43.8 45.4 44.5 110
board
25 Relay RLY6 on PV-
56.8 55.3 56.6 55.1 41.9 43.7 48.5 60
inverter board
26 CT3 on PV-inverter
47.0 46.4 46.9 47.2 40.3 41.2 42.4 105
board
27 C79 on PV-inverter
42.9 42.9 42.9 42.4 39.7 39.8 40.8 110
board
28 Varistor R109 on PV-
44.4 44.1 44.3 43.5 39.7 40.1 41.0 125
inverter board
29 Fuse F1 on PV-
52.0 50.2 52.2 50.0 39.7 39.7 42.6 130
inverter board
30 Grid input internal
46.3 45.7 46.5 45.2 39.8 39.8 41.3 105
wire
31 Grid input terminal
43.9 43.6 43.9 43.2 39.8 39.6 40.6 105
block (internal)
32 CT5 on PV-inverter
43.5 43.6 43.4 43.4 47.7 47.8 42.1 110
board
33 L17 on PV-inverter
43.0 43.2 43.1 43.0 47.7 47.8 42.0 90
board
34 Grid Auxiliary Power
40.2 40.8 40.5 40.4 40.4 40.4 40.0 105
wire
35 L1 on DC-DC board 44.9 44.8 44.4 44.2 44.4 45.6 46.1 110
36 C291 on DC-DC
46.6 46.5 46.1 45.8 46.6 51.6 44.0 85
board
37 Q54 on DC-DC board 50.6 49.3 50.0 48.7 60.3 60.0 47.0 130
38 L29 on DC-DC board 49.7 48.3 49.4 48.9 64.6 66.9 52.0 110
39 C306 on DC-DC
54.0 51.7 53.3 51.0 70.8 70.0 54.3 105
board
40 T12 transformer coil
60.9 57.9 59.3 56.6 86.9 85.5 53.8 110
on DC-DC board

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

41 T12 transformer core


52.5 51.3 52.1 51.9 61.4 69.9 51.0 --
on DC-DC board
42 L26 on DC-DC board 53.7 51.2 52.6 50.3 75.5 74.4 55.4 110
43 L28 on DC-DC board 45.6 43.8 45.4 45.2 66.3 66.0 64.5 110
44 C296 on DC-DC
46.8 44.1 46.3 45.8 73.4 72.5 67.9 105
board
45 T3 transformer coil on
43.2 42.6 45.9 44.9 49.0 49.0 88.3 110
DC-DC board
46 T3 transformer core
43.1 42.5 47.5 46.5 49.1 49.1 87.6 --
on DC-DC board
47 D16 on DC-DC board 42.1 41.8 41.5 41.3 44.1 45.3 65.1 130
48 C33 on DC-DC board 43.6 43.0 43.5 43.3 49.8 50.5 66.1 85
49 C31 on DC-DC board 41.9 41.6 41.5 41.2 44.4 46.7 59.2 105
50 Fuse F2 on DC-DC
45.0 43.6 44.4 43.3 65.0 66.3 79.6 130
board
51 Relay RLY1 on DC-
44.4 44.2 44.4 43.9 46.4 49.7 49.4 70
DC board
52 BAT internal wire 43.0 41.4 42.6 41.0 64.9 65.3 83.1 90
53 BAT terminal block
42.2 40.8 41.4 40.5 54.8 56.3 66.8 120
(internal)
54 Q8 on DC-DC board 42.5 41.6 42.2 42.1 47.8 51.2 54.3 130
55 D94 on DC-DC board 48.3 44.2 47.8 44.2 69.9 69.3 52.9 130
56 Q49 on DC-DC board 52.8 52.7 52.5 52.4 51.9 51.9 51.0 130
57 T9 transformer coil on
50.1 50.0 49.6 49.5 49.3 51.8 48.7 110
DC-DC board
58 T9 transformer core
51.3 51.2 51.0 50.9 50.7 52.6 49.9 --
on DC-DC board
59 Grid Auxiliary Power
42.3 42.4 42.1 42.0 42.1 42.7 41.8 75
terminal block
60 T10 on DC-DC board 41.3 41.5 41.1 41.2 40.7 41.0 41.1 110
61 T11 on DC-DC board 43.2 43.3 43.1 43.1 42.9 43.3 43.8 110
62 D88 on DC-DC board 44.2 45.7 43.8 45.2 40.5 40.5 44.4 130
63 U25 on DC-DC board 43.1 43.6 42.8 43.1 41.9 42.1 43.3 110
64 U26 on DC-DC board 46.0 46.1 46.6 46.7 46.7 46.7 48.3 110
65 U27 on DC-DC board 48.0 47.9 47.9 48.1 47.3 47.5 47.0 110
66 PCB near BAT 41.1 40.7 40.8 40.3 46.1 47.6 52.3 130
67 PCB near Bus circuit 48.9 48.4 48.3 47.6 45.6 45.4 43.9 130
68 The front of unit 41.6 41.7 41.6 41.1 40.1 39.7 40.0 70
69 The flank of unit 45.6 45.1 45.0 44.4 40.9 40.3 40.3 70

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

70 The top of unit 43.5 43.7 43.4 43.0 41.3 41.0 40.9 70
71 The mounting surfac-
46.8 46.6 45.6 46.1 42.4 43.3 41.3 90
es of unit
72 LCD 39.3 40.0 41.1 39.8 39.7 39.3 39.5 70
73 Test ambient temper-
39.3 39.6 41.0 39.2 39.7 39.4 39.5 Ref.
ature 1
Supplementary information:

4.4 TABLE: fault condition tests P


Ambient temperature( C) : 25

40%

component Input Output Test Observation


No. fault
No. (V) (V, kW) time
Clause 4.4.4.1 Component fault tests
Below component single fault applied on PV_inverter board
The fault applied during the unit op-
eration. After applied the fault, the
Q7 (pin 2 to 230 Va.c.,
1 S-C 360 Vd.c. 5min unit shutdown immediately and LCD
Pin 3) 5kW
age. No hazard. Recoverable.
The fault applied during the unit op-
Q1 (pin C tp 230 Va.c., eration. After applied the fault, the
2 S-C 360 Vd.c. 5min
pin E) 5kW unit operated as normal. No dam-
age. No hazard. Recoverable.
The fault applied during the unit op-
eration. After applied the fault, the
230 Va.c., unit shutdown immediately and LCD
3 R93 S-C 360 Vd.c. 5min
5kW display ala
No damage. No hazard. Recovera-
ble.
The fault applied during the unit op-
230 Va.c., eration. After applied the fault, the
4 R201 O-C 360 Vd.c. 5min
5kW unit operated as normal. No dam-
age. No hazard. Recoverable.
The fault applied during the unit op-
eration. After applied the fault, the
unit shutdown immediately and LCD
230 Va.c.,
5 C114 S-C 360 Vd.c. 5min
5kW
cuit breaker overcurrent protection.
No hazard. Unrecoverable.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

The fault applied during the unit op-


230 Va.c., eration. After applied the fault, the
6 R22 O-C 360 Vd.c. 5min
5kW unit operated as normal. No dam-
age. No hazard. Recoverable.
The fault applied during the unit op-
eration. After applied the fault, the
230 Va.c., grid disconnected immediately and
7 R126 O-C 360 Vd.c. 5min
5kW

age. No hazard. Recoverable.


The fault applied during the unit op-
eration, the unit operated as normal
after applied the fault. When the unit
230 Va.c.,
8 RLY7 S-C 360 Vd.c. 5min shutdown and restarted, the unit
5kW
could not restart and LCD display

damage. No hazard. Recoverable.


The fault applied during the unit op-
eration, the unit operated as normal
after applied the fault. When the unit
230 Va.c.,
9 RLY9 S-C 360 Vd.c. 5min shutdown and restarted, the unit
5kW
could not restart and LCD display

damage. No hazard. Recoverable.


The fault applied during the unit op-
eration, the unit operated as normal
CT5(pin 1 to 230 Va.c., after applied the fault. But the grid
10 S-C 360 Vd.c. 5min
pin 4) 5kW output power which displayed on
LCD was wrong. No damage. No
hazard. Recoverable.
The fault applied during the unit op-
eration, the unit operated as normal
CT5(pin 2 to 230Va.c., after applied the fault. But the grid
11 S-C 360 Vd.c. 5min
pin 3) 5kW output power which displayed on
LCD was wrong. No damage. No
hazard. Recoverable.
The fault applied during the unit op-
eration. After applied the fault, the
230 Va.c., grid disconnected immediately and
12 C79 S-C 360 Vd.c. 5min
5kW
F1 was damaged. No hazard. Unre-
coverable.
The fault applied during the unit op-
eration, the unit operated as normal
after applied the fault. When the unit
RLY3 (pin 4 230 Va.c., shutdown and restarted, the unit
13 S-C 360 Vd.c. 5min
to pin 5) 5kW could not restart and LCD display

coverable.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

The fault applied during the unit op-


eration, the unit operated as normal
after applied the fault. When the unit
RLY11 (pin 230 Va.c., shutdown and restarted, the unit
14 S-C 360 Vd.c. 5min
4 to pin 5) 5kW could not restart and LCD display

coverable.
Below component single fault applied on DC-DC board
The fault applied during the unit op-
eration. After applied the fault, the
230 Va.c.,
15 R346 S-C 360 Vd.c. 5min unit shutdown immediately. ZD15,
5kW
C205, C246 and U15 were dam-
aged. No hazard. Unrecoverable.
The fault applied during the unit op-
eration. After applied the fault, the
Q49 (pin D 230 Va.c.,
16 S-C 360 Vd.c. 5min unit shutdown immediately. R301
to pin S) 5kW
and R300 were damaged. No haz-
ard. Unrecoverable.
The fault applied during the unit op-
230 Va.c., eration. After applied the fault, the
17 R300 S-C 360 Vd.c. 5min
5kW unit shutdown immediately. No
damage. No hazard. Recoverable.
The fault applied during the unit op-
eration. After applied the fault, the
U28 (pin 1 230 Va.c., unit shutdown immediately and LCD
18 S-C 360 Vd.c. 5min
to pin 3) 5kW

Recoverable.
The fault applied during the unit op-
U27 (pin 1 230 Va.c., eration. After applied the fault, the
19 S-C 360 Vd.c. 5min
to pin 2) 5kW unit shutdown immediately. No
damage. No hazard. Recoverable.
The fault applied during the unit op-
U27 (pin 3 230 Va.c., eration. After applied the fault, the
20 S-C 360 Vd.c. 5min
to pin 4) 5kW unit shutdown immediately. No
damage. No hazard. Recoverable.
The fault applied during the unit op-
230 Va.c., eration. After applied the fault, the
21 U27 (pin 1) O-C 360 Vd.c. 5min
5kW unit shutdown immediately. No
damage. No hazard. Recoverable.
The fault applied during the unit op-
PV: eration, the unit operated as normal
after applied the fault. When the unit
D88 (pin 1 360 Vd.c. 230 Va.c., shutdown and restarted, the unit
22 S-C 5min
to pin 3) Grid: 5kW / 2kW could restart. When the unit was at
bypass mode, the LCD blacked.
230 Va.c. R366 was damaged. No hazard.
Unrecoverable.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

The fault applied during the unit op-


PV: eration, the unit operated as normal
after applied the fault. When the unit
360 Vd.c. 230 Va.c., shutdown and restarted, the unit
23 C258 S-C 5min
Grid: 5kW / 2kW could restart. When the unit was at
bypass mode, the LCD blacked.
230 Va.c. R366 was damaged. No hazard.
Unrecoverable.
The fault applied during the unit op-
230 Va.c., eration. After applied the fault, the
24 R368 S-C 360 Vd.c. 5min
5kW unit operated as normal. No dam-
age. No hazard. Recoverable.
The fault applied during the unit op-
PV: eration, the unit operated as normal
360 Vd.c. after applied the fault. When the unit
U25 (pin 1 230 Va.c.,
25 S-C 5min shutdown and restarted, the unit
to pin 2) Grid: 5kW / 2kW
could restart. When the unit was at
230 Va.c. bypass mode, the LCD blacked. No
damage. No hazard. Recoverable.
The fault applied during the unit op-
PV: eration, the unit operated as normal
360 Vd.c. after applied the fault. When the unit
U25 (pin 3 230 Va.c.,
26 S-C 5min shutdown and restarted, the unit
to pin 4) Grid: 5kW / 2kW
could restart. When the unit was at
230 Va.c. bypass mode, the LCD blacked. No
damage. No hazard. Recoverable.
The fault applied during the unit op-
PV: eration, the unit operated as normal
360 Vd.c. after applied the fault. When the unit
230 Va.c.,
27 U25 pin 1 O-C 5min shutdown and restarted, the unit
Grid: 5kW / 2kW
could restart. When the unit was at
230 Va.c. bypass mode, the LCD blacked. No
damage. No hazard. Recoverable.
The fault applied during the unit op-
PV: eration, the unit operated as normal
360 Vd.c. after applied the fault. When the unit
U16 (pin 2 230 Va.c.,
28 S-C 5min shutdown and restarted, the unit
to pin 3) Grid: 5kW / 2kW
could restart. When the unit was at
230 Va.c. bypass mode, the LCD blacked. No
damage. No hazard. Recoverable.
The fault applied during the unit op-
PV: eration, the unit operated as normal
after applied the fault. When the unit
360 Vd.c. 230 Va.c., shutdown and restarted, the unit
29 D67 S-C 5min
Grid: 5kW / 2kW could restart. When the unit was at
bypass mode, the LCD blacked.
230 Va.c. C263 and C267 were damaged. No
hazard. Unrecoverable.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

The fault applied during the unit op-


PV: eration, the unit operated as normal
360 Vd.c. 230 Va.c., after applied the fault. When the unit
Q51 (pin D
30 S-C 5kW / 5min shutdown and restarted, the unit
to pin S) BAT: 2.5kW could restart. When the unit was
51.2 Vd.c. supplied by the battery, the LCD
blacked. R379 and R378 were
PV:
The fault applied during the unit op-
360 Vd.c. 230 Va.c.,
eration. After applied the fault, the
31 R379 S-C 5kW / 5min
BAT: unit operated as normal. No dam-
2.5kW
age. No hazard. Recoverable.
51.2 Vd.c.
The fault applied during the unit op-
eration, the unit operated with ab-
PV: normal noise after applied the fault.
360 Vd.c. 230 Va.c., When the unit shutdown and re-
32 R377 S-C 5kW / 5min started, the unit could restart. When
BAT: 2.5kW the unit was supplied by the battery,
51.2 Vd.c. the LCD blacked. U14 and ZD17
were damaged. No hazard. Unre-
coverable.
The fault applied during the unit op-
PV: eration. After applied the fault, the
360 Vd.c. 230 Va.c., unit shutdown immediately and LCD
33 C270 S-C 5kW / 5min
BAT: 2.5kW was damaged. The fuse on the bat-
51.2 Vd.c. tery circuit was damaged. No haz-
ard. Unrecoverable.
The fault applied during the unit op-
PV: eration, the unit operated as normal
after applied the fault. When the unit
360 Vd.c. 230 Va.c.,
shutdown and restarted, the unit
34 D68 S-C 5kW / 5min
BAT: could restart. When the unit was
2.5kW
supplied by the battery, the LCD
51.2 Vd.c.. blacked. C264 was damaged. No
hazard. Unrecoverable.
The fault applied during the unit op-
PV: eration, the unit operated as normal
after applied the fault. When the unit
360 Vd.c. 230 Va.c.,
U26 (pin 1 shutdown and restarted, the unit
35 S-C 5kW / 5min
to pin 2) BAT: could restart. When the unit was on-
2.5kW
ly supplied by the battery, the LCD
51.2 Vd.c. blacked. No damage. No hazard.
Recoverable.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

The fault applied during the unit op-


PV: eration, the unit operated as normal
after applied the fault. When the unit
360 Vd.c. 230 Va.c.,
U26 (pin 3 shutdown and restarted, the unit
36 S-C 5kW / 5min
to pin 4) BAT: could restart. When the unit was on-
2.5kW
ly supplied by the battery, the LCD
51.2 Vd.c. blacked. No damage. No hazard.
Recoverable.
The fault applied during the unit op-
PV: eration, the unit operated as normal
after applied the fault. When the unit
360 Vd.c. 230 Va.c.,
shutdown and restarted, the unit
37 U26 pin 1 S-C 5kW / 5min
BAT: could restart. When the unit was on-
2.5kW
ly supplied by the battery, the LCD
51.2 Vd.c. blacked. No damage. No hazard.
Recoverable.
The fault applied during the unit op-
eration. After applied the fault, the
230 Va.c., unit shutdown immediately and LCD
38 D14 S-C 51.2 Vd.c. 5min
2.5kW DC BUS LOW
VOLT
ard. Unrecoverable.
The fault applied during the unit op-
eration. After applied the fault, the
230 Va.c.,
39 R231 S-C 51.2 Vd.c. 5min
2.5kW The fuses (F1, F2, F3) on the bat-
tery circuit were damaged. No haz-
ard. Unrecoverable.
The fault applied during the unit op-
eration. After applied the fault, the
RLY1 (pin 1 230 Va.c., unit operated as normal. When the
40 S-C 51.2 Vd.c. 5min
to pin 2) 2.5kW unit shutdown and restarted, the
unit could restart. No damage. No
hazard. Recoverable.
The fault applied during the unit op-
eration. After applied the fault, the
Q5 (pin D to 230 Va.c.,
41 S-C 51.2 Vd.c. 5min
pin S) 2.5kW The fuses (F1, F2, F3) on the bat-
tery circuit were damaged. No haz-
ard. Unrecoverable.
The fault applied during the unit op-
eration. After applied the fault, the
Q54 (pin D 51.2 Vd.c. unit shutdown immediately and LCD
42 S-C 360 Vd.c. 5min
to pin S) 2.5kW disp

Recoverable.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

The fault applied during the unit op-


eration. After applied the fault, the
D94 (pin 1 51.2 Vd.c.
43 S-C 360 Vd.c. 5min
to pin 2) 2.5kW The fuses (F1, F2, F3) on the bat-
tery circuit were damaged. No haz-
ard. Unrecoverable.
The fault applied during the unit op-
eration. After applied the fault, the
51.2 Vd.c. unit shutdown immediately and LCD
44 R415 S-C 360 Vd.c. 5min
2.5kW Battery Charging
Over Current Hard
hazard. Recoverable.
Below component single fault applied on control board
The fault applied during the unit op-
eration. After applied the fault, the
U29 (pin 2 230 Va.c., unit operated as normal and LCD
45 S-C 360 Vd.c. 5min
to pin 3) 5kW
No damage. No hazard. Recovera-
ble.
The fault applied during the unit op-
eration. After applied the fault, the
U7 (pin 12 230 Va.c.,
46 S-C 360 Vd.c. 5min
to pin 13) 5kW
7 was damaged.
No hazard. Unrecoverable.
The fault applied during the unit op-
eration. After applied the fault, the
unit shutdown immediately and LCD
U20 (pin 2 230 Va.c.,
47 S-C 360 Vd.c. 5min shutdown
to pin 3) 5kW
and restarted, the unit could not re-
start and LCD display alarmed

age. No hazard. Recoverable.


Clause 4.4.4.4 Transformer short circuit tests
The fault applied during the unit op-
eration. After applied the fault, the
unit operated as normal. When the
T9 (pin 8 to 230 Va.c.,
48 S-C 360 Vd.c. 5min unit shutdown and restarted, the
pin 9) 5kW
unit could restart but the LCD
blacked. No damage. No hazard.
Recoverable.
The fault applied during the unit op-
eration. After applied the fault, the
unit operated as normal. When the
T9 (pin 11 to 230 Va.c.,
49 S-C 360 Vd.c. 5min unit shutdown and restarted, the
pin 12) 5kW
unit could not restart and the LCD
blacked. No damage. No hazard.
Recoverable.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

The fault applied during the unit op-


eration. After applied the fault, the
unit operated as normal. When the
T9 (pin 13 to 230 Va.c.,
50 S-C 360 Vd.c. 5min unit shutdown and restarted, the
pin 14) 5kW
unit could not restart but the LCD
blacked. No damage. No hazard.
Recoverable.
PV: The fault applied during the unit op-
eration. After applied the fault, the
T10 (pin 6 to 360 Vd.c. 230 Va.c., unit operated as normal. When the
51 S-C 5min
pin 9) Grid 5kW / 2kW PV input was removed, the LCD
blacked after a few seconds. No
230 Va.c., damage. No hazard. Recoverable.
PV: The fault applied during the unit op-
eration. After applied the fault, the
T10 (pin 6 to 360 Vd.c. 230 Va.c., unit operated as normal. When the
52 S-C 5min
pin 7) Grid 5kW / 2kW PV input was removed, the LCD
blacked after a few seconds. No
230 Va.c., damage. No hazard. Recoverable.
The fault applied during the unit op-
eration. After applied the fault, the
T11 (pin 6 to 230 Va.c., unit operated as normal. When the
53 S-C 51.2 Vd.c. 5min
pin 9) 2.5kW grid was disconnected, the LCD
blacked after a few seconds. No
damage. No hazard. Recoverable.
The fault applied during the unit op-
eration. After applied the fault, the
T11 (pin 6 to 230 Va.c., unit operated as normal. When the
54 S-C 51.2 Vd.c. 5min
pin 7) 2.5kW grid was disconnected, the LCD
blacked after a few seconds. No
damage. No hazard. Recoverable.
The fault applied during the unit op-
eration. After applied the fault, the
T2 (pin 11 to 230 Va.c., unit shutdown immediately and LCD
55 S-C 51.2 Vd.c. 5min
pin 19) 2.5kW display alar

Recoverable.
The fault applied during the unit op-
eration. After applied the fault, the
T3 (pin 11 to 230 Va.c., unit shutdown immediately and LCD
56 S-C 51.2 Vd.c. 5min
pin 19) 2.5kW OW

Recoverable.
Grid:
230 Va.c.,
The fault applied during the unit op-
5kW
T12 (pin 3 to eration. After applied the fault, the
57 S-C 360 Vd.c. 5min
pin 4) BAT: unit could not charge the battery. No
damage. No hazard. Recoverable.
51.2 Vd.c.
2.5kW
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Grid:
230 Va.c.,
The fault applied during the unit op-
5kW
T12 (pin 4 to eration. After applied the fault, the
58 S-C 360 Vd.c. 5min
pin 5) BAT: unit could not charge the battery. No
damage. No hazard. Recoverable.
51.2 Vd.c.
2.5kW
Grid:
230 Va.c.,
The fault applied during the unit op-
5kW
T8 (pin N1 eration. After applied the fault, the
59 S-C 360 Vd.c. 5min
to pin N2) BAT: unit could not charge the battery. No
damage. No hazard. Recoverable.
51.2 Vd.c.
2.5kW
Grid:
230 Va.c.,
The fault applied during the unit op-
5kW
T8 (pin N4 eration. After applied the fault, the
60 S-C 360 Vd.c. 5min
to pin N5) BAT: unit could not charge the battery. No
damage. No hazard. Recoverable.
51.2 Vd.c.
2.5kW
Clause 4.4.4.7 Output overload
The fault applied during the unit op-
eration, After applied the fault, the
230 Va.c.,
61 AC output O-L 360 Vd.c. 5min unit operated as normal. The AC
5kW
output without overload function. No
damage. No hazard. Recoverable.
The fault applied during the unit op-
eration.
(1) When the unit overload 110%
lasted 10 mins, the LCD display

(2) When the unit overload 125%


lasted 1 min, the LCD display

230 Va.c.,
62 Load output O-L 360 Vd.c. --
2kW (3) When the unit overload 150%
lasted 10 s, the LCD display

(4) When the unit overload 175%


lasted 200 ms, the LCD display

Then the unit shutdown. No dam-


age. No hazard. Recoverable.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

The fault applied during the unit op-


eration, After applied the fault, the
51.2 Vd.c.,
63 BAT output O-L 360 Vd.c. 5min unit operated as normal. The battery
2.5kW
output without overload function. No
damage. No hazard. Recoverable.
Clause 4.4.4.8 Cooling system failure
The fault applied during the unit op-
Fan 1 on eration. After applied the fault, the
230 Va.c.,
64 PV_inverter Blocked 360 Vd.c. 5min unit shutdown immediately and LCD
5kW
board
damage. No hazard. Recoverable.
The fault applied during the unit op-
Fan 2 on eration. After applied the fault, the
230 Va.c.,
65 PV_inverter Blocked 360 Vd.c. 5min unit shutdown immediately and LCD
5kW
board
damage. No hazard. Recoverable.
The fault applied during the unit op-
Fan 1 on eration. After applied the fault, the
230 Va.c.,
66 DC-DC Blocked 360 Vd.c. 5min unit shutdown immediately and LCD
5kW
board
damage. No hazard. Recoverable.
The fault applied during the unit op-
Fan 2 on eration. After applied the fault, the
230 Va.c.,
67 DC-DC Blocked 360 Vd.c. 5min unit shutdown immediately and LCD
5kW
board
damage. No hazard. Recoverable.
The fault applied during the unit op-
eration. After applied the fault, the
Q15 (pin 1 230 Va.c., unit shutdown immediately and LCD
68 S-C 360 Vd.c. 5min
to pin 5) 5kW

hazard. Recoverable.
The fault applied during the unit op-
eration. After applied the fault, the
Q39 (pin 1 230 Va.c., unit shutdown immediately and LCD
69 S-C 360 Vd.c. 5min
to pin 5) 5kW

hazard. Recoverable.
Clause 4.4.4.11 Reverse d.c. connections
The fault applied before the unit op-
eration. After applied the fault, the
230Va.c.,
70 R 360 Vd.c. 5min unit could not start and LCD display
- 5kW
age. No hazard. Recoverable.
The fault applied before the unit op-
eration. After applied the fault, the
230Va.c.,
71 R 51.2 Vd.c. 5min unit could not start and LCD display
- 2.5kW
damage. No hazard. Recoverable.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Clause 4.4.4.13 Mis-wiring with incorrect phase sequence or polarity


The fault applied before the unit op-
AC output L 230 Va.c., eration. After applied the fault, the
72 Mis-wiring 360 Vd.c. 5min
and N 5kW unit operated as normal. No dam-
age. No hazard. Recoverable.
The fault applied before the unit op-
AC output L 230 Va.c., eration. After applied the fault, the
73 Mis-wiring 360 Vd.c. 5min
and PE 5kW unit could not connect to grid. No
damage. No hazard. Recoverable.
The fault applied before the unit op-
AC output Not conne- 230 Va.c., eration. After applied the fault, the
74 360 Vd.c. 5min
PE cted 5kW unit operating as normal. No haz-
ard. No damage. Recoverable.
supplementary information:
(1) S-C: short circuit, O-C: open circuit, O-L: overload, R: reversed.
(2) PV simulator used for apply these fault condition test.

7.3.7 TABLE: Creepage distances and clearances for appliances P


clearance cl and creepage dis- System OVC required cl cl (mm) required dcr
tance dcr at/of: voltage (mm) cr (mm) (mm)
(V)
PV to PE(BI) DC: 550 II (PV) 3.0 3.4 3.0 3.4
AC: 230 III (AC)
PV1 input circuit to signal collec- DC: 550 II (PV) 3.0 4.0 3.0 4.0
tion circuit (BI) AC: 230 III (AC)
PV2 input circuit to signal collec- DC: 550 II (PV) 3.0 3.3 3.0 3.3
tion circuit (BI) AC: 230 III (AC)
Between PV input circuit and DC: 550 3.0 1.07*5=5.4 3.0 1.07*5=5.4
II (PV)
signal collection circuit through
AC: 230 III (AC)
high impedance resistance (BI)
Between PV input circuit and PE DC: 550 3.0 1.07*5=5.4 3.0 1.07*5=5.4
II (PV)
through high impedance re-
AC: 230 III (AC)
sistance (BI)
Between Bus circuit to PE DC: 550 3.0 1.07*5=5.4 3.0 1.07*5=5.4
II (PV)
through high impedance re-
AC: 230 III (AC)
sistance (BI)
Between grid/load circuit to signal DC: 550 3.0 1.07*4=4.3 3.0 1.07*4=4.3
II (PV)
collection circuit through high im-
AC: 230 III (AC)
pedance resistance (BI)
DVC C circuit to signal collection DC: 550 II (PV) 3.0 3.1 3.0 3.1
circuit (CT3 to R118) (BI) AC: 230 III (AC)
DVC C circuit to signal collection DC: 550 II (PV) 3.0 3.5 3.0 3.5
circuit (CT1) (BI) AC: 230 III (AC)
DVC C circuit to signal collection DC: 550 II (PV) 3.0 3.5 3.0 3.5
circuit (CT2) (BI) AC: 230 III (AC)
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

DVC C circuit to signal collection DC: 550 II (PV) 3.0 3.7 3.0 3.7
circuit (CT3) (BI) AC: 230 III (AC)
DVC C circuit to signal collection DC: 550 II (PV) 3.0 3.2 3.0 3.2
circuit (CT4) (BI) AC: 230 III (AC)
DVC C circuit to signal collection DC: 550 II (PV) 3.0 3.0 3.0 3.0
circuit CT5) (BI) AC: 230 III (AC)
DVC C circuit to signal collection DC: 550 II (PV) 3.0 3.3 3.0 3.3
circuit (PCB under RLY6) (BI) AC: 230 III (AC)
DVC C circuit to signal collection DC: 550 II (PV) 3.0 3.2 3.0 3.2
circuit (RLY7) (BI) AC: 230 III (AC)
DVC C circuit to signal collection DC: 550 II (PV) 3.0 3.6 3.0 3.6
circuit (RLY8) (BI) AC: 230 III (AC)
DVC C circuit to signal collection DC: 550 II (PV) 3.0 3.5 3.0 3.5
circuit (RLY9) (BI) AC: 230 III (AC)
DVC C circuit to signal collection DC: 550 II (PV) 3.0 5.4 3.0 5.4
circuit (RLY10) (BI) AC: 230 III (AC)
Between primary and secondary DC: 550 II (PV) 3.0 4.8(3.5 Inner 3.0 4.8(3.5 Inner
of T2 on the DC-DC board (BI) AC: 230 III (AC) layer) layer)
Between primary and secondary DC: 550 II (PV) 3.0 4.8(3.5 Inner 3.0 4.8(3.5 Inner
of T3 on the DC-DC board (BI) AC: 230 III (AC) layer) layer)
Between primary and secondary DC: 550 II (PV) 3.0 5.2(3.5 Inner 3.0 5.2(3.5 Inner
of T12 on the DC-DC board (BI) AC: 230 III (AC) layer) layer)
Between primary and secondary DC: 550 II (PV) 3.0 6.0 3.0 6.0
of T11 on the DC-DC board (BI) AC: 230 III (AC)
Between core and secondary of DC: 550 II (PV) 3.0 3.6 3.0 3.6
T11 on the DC-DC board (BI) AC: 230 III (AC)
Hazardous parts (R370\C249) to DC: 550 II (PV) 3.0 3.4 3.0 3.4
signal collection circuit track (BI) AC: 230 III (AC)
J33(DVC A circuit) to AC input DC: 550 5.5 5.9 5.5 5.9
II (PV)
connector on the DC-DC board
AC: 230 III (AC)
(J31) (RI)
Between primary and secondary DC: 550 3.0 6.0 3.0 6.0
II (PV)
(Pin 11-14) of T9 on the DC-DC
AC: 230 III (AC)
board (BI)
Between secondary (Pin 11-14) DC: 550 3.0 6.0 3.0 6.0
II (PV)
and secondary (Pin 8-9) of T9
AC: 230 III (AC)
on the DC-DC board (SI)
Between primary and secondary DC: 550 5.5 8.0 5.5 8.0
II (PV)
(Pin 8-9) of T9 on the DC-DC
AC: 230 III (AC)
board (RI)
Between core and secondary DC: 550 3.0 4.2 3.0 4.2
II (PV)
(Pin 11-14) of T9 on the DC-DC
AC: 230 III (AC)
board (BI)

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Between core and secondary DC: 550 5.5 8.3 5.5 8.3
II (PV)
(Pin 8-9) of T9 on the DC-DC
AC: 230 III (AC)
board (RI)
Between primary and secondary DC: 550 II (PV) 3.0 7.4 3.0 7.4
of T8 on the DC-DC board (BI) AC: 230 III (AC)
Between primary and secondary DC: 550 II (PV) 3.0 6.2 3.0 6.2
of U25 on the DC-DC board (BI) AC: 230 III (AC)
Between primary and secondary DC: 550 II (PV) 3.0 6.2 3.0 6.2
of U26 on the DC-DC board (BI) AC: 230 III (AC)
Between primary and secondary DC: 550 II (PV) 3.0 6.2 3.0 6.2
of U27 on the DC-DC board (BI) AC: 230 III (AC)
SELV parts(TP4) to hazardous DC: 550 II (PV) 5.5 6.2 5.5 6.2
parts(C284) (RI) AC: 230 III (AC)
PCB track of SELV parts to haz- DC: 550 II (PV) 5.5 6.0 5.5 6.0
ardous parts (RI) AC: 230 III (AC)
PCB track of SELV parts to con- DC: 550 II (PV) 3.0 3.5 3.0 3.5
trol circuit parts (SI) AC: 230 III (AC)
Ground screw H2 to Hazardous DC: 550 II (PV) 3.0 6.6 3.0 6.6
parts on DC-DC board (BI) AC: 230 III (AC)
Ground screw H5 to Hazardous DC: 550 II (PV) 3.0 3.6 3.0 4.9
parts on DC-DC board (BI) AC: 230 III (AC)
Ground screw H7 to Hazardous DC: 550 II (PV) 3.0 6.3 3.0 6.3
parts on DC-DC board (BI) AC: 230 III (AC)
Ground screw H6 to Hazardous DC: 550 II (PV) 3.0 5.7 3.0 5.7
parts on DC-DC board (BI) AC: 230 III (AC)
Ground screw H14 to Hazardous DC: 550 II (PV) 3.0 6.8 3.0 6.8
parts on DC-DC board (BI) AC: 230 III (AC)
Ground screw H8 to Hazardous DC: 550 II (PV) 3.0 6.7 3.0 6.7
parts on DC-DC board (BI) AC: 230 III (AC)
Ground screw H6 to Hazardous DC: 550 II (PV) 3.0 5.3 3.0 5.3
parts on PV board (BI) AC: 230 III (AC)
Ground screw H9 to Hazardous DC: 550 II (PV) 3.0 3.1 3.0 3.1
parts on PV board (BI) AC: 230 III (AC)
Ground screw H10 to Hazardous DC: 550 II (PV) 3.0 3.6 3.0 3.6
parts on PV board (BI) AC: 230 III (AC)
Ground screw H7 to Hazardous DC: 550 II (PV) 3.0 3.1 3.0 3.1
parts on PV board (BI) AC: 230 III (AC)
Ground screw H2 to Hazardous DC: 550 II (PV) 3.0 3.1 3.0 3.1
parts on PV board (BI) AC: 230 III (AC)
Ground screw H1 to Hazardous DC: 550 II (PV) 3.0 3.4 3.0 3.4
parts on PV board (BI) AC: 230 III (AC)
Ground screw H8 to Hazardous DC: 550 II (PV) 3.0 3.2 3.0 3.2
parts on PV board (BI) AC: 230 III (AC)

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Between primary and secondary DC: 550 II (PV) 5.5 5.9 5.5 5.9
of T2 on the display board (RI) AC: 230 III (AC)
Between primary and secondary DC: 550 II (PV) 5.5 6.3 5.5 6.3
of U21 on the display board (RI) AC: 230 III (AC)
Between primary and secondary DC: 550 3.0 3.1 3.0 3.1
II (PV)
of T1 on the IGBT driver board
AC: 230 III (AC)
(BI)
Between primary and secondary DC: 550 3.0 4.0 3.0 6.0
II (PV)
of U1 on the IGBT driver board
AC: 230 III (AC)
(BI)
Supplementary information:
(1) For AC mains circuit, nominal voltage is 230 V and overvoltage category is OVC III, impulse voltage
correspond to mains circuit is 4000 V;
(2) For PV circuit, system voltage is 550 V and overvoltage category is OVC II, impulse voltage corre-
spond to PV circuit is 2945 V;
(3) For battery circuit, is evaluated with basic insulation from AC mains and PV circuit, impulse voltage is
2500 V;

7.3.7.8.3.2 to 7.3.7.8.3.3 TABLE: distance through insulation measurement P

U r.m.s. required di di
distance through insulation di at/of: test voltage (V)
(V) (mm) (mm)
Plastic isolation sheet between upper enclosure 550Vd.c. 1500Vr.m.s. -- 0.25
and PCBA (BI)
230Va.c.
Plastic isolation sheet between PCBA and lower 550Vd.c. 1500Vr.m.s. -- 0.25
enclosure (BI)
230Va.c.
Insulation cover sheet on display (RI) 550Vd.c. 3000Vr.m.s. -- 0.50
230Va.c.
Two layers Insulation tape (RI) 550Vd.c. 3000Vr.m.s. -- Certified
230Va.c.
Supplementary information:

7.5 TABLE: electric strength measurements, impulse voltage test and partial dis- P
charge test
impulse with- partial discharge
test voltage
test voltage applied between: stand voltage extinction voltage result
(V)
(V) (V)
PV terminal and BAT terminal, relay
2120Vd.c. 4000Vpeak N/A Pass
contact short-circuit (BI)
PV terminal and metal enclosure (BI) 2120Vd.c. 4000Vpeak N/A Pass
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

Grid/AC load terminal and BAT termi-


2120Vd.c. 4000Vpeak N/A Pass
nal, relay contact short-circuit (BI)
Grid/AC load terminal and metal en-
2120Vd.c. 4000Vpeak N/A Pass
closure, relay contact short-circuit (BI)
BAT terminal and metal enclosure, re-
2120Vd.c. 4000Vpeak N/A Pass
lay contact short-circuit (BI)
PV terminal and all communication
4240Vd.c 6000Vpeak N/A Pass
port (RI)
PV terminal and accessible plastic en-
4240Vd.c 6000Vpeak N/A Pass
closure of the display (RI)
Grid/AC load terminal and all commu-
nication port, relay contact short-circuit 4240Vd.c 6000Vpeak N/A Pass
(RI)
Grid/AC load terminal and accessible
plastic enclosure of the display, relay 4240Vd.c 6000Vpeak N/A Pass
contact short-circuit (RI)
BAT terminal and all communication
4240Vd.c 6000Vpeak N/A Pass
port, relay contact short-circuit (RI)
BAT terminal and accessible plastic
enclosure of the display, relay contact 4240Vd.c 6000Vpeak N/A Pass
short-circuit (RI)
Supplementary information: Circuit breakers, contactors are closed before apply these tests.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
611mm*547mm*15 IEC 62109-1 Tested with
EAST Group Co., 0mm, thickness:
Metal enclosure Ltd. Sheet metal IEC 62109-2 appliance
1.65mm.
IEC 62477-1

Plastic enclo- 86 mm * 211 mm, IEC 62109-1 Tested with


-- -- thickness: 2 mm.
sure IEC 62109-2 appliance

Material of plas- CHI MEI UL 746B


PA-765A(+) ABS, V-0, 130 °C UL E56070
tic enclosure CORPORATION UL 94
HUIZHOU
TRUSTWIN UL 746B
V-0, 130 °C,
PCB ELECTRONICS TW-8 UL 94 E340729
CTI>175
DEVELOPMENT UL 746C
CO LTD
SHENZHEN 600 Vd.c., 65 Ad.c., UL 1059
PV1 input CONECTION 20 AWG - 6 AWG,
DRTB10 -NR1 105 °C, V-0 UL 486E UL E304128
terminal block ELECTRONICS
CO., LTD. UL 60947-1

SHENZHEN 600 Vd.c., 65 Ad.c., UL 1059


Grid input CONECTION 20 AWG - 6 AWG,
ELECTRONICS DRTB10 -NR1 105 °C, V-0 UL 486E UL E304128
terminal block
CO. LTD. UL 60947-1

SHENZHEN 600 Vd.c., 65 Ad.c., UL 1059


Load input CONECTION 20 AWG - 6 AWG,
ELECTRONICS DRTB10 -NR1 105 °C, V-0 UL 486E UL E304128
terminal block
CO. LTD. UL 60947-1
SHENZHEN 600 Vd.c., 100 UL 1059
BAT terminal CONNECTION Ad.c., 16 AWG - 2
DRTB35-RST UL 486E UL E304128
block ELECTRONIC CO AWG, -40 °C to
LTD 120 °C, V-0 UL 60947-1
3004-V0(rr),
Material of all TORAY Polyamide 66, V-0, UL 746B
CM3004- UL E41797
terminal block INDUSTRIES INC 105 °C UL 94
V0(rr)
PV1/GRID ZHONGLI SCIENCE
11 AWG, VW-1,
input internal & TECHNOLOGY 1015 UL 758 UL E156525
105 °C, 600 Va.c.
wire GROUP CO LTD
ZHONGLI SCIENCE
Load input 11 AWG, VW-1,
& TECHNOLOGY 1015 UL 758 UL E156525
internal wire 105 °C, 600 Va.c.
GROUP CO LTD
GUANGDONG
6 AWG, VW-1,
BAT internal HICHAIN
1032 90 °C, 1000 UL 758 UL E304337
wire ELECTRICITY CO
Va.c./1200 Vd.c.
LTD
ZHONGLI SCIENCE
Internal earthing & TECHNOLOGY 10 AWG, VW-1,
1015 UL 758 UL E156525
wire 105 °C, 600 Va.c.
GROUP CO LTD

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
1500V, 1000VDC, IEC 60947-3
DC switch IMO PRECISION UL E362605
SI25-PM64-4 25A, -50 °C to VDE0660
disconnector CONTROLS LTD TUV
70 °C UL508i
SHENZHEN CLICK IEC 62109-1 Tested with
Boost inductor ELECTRONICS LC184-747 67Ts, 1.2mH, Class
B IEC 62109-2 appliance
CO.,LTD.
UL 746B
KINGBOARD V-0, 130 °C,
- PCB FR-4 UL 94 E123995
LAMINATES LTD CTI>175
UL 746C
Tested with
- Core Various Various --
Iron silicon appliance
TAI-I ELECTRIC
- Wire WIRE & CABLE CO -- 155 °C, MW 5-C UL 1446 UL E85640
LTD
GUANGDONG
JINGDA REA
- Alternative SPECIAL -- 155 °C, MW 5-C UL 1446 UL E223994
ENAMLED WIRE
CO.,LTD.
DONGGUAN
- Epoxy EATTO V-0, 130 °C UL 746C UL E218090
E-500 (XX)
ELECTRONIC
MATERIAL CO LTD
CHANGYUAN CB-HFT*, CB-
300Vrms, 125 °C,
- Tube ELECTRONICS HFT(XY)*, UL 224 UL E180908
VW-1
GROUP CO LTD CYG-MT*
HANG CHEUNG
- Varnish COATINGS 8562* 155 °C UL 1446 UL E200154
(HUIYANG) LTD
- Alternative KYOCERA
TVB2180T*(a) 155 °C UL 1446 UL E83702
CORPORATION
3M COMPANY
ELECTRICAL
- Margin tape 44 D (a) 130 °C UL 510A UL E17385
MARKETS DIV
(EMD)
SHENZHEN CLICK 1.6 x 2P x
IEC 62109-1 Tested with
Inverter inductor TECHNOLOGY LC250-293 82Ts, 800µH
CO.LTD IEC 62109-2 appliance
Class B
TAI-I ELECTRIC
- Wire WIRE & CABLE CO -- 155 °C, MW 5-C UL 1446 UL E85640
LTD
GUANGDONG
JINGDA REA
- Alternative SPECIAL -- 155 °C, MW 5-C UL 1446 UL E223994
ENAMELED WIRE
CO LTD

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
DONGGUAN
- Epoxy EATTO V-0, 130 °C UL 746C UL E218090
E-500 (XX)
ELECTRONIC
MATERIAL CO LTD
CHANGYUAN CB-HFT*, CB-
300Vrms, 125 °C,
- Tube ELECTRONICS HFT(XY)*, UL 224 UL E180908
VW-1
GROUP CO LTD CYG-MT*
HANG CHEUNG
- Varnish COATINGS 8562* 155 °C UL 1446 UL E200154
(HUIYANG) LTD
KYOCERA
- Alternative TVB2180T*(a) 155 °C UL 1446 UL E83702
CORPORATION
JINGJIANG YAHUA
PRESSURE
- Tape PF* (d)(g) 180 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
3M COMPANY
ELECTRICAL
- Margin tape 44 D (a) 130 °C UL 510A UL E17385
MARKETS DIV
(EMD)
IEC 62109-1 Tested with
- Core Various Various
IEC 62109-2 appliance
DONGGUAN UL 507 UL E187236
MGT8012UB- 12Vd.c., 0.66A, -
Fan PROTECHNIC
R25 10 °C to 70 °C TUV
ELECTRIC CO LTD
Plastic isolation
sheet between EAST Group Co., 500 mm * 600 mm, IEC 62109-1 Tested with
Various
upper and lower Ltd. thickness: 0.25mm IEC 62109-2 Appliance
enclosure
Material of SICHUAN
plastic isolation UL 746C
DONGFANG
sheet between DF6025 V-0, 105 °C UL 94 UL E199019
INSULATING
upper and lower MATERIAL CO LTD UL 746B
enclosure
Plastic isolation
sheet between 415mm * 482mm, IEC 62109-1 Tested with
Various Various
PCBA and low- thickness: 0.25mm IEC 62109-2 Appliance
er enclosure
Material of plas-
tic isolation FORMEX, DIV OF UL 746C
FORMEX GK-
sheet between ILLINOIS TOOL V-0, 115 °C UL 94 UL E121855
(a)(b)(f1)
PCBA and low- WORKS INC UL 746B
er enclosure
SHENZHEN
TOPWAY LM256160BF IEC 62109-1 Tested with
LCD display -20 °C to 70 °C
TECHNOLOGY W IEC 62109-2 appliance
CO., LTD.

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
Material of SICHUAN UL 746C
plastic isolation LONGHUA FILM CO PC-1860A-
V-0, 80 °C UL 94 UL E254551
cover sheeton ECO
LTD UL 746B
LCD display
GUANGDONG
Grid Auxiliary HICHAIN 28AWG 4/0AWG,
1015 UL 758 UL E304337
Power wire ELECTRICITY CO 105 °C, 600Va.c.
LTD
--Below list is the critical components on the PV_INVERTER board
THINKING UL 1449
Varistor (R31, ELECTRONIC 820Vdc, 6500A, - UL E314979
R3, R21, R49, TVR20821 IEC/EN
INDUSTRIAL CO 40 °C to 105 °C VDE: 005944
R50, R53) LTD 61051-1
FUTUNG IEC 60384-1, Tested with
X capacitor PMK1K0PS22 1000Vdc, 0.22uF, -
ELECTRONICS IEC 60384-
(C21, C42) J4K0 40 °C to 105 °C appliance
CO., LTD. 16
SHENZHEN
IEC 60384-1, Tested with
X capacitor (C9, SURONG CBB21
630V, 680nF, -
IEC 60384-
C41) CAPACITORS 40 °C to 85 °C appliance
16
CO ,.LTD

SHENZHEN CLICK 20Ts, 2.0mH IEC 62109-1 Tested with


Inductor (L3, ELECTRONICS LC31-060
L17,L6) CO.,LTD. IEC 62109-2 appliance
20Ts, 2.0mH
PACIFIC ELECTRIC
WIRE & CABLE
- Wire PEW/U 130 °C UL1446 UL E201757
(SHENZHEN) CO
LTD
JOHN C DOLPH
- Varnish BC-359 130 °C UL1446 UL E317429
CO.,LTD
SHAW HUOW
- Epoxy ENTERPRISE CO 9001A/9001B V-0, 90 °C UL 746C UL E105888
LTD
SHENZHEN N1: 2.0 mH
IEC 62109-1 Tested with
Alternative YUYUAN POWER CHOKE 208X N2: 2.0 mH
IEC 62109-2 appliance
CO.,LTD Class B
FENG CHING
- Wire xPEW 155 °C UL 1446 UL E172395
METAL CORP
PACIFIC ELECTRIC
WIRE & CABLE
- Alternative UEW/U@ 130 °C UL 1446 UL E201757
(SHENZHEN) CO
LTD
DONGGUAN
- Epoxy EATTO 3300A- V-0, 130 °C UL 746C UL E218090
ELECTRONIC 1/3300B-1
MATERIAL CO LTD

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
IEC 62109-1 Tested with
- Core KAWATESU MA070 T31*19*13mm
IEC 62109-2 appliance
Y capacitor
(C35, C2, C5, 400 Va.c., 470 pF, - IEC/EN60384 VDE
Nanjing Yuyue Elec-
C54, C55, C43, CT7 25 °C to 125 °C, Y1 -14 40008010
tronics Co., Ltd.
C40, C14,
C126, C127)
Nanjing Chieful
Current sensor Science & 5 Vd.c., 15 A, - IEC 62109-1 Tested with
CSM015NPT 25 °C to 85 °C
(CT1, CT2) TECHNOLOGY IEC 62109-2 appliance
CO.,LTD.
Boost IGBT Infineon 600V, 47A, -55 °C IEC 62109-1 Tested with
SPW47N60C3 to 150 °C
(Q7, Q8) Technologies AG IEC 62109-2 appliance
Boost diode 600V, 22A, -55 °C IEC 62109-1 Tested with
Cree Inc C3D16060D to 175 °C
(D1, D2) IEC 62109-2 appliance
KUNSHAN
Insulation paper ZHONGDI V-0, 150 °C, thick- UL 1694
between IGBT MATERIALS TSP-10 & ness: 0.15mm, UL 94 UL E343369
and heat sink TECHNOLOGY CO 26mmx20mm UL 746A
LTD
Bus capacitor
(C15, C116, HUNAN AIHUA ELH2JM471R 550V, 470µF, IEC 62109-1 Tested with
C115, C114, GROUP CO.,LTD 60TT -25 °C to 105 °C IEC 62109-2 appliance
C39)
Inverter IGBT (
Fairchild FGA60N65SM 650 V, 60 A, -55 °C IEC 62109-1 Tested with
Q1, Q2, Q3, Q4, to 175 °C
Semiconductor D IEC 62109-2 appliance
Q5, Q6)
600 V, 2x 15 A, - IEC 62109-1 Tested with
Diode(D3, D4) IXYS Corporation DSEC 30-06A
55 °C to 175 °C IEC 62109-2 appliance
SHENZHEN
Capacitor(C86, MPP474J6240 630 Vd.c, 0.47 µF, - IEC 62109-1 Tested with
SURONG
C87, C84, C85, 815P0 40 °C to 85 °C
CAPACITORS IEC 62109-2 appliance
C16, C17)
CO.,LTD
Current LEM 5 Vd.c., 25 A, -
CKSR 25-NP UL 508 UL E189713
sensor(CT4) SWITZERLAND S A 40 °C to 105 °C
XIAMEN UL 810 UL E256238
X capacitor 475Vd.c.,6.5 uF,
FARATRONIC CO., C6A EN 61071, TUV R
(C118) LTD. -40 °C to 105 °C
EN 61881-1 50266136
Y capacitor
(C121, C117,
C122, C123, Nanjing Yuyue Elec- 400V, 4700pF, - IEC/EN60384 VDE
C62, C64, C61, CT7
tronics Co., Ltd. 25 °C to 125 °C, Y1 -14 40008010
C63, C124,
C132, C119,
C125)

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
Relay (RLY6, Contact 250 Va.c., UL 60947-1 UL E43028
RLY5, RLY8, PANASONIC 31 Aa.c., coil 12V
ALFG2PF12 IEC/EN VDE
RLY10, RLY7, CORPORATION d.c.
-40 °C to 60 °C 61810-1 40023067
RLY9)
EN 50178
Current sensor LEM CTSR 0.3- 0.3A, 5V, -40 °C to
IEC 61010-1 UL E189713
(CT3) SWITZERLAND S A TP/SP17 105 °C
UL 508
XIAMEN IEC/EN VDE
X capacitor 275 Va.c., 2.2 uF, - 60384-14 40000358
FARATRONIC CO., MKP62
(C79, C120) 40 °C to 110 °C, X2
LTD. UL 60384-14 UL E186600
Shantou High-New
Varistor UL E330837
Technology 680V, 6500A, UL1449
(R109,R108, 20D681K VDE
Dev. Zone Songtian -40 °C to 125 °C IEC 61051
R86) 40023049
Enterprise Co., Ltd.
CONQUER
250 Va.c., 40 Aa.c., UL 248-1
Fuse (F1) ELECTRONICS ABE UL E82636
175 °C UL 248-14
CO.,LTD.
N1(4-
SHENZHEN x 1000.5Ts
FERROCOIL N2(3-
Current IEC 62109-1 Tested with
ELECTRONICS EI-28 1Ts
sensor(CT5) TECHNOLOGY IEC 62109-2 appliance
N2(6-
CO.,LTD 1Ts
Class B
CHANG CHUN UL 746
- Bobbin T375J V-0, 150 °C UL E59481
PLASTICS CO LTD UL 94
PACIFIC ELECTRIC
WIRE & CABLE
- Copper wire UEW/U 130 °C, MW 75-C UL 1446 UL E201757
(SHENZHEN) CO
LTD
XINYU
SHENGDAFENG
- Tape SDF-312 130 °C UL 510A UL E317896
ELECTRIC
MATERIAL CO LTD
CHANGYUAN
- Teflon tube ELECTRONICS CB-TT-L 200 °C, VW-1 UL 224 UL E180908
GROUP CO LTD
HANG CHEUNG
- Varnish COATINGS 8562* 155 °C UL 1446 UL E200154
(HUIYANG) LTD

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
N1(4-
x 1000.5Ts
JEPULS N2(3-
TECHNOLOGY IEC 62109-1 Tested with
Alternative LC28-045 1Ts
(SHENZHEN) IEC 62109-2 appliance
CO.,LTD N2(6-
1Ts
Class B
CHANG CHUN UL 746
- Bobbin T375J V-0, 150 °C UL E59481
PLASTICS CO LTD UL 94
E I DUPONT DE UL 746 UL E41938
- Alternative NEMOURS & CO 101L V-0, 130 °C
UL 94 (M)
INC
SHENZHEN
- Copper wire CHENGWEI UEW-E 130 °C, MW 75-C UL 1446 UL E227475
INDUSTRY CO LTD
JINGJIANG YAHUA
PRESSURE
- Mylar tape CT(c)(g) 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
JINGJIANG YAHUA
PRESSURE
- Margin tape WF* (c)(h) 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
CHANGYUAN
- Teflon tube ELECTRONICS CB-TT-L 200 °C, VW-1 UL 224 UL E180908
GROUP CO LTD
HANG CHEUNG
- Varnish COATINGS 8562* 155 °C UL 1446 UL E200154
(HUIYANG) LTD
N1(4-
x 1000.5Ts
SHENZHEN CLICK N2(3-
IEC 62109-1 Tested with
Alternative TECHNOLOGY DB2801-123 1Ts
CO.LTD IEC 62109-2 appliance
N2(6-
1Ts
Class B
CHANG CHUN UL 746
- Bobbin T373J V-0, 150 °C UL E59481
PLASTICS CO LTD UL 94
PACIFIC ELECTRIC
WIRE & CABLE
- Copper wire UEW/U@ 130 °C UL 1446 UL E201757
(SHENZHEN) CO
LTD
JINGJIANG YAHUA
PRESSURE
- Tape PZ* (b) 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
FLUO TECH
- Tube INDUSTRIES CO TFL 200 °C, VW-1 UL 224 UL E175982
LTD
ELANTAS
ELECTRICAL
- Varnish V1630FS 180 °C UL 1446 UL E75225
INSULATION
ELANTAS PDG INC

10Ts;
Inductor (L16, Shenzhen Spitzer SPT- IEC 62109-1 Tested with
L7) Electronic Co., Ltd 42H6284-L N2
IEC 62109-2 appliance
10Ts;
Class B
WUXI JUFENG
COMPOUND LINE
- WIRE CO MW 30-C 180 °C UL 1446 E206882
LTD
TAI-I COPPER
SMEIW MW
- Alternative (GUANZHOU) CO 180 °C UL 1446 E85640
77-C
LTD
- Insulation DUPONT TEIJIN Melinex 0.075×8mm, VTM-2 UL 746
E93687
FILM FILM U S L P 238PV(a) 130 °C UL 94
JINGJIANG YAHUA
- MARGIN PRESSURE
WF* (c)(h) 4mm*0.3 ,130 °C UL 510A E165111
TAPE SENSITIVE GLUE
CO LTD
GUANGZHOU
POCHELY EPOXY, V-0, UL 746
- GLUE ELECTRONIC 5225A/B E204979
130 °C UL 94
MATERIAL CO LTD
KINGBOARD UL 746
- BOBBIN LAMINATES KB-6165 V-0, 130 °C E123995
HOLDINGS LTD UL 94
IEC 62109-1 Tested with
- Core DMEGC R10K
IEC 62109-2 appliance
XIAMEN HONGFA UL 60947-1 VDE
Relay (RLY3, 2A/30VDC
ELECTROACOUSTI HFD3 IEC/EN 40018867
RLY11) C CO LTD 0.5A/125VAC
61810-1 UL E133481

21Ts
High Frequency ShenZhen JiaMeiRui IEC 62109-1 Tested with
Transformer ELECTRONICS JBK-13E-259 20Ts
CO.,LTD IEC 62109-2 appliance
(T1)
21Ts
Class B

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
UL 1694
CHANG CHUN
- Bobbin T375J V-0, 150 °C UL 94 UL E59481
PLASTICS CO LTD
UL 746A
TAI-I ELECTRIC
- Wire WIRE & CABLE CO UEWB 130 °C UL 1446 UL E85640
LTD
JINGJIANG YAHUA
PRESSURE No flame retard-
- Mylar tape SENSITIVE CT-280B UL 510A UL E165111
ant+, 130 °C
GLUE CO LTD
UL 1446
- Triple FURUKAWA UL E206440
TEX-E 130 °C IEC/EN
insulated wire ELECTRIC CO LTD VDE 006735
62368-1
ZHUHAI
CHANGXIAN NEW
- Varnish MATERIALS E962 130 °C UL 1446 UL E335405
TECHNOLOGY CO
LTD
IEC 62109-1 Tested with
- Core TDG EP13 TP4 10*10*10mm
IEC 62109-2 appliance
EAST Group Co., Sheet metal, 220×39×70mm IEC 62109-1 Tested with
Heat sink Ltd. AL6063 IEC 62109-2 appliance
--Below list is the critical components on the DC-DC board
SHENZHEN
FERROCOIL IEC 62109-1 Tested with
Inductor (L1) ELECTRONICS T184-8 65Ts, 304 uH,
TECHNOLOGY Class B IEC 62109-2 appliance
CO.,LTD
PACIFIC ELECTRIC
WIRE & CABLE
- Wire UEW/U@ 130 °C UL 1446 UL E201757
(SHENZHEN) CO
LTD
SHENZHEN
- Varnish HUAJINGMEI 8562/a 155 °C UL 1446 UL E322508
CHEMICAL CO LTD
UL 746E
HON TAI
- Baffle HT-E3502 V-0, 130 °C UL 94 UL E122230
MATERIAL CO LTD
UL 746A
DONGGUAN
- Epoxy EATTO 3300A- V-0, 130 °C UL 746C UL E218090
ELECTRONIC 1/3300B-1
MATERIAL CO LTD
JINGJIANG YAHUA
PRESSURE
- Tape PZ* (b) 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
SHENZHEN CITY
MAHAN IEC 62109-1 Tested with
- Core T184-8
MAGNETOELECTRI IEC 62109-2 appliance
C CO. LTD.
SHENZHEN
X capacitor SURONG MPP105J6311 630V, 1.0UF, V-0, - IEC 62109-1 Tested with
(C291, C290) CAPACITORS 120P0 40 °C to 85 °C, X2 IEC 62109-2 appliance
CO., LTD..
MOSFETS(Q54 Infineon Technolo- IPW65R041C 650V, 68.5A, - IEC 62109-1 Tested with
, Q55) gies AG FD 55 °C to 150 °C IEC 62109-2 appliance
JEPULS
Inductor (L29, TECHNOLOGY IEC 62109-1 Tested with
BCK3001-096 400P x 2C x 12Ts,
L30) (SHENZHEN) IEC 62109-2 appliance
22.6 uH, Class B
CO.,LTD
E I DUPONT DE UL 1694
- Insulation pa-
NEMOURS & CO Nomex 410 220 °C UL 94 UL E34739
per
INC UL 746A
JINGJIANG YAHUA
PRESSURE
-Tape PF* (d)(g) 180 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
SHENZHEN MEIXIN
- Alternative ELECTRONIC CO MXPI-310F 180 °C UL 510A UL E304309
LTD
JINGJIANG YAHUA
PRESSURE
- Margin tape WF* (c)(h) 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
DONGGUAN
- Epoxy EATTO V-0, 130 °C UL 746C UL E218090
E-500 (XX)
ELECTRONIC
MATERIAL CO LTD
KINGBOARD UL 1694
- Bobbin LAMINATES KB-6160C V-0, 130 °C UL 94 UL E123995
HOLDINGS LTD UL 746A
SUZHOU TAIHU
ELECTRIC
- Varnish T-4260(a) 155 °C UL 1446 UL E228349
ADVANCED
MATERIAL CO LTD
KINGBOARD
- PCB LAMINATES FR-4 130 °C, V-0 UL 94 UL E123995
HOLDINGS LTD
TDG HOLDING CO., PQ32/30 IEC 62109-1 Tested with
- Core 30*25*28mm
LTD TP4W IEC 62109-2 appliance
SHENZHEN CLICK N1:LI IEC 62109-1 Tested with
Alternative TECHNOLOGY CO. PQ32-1060 400P x 2C x 12Ts,
LTD 22.6 uH, Class B IEC 62109-2 appliance

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
PACIFIC ELECTRIC
WIRE & CABLE
- Wire MW79-C 155 °C UL 1446 UL E201757
(SHENZHEN) CO
LTD
TAI-I ELECTRIC
- Alternative WIRE & CABLE CO MW79-C 155 °C UL 1446 UL E85640
LTD
JINGJIANG YAHUA
PRESSURE
- Tape PF-301 180 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
UL
- Alternative SYMBIO INC KA180 200 °C UL510A
E50292
JINGJIANG YAHUA
PRESSURE
- Margin tape WF* (c)(h) 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO.LTD
DONGGUAN
- Epoxy EATTO V-0, 130 °C UL 746C UL E218090
E-500 (XX)
ELECTRONIC
MATERIAL CO LTD
E I DUPONT DE UL 1694
- Bobbin NEMOURS & CO Nomex 410 220 °C UL 94 UL E34739
INC UL 746A
ZHUZHOU TIMES UL 1694
- Alternative ELECTRIC 180 °C UL 94 UL E355960
TJ6640NMN
INSULATION CO
LTD UL 746A

- Varnish KYOCERA
TVB2180T*(a) 155 °C UL 1446 UL E83702
CHEMICAL CORP
ELANTAS
ELECTRICAL
- Alternative V1630FS 130 °C UL 1446 UL E75225
INSULATION
ELANTAS PDG INC
SHENGYI
- PCB TECHNOLOGY CO FR-4 130 °C, V-0 UL 94 UL E109769
LTD
KINGBOARD
- Alternative LAMINATES FR-4 130 °C, V-0 UL 94 UL E123995
HOLDINGS LTD
PQ32/30 IEC 62109-1 Tested with
- Core DMEGC 34*30*30mm
DMR95 IEC 62109-2 appliance
X capacitor XIAMEN
630V, 47nF, -40 °C IEC 62109-1 Tested with
(C305, C306, FARATRONIC CO MMKP82
to 105 °C IEC 62109-2 appliance
C307, C308) LTD

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity

200x 4P x 4Ts
N2: COPPER FOIL,

SHENZHEN CLICK 2Ts


Transformer BCK5501- IEC 62109-1 Tested with
TECHNOLOGY N3: COPPER FOIL,
(T12) 1069 IEC 62109-2 appliance
CO,.LTD
2Ts

200x 4P x 4Ts
Class B
E I DUPONT DE UL 1694
- Bobbin NEMOURS & CO 410 220 °C, V-0 UL 94 E34739
INC UL 746A
EE55/55/21 IEC 62109-1 Tested with
- Core ANCI 58*42*9mm
ACP95 IEC 62109-2 appliance
TAI-I ELECTRIC
- Wire WIRE & CABLE CO UEWF 155 °C UL 1446 UL E85640
LTD
PACIFIC ELECTRIC
WIRE & CABLE
- Alternative UEF1/U@ 155 °C UL 1446 UL E201757
(SHENZHEN) CO
LTD
JINGJIANG YAHUA
PRESSURE
- Mylar tape PF-301 180 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
- Margin tape 3M COMPANY 44D(a) 130 °C UL 510A UL E17385
KYOCERA
- Varnish TVB2180T*(a) 155 °C UL 1446 UL E83702
CORPORATION
DONGGUAN
- Epoxy EATTO V-0, 130 °C UL 746C UL E218090
E-500 (XX)
ELECTRONIC
MATERIAL CO LTD
GREAT HOLDING
- Tube INDUSTRIAL CO TFL 200 °C, VW-1 UL 224 UL E156256
LTD

JEPULS 100Ts
Inductor (L13 TECHNOLOGY IEC 62109-1 Tested with
LC12-028
L26) (SHENZHEN) IEC 62109-2 appliance
1Ts
CO.,LTD
Class B
FR530(l)(+)(f1
E I DUPONT DE UL 94
),
- Bobbin NEMOURS & CO V-0, 155 °C UL E41938
FR530L(l)(+)(f UL 746A
INC
1)

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
SHENZHEN
(x)UEW-E-(&)-
- Wire CHENGWEI 130 °C UL 1446 UL E227475
(*)
INDUSTRY CO LTD
FENG CHING
- Alternative xUEW-2 130 °C UL 1446 UL E172395
METAL CORP
SHENZHEN
- Alternative CHENGWEI (x)PEW(EI)-F 155 °C UL 1446 UL E227475
INDUSTRY CO LTD
FENG CHING
- Alternative xPEW 155 °C UL 1446 UL E172395
METAL CORP
DONGGUAN
- Epoxy EATTO 3300A- V-0, 130 °C UL 746C UL E218090
ELECTRONIC 1/3300B-1
MATERIAL CO LTD
JINGJIANG YAHUA
PRESSURE
- Mylar tape WF* (c)(h) 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
KINGBOARD UL 746B
- Epoxy baffle LAMINATES KB-6160C V-0, 130 °C UL 94 UL E123995
HOLDINGS LTD UL 746A
IEC 62109-1 Tested with
- Core JING YUAN CH7 T12.7*7.92*6.35
IEC 62109-2 appliance
N1:
SHENZHEN CLICK 100Ts
IEC 62109-1 Tested with
Alternative TECHNOLOGY LC12-177
CO.LTD 1Ts IEC 62109-2 appliance
Class B
JINGJIANG YAHUA
PRESSURE
- Margin tape WF* (c)(h) 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
PACIFIC ELECTRIC
WIRE & CABLE
- Wire UEW/U@ 130 °C UL 1446 UL E201757
(SHENZHEN) CO
LTD
TAI-I ELECTRIC
- Alternative WIRE & CABLE CO UEWB 130 °C UL 1446 UL E85640
LTD
FR530(l)(+)(f1 UL 1694
E I DUPONT DE
),
- Bobbin NEMOURS & CO V-0, 155 °C UL 94 E41938
FR530L(l)(+)(f
INC UL 746A
1)
DONGGUAN
- Epoxy EATTO 3300A- V-0, 130 °C UL 746C UL E218090
ELECTRONIC 1/3300B-1
MATERIAL CO LTD
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
KINGBOARD UL 1694
- PCB LAMINATES FR-4 V-0, 130 °C UL 94 UL E123995
HOLDINGS LTD UL 746A
IEC 62109-1 Tested with
- Core KINGBOARD R7K T12.7*7.92*6.35C
IEC 62109-2 appliance
3P x
SHENZHEN CLICK 3Ts, 60uH
IEC 62109-1 Tested with
Inductor (L28) TECHNOLOGY LC28-181 3P x
CO.LTD 3Ts, 60uH IEC 62109-2 appliance
Class B
PACIFIC ELECTRIC
WIRE & CABLE
- Wire MW5-C 155 °C UL 1446 UL E201757
(SHENZHEN) CO
LTD
TAI-I ELECTRIC
- Alternative WIRE & CABLE CO MW5-C 155 °C UL 1446 UL E85640
LTD
TA YA ELECTRIC
- Alternative WIRE & CABLE MW5-C 155 °C UL 1446 UL E84201
CO LTD
DONGGUAN
- Epoxy EATTO 3300A- V-0, 130 °C UL 746C UL E218090
ELECTRONIC 1/3300B-1
MATERIAL CO LTD
HANG CHEUNG
- Varnish COATINGS 8562* 155 °C UL 1446 UL E200154
(HUIYANG) LTD
IEC 62109-1 Tested with
- Core DMEGC R7K T28*16*13C
IEC 62109-2 appliance
DONGGUAN WIN
Electrolytic SHINE 063SH332M2 63Vd.c, 3300µF, - IEC 62109-1 Tested with
capacitor ELECTRONIC CO., 240C40J 55°C to 105 °C IEC 62109-2 appliance
(C296, C297) LTD.
X capacitor Xiamen Faratronic 63V, 3.3µF, -55 °C IEC 62109-1 Tested with
(C292, C293, C23
Co. Ltd. to 105 °C IEC 62109-2 appliance
C294, C295)
Diode (D94, 200V, 2×30A, - IEC 62109-1 Tested with
IXYS Corporation DSSK 60-02A
D95) 55°C to 175 °C IEC 62109-2 appliance
Transformer Shenzhen Spitzer N1:N2:N3=20:24:2 IEC 62109-1 Tested with
GR24020T5
(T8) Electronic Co., Ltd 4, 0.64mH, Class B IEC 62109-2 appliance
UL 2352
- Triple COSMOLINK CO. UL 60950-1 UL E213764
TIW-M 130 °C
insulated wire LTD. IEC/EN VDE 138053
62368-1

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
JINGJIANG YAHUA
PRESSURE
- Tape PZ-280 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
JINGJIANG YAHUA
PRESSURE
- Alternative PF*(d)(g) 155 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
CHANGYUAN
-1,
- Tube ELECTRONICS CB-TT-L UL 224 UL E180908
200 °C
GROUP CO LTD
SUZHOU TAIHU
ELECTRIC
- Varnish T-4260(a) 155 °C UL 1446 UL E228349
ADVANCED
MATERIAL CO LTD
GUANGZHOU
POCHELY NEW UL 94
- Glue MATERIAL 5225A/B 130 °C, V-0 UL E204979
TECHNOLOGY CO UL 746B
LTD
CHANG CHUN UL 94
- Bobbin T375J 150 °C, V-0 UL E59481
PLASTICS CO LTD UL 746B
IEC 62109-1 Tested with
- Core NCD LP3 14*14*14mm
IEC 62109-2 appliance

20P x 2P x 8Ts
N2: COPPER FOIL,
25 x 30mm x
JEPULS 4Ts
Transformer TECHNOLOGY IEC 62109-1 Tested with
BCK5501-204 N3: COPPER FOIL,
(T3, T2) (SHENZHEN) IEC 62109-2 appliance
CO.,LTD
4Ts

20P x 2P x 8Ts
Class B
FR530(l)(+)(f1 UL 1694
E I DUPONT DE
),
- Bobbin NEMOURS & CO V-0, 155 °C UL 94 E41938
FR530L(l)(+)(f
INC UL 746A
1)
Ferrite, IEC 62109-1 Tested with
TDG HOLDING CO.,
- Core TP4 55mm*55mm*21m
LTD IEC 62109-2 appliance
m
FENG CHING
- Wire xUEW-2 130 °C UL 1446 UL E172395
METAL CORP

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
PACIFIC ELECTRIC
WIRE & CABLE
- Alternative UEW/U@ 130 °C UL 1446 UL E201757
(SHENZHEN) CO
LTD
TAI-I ELECTRIC
- Alternative WIRE & CABLE CO UEWB 130 °C UL 1446 UL E85640
LTD
JINGJIANG YAHUA
PRESSURE
- Mylar tape CT-280B 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
3M COMPANY
ELECTRICAL
- Alternative 1350F-1 (b) 130 °C UL 510A UL E17385
MARKETS DIV
(EMD)
JINGJIANG YAHUA
PRESSURE
- Margin tape WF* (c)(h) 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
3M COMPANY
ELECTRICAL
- Alternative 44 (a) 130 °C UL 510A UL E17385
MARKETS DIV
(EMD)
GREAT HOLDING
- Teflon Tube INDUSTRIAL CO TFL 200 °C, VW-1 UL 224 UL E156256
LTD
CHANGYUAN
- Alternative ELECTRONICS CB-TT-L 200 °C, VW-1 UL 224 UL E180908
GROUP CO LTD
SUZHOU TAIHU
ELECTRIC
- Varnish T-4260(a) 155 °C UL 1446 UL E228349
ADVANCED
MATERIAL CO LTD
DONGGUAN
- Epoxy EATTO V-0, 130 °C UL 746C UL E218090
E-500 (XX)
ELECTRONIC
MATERIAL CO LTD

20P x 2P x 8Ts
N2: COPPER FOIL,

SHENZHEN CLICK 4Ts


BCK5501- IEC 62109-1 Tested with
Alternative TECHNOLOGY N3: COPPER FOIL,
1063 IEC 62109-2 appliance
CO,.LTD
4Ts

20P x 2P x 8Ts
Class B
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
FR530(l)(+)(f1 UL 1694
E I DUPONT DE
),
- Bobbin NEMOURS & CO V-0, 155 °C UL 94 E41938
FR530L(l)(+)(f
INC UL 746A
1)
Ferrite, IEC 62109-1 Tested with
- Core Various Various 55mm*55mm*21m
m IEC 62109-2 appliance
TAI-I ELECTRIC
- Wire WIRE & CABLE CO UEWB 130 °C UL 1446 UL E85640
LTD
PACIFIC ELECTRIC
WIRE & CABLE
- Alternative UEF1/U@ 155 °C UL 1446 UL E201757
(SHENZHEN) CO
LTD
FENG CHING
- Alternative xUEW 130 °C UL 1446 UL E172395
METAL CORP
JINGJIANG YAHUA
PRESSURE
- Mylar tape CT(b)(g) 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
JINGJIANG YAHUA
PRESSURE
- Margin tape WF* (c)(h) 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
KYOCERA
- Varnish TVB2180T*(a) 155 °C UL 1446 UL E83702
CORPORATION
DONGGUAN
- Epoxy EATTO V-0, 130 °C UL 746C UL E218090
E-500 (XX)
ELECTRONIC
MATERIAL CO LTD
GREAT HOLDING
- Tube INDUSTRIAL CO TFL 200 °C , VW-1 UL 224 UL E156256
LTD
Diode (D16, Advanced Power APT30DQ120 1200V, 30A, -55 °C IEC 62109-1 Tested with
D14, D15, D17) Technology Inc BG* to 175 °C IEC 62109-2 appliance
X capacitor STH-250-20- 250 Va.c., 20 uF, - IEC 62109-1 Tested with
EACO Capacitor Inc
(C33) 44# 40 °C to 85 °C IEC 62109-2 appliance
Electrolytic HUNAN AIHUA ELH1JM472P 63 Vd.c, 4700 uF, - IEC 62109-1 Tested with
capacitor (C31, GROUP CO.,LTD 50KC 40 °C to 105 °C IEC 62109-2 appliance
C30)
CONQUER
Fuse (F1, F2, 250 Va.c., 40 Aa.c., UL 248-1
ELECTRONICS CO ABE(VI) UL E82636
F3) 175 °C UL 248-14
LTD
SONG CHUAN IEC 62109-1 Tested with
MV011P1- 60VDC, 100A, -
Relay (RLY1) PRECISION CO.,
1AH-C 40 °C to 70 °C IEC 62109-2 appliance
LTD

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
Y capacitor Shantou High-New
UL 60384-14 UL E208107
(C26, C27, C28, Technology CE Series
250Va.c., 10000pF,
C29, C135, Dev. Zone Songtian -25 °C to 125°C, Y2 IEC/EN VDE::
60384-14 40025748
C136) Enterprise Co., Ltd.
X capacitor ( SONG CHUAN IEC 62109-1 Tested with
630Vd.c., 0.1uF, -
C38, C39, PRECISION CO., CBB21
40°C to 105°C IEC 62109-2 appliance
C169, C170) LTD
MOSFETS (Q5, Infineon Technolo- 200V, 130A, -55 °C IEC 62109-1 Tested with
Q6, Q7,Q8, Q9, gies AG IRFP4668PBF
to 175 °C IEC 62109-2 appliance
Q10, Q11, Q12)
MOSFETS Fairchild Semicon- 900V, 6A, -55 °C to IEC 62109-1 Tested with
FQP6N90C
(Q49) ductor 150 °C IEC 62109-2 appliance

27Ts

8Ts

SHENZHEN CLICK 6Ts


Transformer IEC 62109-1 Tested with
TECHNOLOGY ETD29
(T9) CO., LTD 2Ts IEC 62109-2 appliance

4Ts

27Ts
Class B
IEC 62109-1 Tested with
- Core DMEGC EC29 DMR40 30*35*25mm
IEC 62109-2 appliance
UL 1694
CHANG CHUN
- Bobbin T375HF V-0, 150 °C UL 94 UL E59481
PLASTICS CO LTD
UL 746A
GREAT HOLDING
- Teflon Tube INDUSTRIAL CO TFL VW-1, 200 °C UL 224 UL E156256
LTD
TA YA ELECTRIC
- Wire WIRE & CABLE CO LZ-UEWB 130 °C, MW 75-C UL 1446 UL E84201
LTD
FENG CHING xUEW
- Alternative 130 °C, MW 75-C UL 1446 UL E172395
METAL CORP
ROSHOW xUEW@/130,
- Alternative TECHNOLOGY CO QA@-x/130 130 °C, MW 75-C UL 1446 UL E215691
LTD
TAI-I ELECTRIC UEW
- Alternative WIRE & CABLE CO 130 °C, MW 75-C UL 1446 UL E85640
LTD

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
JINGJIANG YAHUA
PRESSURE
- Tape CT (b)(g) 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
KYOCERA
- Varnish TVB2180T*(a) 155 °C UL 1446 UL E83702
CORPORATION
JINGJIANG YAHUA
PRESSURE
- Margin tape WF* (c)(h) 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
Grid Auxiliary YUEQING HENGJIU IEC 62109-1 Tested with
250V, 10A, -25 °C
Power terminal INDUSTRIAL HA396
to 75 °C IEC 62109-2 appliance
block(J21, J31) CO.,LTD
DONGGUAN CITY UL 746C
Material of J21, FENG TONG ST-PBT 301 V-0, 75 °C UL 94 UL E352852
J31 PLASTIC CO LTD UL 746B

SHENZHEN 10Ts, 580 uH


IEC 62109-1 Tested with
Inductor (L20) YUYUAN POWER T16*12*8C
10Ts, 580 uH IEC 62109-2 appliance
CO.,LTD
Class B
PACIFIC ELECTRIC
WIRE & CABLE
- Wire PEWH/U 180 °C UL 1446 UL E201757
(SHENZHEN) CO
LTD
KINGBOARD UL 1694
- Bobbin LAMINATES KB-6150 V-0, 130 °C UL 94 UL E123995
HOLDINGS LTD UL 746A
GREAT HOLDING
- Tube INDUSTRIAL CO TFL VW-1, 200 °C UL 224 UL E156256
LTD
DONGGUAN
- Epoxy EATTO 3300A- V-0, 130 °C UL 746C UL E218090
ELECTRONIC 1/3300B-1
MATERIAL CO LTD
SHEN ZHEN
NOBLE FLOWER UL 746E
- Varnish TECHNOLOGY RT9669 V-0, 260 °C UL E480212
UL 94
INDUSTRIAL CO
LTD
IEC 62109-1 Tested with
- Core T001 R10K T16*12*8C, 130
IEC 62109-2 appliance

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
Y capacitor
(C217, C221, NAN JING YUYUE 400V,1000pF UL 60384-14 UL E237728
C313, C321, UL: CT7, 2E
ELECTRONICS CO -25 °C to 125 °C, IEC/EN VDE
C322, C218, LTD VDE: CT7
Y1 60384-14 40008010
C222, C219,
C220)
630Vd.c., 2.2uF, -
X capacitor Xiamen Faratronic IEC 62109-1 Tested with
C37 40 °C to 105 °C
(C285) Co. Ltd. IEC 62109-2 appliance
V-0
LITE-ON Isolation 5000 UL 1577 UL E113898
Optocoupler TECHNOLOGY LTV-816 Vr.m.s, -30 °C to IEC/EN VDE:
(U27, U25, U26) CORP 110 °C 60747-5-5 40015248

48Ts

72Ts
SHENZHEN CLICK IEC 62109-1 Tested with
Transformer TECHNOLOGY EE25 8Ts
(T10) CO,.LTD IEC 62109-2 appliance
7Ts

48Ts
Class B
UL 1694
CHANG CHUN
- Bobbin T375HF V-0, 150 °C UL 94 UL E59481
PLASTICS CO LTD
UL 746A
28*20*25mm, IEC 62109-1 Tested with
- Core DMEGC EI25C DMR40
130 °C IEC 62109-2 appliance
GREAT HOLDING
- Tube INDUSTRIAL CO TFL VW-1, 200 °C UL 224 UL E156256
LTD
PACIFIC ELECTRIC
WIRE & CABLE
- Wire UEW/U@ 130 °C, MW 75-C UL 1446 UL E201757
(SHENZHEN) CO
LTD
TA YA ELECTRIC
- Alternative WIRE & CABLE CO LZ-UEWB 130 °C, MW 75-C UL 1446 UL E84201
LTD
TAI-I ELECTRIC UEW
- Alternative WIRE & CABLE CO 130 °C, MW 75-C UL 1446 UL E85640
LTD
ROSHOW xUEW@/130,
- Alternative TECHNOLOGY CO QA@-x/130 130 °C, MW 75-C UL 1446 UL E215691
LTD
FENG CHING xUEW
- Alternative 130 °C, MW 75-C UL 1446 UL E172395
METAL CORP
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
JINGJIANG YAHUA
PRESSURE
- Tape CT (b)(g) 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
KYOCERA
- Varnish TVB2180T*(a) 155 °C UL 1446 UL E83702
CORPORATION
JINGJIANG YAHUA
PRESSURE
- Margin tape WF* (c)(h) 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
SHANTOU HIGH-
NEW
TECHNOLOGY UL 60384-14 UL E208107
X capacitor 275V, 0.33uF, -
DEVELOPMNT MPX
(C259, C260) 40 °C to 110 °C, X2 IEC/EN VDE
ZONE SONGTIAN 60384-14 40034679
ENTERPRISE CO
LTD
SHENZHEN UL 60384-14 UL E314875
SURONG 280V, 0.33uF, -
- Alternative MPX/MKP
CAPACITORS CO 40 °C to 110 °C, X2 IEC/EN VDE
LTD 60384-14 40008924
SHEN ZHEN XING
HONG YANG 800V, 1A, -55 °C to IEC 62109-1 Tested with
D88 DB106
ELECTRONIC 150 °C IEC 62109-2 appliance
CO.,LTD
FAIRCHILD
MOSFETS 900V, 4A, -55 °C to IEC 62109-1 Tested with
SEMICONDUCTOR FQPF4N90C
(Q50) 150 °C IEC 62109-2 appliance
CORP
SHENZHEN N1: 2.0 mH
Inductor (L21, PPI184040*2p IEC 62109-1 Tested with
YUYUAN POWER N2: 2.0 mH
L22) cs IEC 62109-2 appliance
CO., LTD Class B
IEC 62109-1 Tested with
- Core POCO PPI184040 T9*5*3C
IEC 62109-2 appliance
PACIFIC ELECTRIC
WIRE & CABLE
- Wire PEWH/U 180 °C, MW 30-C UL 1446 UL E201757
(SHENZHEN) CO
LTD
SHEN ZHEN
NOBLE FLOWER UL 746E
- Varnish TECHNOLOGY RT9669 V-0, 260 °C UL E480212
UL 94
INDUSTRIAL CO
LTD
KINGBOARD UL 746E
- PCB LAMINATES KB-6160C V-0, 130 °C UL E123995
UL 94
HOLDINGS LTD

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
JINGJIANG YAHUA
- Tape PRESSURE CT-280B 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD
DONGGUAN
- Epoxy EATTO 3300A- V-0, 130 °C UL 746C UL E218090
ELECTRONIC 1/3300B-1
MATERIAL CO LTD

15Ts

90Ts
SHENZHEN CLICK IEC 62109-1 Tested with
Transformer TECHNOLOGY EI25 10Ts
(T11) CO,.LTD IEC 62109-2 appliance
10Ts

15Ts
Class B
UL 1694
CHANG CHUN
- Bobbin T375HF V-0, 150 °C UL 94 UL E59481
PLASTICS CO LTD
UL 746A
IEC 62109-1 Tested with
- Core Various Various 28.0x 6.5x23.5mm
IEC 62109-2 appliance
GREAT HOLDING
- Tube INDUSTRIAL CO TFL VW-1, 200 °C UL 224 UL E156256
LTD
PACIFIC ELECTRIC
WIRE & CABLE
- Wire UEW/U@ 130 °C, MW 75-C UL 1446 UL E201757
(SHENZHEN) CO
LTD
- Alternative TA YA ELECTRIC
WIRE & CABLE CO LZ-UEWB 130 °C, MW 75-C UL 1446 UL E84201
LTD
- Alternative TAI-I ELECTRIC UEW
WIRE & CABLE CO 130 °C MW 75-C UL 1446 UL E85640
LTD
- Alternative ROSHOW xUEW@/130,
TECHNOLOGY CO QA@-x/130 130 °C, MW 75-C UL 1446 UL E215691
LTD
- Alternative FENG CHING xUEW
130 °C, MW 75-C UL 1446 UL E172395
METAL CORP
JINGJIANG YAHUA
PRESSURE
- Tape CT (b)(g) 130 °C UL 510A UL E165111
SENSITIVE GLUE
CO LTD

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
KYOCERA
- Varnish TVB2180T*(a) 155 °C UL 1446 UL E83702
CORPORATION
JINGJIANG YAHUA
PRESSURE Flame retardant+,
- Margin tape WF* (c)(h) UL 510A UL E165111
SENSITIVE GLUE 130 °C
CO LTD
XIAMEN IEC 62109-1 Tested with
X capacitor 63V, 470nF, -55 °C
FARATRONIC CO C24
(C269) to 125 °C IEC 62109-2 appliance
LTD
MOSFETS Vishay Intertechnol- 400V, 10A, - 55 to IEC 62109-1 Tested with
IRF740PBF
(Q51) ogy, Inc., 150 °C IEC 62109-2 appliance
EAST Group Co., IEC 62109-1 Tested with
Heat sink AL6063 279×72×40mm
Ltd. IEC 62109-2 appliance
--Below list is the critical components on the IGBT Driver board
N1: 2UEW
SHENZHEN CLICK Ø0.13×1P 240TS
Transformer IEC 62109-1 Tested with
TECHNOLOGY EE-10 N2: 2UEW
(T1) CO,.LTD Ø0.14×1P 113TS IEC 62109-2 appliance
Class B
CHANG CHUN
- Bobbin PLASTLCS CO., T375HF V-0, 150 °C UL94 UL E59481
LTD
DMEGC IEC 62109-1 Tested with
- Core MAGNETICS CO., EE10 R10K 12×13×5mm
LTD IEC 62109-2 appliance
IEC 62109-1 Tested with
- Alternative GUANDA EE10 GH10 12×13×5mm
IEC 62109-2 appliance
JINGJIANG YAHUA
PRESSURE
- Tape CT (b)(g) 130 °C UL 510A E165111
SENSITIVE GLUE
FTY
PACIFIC ELECTRIC
- Wire WIRE & CABLE UEF1/U@ MW-79C, 155 °C UL 1446 E201757
CO., LTD
TA YA ELECTRIC
- Alternative WIRE & CABLE LZ-UEWB MW-79C, 130 °C UL 1446 E84201
CO., LTD
TAI-I ELECTRIC UEWF
- Alternative WIRE & CABLE MW-79C, 155 °C UL 1446 E85640
CO., LTD
ROSHOW
xUEW@/155,
- Alternative TECHNOLOGY MW-79C, 155 °C UL 1446 E215691
QA@-x/155
CO ., LTD
FENG CHING
- Alternative xFSW MW-79C, 155 °C UL 1446 E172395
METAL CORP

TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
KYOCERA
- Varnish TVB2180T*(a) MW 28-C, 155 °C UL 1446 E83702
CORPORATION
GREAT HOLDING
-Tube INDUSTRIAL CO., TFL VW-1, 200 °C UL 224 E156256
LTD
DONGGUAN
EATTO UL 94
-EPOXY ELECTRONIC E-500(XX) V-0, 130 °C E218090
MATERIAL CO., UL 746C
LTD
FAIRCHILD
Optocoupler Isolation 5000Vrms
SEMICONDUCTOR FOD3150 UL1577 UL E90700
(U1) -40 °C to 100 °C
CORP
--Below list is the critical components on the control board
TMS320F2837 IEC 62109-1 Tested with
MCU (U3) Texas Instruments -40 °C to 125 °C
7SZWTT IEC 62109-2 appliance
--Below list is the critical components on the LCD board
SHENZHEN CLICK IEC 62109-1 Tested with
Transformer 50mA:5mA, -20 °C
TECHNOGY CO., TB1301-005
(T2) to 70 °C IEC 62109-2 appliance
LTD
TAI-I ELECTRIC
-MAGNET WIRE & CABLE CO UEWF-E MW 80-C,155 °C UL 1446 E85640
WIRE LTD
FENG CHING
-Alternative xFSW-NY MW 80-C,155 °C UL 1446 E172395
METAL CORP
UL 746A
CHANG CHUN 120 °C, V-0, thick-
-Case 4115(f1) UL 94 E59481
PLASTICS CO LTD ness:0.75mm
UL 746B
UL 746A
CHANG CHUN 140 °C, V-0, thick-
- Alternative 4130 UL 94 E59481
PLASTICS CO LTD ness:0.74mm
UL 746B
UL 746A
CHANG CHUN 120 °C, V-0, thick-
- Base 4115(f1) UL 94 E59481
PLASTICS CO LTD ness: 0.75mm
UL 746B
UL 746A
CHANG CHUN 140 °C, V-0, thick-
- Alternative 4130 UL 94 E59481
PLASTICS CO LTD ness: 0.74mm
UL 746B
GUANGZHOU
WELLS UL 94
- EPOXY 9002GA/B-SY V-0, 90 °C E229633
ELECTRONIC UL 746C
MATERIAL CO LTD
DONGGUAN
EATTO 3300A- UL 94
- Alternative V-0, 130 °C E218090
ELECTRONIC 1/3300B-1 UL 746C
MATERIAL CO LTD
TRF_IEC62109_1B
IEC 62109-1
Clause Requirement Test Result Remark Verdict

list of critical components


Manufacturer/ Mark(s) of
Object / part No. Type / model Technical data Standard
trademark conformity
UL: TEXAS
INSTRUMENTS VDE
TUCSON CORP UL 1577 40016131
ISO1050DUB -40 °C to 125 °C,
U21 VDE: TEXAS R isolation 2500Va.c. DIN V VDE V UL E181974
INSTRUMENTS 0884-10
DEUTSCHLAND
GMBH
Note:
(1) If no special indicate, list of critical components are applied for all models.
(2) Throughout this file (CDF) a commais used as the decimal separator.

........ End of test report

TRF_IEC62109_1B
TEST REPORT
IEC 62109-2:2011
Safety of power converters for use in photovoltaic power systems
Part 2: Particular requirements for inverters

Report Number. ............................ : 64.290.18.05995.01 part 2 of 2


Date of issue ................................. : 2019-04-08

Total number of pages ................. : 30 pages

.......................... : EAST Group Co., Ltd.

Address......................................... : No.6 Northern Industry Road, Songshan Lake Sci. & Tech.
Industry Park, 523808 DongGuan City, Guangdong Province,
PEOPLE'S REPUBLIC OF CHINA

Test specification:
Standard ....................................... : IEC/EN 62109-2:2011
Test procedure ............................. : CE_LVD
Non- N/A
Test Report Form No.................... : IEC62109_2B

Test Report Form(s) Originator ... : LCIE - Laboratoire Central des Industries Electriques
Master TRF ................................... : Dated 2016-08
Copyright © 2010 Worldwide System for Conformity Testing and Certification of Electrotechnical
Equipment and Components (IECEE), Geneva, Switzerland. All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copyright
owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the reader's
interpretation of the reproduced material due to its placement and context.

If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the
CB Scheme procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory
and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
General disclaimer:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing CB Testing
Laboratory. The authenticity of this Test Report and its contents can be verified by contacting the NCB,
responsible for this Test Report.

TRF_IEC62109_2B
List of Attachments (including a total number of pages in each attachment):
This test report contains 2 parts listed in below table:
Item Description Pages
Part 1 IEC/EN 62109-1:2010 test report 103
Part 2 IEC/EN 62109-2:2011 test report 30
This test report shall be also used in conjunction with 12 pages of photo documentation.

Summary of testing:
All tests were carried out according to IEC 62109-2(ed.1). The text of IEC 62109-2(ed.1) was approved
by
CENELEC as a European Standard without any modification.

Tests performed (name of test and test clause):

Clause Requirement
4.4.4.15 Fault-tolerance of protection for grid-interactive inverters
4.4.4.17 Cooling system failure Blanketing test
4.7.4.2 Steady state output voltage at nominal DC input
4.7.4.3 Steady state output voltage across the DC input range
4.7.4.4 Load step response of the output voltage at nominal DC input
4.7.4.5 Steady state output frequency
4.7.5.2 Sinusoidal output voltage waveform requirements
4.8.2.1 Array insulation resistance detection for inverters for ungrounded arrays
4.8.3.5 Protection by residual current monitoring

Summary of compliance with National Differences (List of countries addressed):


The product fulfils the requirements of _________ (insert standard number and edition and delete the
text in parenthesis, leave it blank or delete the whole sentence, if not applicable)

Copy of marking plate:


The artwork below may be only a draft. The use of certification marks on a product must be authorized
by the respective NCBs that own these marks.
See Report No.: 64.290.18.05995.01 part 1 of 2.
Test item particulars................................................ :
Equipment mobility ................................................. : movable hand-held stationary
fixed transportable for building-in
Connection to the mains ......................................... : pluggable equipment direct plug-in
permanent connection for building-in
Environmental category .......................................... : outdoor indoor indoor
Unconditional conditional
Over voltage category Mains .................................. : OVC I OVC II OVC III OVC IV
Over voltage category PV ....................................... : OVC I OVC II OVC III OVC IV
Mains supply tolerance (%) ..................................... : +/- 10%
Tested for power systems ....................................... : TN system
IT testing, phase-phase voltage (V) ......................... : N/A
Class of equipment ................................................. : Class I Class II Class III
Not classified
Mass of equipment (kg)........................................... : Net weight: 22.3 kg (Approx.)
611*547*150
Pollution degree ...................................................... : PD II
IP protection class................................................... : IP 20 (indoor use only)
Testing .................................................................... :
Date of receipt of test item ...................................... : 2018-10-29
Date (s) of performance of tests .............................. : 2018-11-01 to 2019-03-18
Possible test case verdicts:
- test case does not apply to the test object ............. : N/A
- test object does meet the requirement .................. : P (Pass)
- test object was not evaluated for the requirement . : N/E
- test object does not meet the requirement ............ : F (Fail)
General remarks:
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
The tests result presented in this report relate only to the object tested.
This report shall not be reproduced except in full without the written approval of the testing laboratory.
List of test equipment must be kept on file and available for review.
Additional test data and/or information provided in the attachments to this report.
Throughout this report a comma / point is used as the decimal separator.
Abbreviations used in the report:
Basic insulation (BI); Supplementary insulation (SI); Double insulation (DI); Reinforced insulation (RI);
Functional insulation (FI); Single fault condition (SFC); Normal condition (NC); Supply overvoltage category
(OVC); Pollution degree (PD), CDF (Data form for electrical equipment and machinery)
-clause 4.2.5 of IECEE 02:
The application for obtaining a CB Test Certificate Yes
includes more than one factory location and a
Not applicable
declaration from the Manufacturer stating that the
sample(s) submitted for evaluation is (are)
representative of the products from each factory has
been provided .......................................................... :
When differences exist; they shall be identified in the General product information section.

Name and address of factory (ies) ........................ :


Factory name: EAST Group Co., Ltd.

Address: No.6 Northern Industry Road, Songshan Lake Sci. & Tech. Industry Park, 523808 DongGuan City,
Guangdong Province, PEOPLE'S REPUBLIC OF CHINA

General product information:


See Report No.: 64.290.18.05995.01 part 1 of 2

Model different:
N/A

Electrical Ratings:
See Report No.: 64.290.18.05995.01 part 1 of 2
IEC 62109-2
Clause Requirement Test Result Remark Verdict

4 General testing requirements P


4.4.4 Single fault conditions to be applied P
4.4.4.15 Fault-tolerance of protection for grid-interactive P
inverters
4.4.4.15.1 Fault-tolerance of residual current monitoring P
according to 4.8.3.5: the residual current
monitoring system operates properly
a) ..- The inverter ceases to operate (see appended table) P
4.4.4.15.1
- Indicates a fault in accordance with §13.9 P

- Disconnect from the mains P

- not re-connect after any sequence of P


removing and reconnecting PV power
- not re-connect after any sequence of P
removing and reconnecting AC power
- not re-connect after any sequence of P
removing and reconnecting both PV and
AC power
b)..- The inverter continues to operate P
- the residual current monitoring system P
operates properly under single fault
condition
- Indicates a fault in accordance with §13.9 P
c) ..- The inverter continues to operate regardless N/A
of loss of residual current monitoring functionality
- not re-connect after any sequence of N/A
removing and reconnecting PV power
- not re-connect after any sequence of N/A
removing and reconnecting AC power
- not re-connect after any sequence of N/A
removing and reconnecting both PV and
AC power
- Indicates a fault in accordance with §13.9 N/A
4.4.4.15.2 Fault-tolerance of automatic disconnecting means P
4.4.4.15.2. The means provided for automatic disconnection P
1 of a grid-interactive inverter from the mains shall:
- disconnect all grounded current-carrying P
IEC 62109-2
Clause Requirement Test Result Remark Verdict

conductors from the mains


- disconnect all ungrounded current-carrying P
conductors from the mains
- be such that with a single fault applied to the See appended table P
disconnection means or to any other location 4.4.4.15.2 Fault-tolerance of
in the inverter, at least basic insulation or automatic disconnecting
simple separation is maintained between the
PV array and the mains when the
disconnecting means is intended to be in the
open state.
4.4.4.15.2. Design of insulation or separation complies with P
2 requirements of 7.3.7 of Part 1: report here Part 1
comment and verdict.
4.4.4.15.2. For non-isolated inverter, automatic checking of (see appended table) P
3 the isolation provided by a disconnect means after
single fault.
If the check fail: P

- any still-functional disconnection means shall


be left in the open position
- at least basic or simple separation shall be P
maintained between the PV input and the
mains
- the inverter shall not start operation P

- the inverter shall indicate a fault in P


accordance with 13.9
4.4.4.16 A stand-alone inverter with a transfer switch to Stand-alone mode was P
transfer AC loads from the mains or other AC checked by the tests
bypass source to the inverter output: accordingly for model:
EA5KHD
- shall continue to operate normally P
- shall not present a risk of fire as the result of P
an out-of-phase transfer
- shall not present a risk of shock as the result P
of an out-of-phase transfer
- And having control preventing switching: P
components
4.4.4.17 Cooling system failure Blanketing test See appended test table P
Cooling system failure
No hazards according to the criteria of sub-clause
Blanketing test.
4.4.3 of Part 1 shall result from blanketing the
inverter.
This test is not required for inverters restricted to
IEC 62109-2
Clause Requirement Test Result Remark Verdict

use only in closed electrical operating areas.


Test stop condition: time duration value or P

4.7 Electrical ratings tests P


4.7.4 Stand-alone Inverter AC output voltage and frequency P
4.7.4.1 General P
4.7.4.2 Steady state output voltage at nominal DC input (See attached table) P
The steady-state AC output voltage shall not be
less than 90 % or more than 110 % of the rated
nominal voltage with the inverter supplied with its
nominal value of DC input voltage.
4.7.4.3 Steady state output voltage across the DC input (See attached table) P
range
The steady-state AC output voltage shall not be
less than 85 % or more than 110 % of the rated
nominal voltage with the inverter supplied with
any value within the rated range of DC input
voltage.
4.7.4.4 Load step response of the output voltage at (See attached table) P
nominal DC input
The AC output voltage shall not be less than 85 %
or more than 110 % of the rated nominal voltage
for more than 1,5 s after application or removal of
a resistive load.
4.7.4.5 Steady state output frequency (See attached table) P
The steady-state AC output frequency shall not
vary from the nominal value by more than +4 %
or 6 %.
4.7.5 Stand-alone inverter output voltage waveform P
4.7.5.1 General P
4.7.5.2 The AC output voltage waveform of a sinusoidal (See attached table) P
output stand-alone inverter shall have a total
harmonic distortion (THD) not exceeding of 10 %
and no individual harmonic at a level exceeding
6 %.
4.7.5.3 Non-sinusoidal output waveform requirements N/A
4.7.5.3.1 General N/A
4.7.5.3.2 The total harmonic distortion (THD) of the voltage N/A
waveform shall not exceed 40 %.
4.7.5.3.3 The slope of the rising and falling edges of the N/A
IEC 62109-2
Clause Requirement Test Result Remark Verdict

positive and negative half-cycles of the voltage


waveform shall not exceed 10 V/µs measured
between the points at which the waveform has a
voltage of 10 % and 90 % of the peak voltage for
that half-cycle.
4.7.5.3.4 The absolute value of the peak voltage of the N/A
positive and negative half-cycles of the waveform
shall not exceed 1,414 times 110 % of the RMS
value of the rated nominal AC output voltage.
4.7.5.4 Information requirements for non-sinusoidal N/A
waveforms
The instructions provided with a stand-alone
inverter not complying with 4.7.5.2 shall include
the information in 5.3.2.6.
4.7.5.5 Output voltage waveform requirements for inverters for dedicated loads. N/A
For an inverter that is intended only for use with a known dedicated load, the
following requirements may be used as an alternative to the waveform
requirements in 4.7.5.2 to 4.7.5.3.
The combination of the inverter and dedicated N/A
load shall be evaluated to ensure that the output
waveform does not cause any hazards in the load
equipment and inverter, or cause the load
equipment to fail to comply with the applicable
product safety standards.
The inverter shall be marked with symbols 9 and N/A
15 of Table C.1 of Part 1.
The installation instructions provided with the N/A
inverter shall include the information in 5.3.2.13.
4.8 Additional tests for grid-interactive inverters P
4.8.1 General requirements regarding inverter isolation P
and array grounding
- Ungrounded. P

- Transformer-less type. P

4.8.2 Array insulation resistance detection for inverters Ungrounded. P


for ungrounded and functionally grounded arrays
4.8.2.1 Array insulation resistance detection for inverters P
for ungrounded arrays
Inverter shall have means to measure DC P
insulation resistance from PV input (array) to
ground before starting operation
Or Inverter shall be provided with instruction in N/A
IEC 62109-2
Clause Requirement Test Result Remark Verdict

accordance with 5.3.2.11.


Measured DC insula P
Inverter measurement circuit shall be capable of The limit of the PV array P
detecting insulation resistance below the limit insulation resistance:
Vmax PV =550 Vd.c.
value R= Vmax/30mA under normal conditions
(see appended table)
Inverter measurement circuit shall be capable of
detecting insulation resistance below the limit
value R= Vmax/30mA with ground fault in the PV
array
Isolated inverters shall indicate a fault if the P
insulation resistance is less than the limit value
Isolated inverter fault indication maintained until P
insulation resistance has recovered to a value
higher than the limit value
Non-isolated inverters, or inverters with isolation not complying with the leakage P
current limits in the minimum inverter isolation requirements in Table 30:
- shall indicate a fault in accordance with 13.9 P
- shall not connect to the mains P
4.8.2.2 Array insulation resistance detection for inverters N/A
for functionally grounded arrays
a-1)The value of the total resistance, including N/A
the intentional resistance for array functional
grounding, the expected insulation resistance of
the array to ground, and the resistance of any
other networks connected to ground (for example
measurement networks) must not be lower than R
= (VMAX PV/30 mA) ohms.
a-2) The installation instructions shall include the N/A
information required in 5.3.2.12.
b-1) As an alternative to a), or if a resistor value N/A
lower than in a) is used, the inverter shall
incorporate means to detect, during operation, if
the total current through the resistor and any
networks (for example measurement networks) in
parallel with it, exceeds the residual current
values and times in Table 31
b-2) Inverter shall either disconnect the resistor or N/A

b-3) If the inverter is a non-isolated inverter, or N/A


has isolation not complying with the leakage
current limits in the minimum inverter isolation
requirements in Table 30, it shall also disconnect
IEC 62109-2
Clause Requirement Test Result Remark Verdict

from the mains.


c) The inverter shall have means to measure the N/A
DC insulation resistance from the PV input to
ground before starting operation, in accordance
with 4.8.2.1.
4.8.3 Array residual current detection P
4.8.3.1 General P
4.8.3.2 30 mA touch current type test for isolated Transformer- less type N/A
inverters
4.8.3.3 Fire hazard residual current type test for isolated Transformer- less type N/A
inverters
4.8.3.4 N/A
- The requirement for additional protection in N/A
4.8.3.1 can be met by provision of an RCD
with a residual current setting of 30 mA,
located between the inverter and the mains.
- The selection of the RCD type to ensure N/A
compatibility with the inverter must be made
according to rules for RCD selection in Part 1.
- The RCD provided integral to the inverter, or N/A
- The RDC provided by the installer if details of N/A
the rating, type, and location for the RCD are
given in the installation instructions per
5.3.2.9.
4.8.3.5 Protection by residual current monitoring P
4.8.3.5.1 General P
Where required by Table 30, the inverter shall P
provide residual current monitoring that functions
whenever the inverter is connected to the mains
with the automatic disconnection means closed.
The residual current monitoring means shall P
measure the total (both a.c. and d.c. components)
RMS current.
As indicated in Table 30 for different inverter P
types, array types, and inverter isolation levels,
detection may be required for excessive
continuous residual current, excessive sudden
changes in residual current, or both, according to
the following limits:
a) Continuous residual current: The inverter shall disconnect within 0,3 s and P
indicate a fault in accordance with 13.9 if the continuous residual current exceeds:
IEC 62109-2
Clause Requirement Test Result Remark Verdict

- maximum 300 mA for inverters with P

- maximum 10 mA per kVA of rated continuous N/A


output power for inverters with continuous
output power rating > 30 kVA.
The inverter may attempt to re-connect if the
array insulation resistance meets the limit in 4.8.2.
b) Sudden changes in residual current: The P
inverter shall disconnect from the mains within the
time specified in Table 31
The inverter indicates a fault in accordance with P
13.9, if a sudden increase in the RMS residual
current is detected exceeding the value in the
table.
The inverter may attempt to re-connect if the
array insulation resistance meets the limit in 4.8.2.
4.8.3.5.2 Test for detection of excessive continuous P
residual current: test repeated 5 times and time to
disconnect shall not exceed 0,3 s.
4.8.3.5.3 Test for detection of sudden changes in residual P
current repeated 5 times and each of the 5 results
shall not exceed the time limit indicated in for
each row (30mA, 60mA and150mA) of Table 31.
4.8.3.6 Systems located in closed electrical operating N/A
areas
The protection against shock hazard is not N/A
required if the installation information provided
with the inverter indicates the restriction for use in
a closed electrical operating area, and
Installation information indicates what forms of N/A
shock hazard protection are and are not provided
integral to the inverter, in accordance with 5.3.2.7.
The inverter shall be marked as in 5.2.2.6. N/A
5 MARKING AND DOCUMENTATION P
5.1 Marking P
5.1.4 Equipment ratings P
PV input ratings: See marking label. P
- Vmax PV (absolute maximum) (d.c. V) P
- Isc PV (absolute maximum) (d.c. A) P
a.c. output ratings: See marking label. P
IEC 62109-2
Clause Requirement Test Result Remark Verdict

- Voltage (nominal or range) (a.c. V) P


- Current (maximum continuous) (a.c. A) P
- Frequency (nominal or range) (Hz) P
- Power (maximum continuous) (W or VA) P
- Power factor range P
a.c input ratings: See marking label. P
- Voltage (nominal or range) (a.c. V) P
- Current (maximum continuous) (a.c. A) P
- Frequency (nominal or range) (Hz) P
d.c. output ratings: P
- Voltage (nominal or range) (d.c. V) P
- Current (maximum continuous) (d.c. A) P
Protective class (I or II or III) I P
Ingress protection (IP) rating per part 1 IP 20 P
An inverter that is adjustable for more than one N/A
nominal output voltage shall be marked to indicate
the particular voltage for which it is set when
shipped from the factory.
5.2 Warning markings P
5.2.2 Content for warning markings P
5.2.2.6 Inverters for closed electrical operating areas N/A
Where required by 4.8.3.6, an inverter not N/A
provided with full protection against shock hazard
on the PV array shall be marked with a warning
that the inverter is only for use in a closed
electrical operating area, and referring to the
installation instructions.
5.3 Documentation P
5.3.2 Information related to installation P
5.3.2.1 Ratings. Subclause 5.3.2 of Part 1 requires the documentation to include ratings P
information for each input and output. For inverters this information shall be as in
Table 33 below. Only those ratings that are applicable based on the type of
inverter are required.
PV input quantities : See user manual P
- Vmax PV (absolute maximum) (d.c. V) P
- PV input operating voltage range (d.c. V) P
- Maximum operating PV input current (d.c. A) P
IEC 62109-2
Clause Requirement Test Result Remark Verdict

- Isc PV (absolute maximum) (d.c. A) P


- Max. inverter backfeed current to the array P
(a.c. or d.c. A)
a.c. output quantities: P
- Voltage (nominal or range) (a.c. V) P
- Current (maximum continuous) (a.c. A) P
- Current (inrush) (a.c. A, peak and duration) P
- Frequency (nominal or range) (Hz) P
- Power (maximum continuous) (W or VA) P
- Power factor range P
- Maximum output fault current (a.c. A, peak P
and duration or RMS)
- Maximum output overcurrent protection (a.c. P
A)
a.c. input quantities: P
- Voltage (nominal or range) (a.c. V) P
- Current (maximum continuous) (a.c. A) P
- Current (inrush) (a.c. A, peak and duration) P
- Frequency (nominal or range) (Hz) P
d.c input (other than PV) quantities: P
- Voltage (nominal or range) (d.c. V) P
- Nominal battery voltage (d.c. V) P
- Current (maximum continuous) (d.c. A) P
d.c. output quantities: P
- Voltage (nominal or range) (d.c. V) P
- Nominal battery voltage (d.c. V) P
- Current (maximum continuous) (d.c. A) P
Protective class (I or II or III) I P
Ingress protection (IP) rating per part 1 IP20 P
5.3.2.2 Grid-interactive inverter setpoints Non-adjustable to operator, N/A
setted by manufacture before
shipment
IEC 62109-2
Clause Requirement Test Result Remark Verdict

For a grid-interactive unit with field adjustable trip N/A


points, trip times, or reconnect times, the
presence of such controls, the means for
adjustment, the factory default values, and the
limits of the ranges of adjustability shall be
provided in the documentation for the PCE or in
other format such as on a website. Provided
.
The setting of field adjustable setpoints shall be N/A
accessible rom the PCE
5.3.2.3 Transformers and isolation Transformer-less N/A
whether an internal isolation transformer is N/A
provided, and if so, what level of insulation
(functional, basic, reinforced, or double) is
provided by that transformer. The instructions
shall also indicate what the resulting installation
requirements are regarding such things as
earthing or not earthing the array, providing
external residual current detection devices, etc.
An inverter shall be provided with information to the installer regarding: N/A
- providing of internal isolation transformer N/A
- the level of insulation (functional, basic, N/A
reinforced, or double)
The instructions shall also indicate what the resulting installation requirements are N/A
regarding:
- earthing or not earthing the array Not earthing N/A
- providing external residual current detection N/A
devices
- requiring an external isolation transformer, N/A
5.3.2.4 Transformers required but not provided N/A
An inverter that requires an external isolation transformer not provided with the
unit, shall be provided with instructions that specify, and for the external isolation
N/A
transformer with which it is intended to be used:
- the configuration type N/A
- electrical ratings N/A
- environmental ratings N/A
5.3.2.5 PV modules for non-isolated inverters P
Non-isolated inverters shall be provided with P
installation instructions that require PV modules
that have an IEC 61730 Class A rating
IEC 62109-2
Clause Requirement Test Result Remark Verdict

If the maximum AC mains operating voltage is N/A


higher than the PV array maximum system
voltage then the instructions shall require PV
modules that have a maximum system voltage
rating based upon the AC mains voltage.
5.3.2.6 Non-sinusoidal output waveform information N/A
The instruction manual for a stand-alone inverter not complying with 4.7.5.2 shall N/A
include a warning that:
- the waveform is not sinusoidal, N/A
- some loads may experience increased N/A
heating,
- the user should consult the manufacturers of N/A
the intended load equipment before operating
that load with the inverter
The inverter manufacturer shall provide information regarding: N/A
- what types of loads may experience increased N/A
heating
- recommendations for maximum operating N/A
times with such loads
The inverter manufacturer shall specify for the waveforms as determined by the N/A
testing in 4.7.5.3.2 through 4.7.5.3.4.:
- THD N/A
- slope N/A
- peak voltage N/A
5.3.2.7 Systems located in closed electrical operating N/A
areas
Where required by 4.8.3.6, an inverter not provided with full protection against N/A
shock hazard on the PV array shall be provided with installation instructions:
- requiring that the inverter and the array must N/A
be installed in closed electrical operating
areas
- indicating which forms of shock hazard N/A
protection are and are not provided integral to
the inverter (for example the RCD, isolation
transformer complying with the 30 mA touch
current limit, or residual current monitoring for
sudden changes)
5.3.2.8 Stand-alone inverter output circuit bonding P
Where required by 7.3.10, the documentation for an inverter shall include the P
following:
IEC 62109-2
Clause Requirement Test Result Remark Verdict

- if output circuit bonding is required but is not N/A


provided integral to the inverter, the required
means shall be described in the installation
instructions, including which conductor is to be
bonded and the required current carrying
capability or cross-section of the bonding
means;
- if the output circuit is intended to be floating, P
the documentation for the inverter shall
indicate that the output is floating.
5.3.2.9 N/A
Where the requirement for additional protection in N/A
4.8.3.1 is met by requiring an RCD that is not
provided integral to the inverter, as allowed by
4.8.3.4, the installation instructions shall state the
need for the RCD,.
and shall specify its rating, type, and required N/A
circuit location
5.3.2.10 Remote indication of faults P
The installation instructions shall include an P
explanation of how to properly make connections
to (where applicable), and use, the electrical or
electronic fault indication required by 13.9.
5.3.2.11 External array insulation resistance measurement N/A
and response
The installation instructions for an inverter for use with ungrounded arrays that N/A
does not incorporate all the aspects of the insulation resistance measurement and
response requirements in 4.8.2.1, must include:
- for isolated inverters: an explanation of what N/A
aspects of array insulation resistance
measurement and response are not provided, and
- an instruction to consult local regulations to N/A
determine if any additional functions are
required or not;
- for non-isolated inverters: an explanation of N/A
what external equipment must be provided in
the system, and
- what the setpoints and response implemented N/A
by that equipment must be, and:
- how that equipment is to be interfaced with N/A
the rest of the system.
5.3.2.12 Array functional grounding information N/A
IEC 62109-2
Clause Requirement Test Result Remark Verdict

Where approach a) of 4.8.2.2 is used, the installation instructions for the inverter N/A
shall include all of the following:
a) the value of the total resistance between the N/A
PV circuit and ground integral to the

b) the minimum array insulation resistance to N/A


ground that system designer or installer must
meet when selecting the PV panel and system
design, based on the minimum value that the
design of the PV functional grounding in the

c) the minimum value of the total resistance R = N/A


VMAX PV/30 mA that the system must meet,
with an explanation of how to calculate the

d) a warning that there is a risk of shock hazard N/A


if the total minimum resistance requirement is
not met.
5.3.2.13 Stand-alone inverters for dedicated loads N/A
Where the approach of 4.7.5.5 is used, the N/A
installation instructions for the inverter shall
include a warning that the inverter is only to be
used with the dedicated load for which it was
evaluated, and
shall specify the dedicated load. N/A
5.3.2.14 Identification of firmware version(s) P
An inverter utilizing firmware for any protective P
functions shall provide means to identify the
firmware version.
This can be a marking, but the information can The firmware version can be P
also be provided by a display panel, identified on the display
communications port or any other type of user panel.

7 Protection against electric shock and energy hazards P


7.3 Protection against electric shock P
7.3.10 Additional requirements for stand-alone inverters P
One circuit conductor bonded to earth to create a IT system, neutral was N/A
grounded conductor and an earthed system. floating.
The means used to bond the grounded conductor N/A
to protective earth provided within the inverter or
IEC 62109-2
Clause Requirement Test Result Remark Verdict

as part of the installation P


If not provided integral to the inverter, the required P
means shall be described in the installation
instructions as per 5.3.2.8.
The means used to bond the grounded conductor P
to protective earth shall comply with the
requirements for protective bonding in Part 1,
If the bond can only ever carry fault currents in P
stand-alone mode, the maximum current for the
bond is determined by the inverter maximum
output fault current.
Output circuit bonding arrangements shall ensure P
that in any mode of operation, the system only
has the grounded circuit conductor bonded to
earth in one place at a time..
Switching arrangements may be used, in which N/A
case the switching device used is to be subjected
to the bond impedance test along with the rest of
the bonding path
Inverters intended to have a circuit conductor P
bonded to earth shall not impose any normal
current on the bond except for leakage current.
Outputs that are intentionally floating with no P
circuit conductor bonded to ground, must not have
any voltages with respect to ground that are a
shock hazard in accordance with Clause 7 of
Parts 1 and 2.
The documentation for the inverter shall indicate P
that the output is floating as per 5.3.2.8.
7.3.11 Functionally grounded arrays N/A
All PV conductors in a functionally grounded array N/A
shall be treated as being live parts with respect to
protection against electric shock.

9 Protection against fire hazards P


9.3 Short-circuit and overcurrent protection P
9.3.4 Inverter backfeed current onto the array P
The backfeed current testing and documentation requirements in Part 1 apply, P
including but not limited to the following.
Inverter backfeed current onto the PV array P
IEC 62109-2
Clause Requirement Test Result Remark Verdict

This inverter backfeed current value shall be P


provided in the installation instructions regardless
of the value of the current, in accordance with
Table 33.

13 Physical requirements P
13.9 Fault indication P
Where this Part 2 requires the inverter to indicate a fault, both of the following P
shall be provided:
a) a visible or audible indication, integral to the P
inverter, and detectable from outside the
inverter, and
b) an electrical or electronic indication that can P
be remotely accessed and used.
The installation instructions shall include P
information regarding how to properly make
connections (where applicable) and use the
electrical or electronic means in b) above, in
accordance with 5.3.2.10.
IEC 62109-2
Clause Requirement Test Result Remark Verdict

4.4.4 TABLE: Single fault condition to be applied P

Ambient temperature ( C) ................................. : 25 C


Power source for EUT: Manufacturer, model/type,
--
output rating ...................................................... :
4.4.4.15.1 Fault-tolerance of residual current monitoring
Component Fault Supply voltage Test time Fuse # Fuse Observation
No. (V) current
(A)
The fault applied during the
unit operation. After applied
CT1 (pin 8 to the fault, the PV input
Short PV: 360Vd.c.
pin 9) on PV 5min -- -- shutdown and LCD display
circuit AC: 230Va.c.
board
damage. No hazard.
Recoverable.
The fault applied during the
unit operation. After applied
CT2 (pin 8 to the fault, the PV input
Short PV: 360Vd.c.
pin 9) on PV 5min -- -- shutdown and LCD display
circuit AC: 230Va.c.
board
damage. No hazard.
Recoverable.
The fault applied during the
unit operation. After applied
Open PV: 360Vd.c.
R22 5min -- -- the fault, the unit operated
circuit AC: 230Va.c.
as normal. No damage. No
hazard. Recoverable.
The fault applied during the
unit operation. After applied
the fault, the PV input
R213 on PV Open PV: 360Vd.c. shutdown and LCD display
5min -- --
board circuit AC: 230Va.c.
turn into bypass mode. No
damage. No hazard.
Recoverable.
The fault applied during the
unit operation, the unit
operated as normal after
applied the fault. When the
RLY3 (pin 4 to Short PV: 360Vd.c. unit shutdown and restarted,
5min -- --
pin 5) circuit AC: 230Va.c. the unit could not restart and
LCD display alarmed

No damage. No hazard.
Recoverable.
IEC 62109-2
Clause Requirement Test Result Remark Verdict

The fault applied during the


unit operation, the unit
operated as normal after
applied the fault. When the
RLY11 (pin 4 to Short PV: 360Vd.c. unit shutdown and restarted,
5min -- --
pin 5) circuit AC: 230Va.c. the unit could not restart and
LCD display alarmed

No damage. No hazard.
Recoverable.
The fault applied during the
unit operation. After applied
U9 (VCC to the fault, the unit shutdown
Short PV: 360Vd.c.
GEN) on control 5min -- -- immediately and LCD
circuit AC: 230Va.c.
board display alarmed " SYS CAN
. Q3 was damaged. No
hazard. Unrecoverable.

The fault applied during the


T9 (pin14 after
unit operation. After applied
D87 to pin 11) Short PV: 360Vd.c.
5min -- -- the fault, the unit shutdown
on DC-DC circuit AC: 230Va.c.
immediately and LCD
board
blacked. No damage. No
hazard. Recoverable.
The fault applied during the
unit operation. After applied
U15 (pin 3 to pin
Short PV: 360Vd.c. the fault, the unit shutdown
5) on DC-DC 5min -- --
circuit AC: 230Va.c. immediately and LCD
board
blacked. No damage. No
hazard. Recoverable.
The fault applied during the
unit operation. After applied
the fault, the unit operated
U25 (pin 7 to
Short PV: 360Vd.c. as normal. When the PV
pin 8) on control 5min -- --
circuit AC: 230Va.c. input was removed, the LCD
board
blacked after a few seconds.
No damage. No hazard.
Recoverable.
Supplementary information:
IEC 62109-2
Clause Requirement Test Result Remark Verdict

4.4.4 TABLE: Single fault condition to be applied P

Ambient temperature ( C) .................................. : 25 C


Power source for EUT: Manufacturer, model/type,
--
output rating ...................................................... :
4.4.4.15.2 Fault-tolerance of automatic disconnecting means
Component Fault Grid voltage Test time Fuse # Fuse Observation
No. (V) current
(A)
The fault applied during the unit
operation, the unit operated as
normal after applied the fault.
When the unit shutdown and
Short PV: 360Vd.c.
RLY5 5min -- -- restarted, the unit could not
circuit AC: 230Va.c.
restart and LCD display alarmed

damage. No hazard.
Recoverable.
The fault applied during the unit
operation, the unit operated as
normal after applied the fault.
When the unit shutdown and
Short PV: 360Vd.c.
RLY6 5min -- -- restarted, the unit could not
circuit AC: 230Va.c.
restart and LCD display alarmed

damage. No hazard.
Recoverable.
The fault applied during the unit
operation, the unit operated as
normal after applied the fault.
When the unit shutdown and
Short PV: 360Vd.c.
RLY8 5min -- -- restarted, the unit could not
circuit AC: 230Va.c.
restart and LCD display alarmed

damage. No hazard.
Recoverable.
The fault applied during the unit
operation, the unit operated as
normal after applied the fault.
When the unit shutdown and
Short PV: 360Vd.c.
RLY10 5min -- -- restarted, the unit could not
circuit AC: 230Va.c.
restart and LCD display alarmed

damage. No hazard.
Recoverable.
Check that the relays fulfil the basic insulation or simple separation
Yes
based on the PV circuit working voltage.
Each active phase can be switched. (L and N) Yes
Supplementary information: The investor can disconnect from grid during a relay occurred a single failure.
IEC 62109-2
Clause Requirement Test Result Remark Verdict

4.4.4.17 Cooling system failure Blanketing test P

Test voltage (Vd.c.) ........................ 360Vd.c.


Test current (Id.c.) 12Ad.c., 12Ad.c.
Test voltage (Va.c.) ........................ 230Va.c.
Test current (Ia.c.) 21.7Aa.c.
tamb1 ( C) ........................................ 26.0 C
tamb2 ( C) ........................................ 26.0 C
Test
7 hours

maximum temperature T of part/at:: T ( C) Tmax ( C)

Enclosure outer surface, rear 53.6 90


Enclosure outer surface, front 57.5 90
Enclosure outer surface, left side 51.0 90
Mounting surfaces 56.9 90
Supplementary information:
Operation mode: PV supply to grid and battery (5.5kW), during the test, no hazard.

4.7.4.2 & Steady state output voltage at nominal DC input & P


4.7.4.3 & Steady state output voltage across the DC input range &
4.7.4.4 & Load step response of the output voltage at nominal DC input &
4.7.4.5 Steady state output frequency
AC output U (V) Frequency (Hz) Condition/status Comments
L1 L2 L1 L2 L1 L2
232.0 -- -- 50.00 -- -- Without load PV supply the AC load,
Resistive load at PV voltage: 250 Vd.c.
231.7 -- -- 50.01 -- --
application
231.8 -- -- 49.98 -- -- Resistive load removal
232.0 -- -- 49.99 -- -- Without load PV supply the AC load,
Resistive load at PV voltage: 360 Vd.c.
231.8 -- -- 50.01 -- --
application
231.8 -- -- 50.01 -- -- Resistive load removal
232.3 -- -- 49.99 -- -- Without load
Resistive load PV supply the AC load,
231.7 -- -- 49.99 -- -- at PV voltage: 450 Vd.c.
application
232.3 50.01 Resistive load removal
IEC 62109-2
Clause Requirement Test Result Remark Verdict

AC output U (V) Frequency (Hz) Condition/status Comments


L1 L2 L3 L1 L2 L3
232.1 -- -- 49.98 -- -- Without load Battery supply the AC
load, and battery supply
Resistive load at 46.4 Vd.c..
232.4 -- -- 49.99 -- --
application
Battery type: Lithium.
231.8 -- -- 50.00 -- -- Resistive load removal

232.2 -- -- 50.00 -- -- Without load Battery supply the AC


load, and battery supply
Resistive load at 51.2 Vd.c..
232.1 -- -- 50.00 -- --
application
Battery type: Lithium.
231.8 -- -- 50.01 -- -- Resistive load removal

232.0 -- -- 50.01 -- -- Without load Battery supply the AC


load, and battery supply
Resistive load at 57.6 Vd.c.
231.7 -- -- 50.00 -- --
application
Battery type: Lithium.
231.9 -- -- 49.99 -- -- Resistive load removal

232.3 -- -- 49.99 -- -- Without load Battery supply the AC


load, and battery supply
Resistive load at 40 Vd.c..
232.1 -- -- 49.99 -- --
application
Battery type: Lead-acid.
232.0 -- -- 50.01 -- -- Resistive load removal

232.3 -- -- 50.00 -- -- Without load Battery supply the AC


load, and battery supply
Resistive load at 48 Vd.c..
232.4 -- -- 50.00 -- --
application
Battery type: Lead-acid.
232.0 -- -- 50.00 -- -- Resistive load removal

232.4 -- -- 50.00 -- -- Without load Battery supply the AC


load, and battery supply
Resistive load at 58 Vd.c.
231.9 -- -- 49.99 -- --
application
Battery type: Lead-acid.
232.6 -- -- 50.00 -- -- Resistive load removal

Supplementary information:
IEC 62109-2
Clause Requirement Test Result Remark Verdict

4.7.5.2 Sinusoidal output voltage waveform requirements P

Model EA5KHD

P/ Prated : % of rated output power Limits (% of


Harmonic.
Nr.(U) 5% 50% 100% Fundamental)

2 0.116% 0.018% 0.005% 6%


3 0.148% 0.931% 0.991% 6%
4 0.054% 0.011% 0.007% 6%
5 0.199% 0.490% 0.570% 6%
6 0.025% 0.014% 0.002% 6%
7 0.083% 0.296% 0.396% 6%
8 0.031% 0.010% 0.003% 6%
9 0.049% 0.192% 0.278% 6%
10 0.015% 0.009% 0.005% 6%
11 0.045% 0.122% 0.203% 6%
12 0.014% 0.001% 0.005% 6%
13 0.053% 0.081% 0.171% 6%
14 0.013% 0.021% 0.007% 6%
15 0.051% 0.055% 0.126% 6%
16 0.016% 0.015% 0.002% 6%
17 0.042% 0.022% 0.103% 6%
18 0.009% 0.007% 0.007% 6%
19 0.059% 0.018% 0.086% 6%
20 0.026% 0.012% 0.006% 6%
21 0.052% 0.012% 0.087% 6%
22 0.019% 0.003% 0.010% 6%
23 0.080% 0.014% 0.078% 6%
24 0.042% 0.010% 0.012% 6%
25 0.093% 0.012% 0.041% 6%
26 0.011% 0.025% 0.011% 6%
27 0.089% 0.016% 0.028% 6%
28 0.024% 0.042% 0.015% 6%
29 0.078% 0.016% 0.017% 6%
30 0.014% 0.007% 0.006% 6%
31 0.044% 0.008% 0.017% 6%
IEC 62109-2
Clause Requirement Test Result Remark Verdict

32 0.015% 0.007% 0.007% 6%


33 0.030% 0.022% 0.014% 6%
34 0.018% 0.003% 0.006% 6%
35 0.025% 0.014% 0.011% 6%
36 0.005% 0.006% 0.005% 6%
37 0.017% 0.014% 0.007% 6%
38 0.004% 0.004% 0.005% 6%
39 0.012% 0.007% 0.004% 6%
40 0.008% 0.011% 0.003% 6%
THD (2-
0.379% 1.125% 1.291% 10%
40)
Supplementary information: PV supply to AC load output

4.7.5.2 Sinusoidal output voltage waveform requirements P

Model EA5KHD

P/ Prated : % of rated output power Limits (% of


Harmonic.
Nr.(U) 5% 50% 100% Fundamental)

2 0.129% 0.009% 0.011% 6%


3 0.164% 0.952% 0.992% 6%
4 0.049% 0.019% 0.004% 6%
5 0.229% 0.508% 0.576% 6%
6 0.024% 0.009% 0.003% 6%
7 0.046% 0.303% 0.377% 6%
8 0.022% 0.012% 0.010% 6%
9 0.042% 0.197% 0.272% 6%
10 0.022% 0.016% 0.005% 6%
11 0.051% 0.136% 0.210% 6%
12 0.016% 0.004% 0.006% 6%
13 0.054% 0.088% 0.159% 6%
14 0.020% 0.015% 0.017% 6%
15 0.049% 0.061% 0.131% 6%
16 0.009% 0.006% 0.012% 6%
17 0.046% 0.048% 0.102% 6%
18 0.018% 0.011% 0.011% 6%
19 0.061% 0.027% 0.078% 6%
IEC 62109-2
Clause Requirement Test Result Remark Verdict

20 0.012% 0.011% 0.003% 6%


21 0.064% 0.024% 0.068% 6%
22 0.039% 0.008% 0.017% 6%
23 0.071% 0.013% 0.048% 6%
24 0.033% 0.044% 0.015% 6%
25 0.088% 0.013% 0.041% 6%
26 0.010% 0.017% 0.030% 6%
27 0.082% 0.013% 0.020% 6%
28 0.018% 0.024% 0.010% 6%
29 0.067% 0.016% 0.018% 6%
30 0.012% 0.021% 0.011% 6%
31 0.049% 0.022% 0.006% 6%
32 0.025% 0.018% 0.008% 6%
33 0.036% 0.021% 0.006% 6%
34 0.011% 0.009% 0.007% 6%
35 0.022% 0.015% 0.008% 6%
36 0.002% 0.007% 0.004% 6%
37 0.015% 0.020% 0.003% 6%
38 0.004% 0.004% 0.003% 6%
39 0.008% 0.015% 0.002% 6%
40 0.011% 0.007% 0.004% 6%
THD (2-
0.396% 1.157% 1.284% 10%
40)
Supplementary information: Battery supply to AC load output

4.8.2 TABLE: Array insulation resistance detection for inverters for ungrounded and P
functionally grounded arrays
4.8.2.1 Array insulation resistance detection for inverters for ungrounded arrays P
DC Voltage DC Voltage for Resistance between Required Insulation Result
below minimum inverter begin ground and PV input resistance
operating voltage operation terminal R = (VMAX PV / 30mA)
(V) (V)
PV+, (tracker 1)
The unit could not
operate and LCD display
115 150 16500 18333 INSU.TO
GROUND IMPE.
OCCUR
IEC 62109-2
Clause Requirement Test Result Remark Verdict

PV+, (tracker 2)
The unit could not
operate and LCD display
115 150 16500 18333 INSU.TO
GROUND IMPE.
OCCUR
PV-, (tracker 1)
The unit could not
operate and LCD display
115 150 16500 18333 INSU.TO
GROUND IMPE.
OCCUR
PV-, (tracker 2)
The unit could not
operate and LCD display
115 150 16500 18333 INSU.TO
GROUND IMPE.
OCCUR
Note:
For isolated inverters, shall indicate a fault in accordance with 13.9 (operation is allowed); the fault indication
shall be maintained until the array insulation resistance has recovered to a value higher than the limit above
For non-isolated inverters, or inverters with isolation not complying with the leakage current limits in the
minimum inverter isolation requirements in Table 30, shall indicate a fault in accordance with 13.9, and shall
not connect to the mains; the inverter may continue to make the measurement, may stop indicating a fault
and may connect to the mains if the array insulation resistance has recovered to a value higher than the limit
above.
It is not required to test all PV input terminals if analysis of the design indicates that one or more terminals
can be expected to have the same result, for example where multiple PV string inputs are in parallel.
Supplementary information:
1. The setting isolation resistor value is 20 k .
2. All above tests indicate a fault in accordance with clause 13.9

4.8.3.5 TABLE: Protection by residual current monitoring P

Test conditions: See below

4.8.3.5.2 Test for detection of excessive continuous residual current P

PV Output Baseline Measured trigger time (ms), shall < 300 ms


Tracker Input
trigger
No. (+ or -) (Vd.c.) (Va.c., kW) (repeat 5 times)
current (mA)

1 + 360 230, 5 220 60 56 69 57 96


1 - 360 230, 5 225 67 44 57 76 67
Note:
maximum 300mA for inverters with continuous output po
maximum 10mA per kVA of rated continuous output power for inverters with continuous output power
IEC 62109-2
Clause Requirement Test Result Remark Verdict

rating > 30 kVA.


This test shall be repeated 5 times, and for all 5 tests the time to disconnect shall not exceed 300 ms.
The test is repeated for each PV input terminal. It is not required to test all PV input terminals if analysis of
the design indicates that one or more terminals can be expected to have the same result, for example
where multiple PV string inputs are in parallel.
Supplementary information:
All above tests indicate a fault in accordance with clause 13.9.

4.8.3.5 TABLE: Protection by residual current monitoring P

Test conditions: See below

4.8.3.5.3 TABLE: Test for detection of sudden changes in residual current P

PV Output Baseline Measured trigger time (ms), shall < 300 ms


Tracker Input
trigger for (30 mA); <150 ms for (60 mA); <40 ms for
No. (+ or -) (Vd.c.) (Va.c., kW) current (mA) (150 mA) (repeat 5 times)
30 mA sudden changes in residual current
1 + 360 230, 5 220 246 243 246 250 251
1 - 360 230, 5 225 260 248 265 261 249
60 mA sudden changes in residual current
1 + 360 230, 5 220 121 142 115 136 124
1 - 360 230, 5 225 135 144 138 146 142
150 mA sudden changes in residual current
1 + 360 230, 5 220 30 35 40 30 30
1 - 360 230, 5 225 32 26 35 35 36
Note:
The capacitive current is risen until disconnection.
Test condition: Ic + 30/60/150mA <= Icmax. R1 is set that 30/60/150mA Flow and switch S is closed.
Supplementary information:
t