Electrical Technical Specifications _School, Gym and Kindergarten Electrical Technical Specifications _School, Gym and Kindergarten

“Ramazan Karaj”, Nikel “Ramazan Karaj”, Nikel

▪ Installed power: 53 W;
▪ Net lumen output: 3700 lm; J. Lighting pole H=4.8m
▪ IP Protection Degree: IP 65;
▪ Insulation class: II; Tapered steel lighting pole. With hole for insertion of power supply cable, pole head connection, ø60.
▪ Class Protection: IK 09;
For the version with base, 4 log bolts to be sunk into the ground, bolts and lids must be purchased.
▪ Dimension: Ø585, 550mm
▪ Surface finish: Grey 9007; Size of inspection window 45x186 (h 4000), supplied with protection fuse holder, 2 fuses, 16A,
▪ Weight: 1.4 kg removable terminal block, 4 poles/3 holes = 10sqmm and shunt 2,5sqmm. Standard insulation
class II. When using Insulation Class I fixtures, appropriate grounding connections should be
I. LED projector 100W, IP66 for outdoor facade lighting included in the system. NOTE. Before selecting the appropriate pole, make all necessary
wind pressure resistance tests, pursuant to the Standards or Legislative Decrees in force in the
countries where the pole will be mounted and based on the assumed loads specified in
Standard EN 40-3-1. An accurate and suitable protection or insulation of the surfaces
involved is recommended to avoid any direct contact with the new masonry or concrete
screed.

Technical features:
▪ Dimension total: 4800mm, ø 120mm
Figure 23 : LED floodlight 100W, IP66, for outdoor lighting ▪ Height aboveground: 4000mm
▪ Height underground: 800mm
Technical features: ▪ Insulation class: II
▪ Light Source: LED Technology 4000K. ▪ Surface finish: Grey 9007
▪ Housing/cover: in die-cast aluminum with cooling fins ▪ Weight: 44 kg
▪ Diffuser: 5mm thick tempered glass, resistant to thermal shocks and impacts
▪ Painting: the standard powder coating consists of a first metal surface
pretreatment stage and of single layer of UV-stabilized, corrosion and salt resistant 4. IT & TELEPHONY NETWORK
polyester powder coating.
▪ Regulations: Produced according to applicable EN60598-1 CEI 34-21 standards, IP65, The project of IT and Telephone Network consists of installation of LAN and Telephone network in
IK09 degree of protection according to EN 60529 standards. full compliance with the design task. Based on the norms of reference the entire premises must be
▪ Equipment: Equipment: external connector for quick installation. Silicone rubber equipped with IT and Telephone outlet RJ45, to make a system of communication and data
gasket; external screws and bolts in stainless steel; air recirculation valve. Electronic transmission as well as possible.
safety device to protect the LED module and the related ballast compliant with EN
61547. It works in two modes: - differential mode: surge between power cables and Rack-s installed in the building are as follows:
between the phase and neutral. - common mode: surge between power, L/N and ▪ RACK - (School building)
ground cables or between the fixture’s body if it is of class II and installed on a metal Standard Floor standing Rack/Cabinet/ Enclosure– 19″, 32U (W600xD800xH1460)
pole. Upon request: protection up to 10KV. Coating. compliant with UNI EN ISO The computer rack contains:
- 4 x Patch panel for IT network with 24 RJ-45 ports, FTP Cat 6;
9227 Corrosion tests in artificial atmospheres for aggressive environments.
- 1 x Patch panel for CCTV network with 24 RJ-45 ports, FTP Cat 6;
▪ Power factor: >= 0.9 - 1 x Patch panel for telephony network with 24 RJ-45 ports, FTP Cat 6;
▪ Luminous flux maintenance .80%: 80000h (L80B20) - 4 x Internet switch with 24 RJ-45 port + 2 optical port, FTP Cat.6;
▪ Light System: symmetric wide beam; - 5 x Patch Guide RJ45 FTP Cat6;
▪ Voltage: 220-240 V, 50-60 Hz; - 1 x Supply module with 8 " Universal 2P+T " sockets 230V, 16A + PE;
▪ Installed power: 100W; - 1 x ventilation group with 2 fan module;
▪ Net lumen output: 10000 lm; - 1 x Telephone Switchboard PBX;
▪ IP Protection Degree: IP 66; - 1 x Switch, 24Port, POE, Managed;
▪ Insulation class: II - 1 x NVR 24 Channel CCTV System;
▪ Class Protection: IK 08; - 1 x Grounding Bar.
▪ Dimension: L333xW85xH568mm
▪ Surface finish: Graphite;
▪ RACK - (Gym building)
▪ Weight: 5.3 kg
Standard Floor standing Rack/Cabinet/ Enclosure– 19″, 8U (W600xD450xH360)
The computer rack contains:
- 1 x Patch Guide RJ45 FTP Cat6;
25 26
Electrical Technical Specifications _School, Gym and Kindergarten Electrical Technical Specifications _School, Gym and Kindergarten
“Ramazan Karaj”, Nikel “Ramazan Karaj”, Nikel

- 1 x Supply module with 8 " Universal 2P+T " sockets 230V, 16A + PE; - Transmission: ISO/IEC11801, EN50173, IEC61156-5; EN50288-5-1;ANSI/TIA568-C2
- 1 x ventilation group with 2 fan module; - Fire: IEC 60332-1-2; EN 60332-1-2 (IEC 60332-3-25 for special fire retardant “Exhalent
- 1 x Switch, 16Port, POE, Managed; sheath);
- 1 x Grounding Bar.
- Smoke (LSZH only): IEC 60754-1 and -2, IEC 61034-1 and IEC 61034-2;
- Solid bare copper conductor;
▪ RACK - (Kindergarten building)
Standard Floor standing Rack/Cabinet/ Enclosure– 19″, 15U (W600xD600xW760) - Color-coded PE insulation;
The computer rack contains: - Rip cord (optional);
- 2 x Patch panel for IT network with 24 RJ-45 ports, FTP Cat 6; - PVC or LSZH jacket;
- 1 x Internet switch with 24 RJ-45 port + 2 optical port, FTP Cat.6; - Packaging: Reel, Reel in Box.
- 2 x Patch Guide RJ45 FTP Cat6;
- 2 x Supply module with 8 " Universal 2P+T " sockets 230V, 16A + PE; ▪ Construction:
- 1 x ventilation group with 2 fan module;
- 1 x Switch, 16Port, POE, Managed;
- 1 x NVR 12 Channel CCTV System;
- 1 x Grounding Bar.

▪ Technical features for RACK Cabinet


- Installation Ready
- Reliable structure with welded Frameworks
- Elegant design with Tempered Glass door
- Wide Front Door swing angle over 180 degrees
- Easily removable side panels with lock
- Hassle-free installation method (Patent)
- Additional wheels and legs for further stand-alone
- Integration (Optional)
- Up to IP20 protection
- Load rating at 60kg
- Top and Bottom modular cable entrance
- Colour- Fully powder coated ▪ Electrical Specification:
- (RAL7035 Light Grey/ RAL9004 Black)

▪ Compliance:
Comply with ANSI/ EIA RS-310-D, DIN414197 part 1, IEC297-2, DIN41494 part 7,
GB/T3047.2-92 standard.

▪ Mechanical Specification:

Figure 24 : FTP CAT6 cable


▪ Description:
- Rated temperature:70℃
- Reference standard:

27 28