3.0 Work Instructions of Recommended Test Equipment


3.1 Any new test equipment preferred to be used by Contractors in performing
commissioning activities must have proper approval from CSD technical
support and coordination division and must be agreed to be included in the
following list.
3.2 Recommended Test Equipment List

Test Equipment Details


Type of Test Description
Name Manufacturer Model
The FREJA 300 relay testing
Megger
FREJA 300 FREJA 300 system is a computer-aided relay
(Programma)
testing and simulation system.
The test sets are the universal
solution for testing all generations
and types of protection relays. It
CMC 356
is capable of testing even high-
burden electromechanical relays
OMICRON CMC 256plus
OMICRON with very high power demands.
CMC series
High accuracy and versatility for
CMC 353
testing static and numerical
relays of all types Integrated
secondary testing network for testing IEC 61850
of protective relay IEDs.
equipment The SVERKER750 and
SVERKER780 features many
functions that make relay testing
more efficient (inject 3 phases
current or voltage is not
SVERKER
available). You can also test
750/760
Megger directional protective equipment
SVERKER
(Programma) efficiantly by means of the built-in
SVERKER 780
variable voltage source. In
SVERKER780 this has a
continuous phase shift function
and adjustable frequency as well.
Automatic reclosing devices can
also be tested – just as easily.
The CPC 100 is for testing
current transformers and voltage
transformers. 800 A or 2 kV can
CPC 100 OMICRON CPC 100 Primary Injection be fed into the primary side,
Test which can be increased to 2000
A or 12 kV through the use of
amplifiers
ODEN A Megger ODEN A A powerful test system designed
Archiving System Website: http://AMAS TP-NG-6250-001-007
NATIONAL GRID

Title: Index Number:


WI-NG-6460-002-110
Recommended Test Equipment List Page Number:
3 of 9

(Programma) for primary injection testing and


the transformation ratio of current
transformers. Up to 8 kA can be
generated
The CT Analyzer automatically
determines all relevant current
transformer values and compares
the results with the selected
Model not CT Tests (polarity,
CT Analyzer Omicron standard. The device evaluates
mentioned. ratio, winding
resistance, the current transformer as per the
magnetization IEC or IEEE standard within
curve,..)
seconds with the push of a
button.
Electrical tests on transformers,
CT & PT
Omicron CPC current transformers, voltage
tester.
transformers,
With VOTANO 100, you can
determine winding resistance,
short-circuit impedances,
magnetic characteristics,
VOTANO
Omicron transformation ratio and phase
100
PT tester. VT test angle. The measured results are
automatically assessed in
accordance with IEEE and IEC
standards.
Megger MAGNUS is used to turn-ratio
MAGNUS
(Programma) tests on voltage transformers
5 kV Insulation BM11D Insulation resistance tester with
Resistance Megger up to 5kV applied voltage and
Tester with a built in timer
Megger’s new range of DC
insulation testers MIT515,
MIT525,MIT1025 and MIT1525
5 kV, 10 kV,
are targeted at original equipment
15 kV DC
Manufacturers and industrial
Insulation Megger MIT1525 companies. The top of the range
Resistance
Insulation MIT1525 performs insulation
Testers
Resistance resistance tests up to 15 kV with
a 30TW maximum resistance and
an accuracy of ±5 % from
10 Kv DC Megger MIT1020/2
Insulation Analog/Digital 10 kV Megger;
Megger MIT 1020
Resistance 500, 1000, 2500, 5000, 10,000 V;
Testers 35 Tohms; Cat IV 600V
5 kV
diagnostic
Megger MIT520/2
insulation
resistance
Archiving System Website: http://AMAS TP-NG-6250-001-007
NATIONAL GRID

Title: Index Number:


WI-NG-6460-002-110
Recommended Test Equipment List Page Number:
4 of 9

tester

The DELTA-2000 is a fully


automatic 10 kV insulation power
10 kV factor test set designed for
Automated condition assessment of electrical
Insulation Megger DELTA-2000 insulation in high voltage
Power Factor Insulation apparatus, such as transformers,
Test Set Power Factor Test bushings, circuit breakers,
cables, lightning arresters and
rotating machinery.
5-kV
Insulation
Resistance
Megger BM 21
Tester
Measuring Phase
angle between two
ZERA Phase currents during
ZERA D/T types
Angle Meter Stability &
Sensitivity tests and
on load test
Such as measuring phase rotation in all
Fluke
Phase rotation Fluke 9040 areas where three phase
On-load tests
indicator and supplies
Kyoritsu
Kyoritsu 8031
Fluke –115,170, Measuring Voltage AC/DC,
Fluke 177,179,187, Current AC/DC, temperature,
Frequency and capacitance
287 Resistance, continuity and diode
Multi Meter Multi Meter The ultimate electronic
component verifier measures
AMPROBE LCR55A inductance, capacitance,
resistance, transistors, diodes
and microwave diodes
VLF hipot is just an AC output
tester but with an output
frequency of 0.1 Hz or lower
rather than 50/60Hz. Although
the frequency is very low, it is still
HI POT an alternating current with
Tester( VLF polarity reversals every half
VLF
company
VLF-28CM HV. testing cycle. At 0.1 Hz output, rather
HV than 60Hz, it takes 600 times
E uip e t’s) less current and power to apply
an AC voltage to a capacitive
load, like a long cable. There is
no better way to verify the AC
integrity of a cable than to hipot it
with AC voltage.

Archiving System Website: http://AMAS TP-NG-6250-001-007


NATIONAL GRID

Title: Index Number:


WI-NG-6460-002-110
Recommended Test Equipment List Page Number:
5 of 9

Moisture is the most important


criteria for the determination of
Electronic the gas quality. This device has
moisture been designed specially for SF6
measuring SF6 Dew Point moisture measurements. It also
device with DILO 3-037-R001 shows a higher resistance
dew point Test against contamination and SF6
indication of decomposition products than
SF6 conventional moisture sensors
and even minimises the usual
long time drifting.
This device serves for measuring
the gas purity necessary to
maintain the dielectric property
for arc quenching in circuit
SF6 Volume
SF6 Gas Purity breakers. Thanks to the speed of
percentage
DILO DILO 3-027- sound measurement developed
measuring R002 Test by DILO it provides results
device
immediately. The microprocessor
installed converts the values
measured into the SF6 volume
percentage.
SF6-Leak SF6 Gas Leakage
DILO 3-033 - R 002
Pointer Test
Fluke – Secondary
Clamp on Measuring Secondary Currents
Meter Digital
Fluke 323,381,362,33 Currents
6,337 Measurement
The TTR300 Series of three-
phase transformer turns ratio test
Three-Phase
sets are designed to measure the
Transformer Transformer Turns
Megger TTR 300 Series turns ratio of power, instrument,
Turns Ratio Ratio meter
and distribution transformers in a
Test Set
substation or manufacturing
environment.
The MOM200A is designed to
check and measure contact
resistances in high voltage circuit
breakers, disconnecting switches
Megger MOM200A
(isolators) and busbar joints. This
unit is an excellent choice when
200 amperes or less are needed
Micro- Contact Resistance for measurement
Ohmmeter test Microhmmeters are used to
measure contact resistances in
highvoltage breakers,
Megger MOM600A disconnecting switches
(isolators), knife-contact fuses,
bus joints, line joints etc.
MOM690™ features
Megger MOM690A microprocessor-based
Archiving System Website: http://AMAS TP-NG-6250-001-007
NATIONAL GRID

Title: Index Number:


WI-NG-6460-002-110
Recommended Test Equipment List Page Number:
6 of 9

measurement, storage and


reporting. The built-in software
enables you to carry out an
individual test or an entire series
of tests and store the results.
The MEGGER DUCTER
DLRO10 and DUCTER
DLRO10X bring new standards
to low resistance measurement.
Both are fully automatic
instruments, selecting the most
suitable test current, up to 10 A
dc to measure resistance from
0.1 µΩ to 2000 Ω on one of
DLRO10
Megger seven ranges. For users who
Winding DLRO10X
Winding Resistance desire more control over the
Resistance
test measurement process, DLRO
OHM meter
10X uses a menu system
controlled by a two-axis paddle to
allow manual selection of the test
current. DLRO10X also adds
real-time download of results and
on-board storage for later
download to a PC.
Megger DLRO200 measures
Megger DLRO 200 resistances between 0.1 μΩ and
1 Ω, at high currents.
Power DELTA4000 series is a fully
automatic 12 kV insulation power
Transformers
factor / dissipation factor (tan
12 kV dissipation factor delta) test set designed for
Insulation
Megger
DELTA4000 test condition assessment of
Diagnostic Series electrical insulation in high
System voltage apparatus such as
transformers, bushings, circuit
breakers, cables, lightning
arresters, and rotating machinery
60 kV, 80 kV Megger’s automatic laboratory oil
and 100 kV test sets perform accurate
Oil Breakdown
automatic Megger OTSAF series breakdown voltage tests on
Test
laboratory oil mineral, ester and silicon
test sets insulating liquids
Circuit Megger
(Programma)
EGIL Circuit Breaker Analyzer
Breaker
Megger
TM1600/MA61 System
Analyzer (Programma) Primarily used to measures a
Test Megger CB Timing test
TM1800 i uit eake ’s ti i g y le
equipment (Programma)
AC/DC Megger Separate outputs for close
(Programma)
B10E
Power coil, trip coil and spring
Archiving System Website: http://AMAS TP-NG-6250-001-007
NATIONAL GRID

Title: Index Number:


WI-NG-6460-002-110
Recommended Test Equipment List Page Number:
7 of 9

Supply charging motor voltage and


Direct triggering for minimum
trip voltage testing
A timer is often needed for use
with the CSU600A current
supply unit or ODEN A
primary current injection test
system. Testing relays with
SVERKER 650 also requires
an extra timer if more than one
timing cycle is to be measured.
Digital Timer Megger TM200 Timing test
Timer TM200 is ideal for
these tasks thanks to its
precise accuracy, its broad
application range and its
compact dimensions. Timer
TM200 is the obvious choice
for maintenance work in
substations.
To determine battery capacity is
to conduct a discharge test.
The TORKEL 820™ Battery-
Load Unit features a unique
design that combines efficiency
with portability. You can
Battery Load
Megger Torkel 820, discharge 24 and 48 V batteries
tester at a current of 270 A, and 12 V
batteries at 135 A. Moreover, two
or more TORKEL 820™ units
and/or extra load units, TXL, can
Measurement of be linked together if you need
total battery higher current.
current while TORKEL® 840 - UTILITY is used
regulating it at a for battery systems ranging from
constant level. 12 to 250 V – often encountered
in switchgear and similar
equipment. Discharging can take
place at up to 110 A, and if
Battery Load higher current is needed, two or
Megger Torkel840/860 more TORKEL 840 units, or extra
tester
load units (TXL), can be linked
together. Tests can be conducted
at constant current, constant
power, constant resistance or in
accordance with a pre-selected
load profile.

Archiving System Website: http://AMAS TP-NG-6250-001-007


NATIONAL GRID

Title: Index Number:


WI-NG-6460-002-110
Recommended Test Equipment List Page Number:
8 of 9

Three phase
power
network
analyser,
energy meter CALMET CALPORT 100A Energy Meter test Energy Meter test
and
instrument
transformer
tester
The Broman 861A temperature
calibrator is a
portable apparatus designed
Temperature Temperature primarily for
MILLER BROMAN 861A checking the winding
Calibrator calibrator
temperature indicators
(WTIs) on large oil-cooled power
transformers.
Compact and robust device for
portable use onsite.
Oil Test voltages from 0 to 75 kVrms
Repeatable breakdown
breakdown Oil breakdown measurements in mineral,
BAUR DPA 75 C
voltage voltage tester silicone and plant oils
tester Reliable measurement results
due to its short switch-off time (<
10 μs)
BAUR as an international leading
supplier of VLF test technology
offers viola TD, a device with
VLF Cable high power in an extremely
Cable high compact design. With the output
Test BAUR VILOA voltage of 42.5 kVrms (60
voltage test
System kVpeak), the device is suitable
for testing and diagnostics on
cable with a rated voltage up to
35 kV.
Revenue/En
ergy Revenue/Energy
Omicron
measuremen Measurement
t device

Archiving System Website: http://AMAS TP-NG-6250-001-007


NATIONAL GRID

Title: Index Number:


WI-NG-6460-002-110
Recommended Test Equipment List Page Number:
9 of 9

4.0 REFERENCES

Index Number /
Title
Reference Number
PR-NG-6460-002 Project Commissioning Procedure

5.0 REVISION HISTORY

Version Date Brief Description of Change / Annual Review


00 2015-08-12 First issue.

This document shall comply in accordance with the existing Company’s Rules and Regulations.
Any modifications therein found not conformance with the document shall be declared invalid.
For clarification and verification on this document, contact the following:

Engr. Tarek Mohammad Ahmad


Technical Support and Coordination Division
Commissioning Services Department
Technical Services Business Line
Extension No. 77469 Email: 69608@ngrid.sa

Archiving System Website: http://AMAS TP-NG-6250-001-007