www.hilti.co.id/content/hilti/A2/ID/en/engineering/software/anchor-design-software.html Profis Anchor 2.9.

0
Company: PT. Whidia Bharaya Page: 1
Specifier: Engineer Project: Colo XL rev. 11
Address: Jl. Katalia I no. 20 Palmerah Sub-Project I Pos. No.: Tj. Agung
Phone I Fax: 021 565 5775 | 021 565 5775 Date: 05/07/2024
E-Mail: admin@whidia-bharaya.co.id

Specifier's comments: Counterweight Strengthening

1 Input data
Anchor type and diameter: HIT-RE 500 V3 + HAS-U 5.8 M12
Effective embedment depth: hef,opti = 71 mm (hef,limit = 72 mm)
Material: 5.8
Evaluation Service Report: ESR-3814
Issued I Valid: 1/1/2020 | 1/1/2021
Proof: Design method ACI 318-14 / Chem
Stand-off installation: eb = 0 mm (no stand-off); t = 10 mm
Anchor plate: lx x ly x t = 400 mm x 700 mm x 10 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: cracked concrete, , fc' = 2,828 psi; h = 100 mm, Temp. short/long: 30/30 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id/content/hilti/A2/ID/en/engineering/software/anchor-design-software.html Profis Anchor 2.9.0
Company: PT. Whidia Bharaya Page: 2
Specifier: Engineer Project: Colo XL rev. 11
Address: Jl. Katalia I no. 20 Palmerah Sub-Project I Pos. No.: Tj. Agung
Phone I Fax: 021 565 5775 | 021 565 5775 Date: 05/07/2024
E-Mail: admin@whidia-bharaya.co.id

2 Load case/Resulting anchor forces 1 2y 3


Load case: Design loads

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 10.147 0.000 0.000 0.000
2 10.147 0.000 0.000 0.000 x
3 10.147 0.000 0.000 0.000 Tension
4 10.147 0.000 0.000 0.000
5 10.147 0.000 0.000 0.000
6 10.147 0.000 0.000 0.000

max. concrete compressive strain: - [‰]


max. concrete compressive stress: - [N/mm2] 4 5 6
resulting tension force in (x/y)=(0/0): 60.880 [kN]
resulting compression force in (x/y)=(0/0): 0.000 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

3 Tension load
Load Nua [kN] Capacity f Nn [kN] Utilization bN = Nua/f Nn Status
Steel Strength* 10.147 27.300 38 OK
Bond Strength** 60.880 61.287 100 OK
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 60.880 63.434 96 OK
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


Nsa = ESR value refer to ICC-ES ESR-3814
f Nsa ≥ Nua ACI 318-14 Table 17.3.1.1

Variables
Ase,N [mm2] futa [N/mm2]
84 500.00
Calculations
Nsa [kN]
42.000
Results
Nsa [kN] f steel f Nsa [kN] Nua [kN]
42.000 0.650 27.300 10.147

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id/content/hilti/A2/ID/en/engineering/software/anchor-design-software.html Profis Anchor 2.9.0
Company: PT. Whidia Bharaya Page: 3
Specifier: Engineer Project: Colo XL rev. 11
Address: Jl. Katalia I no. 20 Palmerah Sub-Project I Pos. No.: Tj. Agung
Phone I Fax: 021 565 5775 | 021 565 5775 Date: 05/07/2024
E-Mail: admin@whidia-bharaya.co.id

3.2 Bond Strength

Nag = (AA ) y
Na
Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ACI 318-14 Eq. (17.4.5.1.b)
f Nag ≥ Nua ACI 318-14 Table 17.3.1.1
ANa = see ACI 318-14, Section 17.4.5.1, Fig. R 17.4.5.1(b)
ANa0 = (2 cNa)2 ACI 318-14 Eq. (17.4.5.1c)
cNa = 10 da √ t uncr
1100
ACI 318-14 Eq. (17.4.5.1d)

( )
1
y ec,Na = e' ≤ 1.0 ACI 318-14 Eq. (17.4.5.3)
1+ N
cNa
y ed,Na = 0.7 + 0.3 ( ) ca,min
cNa
≤ 1.0 ACI 318-14 Eq. (17.4.5.4b)

y cp,Na = MAX ( )
ca,min cNa
,
cac cac
≤ 1.0 ACI 318-14 Eq. (17.4.5.5b)
Nba = l a · t k,c · p · da · hef ACI 318-14 Eq. (17.4.5.2)

Variables
2 2
t k,c,uncr [N/mm ] da [mm] hef [mm] ca,min [mm] aoverhead t k,c [N/mm ]
16.50 12 71 ∞ 1.000 8.96
ec1,N [mm] ec2,N [mm] cac [mm] la
0 0 164 1.000
Calculations
cNa [mm] ANa [mm2] ANa0 [mm2] y ed,Na
176 488,023 124,192 1.000
y ec1,Na y ec2,Na y cp,Na Nba [kN]
1.000 1.000 1.000 23.994
Results
Nag [kN] f bond f Nag [kN] Nua [kN]
94.287 0.650 61.287 60.880

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id/content/hilti/A2/ID/en/engineering/software/anchor-design-software.html Profis Anchor 2.9.0
Company: PT. Whidia Bharaya Page: 4
Specifier: Engineer Project: Colo XL rev. 11
Address: Jl. Katalia I no. 20 Palmerah Sub-Project I Pos. No.: Tj. Agung
Phone I Fax: 021 565 5775 | 021 565 5775 Date: 05/07/2024
E-Mail: admin@whidia-bharaya.co.id

3.3 Concrete Breakout Strength

Ncbg = (AA ) y
Nc
Nc0
ec,N y ed,N y c,N y cp,N Nb ACI 318-14 Eq. (17.4.2.1b)
f Ncbg ≥ Nua ACI 318-14 Table 17.3.1.1
ANc see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b)
ANc0 = 9 h2ef ACI 318-14 Eq. (17.4.2.1c)

( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-14 Eq. (17.4.2.4)
1+
3 hef
y ed,N = 0.7 + 0.3 (
ca,min
1.5hef )
≤ 1.0 ACI 318-14 Eq. (17.4.2.5b)

y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-14 Eq. (17.4.2.7b)
1.5
Nb = kc l a √fc hef
'
ACI 318-14 Eq. (17.4.2.2a)

Variables
hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm] y c,N
71 0 0 ∞ 1.000

cac [mm] kc la f'c [psi]


164 17 1.000 2,828

Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
235,578 45,369 1.000 1.000 1.000 1.000 18.794
Results
Ncbg [kN] f concrete f Ncbg [kN] Nua [kN]
97.590 0.650 63.434 60.880

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id/content/hilti/A2/ID/en/engineering/software/anchor-design-software.html Profis Anchor 2.9.0
Company: PT. Whidia Bharaya Page: 5
Specifier: Engineer Project: Colo XL rev. 11
Address: Jl. Katalia I no. 20 Palmerah Sub-Project I Pos. No.: Tj. Agung
Phone I Fax: 021 565 5775 | 021 565 5775 Date: 05/07/2024
E-Mail: admin@whidia-bharaya.co.id

4 Shear load
Load Vua [kN] Capacity f Vn [kN] Utilization bV = Vua/f Vn Status
Steel Strength* N/A N/A N/A N/A
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength controls)* N/A N/A N/A N/A
Concrete edge failure in direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (relevant anchors)

5 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid anchor plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-14,
Section 17.8.1.

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id/content/hilti/A2/ID/en/engineering/software/anchor-design-software.html Profis Anchor 2.9.0
Company: PT. Whidia Bharaya Page: 6
Specifier: Engineer Project: Colo XL rev. 11
Address: Jl. Katalia I no. 20 Palmerah Sub-Project I Pos. No.: Tj. Agung
Phone I Fax: 021 565 5775 | 021 565 5775 Date: 05/07/2024
E-Mail: admin@whidia-bharaya.co.id

6 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-RE 500 V3 + HAS-U 5.8 M12
Profile: no profile Installation torque: 0.040 kNm
Hole diameter in the fixture: df = 14 mm Hole diameter in the base material: 14 mm
Plate thickness (input): 10 mm Hole depth in the base material: 71 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 99 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to
instructions for use is required

6.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Compressed air with required • Dispenser including cassette and mixer
• Properly sized drill bit accessories to blow from the bottom of • Torque wrench
the hole
• Proper diameter wire brush
y

200 200
25

1 2 3
350
650

x
350

4 5 6
25

30 170 170 30

Coordinates Anchor mm
Anchor x y c-x c+x c-y c+y Anchor x y c-x c+x c-y c+y
1 -170 325 - - - - 4 -170 -325 - - - -
2 0 325 - - - - 5 0 -325 - - - -
3 170 325 - - - - 6 170 -325 - - - -

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id/content/hilti/A2/ID/en/engineering/software/anchor-design-software.html Profis Anchor 2.9.0
Company: PT. Whidia Bharaya Page: 7
Specifier: Engineer Project: Colo XL rev. 11
Address: Jl. Katalia I no. 20 Palmerah Sub-Project I Pos. No.: Tj. Agung
Phone I Fax: 021 565 5775 | 021 565 5775 Date: 05/07/2024
E-Mail: admin@whidia-bharaya.co.id

7 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan