1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

NOTES

06-P-301A/B 06-T-301 1. TYPICAL DRAWING, EQUIPMENT INSIDE VENDOR BATTERY


DEEP WELL PUMP RAW WATER TANK LIMIT AREA TO BE DETAILED BY VENDOR
A A
CAPACITY : 16.8 m³/h OPERATING PRESS. : ATM barg
POWER : 0.697 kW OPERATING TEMP. : AMB °C
SUCT/DISC : 0.0 / 4.0 barg DIMENSION (Dx H) : 1440 x 1564 mm
MATERIAL CASING / IMPELLER : - CAPACITY : 2.55 m³
MATERIAL : -

B B

06-Z-301

BY CONTRACTOR BY VENDOR (NOTE 1)

C C

06-3"-RW-001-A3A-NI
D D
SPARE 24"
MH
2" NOZZLE
2" N6
N1
3" N5
OVER FLOW
H : AUTO STOP 06 2" HHLL = 1414 3" LINE
LS
L : AUTO RUN XXX N2 N6
HLL = 914

E E

06-T-301

LLL = 855
3"-A3A M
LLLL = 355
F F

3"-A3A
3" 06-3"-RW-002-A3A-NI
N3 FILTERED WATER
2" 3"-A3A
SHT2 2024LNG-I-PR-PID-06-009
N4
EL. (HOLD) TO RESERVE OSMOSIS PACKAGE
MULTI MEDIA FILTER MULTI MEDIA FILTER

G G
REFERENCE DRAWINGS

2"-A3A

M
H H

M
06-2"-RW-003-A3A-NI
06-3"-RW-004-A3A-NI

1 10 JUNE 2024 ISSUED FOR REVIEW AGG HST ISA


REY
DRAWN CHECKED APPROVED
REV DATE DESCRIPTION PREPARED
I THIS DRAWING EMBODIES PROPRIETARY INFORMATION OF PT. ENVIROMATE TECHNOLOGY INTERNATIONAL, THIS I
DRAWING OR THE MATERIAL DESCRIBED THEREON MAY NOT BE COPIED OR DISCLOSED IN ANY FORM OR MEDIUM TO
THIRD PARTIES, OR USED FOR OTHER THAN THE PURPOSE FOR IN ANY FORM OR MEDIUM TO THIRD PARTIES, OR USED

06-P-301A/B FOR OTHER THAN THE PURPOSE FOR WHICH IT HAS BEEN PROVIDED, IN WHOLE OR IN PART IN ANY MANNER EXCEPT AS
EXPRESSLY PERMITTED BY PT. ENVIROMATE TECHNOLOGY INTERNATIONAL.

XXXX PROJECT :
RW
DEVELOPMENT AND OPERATION OF
LNG INFRASTRUCTURE SERVICE FOR
GAS POWER PLANT IN NUSA TENGGARA CLUSTER
OWNER :
J J

PT. ENVIROMATE TECHNOLOGY INTERNATIONAL

TITLE :

PIPING & INSTRUMENT DIAGRAM


K K
SERVICE WATER
FILE NAME :

KUPANG
NTS - 2024LNG-I-PR-PID-06-009 1OF3 1
SCALE JOB NO. DRAWING NO. SHT NO. REV.
A1 (841x594)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

NOTES
06-Z-301
WATER TREATMENT PACKAGE 1. TYPICAL DRAWING, EQUIPMENT INSIDE VENDOR BATTERY
LIMIT AREA TO BE DETAILED BY VENDOR
A A
SERVICE : SERVICE WATER
3
CAPACITY : 8.5 m /h

PUMP COMMON
RUNNING ALARM
HH H H H H H H H
06 06 06 06 06 06 06 06 06 06
LI AI AI XL AI PDI UA FI AI PI
001 006 006 006 006 001 006 001 007 001
LL COND PH SILICA L TURBIDITY

B B

06-Z-301
NOTE 1

C C
LCP
BIOCIDE DOSING PUMP

UCP FOR RO PACKAGE

D D

BIOCIDE TANK

06
M PI
XXX

06 OXYDATOR PUMP
PI
E XXX E

HIGH PRESSURE
PUMP A 06 06 COND 06 PH 06 SiO2
FM AI AI AI
XXX XXX XXX XXX
OXYDATOR TANK

F PRODUCT WATER F
SHT3 2024LNG-I-PR-PID-06-009
TO PRODUCT WATER TANK

06 06
PI PS
06 XXX XXX 06
PT M PI
XXX XXX

G FILTERED WATER G
SHT1 2024LNG-I-PR-PID-06-009 REFERENCE DRAWINGS
FROM MULTI MEDIA FILTER
06
PI
HIGH PRESSURE XXX
PUMP B

ACID DOSING PUMP


H 06 06 H
PI FM
XXX XXX

ACID TANK
1 10 JUNE 2024 ISSUED FOR REVIEW AGG HST ISA
REY
DRAWN CHECKED APPROVED
REV DATE DESCRIPTION PREPARED
I THIS DRAWING EMBODIES PROPRIETARY INFORMATION OF PT. ENVIROMATE TECHNOLOGY INTERNATIONAL, THIS I
DRAWING OR THE MATERIAL DESCRIBED THEREON MAY NOT BE COPIED OR DISCLOSED IN ANY FORM OR MEDIUM TO
THIRD PARTIES, OR USED FOR OTHER THAN THE PURPOSE FOR IN ANY FORM OR MEDIUM TO THIRD PARTIES, OR USED
FOR OTHER THAN THE PURPOSE FOR WHICH IT HAS BEEN PROVIDED, IN WHOLE OR IN PART IN ANY MANNER EXCEPT AS
EXPRESSLY PERMITTED BY PT. ENVIROMATE TECHNOLOGY INTERNATIONAL.

M PROJECT :
DEVELOPMENT AND OPERATION OF
LNG INFRASTRUCTURE SERVICE FOR
GAS POWER PLANT IN NUSA TENGGARA CLUSTER
OWNER :
J J
CIP TANK
CATRIDGE FILTER CIP PUMP PT. ENVIROMATE TECHNOLOGY INTERNATIONAL

TITLE :

PIPING & INSTRUMENT DIAGRAM


K K
XXXX SERVICE WATER
FILE NAME :

SW KUPANG
NTS - 2024LNG-I-PR-PID-06-009 2OF3 1
SCALE JOB NO. DRAWING NO. SHT NO. REV.
A1 (841x594)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

NOTES

06-P-302A/B 06-P-303A/B 1. TYPICAL DRAWING, EQUIPMENT INSIDE VENDOR BATTERY


FIRE WATER DISTRIBUTION PUMP UTILITY PUMP LIMIT AREA TO BE DETAILED BY VENDOR
A A
CAPACITY : 25.00 m³/h CAPACITY : 4.00 m³/h
POWER : 2.649 kW POWER : 0.871 kW
SUCT/DISC : 0.5 / 2.0 barg SUCT/DISC : 0.5 / 5.5 barg
MATERIAL CASING / IMPELLER : - MATERIAL CASING / IMPELLER : -

B B
06
PG
068

06-Z-301 06 M 3/4"-A33Y
STR FIRE WATER
NOTE 1 001 06-3"-FW-001-A33Y-NI
SHT1 2024LNG-I-PR-PID-06-010
06-4"-SW-001-A3A-NI
3"-A33Y 3"-A33Y TO FIRE WATER TANK
4"-A3A
3/4"-A3A 06-P-302A
C C

06-3"-FW-006-A33Y-NI
D D
06
PG
069

06 M 3/4"-A33Y
STR
PRODUCT WATER 006
SHT2 2024LNG-I-PR-PID-06-009 06-4"-SW-004-A3A-NI 3"-A33Y 3"-A33Y
TO PRODUCT WATER TANK
4"-A3A
3/4"-A3A 06-P-302B
E E

PRODUCT TANK

F 06-4"-SW-001-A3A-NI F

EL. (HOLD)

06
PG
060

G
06 M 3/4"-A3A
G
STR
006 06-2"-SW-006-A3A-NI REFERENCE DRAWINGS
06-2"-SW-006-A3A-NI 2"-A3A 2"-A3A
2"-A3A 06-1 1/2"-SW-007-A3A-NI
3/4"-A3A
SERVICE WATER
06-P-303A - -
1 1/2"-A3A TO JETTY

SERVICE WATER
H 06-1 1/2"-SW-008-A3A-NI H
- -
1 1/2"-A3A TO DIESEL TANK AREA

06-2"-SW-006-A3A-NI
SERVICE WATER
06-1 1/2"-SW-009-A3A-NI
- -
1 1/2"-A3A TO OFFICE

1 10 JUNE 2024 ISSUED FOR REVIEW AGG HST ISA


REY
SERVICE WATER
06-1 1/2"-SW-060-A3A-NI REV DATE DESCRIPTION
DRAWN CHECKED APPROVED
- - PREPARED
I 1 1/2"-A3A TO CONTROL ROOM THIS DRAWING EMBODIES PROPRIETARY INFORMATION OF PT. ENVIROMATE TECHNOLOGY INTERNATIONAL, THIS I
DRAWING OR THE MATERIAL DESCRIBED THEREON MAY NOT BE COPIED OR DISCLOSED IN ANY FORM OR MEDIUM TO
THIRD PARTIES, OR USED FOR OTHER THAN THE PURPOSE FOR IN ANY FORM OR MEDIUM TO THIRD PARTIES, OR USED
FOR OTHER THAN THE PURPOSE FOR WHICH IT HAS BEEN PROVIDED, IN WHOLE OR IN PART IN ANY MANNER EXCEPT AS
06 SERVICE WATER EXPRESSLY PERMITTED BY PT. ENVIROMATE TECHNOLOGY INTERNATIONAL.
PG 06-1 1/2"-SW-061-A3A-NI
- - PROJECT :
061
1 1/2"-A3A TO POST GUARD
DEVELOPMENT AND OPERATION OF
06 M 3/4"-A3A LNG INFRASTRUCTURE SERVICE FOR
STR
SERVICE WATER
006 06-1 1/2"-SW-062-A3A-NI GAS POWER PLANT IN NUSA TENGGARA CLUSTER
- -
06-2"-SW-006-A3A-NI 2"-A3A 2"-A3A 1 1/2"-A3A TO VAPORIZER AREA OWNER :
J 2"-A3A J
3/4"-A3A

SERVICE WATER
06-P-303B 06-1 1/2"-SW-063-A3A-NI PT. ENVIROMATE TECHNOLOGY INTERNATIONAL

- -
1 1/2"-A3A TO VENT STACK

SERVICE WATER
06-1 1/2"-SW-064-A3A-NI TITLE :
- -
1 1/2"-A3A TO SEA WATER PUMP
PIPING & INSTRUMENT DIAGRAM
K K
SERVICE WATER
FILE NAME :

KUPANG
NTS - 2024LNG-I-PR-PID-06-009 3OF3 1
SCALE JOB NO. DRAWING NO. SHT NO. REV.
A1 (841x594)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16