Professional Documents
Culture Documents
CW
CW
0
Company: PT. Whidia Bharaya Page: 1
Specifier: Engineer Project: Colo XL rev. 11
Address: Jl. Katalia I no. 20 Palmerah Sub-Project I Pos. No.: Tj. Agung
Phone I Fax: 021 565 5775 | 021 565 5775 Date: 05/07/2024
E-Mail: admin@whidia-bharaya.co.id
1 Input data
Anchor type and diameter: HIT-RE 500 V3 + HAS-U 5.8 M12
Effective embedment depth: hef,opti = 71 mm (hef,limit = 72 mm)
Material: 5.8
Evaluation Service Report: ESR-3814
Issued I Valid: 1/1/2020 | 1/1/2021
Proof: Design method ACI 318-14 / Chem
Stand-off installation: eb = 0 mm (no stand-off); t = 10 mm
Anchor plate: lx x ly x t = 400 mm x 700 mm x 10 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: cracked concrete, , fc' = 2,828 psi; h = 100 mm, Temp. short/long: 30/30 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id/content/hilti/A2/ID/en/engineering/software/anchor-design-software.html Profis Anchor 2.9.0
Company: PT. Whidia Bharaya Page: 2
Specifier: Engineer Project: Colo XL rev. 11
Address: Jl. Katalia I no. 20 Palmerah Sub-Project I Pos. No.: Tj. Agung
Phone I Fax: 021 565 5775 | 021 565 5775 Date: 05/07/2024
E-Mail: admin@whidia-bharaya.co.id
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [kN] Capacity f Nn [kN] Utilization bN = Nua/f Nn Status
Steel Strength* 10.147 27.300 38 OK
Bond Strength** 60.880 61.287 100 OK
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 60.880 63.434 96 OK
* anchor having the highest loading **anchor group (anchors in tension)
Variables
Ase,N [mm2] futa [N/mm2]
84 500.00
Calculations
Nsa [kN]
42.000
Results
Nsa [kN] f steel f Nsa [kN] Nua [kN]
42.000 0.650 27.300 10.147
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id/content/hilti/A2/ID/en/engineering/software/anchor-design-software.html Profis Anchor 2.9.0
Company: PT. Whidia Bharaya Page: 3
Specifier: Engineer Project: Colo XL rev. 11
Address: Jl. Katalia I no. 20 Palmerah Sub-Project I Pos. No.: Tj. Agung
Phone I Fax: 021 565 5775 | 021 565 5775 Date: 05/07/2024
E-Mail: admin@whidia-bharaya.co.id
Nag = (AA ) y
Na
Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ACI 318-14 Eq. (17.4.5.1.b)
f Nag ≥ Nua ACI 318-14 Table 17.3.1.1
ANa = see ACI 318-14, Section 17.4.5.1, Fig. R 17.4.5.1(b)
ANa0 = (2 cNa)2 ACI 318-14 Eq. (17.4.5.1c)
cNa = 10 da √ t uncr
1100
ACI 318-14 Eq. (17.4.5.1d)
( )
1
y ec,Na = e' ≤ 1.0 ACI 318-14 Eq. (17.4.5.3)
1+ N
cNa
y ed,Na = 0.7 + 0.3 ( ) ca,min
cNa
≤ 1.0 ACI 318-14 Eq. (17.4.5.4b)
y cp,Na = MAX ( )
ca,min cNa
,
cac cac
≤ 1.0 ACI 318-14 Eq. (17.4.5.5b)
Nba = l a · t k,c · p · da · hef ACI 318-14 Eq. (17.4.5.2)
Variables
2 2
t k,c,uncr [N/mm ] da [mm] hef [mm] ca,min [mm] aoverhead t k,c [N/mm ]
16.50 12 71 ∞ 1.000 8.96
ec1,N [mm] ec2,N [mm] cac [mm] la
0 0 164 1.000
Calculations
cNa [mm] ANa [mm2] ANa0 [mm2] y ed,Na
176 488,023 124,192 1.000
y ec1,Na y ec2,Na y cp,Na Nba [kN]
1.000 1.000 1.000 23.994
Results
Nag [kN] f bond f Nag [kN] Nua [kN]
94.287 0.650 61.287 60.880
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id/content/hilti/A2/ID/en/engineering/software/anchor-design-software.html Profis Anchor 2.9.0
Company: PT. Whidia Bharaya Page: 4
Specifier: Engineer Project: Colo XL rev. 11
Address: Jl. Katalia I no. 20 Palmerah Sub-Project I Pos. No.: Tj. Agung
Phone I Fax: 021 565 5775 | 021 565 5775 Date: 05/07/2024
E-Mail: admin@whidia-bharaya.co.id
Ncbg = (AA ) y
Nc
Nc0
ec,N y ed,N y c,N y cp,N Nb ACI 318-14 Eq. (17.4.2.1b)
f Ncbg ≥ Nua ACI 318-14 Table 17.3.1.1
ANc see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b)
ANc0 = 9 h2ef ACI 318-14 Eq. (17.4.2.1c)
( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-14 Eq. (17.4.2.4)
1+
3 hef
y ed,N = 0.7 + 0.3 (
ca,min
1.5hef )
≤ 1.0 ACI 318-14 Eq. (17.4.2.5b)
y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-14 Eq. (17.4.2.7b)
1.5
Nb = kc l a √fc hef
'
ACI 318-14 Eq. (17.4.2.2a)
Variables
hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm] y c,N
71 0 0 ∞ 1.000
Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
235,578 45,369 1.000 1.000 1.000 1.000 18.794
Results
Ncbg [kN] f concrete f Ncbg [kN] Nua [kN]
97.590 0.650 63.434 60.880
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id/content/hilti/A2/ID/en/engineering/software/anchor-design-software.html Profis Anchor 2.9.0
Company: PT. Whidia Bharaya Page: 5
Specifier: Engineer Project: Colo XL rev. 11
Address: Jl. Katalia I no. 20 Palmerah Sub-Project I Pos. No.: Tj. Agung
Phone I Fax: 021 565 5775 | 021 565 5775 Date: 05/07/2024
E-Mail: admin@whidia-bharaya.co.id
4 Shear load
Load Vua [kN] Capacity f Vn [kN] Utilization bV = Vua/f Vn Status
Steel Strength* N/A N/A N/A N/A
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength controls)* N/A N/A N/A N/A
Concrete edge failure in direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (relevant anchors)
5 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid anchor plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-14,
Section 17.8.1.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id/content/hilti/A2/ID/en/engineering/software/anchor-design-software.html Profis Anchor 2.9.0
Company: PT. Whidia Bharaya Page: 6
Specifier: Engineer Project: Colo XL rev. 11
Address: Jl. Katalia I no. 20 Palmerah Sub-Project I Pos. No.: Tj. Agung
Phone I Fax: 021 565 5775 | 021 565 5775 Date: 05/07/2024
E-Mail: admin@whidia-bharaya.co.id
6 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-RE 500 V3 + HAS-U 5.8 M12
Profile: no profile Installation torque: 0.040 kNm
Hole diameter in the fixture: df = 14 mm Hole diameter in the base material: 14 mm
Plate thickness (input): 10 mm Hole depth in the base material: 71 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 99 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to
instructions for use is required
200 200
25
1 2 3
350
650
x
350
4 5 6
25
30 170 170 30
Coordinates Anchor mm
Anchor x y c-x c+x c-y c+y Anchor x y c-x c+x c-y c+y
1 -170 325 - - - - 4 -170 -325 - - - -
2 0 325 - - - - 5 0 -325 - - - -
3 170 325 - - - - 6 170 -325 - - - -
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id/content/hilti/A2/ID/en/engineering/software/anchor-design-software.html Profis Anchor 2.9.0
Company: PT. Whidia Bharaya Page: 7
Specifier: Engineer Project: Colo XL rev. 11
Address: Jl. Katalia I no. 20 Palmerah Sub-Project I Pos. No.: Tj. Agung
Phone I Fax: 021 565 5775 | 021 565 5775 Date: 05/07/2024
E-Mail: admin@whidia-bharaya.co.id
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan