K 604503_04 1
4.3.2 LONIBV PCB . . . . . . . . . . . . . . . . . . . . . . . . 55
4.3.3 LONCOP PCB . . . . . . . . . . . . . . . . . . . . . . . 56
4.3.4 NW PCBs . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
4.3.5 LONMXB PCB . . . . . . . . . . . . . . . . . . . . . . . 58
4.4 Hoistway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
4.4.1 LONCUB PCB . . . . . . . . . . . . . . . . . . . . . . . 60
4.4.2 NWRIO4 PCB . . . . . . . . . . . . . . . . . . . . . . . 61
4.4.3 LONCUS PCB . . . . . . . . . . . . . . . . . . . . . . . 62
4.4.4 LONDI/LONDY/LONPBD PCB . . . . . . . . . . . 63
4.4.5 NWSL/NWPBC/NWLC PCB . . . . . . . . . . . . 63
4.4.6 SLCU/SLCUM PCB . . . . . . . . . . . . . . . . . . . 63
4.4.7 SLCUX PCB . . . . . . . . . . . . . . . . . . . . . . . . . 64
4.5 * Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
4.5.1 * VARIOcon PCB . . . . . . . . . . . . . . . . . . . . . 65
5 * Fault Rectification acc. to Symptoms . . . . . . . . . . . . 72
5.1 Miconic MX-GC . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
5.2 * Drive System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
5.3 Varidor30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
5.3.1 Operating Indicators (LEDs H1 and H2) . . . 84
5.3.2 Flash intervals, LED H1 (red) . . . . . . . . . . . . 84
5.3.3 Error Codes with SSM . . . . . . . . . . . . . . . . . 85
6 * Additional Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . 86
6.1 * Unsuccessful Test Procedure . . . . . . . . . . . . . . . . 86
6.2 VARIOsys Software Download . . . . . . . . . . . . . . . . 90
6.3 Chip Card Expansion. . . . . . . . . . . . . . . . . . . . . . . . 92
A.1 *Most Used BMK Codes . . . . . . . . . . . . . . . . . . . . . . . . 94
A.2 * Changes since K 604503_03 Version. . . . . . . . . . . . . 95
2 K 604503_04
1 * General Notes
1.1 Introduction
The concept of this quick reference is to provide the maintenance
people with an appropriate tool for trouble shooting of electrical
components MX-GC Rel. 5.2 (SMLCD) with Variodyn VF11.. 44BR.
Range of application: Schindler EuroLift Program.
This quick reference does not claim to include all information.
Further Information:
K 604503_04 3
1.2 Abbreviations and Designations
Abbreviation Explanation Remarks
AGSI Absolute Encoder Shaft Absolute position encoder
Information with tooth belt in hoistway
ALSIS Absolute Linear Shaft Absolute position encoder
Information System with magnetic band
ASIXA Application Specific On base module, includes
Interface Board MX-GC integrated 4-line SMLCD
BAT Battery Emergency supply
BCMxxx Brake Control Module In AS
BIB Building Interface Box For external I/Os
BMK Code LON nodes IDs Addresses LON bus
CADI GC Computer Aided
Diagnosis Instrument
CCS Chip Card Select LED on MX-UI
COP Car Operating Panel
DBV Push Button Overspeed On power supply module
Governor
DM236 Special alarm and gong For Italy only
function
DUEISK-A Push Button Monitoring On MX-UI
Current Safety Circuit
ENDAT Absolute Value Encoder Detects deviation rotor-
Rotor Position MH stator from zero position
GCIOB Global Controller Input/ On ASIXA.. PCB,
Output for MX-GC Rel. ≥ 4.0
JHO Main Switch Options On power supply module
JHSG Stop Switch Pit
JLBS Switch Hoistway Lighting On power supply module
JRH Switch Recall Control On ASIXA.. PCB
4 K 604503_04
Abbreviation Explanation Remarks
KLSG Contact Pit Ladder In pit
KP Contact Buffer In pit
KPG Contact Buffer In pit
Counterweight
KSSBV Contact Slack Cable In pit
Overspeed Governor
KUET/2KUET Contact Door Bridging Magnetic or optical device
KWL Contact Maintenance Car roof
Hatch
LBS Lamp Hoistway Lighting
LIP Landing Indicating Panel Floor indicator
LIPDY LIP LED dot display Direction- and position
indicator
LON Local Operating Network Serial bus system
LONC LON Car From AS to OKR
LONCOP LON Car Operating
Panel
LONCUB LON Controller Unit Big In BIB
LONCUS LON Controller Unit
Small
LONDI LON Direction Indicator
LONDY LON LED dot display LON direction- and
position indicator
LONIBV LON Interface Board Door drive interface
Varidor Varidor30
LONIC LON Interface Car In OKR
LONLMS-3 Load Measurement
LONPBD LON Push Button Down
LONS/ LON Landing 2LONS with 2. access side
2LONS
K 604503_04 5
Abbreviation Explanation Remarks
LONT LON Car Door From OKR to DIB
LONTC LON Car Operating From OKR to CIM
Panel
LOP Landing Operating Panel On MX-UI
LR-U/D Lamp Direction On MX-UI
UP/DOWN
LTRT Lamp Door Trigger On MX-UI
LUEISK Lamp Monitoring Current On MX-UI
Safety Circuit
MGBV Magnet Activation
Overspeed Governor
MX-UI User interface on ASIXA.. With integrated 4-line
PCB SMLCD
NGL Power Supply Lift LED on MX-UI
NGO Power Supply Options LED on MX-UI
2NGO Additional Power Supply LED on MX-UI
Options
NSG Emergency Power Unit In AS
NWDB Neuron Wire Door
Buttons
NWDI Neuron Wire Direction
Indicator
NWDY Neuron Wire LED Dot Direction- and position
Display indicator
NWLC Neuron Wire Lamp Configurable lamp ele-
Configurable ment
NWPBC Neuron Wire Push Button Configurable lamp or
Configurable switch element
NWPBD Neuron Wire Push Button
Down
6 K 604503_04
Abbreviation Explanation Remarks
NWPBU Neuron Wire Push Button
UP
NWPB5 Neuron Wire 5 Push 5 call buttons for COP
Button
NWRIO4 Neuron Wire Relays 4 Configurable I/Os for BIB
I/Os
NWSL Neuron Wire Switch Light Configurable switch ele-
ment
OCP Overcurrent Protection Integrated in SKiiP module
PAS Socket Control Cabinet
PC Socket Car
PCT Physical Config. Table
PMA350 Permanent Magnet For Aramid ropes
Synchronous Motor
PMSxxx Permanent Magnet For steel ropes
Synchronous Motor
POWC Power Supply Car From AS to OKR
POWT Power Supply Door Drive From OKR to door drive
PSG Socket Pit
PT100 Temperature sensor +0.39Ω / 1° C
100 Ω at 0° C e.g. 40° C = 115.6 Ω
RB Relays Brake On ASIXA.. PCB
RLC-A Relay Car Light OFF On LONIC PCB
RS422 Serial interface elevator Communication between
control to FC control and drive
RSK/RSK1 Relay Safety Circuit On ASIXA.. PCB
RUET/RUET1 Relay Door Bridging On LONIC PCB
RVEC-A Relay Car Ventilator OFF On LONIC PCB
Rx Receiving data
K 604503_04 7
Abbreviation Explanation Remarks
SB/SB1 Contactor Brake On BCM2 PCB
SCT Service Config. Table
SGRW Charging contactor With current limitation
SH Main Contactor Charging contactor
SIBS Fuse Hoistway Lighting On power supply module
SIL Fuse Light Supply On power supply module
SINCOS Sine Encoder Motor encoder
SIS Fuse Control System On power supply module
SKiiP FC Power Electronics Semikron
SMLCD Service Module LCD On ASIXA.. PCB
SSM Small Service Module Service tool Varidor30
SZ 1/2 Hoistway access side 1/2
TDIV Digital Speed Encoder On hoisting motor
THMH Temperature sensor on
hoisting motor
TT Telephone line
Tx Transmitting data
T1 - T5 Diagnostics safety circuit LEDs on MX-UI
UZK DC link voltage 564 VDC (mains
400 VAC)
VARIOcon Control PCB for VFxxBR VARIOsys
VARIOsys
VARIOsys Closed loop ctrl system VFxxBR VARIOsys
VCOM Group communication
VRSK Amplifier Relay Safety
Circuit
8 K 604503_04
2 System Overview
2.1 Elevator Control
System Overview
K 604503_04 9
2.2 Communication
Communication
10 K 604503_04
2.4 Control Cabinet MRL
K 604503_04 11
2.5 Safety Circuit
The safety circuit is supplied with 24..52 V regulated DC voltage. This
compensates for safety circuit voltage losses from long lengths of
cable, oxidized contacts etc.
Note!
With open safety circuit, the voltage is 52 VDC!
12 K 604503_04
Schematic Overview KUET/KUET1 and AGSI
K 604503_04 13
Belt length [m] +N (Number of ad- F [kg] (correspond-
ditional teeth) ing power)
15 6 3
24 10 5
45 19 8
80 33 15
After having the tooth belt tensioned, execute the following steps:
• Execute Measuring Travel
• Adjust "Tacho Factor" if necessary
• Check Leveling Accuracy and adjust if necessary
2.6.2 ALSIS System
00001225
placing the Guiding around the band pushing the guides into the sensor
1 = Slot 2 = Screw 3 = Fixation clip
14 K 604503_04
Threading the Magnetic Band
1 Car
2 Wall
3 Cable tie
4 Magnetic band, magnetic side, be-
hind steel side
5 Upper Magnetic band fixation
K 604503_04 15
LED Description Remark
Status
Green Normal status Power is ON.
ON
Green No power • Check that ALSIS connector is plugged.
OFF • Check that main power is ON.
Yellow Normal status SSI communication occurs.
Blinking
Yellow No SSI com- Check that control and travelling cables
OFF munication are correctly installed.
Red Normal status No error.
OFF
Red Error Check that magnetic band is correctly
ON mounted (magnetic side facing sensor).
LEDs
1 Red
2 Yellow
3 Green
16 K 604503_04
2.7 *Critical I/Os and Service TAB
Danger
Proper functioning of critical I/Os in an installation is safety
relevant. Therefore following points must be considered:
• All critical I/Os must be realized with normally closed
contacts.
• In multiplex installations, critical I/Os must be connected
to two different elevators in the group. The two contacts
must be galvanically separated (see graphic below).
Service TAB
Critical I/Os are monitored by the MX-GC software. If a node with a
critical I/O gets lost, the service TAB (technical out of service) will be
activated after a delay of 30 minutes.
Caution
Activation of “Service Visit” by SMLCD temporarily deacti-
vates the monitoring of critical I/Os. This is only allowed
during maintenance work on the installation and prevents
the whole elevator group going to service TAB.
K 604503_04 17
3 User Interface MX-UI with SMLCD
3.1 Switches and Indicators MX-UI
Position Name
1 Status voltage supply and LED door trigger
2 Indication for safety circuit diagnostic
3 Chip card, Lift-ID
4 Direction- and floor level LEDs
5 Installation travel mode switch JMOF
6 Status information group- and lift communication
7 4-line SMLCD
8 Operation keys SMLCD
18 K 604503_04
LED Indicators
LED Status Description
BATT ON Status emergency power: ON when capacity
of battery is below 10 % of rated value
CCS blinks Data being read from chip card, PCT/SCT
being generated
ON Valid chip card available. Normal status
OFF No or not valid chip card available
DUEISK-A ON Short circuit in safety circuit. Reset switch
must be pressed after clearing short circuit
JMOF ON Installation travel is activated
LON OFF LON application not functioning
blinks Blinks four times (repeated): LON
communication not functioning
blinks ir- LON application/communication OK
regularly
LR-U ON Car is travelling upwards
LR-D ON Car is travelling downwards
LTRT ON Door trigger is active
LUET ON Car on floor level (information KUET)
NGL ON 24 VDC from NGL available
(2)NGO ON 24 VDC from (2)NGO available
Rx/Tx OFF No Ethernet communication available
flickers Ethernet connections communicating
ON Ethernet connections available, but no
communication
T1..T5 ON Safety circuit is closed
K 604503_04 19
3.2 Main Menu SMLCD
Pos. Description
1 Status LON/BIO software download / freeze:
blinking "%" Software download to LON/BIO node in
progress
"?" Freeze for LON or BIO nodes necessary
blinking "?" Executing freeze command
blinking "!" Freeze not successful
"!" Missing or new LON/BIO nodes after
freeze
blank Freeze done and no changes with
LON/BIO nodes
2 Status Master (M = Master, blank = not Master)
3 Status Service Visit (service visit active if "*" is blinking)
4 Car load in% of nominal load or load status with contacts
5 Lift name or lift number (default A, B, C..)
20 K 604503_04
Pos. Description
6 Status Drive:
0 Drive at standstill
+ Drive accelerating
= Drive at constant speed
- Drive decelerating
F Drive not available
? Status unknown
7 Status Car:
= Car at standstill inside door zone
# Car at standstill outside door zone
↑ Travelling direction UP
↓ Travelling direction DOWN
? Status unknown
8 Current floor selector value (1 until n)
9 Status travel control (in error condition the error number of
travel control will be shown alternating)
10 Indicates if car is below (-) or above (+) closest floor during
power failure (supply from battery). Closest floor is indicated
in point 8. If car stands in door zone two dashes appear. See
also point 11.
11 Distance to closest floor during power failure (supply from
battery). See also point 10.
12 Status Door:
½ Door Side
Door open
Door closing
K 604503_04 21
Pos. Description
Door opening
Door closed
Door locked
Door stopped
?? Status unknown
22 K 604503_04
Level 1 Level 2 Level 3
HighTorqueTrip
Services Services JAB
Services JRV
Services SAB
Services JBF
LMS Commission Nominal Load
Empty Car
Full Load
System Check
Empty Car Bot
Empty Car Top
Empty Car Mid
Program I/O Fun
Adj. Floor Levelling
Drv End Commis
Freeze Node Tree
Unlock Terminal
Teach-in mode
SMLCDLanguage US English
French
...
MC CommissStat 0 = Not Commiss.
1 = ...
7 = Sys Commiss.
Tests Servitel Call Reg Center
Aux Center
VF Test DC Link Test t0
K 604503_04 23
Level 1 Level 2 Level 3
CurrentLoop t1
EstimMotorPara
Direction Test t2
ZeroPositionTest
EstimatInertia t3
Memory Test
...
Magnetec Tests Self Tune Function
Diagnostics Function
Ck Empty Car
Acceptance Test Brake Test
EN81 Test
...
Status Group
Status Drive
Board I/Os
Versions GC Software
Drive Software
Date & Time
Load
Position Abs.
Rel. Car Pos.
Node List
LON nodes CH1
LON nodes CH2
BIO nodes type
Floor Enables Normal Floors
24 K 604503_04
Level 1 Level 2 Level 3
Secured Floors
Calls ...
LON SW-Download
Available Srv
Oil Temp
Brake Test
Drive AMPS
DMC
MC_CommissStat
Parameter Group Floor Markings
Call Space
Walk Time Mult
Riser Car Dist
Walking Speed
Allocation Dir
Lift Over The Hill
Min Board Time
Min Exit Time
Parking Mode
Early Door Open
...
Door HoldOpen Exit
HoldOpen Board
Final Timer
Min Door Open
2.Door ...
Car Delay Cab Light
K 604503_04 25
Level 1 Level 2 Level 3
Minimal Load
Main Floor
Gong Floor Pass
Fan Mode
Services JAB Floor
JBF Alternative Floor
Park Floor
...
Drive General V-Insp
V-Recall
V-Relevel
V4
A2
A6
A-Relevel
J1
J3
J5
J7
J-Relevel
KSE-Distance
KSERE-Dist
Relevel Dist
Max Door Zone
Unbalance Bot
Unbalance Top
Win Auto Tacho
26 K 604503_04
Level 1 Level 2 Level 3
Res Auto Tacho
Early Brake
FS_Nom
US_Nom
IS_Nom
Pole Pairs
Min Distance
On-Level Dist
TR (ZeroPos)
A-NTSD
Mot Temp Limit
Speed Reg Mode
Drive Settings Tacho Factor
Nominal Load
Reeving Factor
TachFactrMotor
Gear Ratio
TractnDiameter
Inertias
Code Type
ETSL Type
Encoder Type
Gear Type
InvInputVoltage
Nominal Speed
Inverter
Id Motor
K 604503_04 27
Level 1 Level 2 Level 3
ShaftInfoType
Brake
Load Type
PhaseDir.
Servitel ...
System Date
Time
LCD Password
ErrorLog Show
Show All
Clear Errors
Statistics Car Trips
Door Trips
2.Door Trips
Run Hours
Clear
Note!
Excerpt of the most used "Drive General" parameters.
28 K 604503_04
Parameter Description
GENERAL Note:
FS_NOM, US_NOM, IS_NOM, Pole Pairs
Automatically set as soon as parameter "Motor Id." receives
the last 4 digits of hoisting motor Id. Number.
“Id Motor” Complete listing see:
PARAMETER LIST Q 41601303
Name Description
FS_NOM [Hz] Motor Frequency. Nominal frequency of MH.
US_NOM [V] Motor Voltage. Nominal voltage of MH.
IS_NOM [A] Nominal current of MH.
In case the MH has more than one winding: Be
careful. Enter the correct current value specified for
the motor winding which will be supplied by the FC
(normally the 4 pole / 2 pole pair winding, if available)
Pole Pairs Number of pole pairs of MH. Examples:
=33 for EuroLift PMS230 / PMA350 motor type
=10 for EuroLift SM250 / PMS420 motor type
=20 for PMS400 motor type.
K 604503_04 29
Name Description during “Normal Travel”
J5 [mm/s3] 3rd rounding (Jerk) default value is 800
A6 [mm/s2] Constant deceleration, default value is 600
J7 [mm/s3] 4th rounding, default value is 800
Name Description
KSE Contact hoistway end. Distance from KSE switches to
Distance bottom/top floor level (parameter).
KSERE Dist Contact hoistway end inspection (parameter)
TR Synchronous Motor: Deviation [°] between the rotor
(ZeroPos) position and the encoder position. (0 - 359.999)
Value determined with “ZeroPosition t3” Test.
Only a xxx.xxx value reflects a successful test t3.
(0.000 is invalid).
Mot Temp Based on value of "Motor Type" (setting), consisting
Limit of the last 4 digits of the Motor Id. No., the correct
motor parameters will be selected from VecSys-,
respectively from VARIOsys database.
140°C all FM/VM/PMS machines
90°C FMB130-(LANC)
120°C FMB130-(MLS) and Basic
140°C all other default
Speed Reg for MX-GC SW Rel ≥ 2.56 only
Mode Selection of a “Distance Based” or a “Time Based”
travel curve.
• Time based, travel curve follows a time target.
• Distance based, travel curve reference values get
brought in line with actual travel curve values.
30 K 604503_04
Note!
• "Based on the value of "Inverter" (setting), the correct
inverter parameters will be selected from the VARIOsys
database.
• Based on the value of "Motor Type" (setting), consisting
of the last 4 digits of the Motor Id. No., the correct motor
parameters will be selected from the VARIOsys
database.
• During commissioning, the settings, respectively the pa-
rameters will automatically be downloaded to FC.
Parameter Description
Name Description
Tacho Shows how many increments must be sent from distance
Factor encoder to Travel Ctrl, to indicate that a distance of 1 m
has been traveled in hoistway [incr./m]. Example:
=03200[inc/m] AGSI
=04000[inc/m] ALSIS
Nominal Nominal load car
Load Example: =01000[kg]
Reeving Also "Roping". Reeving factor KZU. Examples:
Factor =2:1 for KZU 2:1
=1:1 for KZU 1:1
=2:1 for KZU 4:2
TachFac- Number of signals (pulses or sine waves) from motor
trMotor encoder sent to "Motor Control" (VecSys / VARIOsys) per
one revolution of the MH. Examples:
=2000[inc/rev] for IG2000
=10000[inc/rev] for IG10000
=2048[inc/rev] (sinusoidal signals) for sine wave
generator 2048 with EnDat function (encoder SINCOS
2048 EnDat) if PMS230, PMS400/420, PMA350, SM250
installed
Gear Gear ratio IW. Examples:
Ratio =GEARLESS(1)for PMS230, PMS400/420, PMA350,
SM250
K 604503_04 31
Name Description
TractnDi- Traction sheave diameter DD. Examples:
ameter =0.410[m] 410 mm (PMS230, PMS400, PMS420 A/B/C)
=0.450[m] 450 mm (SM250, PMS420 D/E)
=0.260[m] 260 mm (PMA350)
Inertias Mass moment of inertia. Total mass moment of inertia of
all moving parts at rated load.
• New Installation: During commissioning, value "Inertia"
will be automatically initialized as PCT/Chip card
parameter and therefore does not need to be
entered
Examples:Worm gear: 0,2..2,5 (typical value)
Gearless: 25..110 (typical value)
Code Depending on country-specific regulations, "Code Type"
Type allows different handling of parameters. Examples:
=EN81 for EN81 European Standard, Asia, Africa
=USA A17 2000 for US Standard A17
=HKG for Hongkong
ETSL Deceleration monitoring at hoistway ends for elevators
Type with short buffer stroke. Examples:
=RSE for centrifugal switch with RSE contact and relay
=ETSL for "ETSL" independent speed monitoring with
optical sampling at hoistway ends
=NONE for no deceleration monitoring at hoistway ends
Encoder Type of motor encoder. Examples:
Type =INCREMENTAL for pulse transmitter type IG2000/
IG10000 (Asynchronous motors)
=SINE_WAVE for sine wave motor encoder 2048 with
EnDat function (SINCOS 2048 EnDat) with synchronous
motors PMS230, PMS400/420, PMA350, SM250,
PMA350
Gear Type =GEARLESS for gearless machine
=SGB for SGB type machines
=WORM.GEAR for worm gear
=PLANET.GEAR for planetary gear
32 K 604503_04
Name Description
Inverter Input voltage to FC. Mains voltage or adapter transformer
Input output voltage.
Voltage =480V, =460V, =415V, =400V, =380V, =230V
Nominal Nominal speed of car. Example:
Speed =01.600[m/s]
Inverter Depending on FC installed, "Inverter" must contain one
of the following values: VARIOsys
=VF11BR, =VF22BR, =VF33BR, =VF44BR, =VF88BR
K 604503_04 33
Name Description
Motor Id. Contains the last 4 digits of motor Id. number (see “Pa-
rameter List” Q 41601303):
=+04564 EuroLift PMS230-C432 (Mot.12.0 kW)
=+04565 EuroLift PMS230-A1060 (Mot. 4.8kW)
=+04566 EuroLift PMS230-B860 (Mot. 6.8 kW)
=+04567 EuroLift PMS230-C676 (Mot. 6.8 kW)
=+04568 EuroLift PMS230-C540 (Mot. 10.9 kW)
=+04569 EuroLift PMA350-C352 (Mot. 17.2 kW)
=+04624 EuroLift PMA350-C540 (Mot. 10.9 kW)
=+04621 EuroLift PMS300-D412 (Mot. 10.8kW)
=+04623 EuroLift PMS300-D412 (Mot. 18.9kW)
=+04622 EuroLift PMS300-D336 (Mot. 18.9kW)
=+04641 EuroLift SM250.60-20-624 (Mot. 8.5 kW)
=+04642 EuroLift SM250.60-20-624 (Mot. 10.8 kW)
=+04643 EuroLift SM250.60-20-432 (Mot. 14.0 kW)
=+04644 EuroLift SM250.60-20-432 (Mot. 17.2 kW)
34 K 604503_04
Name Description
Motor Id. =+04688 EuroLift PMS420-E288 (Mot 25.0 kW)
continue =+04689 EuroLift PMS420-E240 (Mot 28.5 kW)
=+04691 EuroLift PMS420-D672 (Mot 10.8 kW)
=+04692 EuroLift PMS420-D416 (Mot 18.9 kW)
=+04693 EuroLift PMS420-D288 (Mot 26.9 kW)
=+04694 EuroLift PMS420-E592 (Mot 14.2 kW)
=+04695 EuroLift PMS420-E368 (Mot 25.0 kW)
=+04696 EuroLift PMS420-E272 (Mot 35.5 kW)
K 604503_04 35
Name Description
Phase Dir MRL, see next “Phase Dir”
MR, with PMS400 motor
U U
V V
SMLCD, Login - Parameter - Drive Settings - Phase Dir
W W Phase Dir = 3 Phase Dir = 2
36 K 604503_04
Name Description
Phase Dir Synchronous Motors: For installations where traction
continue sheave turns clockwise when elevator travels upwards.
Phase Dir. = 1 for PMS230/300, PMA350
U U
Phase Dir. = 1 for PMS420 pre-series/zero series
V V
W W
Phase Dir. = 3 for SM250, PMS420 series
K 604503_04 37
3.5 Test Procedures
Note!
• If a test is interrupted by the system, refer to
“Unsuccessful Test Procedures”.
• For the execution of the tests, refer to the relevant
commissioning instruction.
Description of Test Function
Name of Description
Test
DC Link Verifies DC Link operation with voltage measurement,
Test t0 function of SH, SGRW, rectifier and status of capacitor
battery, braking chopper operation. If required, DC Link
capacitors will be reformed (see "CapFormingTest").
Conditions: Safety circuit closed (SH)
Execution: Refer to "Tests" in K 604441 Commissioning.
Current- Verifies FC (SKiiP), wiring from FC to MH, inductivity,
Loop t1 load symmetry and that the circuit from FC to MH is
closed and a symmetrical current flows.
Conditions: Safety circuit closed (SH)
ZeroPosi- Permanent Magnet-Synchronous motors
tion t3 (PMS230/400/420 PMA350/SM250) only:
Determines by how many degrees the position of
absolute value encoder of MH differs from rotor zero
position. Result of this test is in parameter "TR
(ZeroPos)”.
Conditions:
• MH has to be equipped with an absolute value
encoder "SINCOS2048 EnDat".
• Successful DC Link Test and Current Loop Test
• Safety circuit closed (SH)
• Test must not be interrupted, otherwise an incorrect
value will be saved.
Execution: Refer to "Tests" in K 604441 Commissioning.
38 K 604503_04
Name of Description
Test
Memory Checks FC RAM using Read - Write - Read cycles.
Test Result = True/False.
Fan Test Switches the heat sink fans on for ~5 seconds
LED Test Verifies LEDs ERROR, OK, PARAMETER on VARIOcon
Charge Checks whether the DC Link gets properly charged using
DCLTest SGRW and SH.
Condition: The safety circuit closed.
Dis- Checks whether DC Link gets properly discharged using
chargD- brake resistors
CLTst
CapForm- Verifies condition of capacitor battery. In case
ingTest reconditioning is required, a capacitor pulse forming will
be carried out. This forming can take up to 5 minutes. DC
Link capacitors get charged in short, gradually
lengthened bursts using SGRW.
If not successful after several tests, capacitor battery
must be replaced.
Commissioning LMS
Note!
Load Measurement
To get correct LMS Commissioning Instruction Number,
please refer to:
• Overall Commissioning Miconic MX-GC (SMLCD) Rel. ≥
4.0 and ≤ 6.0 with Variodyn VF11..88BR (VARIOsys) for
PMS, PMA, SM250 Synchronous Motors K 604451.
K 604503_04 39
4 * Diagnostics
General Information
Caution
• Do not execute electric works when installation is live
• VF11..44BR only: Removing the FC cover results in loss
of warranty claim.
Note
• In case of a serious malfunction and MX-UI with SMLCD
is not sufficient, CADI GC can be used
• To switch OFF LONIBV PCB, JHCT must be pressed and
connector X6 (LONT) disconnected.
40 K 604503_04
Reset VFxxBR (VARIOsys)
• JH OFF - wait 3 seconds - JH ON or
• Press 3 seconds “Reset” on VARIOcon PCB
Reset MX-GC
Press "Reset" on GCIOB360 PCB once. Wait until system is booted.
Emergency Stop
Trigger emergency stop only by opening safety circuit (JHM, JHC).
Do not trigger an emergency stop by switching JH OFF.
K 604503_04 41
4.1 Procedure
Action
↓
Power Supply --------- • “User Interface MX-UI with SMLCD”
OK? • Installation Wiring Diagrams
• “Visual Check” in K 604442 Diagnostics..
↓
Safety Circuit --------- • Check LEDs on MX-UI
OK? • Installation Wiring Diagrams
↓
No Travel Initia- --------- • “Fault Rectification acc. to Symptoms”
tion Possible • “Visual Check” in K 604442 Diagnostics..
↓
Travel --------- • “Visual Check” in K 604442 Diagnostics..
Interrupted by • “Fault Rectification acc. to Symptoms” in
Emergency K 604442 Diagnostics...
Stop • SMLCD - ErrorLog
• CADI GC
↓
Other Fault --------- • “Visual Check” in K 604442 Diagnostics..
Symptoms • “Fault Rectification acc. to Symptoms” in
K 604442 Diagnostics...
• SMLCD - ErrorLog
• CADI GC
• “Additional Diagnostics” in K 604442 Di-
agnostics...
42 K 604503_04
4.2 Control Cabinet
4.2.1 ASIXA 32 PCB
ASIXA32 PCB
K 604503_04 43
Pos. Designation Description
5 2LONS LON Hoistway (2. Side)
6 AGSI Absolute Encoder Hoistway Information
7 LUET Lamp Overbridging Door
8 ETHERNET Ethernet Group Connector
9 GNT RS232 RS232 communication to Device Telealarm
10 DRIVE RS422 RS422 communication to Drive
11 BAT Battery
12 GNT Telealarm Device
13 ZQF Travel Counter
14 POW 236 Power Alarm Device for Italy
15 KTHM Contact Thermal Machine Room
16 KKSA Contact Supervision Rope Aramid
17 BCM Brake Control Module
18 Safety Circuit:
a) SK1 a) Phase Control Relay
b) SKS b) Hoistway
c) SKC c) Car
d) KTS d) Hoistway Doors
e) KV e) Door locking (manual doors)
f) RH f) Bypass Operation (only Hong Kong)
g) SK2 g) Reserve 2
19 MGB Magnetic Brake
20 X15A Logic signals to Drive
21 X15B Logic signals to Drive
22 PSW Power Supply monitoring BCMZA 1
23 GW Gateway Building Bus
24 2NGO Power Supply Options
25 NGO Power Supply Options
26 NGL Power Supply Unit Elevator
44 K 604503_04
Pos. LED Status Description Fault Rectification
27 / 29 RSK1 (27) OFF RSK(1) inactive None
RSK (29) ON RSK(1) active Travel initiation
28 VRSK OFF VRSK inactive None
ON VRSK active Travel initiation
30 RB OFF Normal status None
ON Brake is released Travel initiation
K 604503_04 45
4.2.2 GCIOB 360 PCB
46 K 604503_04
LED Status Description Fault Rectification
ERROR OFF Normal Status None
(Red)
ON No valid configura- Perform chip card
tion (PCT) expansion or PCT
download
No valid SCT Perform chip card
expansion or SCT
download
Wrong Lift-ID num- Check Lift-ID on user
ber interface MX-UI
blinks No or no valid Base software download
base software
WDOG blinks Normal status None
(green) OFF/ON CPU is not working Perform base software
properly download
Hardware fault Replace GCIOB 360 PCB
CPU flickers Normal status None
(green) OFF CPU is not working Perform base software
properly download
Hardware fault Replace GCIOB 360 PCB
STATUS OFF* Normal status None
(green) * Perhaps LED
may lit extremely
dim (also normal
status)
K 604503_04 47
4.2.3 Brake Module BCM2
LED Indicators
KB KB1 RB Description Fault Rectification
OFF OFF OFF No voltage supply Check JH, SIA, SIS
KB faulty connected Rectify according
installation wiring
diagram
ON OFF OFF Normal display standstill none
OFF ON OFF Plug MBG and MGB1 Plug connectors
interchanged by mistake correctly in accurate
place
Both KB and KB1 faulty Rectify according
connected installation wiring
diagram
OFF ON ON Brake active None
Diagnosis via LEDs
48 K 604503_04
Measuring Points Coil Contact Value
Plug MGB1 pin1 - MGB1 pin 2 MGB1 ~ 26 Ω
Plug MGB1 pin3 - MGB1 pin 4 KB1 NO ∞ Ω
Brake Coils and KB Contacts
Note
Within a cycle of 40 minutes,
battery 1 and battery 2 get
alternately charged during
approximately 3 minutes. After
this cycle of 40 minutes the
batteries get monitored and, in
case the value is = 50%, the
result gets displayed via the
LEDs (0%BATT./ 50%BATT. etc.).
Pressing button "BATT.TEST" al-
lows to monitor and display the
status of batteries within the
above mentioned cycle.
K 604503_04 49
Function Status Meaning of
ERROR OFF Normal State
ON General error of a critical component like:
• Power supply missing
• No - or delayed feedback from MGB or
related relays
POW.OK ON Needed supplies are correct.
KB1 OFF/ON Status KB1 contact. ON = closed
KB OFF/ON Status KB contact. ON = closed
0%BATT.2 OFF/ON Status BATT.2. ON = BATT.2 empty
50%BATT.2 OFF/ON Status BATT.2. ON = BATT.2 0-50% loaded
0%BATT.1 OFF/ON Status BATT.1. ON = BATT.1 empty
50%BATT.1 OFF/ON Status BATT.1. ON = BATT.1 0-50% loaded
RB OFF/ON Status RB relay. ON = Relay energized
Note
For a thorough investigation, refer to installation wiring
diagram EC-MXGC200.3
50 K 604503_04
Check proper connection (EC-MXGC200.3) and resistance values.
K 604503_04 51
LED Indicators at Standstill
Function Status Description (display at standstill)
BRK-OP OFF Normal display at standstill
KB (N_KB) ON KB contact closed (not activated)
KB1 OFF KB1 contact open (not activated)
SB (N_SB) ON Status SB contactor. ON = inactive
SB1 (N_SB1) ON Status SB1 contactor. ON = inactive
ZSB OFF Status ZSB timer. OFF = inactive
52 K 604503_04
2 Brake Control Diagnosis Coils and Brake Contacts
4.3 Car
4.3.1 LONIC PCB
LONIC3 PCB
K 604503_04 53
LED Indicators
LED Status Description Fault Rectification
SERV OFF Normal status None
(Red)
ON Firmware missing Replace PCB
blinks LON node not Switches OFF after
configured, download
download active
APPL blinks, OFF Normal status None
(green) every 2 s
OFF No power supply Check power supply
Application Press service pin. If
software missing not OK, double reset
on GCIOB 360 PCB
PCB defective Replace PCB
APPL OFF, ON LON Check LON bus for
continue every 2 s communication not correct wiring. Also
working properly check for short circuit.
24 V ON Normal status None
(green) OFF 24 VDC power Check power supply
supply missing by using installation
wiring diagram
RLC-A ON Normal status (car None
(green) light reduction
active)
OFF Car light reduction
inactive
RVEC-A ON Normal status (car
(green) fan inactive)
OFF Car fan active
RUET (1) OFF Normal status
(green)
ON Relays RUET /
RUET1 active
54 K 604503_04
4.3.2 LONIBV PCB
LED Indicators
LED Status Description Fault Rectification
SERV OFF Normal status None
(Red) ON Firmware missing Replace PCB
blinks LON node not Switches OFF after
configured, download
download active
APPL blinks Normal status None
(green) OFF No power supply Check power supply
Application Press service pin. If not
software missing OK, double reset on
GCIOB 360 PCB
PCB defective Replace PCB
P0 ON Normal status None
(green)
OFF 24 VDC power Check power supply by
supply missing using installation wiring
diagram
K 604503_04 55
Switches
Switch Pos. Description Fault Rectification
ACCESS SZ1/SZ2 Setting door drive None
SIDE access side 1/2
LONCOP PCB
LED Indicators
LED Status Description Fault Rectification
SERV OFF Normal status None
(Red)
ON Firmware missing Replace PCB
LED LON node not con- Switches OFF after
blinks figured, download download
active
56 K 604503_04
LED Status Description Fault Rectification
APPL blinks Normal status None
(green)
OFF No power supply Check power supply
Application Press service pin. If not
software missing OK, double reset on
GCIOB PCB
Print defective Replace PCB
P0 ON Normal status None
(green)
OFF 24 VDC power Check power supply by
supply missing using installation wiring
diagram
OFF Normal status None
ON In alarm status:
help is coming
(2x yellow)
OFF Normal status None
ON Service LX
(overload) is active
(2x yellow)
OFF Normal status None
ON In alarm status:
alarm
(2x yellow) acknowledged
Switches
Switch Pos. Description Fault Rectifi-
cation
MODE S/R Three rows (car calls) on car Series (S)
operating panel operate in Column (R)
series (S) or as column (R)
K 604503_04 57
Switch Pos. Description Fault Rectifi-
cation
OUT1 / SZ1/SZ2 Switches for access sides (SZ
OUT2 / 1/2):
OUT3
For series (S)
• OUT1 and OUT3: For which
side are DT-O/ DT-S active
• OUT2: For which side are
car calls DC active
For column (R)
• OUT1, OUT2 and OUT3:
For which side are car calls
(DC) and DT-O/DT-S active
LOCATION 0-F No settings necessary
4.3.4 NW PCBs
A description of the configurable NW-PCBs is in chapter "Hoistway".
58 K 604503_04
LED Indicators
LED Status Description Fault Rectification
+24V ON Normal status None
(green)
OFF No 24 VDC power Check power supply
supply from LONIC
APPL blinks Normal status None
(yellow)
OFF LON node not LON SW download ac-
configured tive
Application software Press service pin. If not
missing OK, double reset GCIOB
Print defective Replace PCB
blinks peri- LON communication Check LON bus for cor-
odically 4x not properly rect wiring, short circuit
or defective nodes.
SERV OFF Normal status None
(red) ON Firmware missing Replace PCB
blinks Node not Switches OFF after
configured, download
download active
Switches
Switch Pos. Description Remark
Offset 0-F Offset value of floor Always at “0” with
numbers MX-Basic fixtures
Hoistway SZ1/SZ2 Door access side
Entrance
K 604503_04 59
4.4 Hoistway
4.4.1 LONCUB PCB
LED Indicators
LED Status Description Fault Rectification
SERV OFF Normal status None
(Red)
ON Firmware missing Replace PCB
blinks Node not configured, Switches OFF after
download active download
APPL blinks, OFF Normal status None
(green) every 2 s
OFF No power supply Check power supply
Application software Press service pin. If not
missing OK, double reset GCIOB
Print defective Replace PCB
OFF, ON LON communication Check LON bus for cor-
every 2 s not working properly rect wiring/short circuit
24 V ON Normal status None
(green)
OFF 24 VDC power Check power supply
supply missing
60 K 604503_04
Switches
Switch Pos. Description Fault Rectification
ACCESS SZ1/Z2 Set according None
SIDE installation wiring
diagram
HIGH/LOW O-F Set according If no setting required
2 rotary installation wiring set rotary switch to
switches diagram position "01"
Switches
Switch Pos. Description Fault Rectification
HIGH/LOW O-F Setting of function of Always hexadecimal.
2 rotary external signal Example Building
switches according to BMK monitoring (RBF, RE-
list or installation A, RIB, RSM):
schematic E2 (E = High, 2 = Low)
K 604503_04 61
4.4.3 LONCUS PCB
LED Indicators
LED Status Description Fault Rectification
SERV OFF Normal status None
(Red)
ON Firmware missing Replace PCB
blinks LON node not Switches OFF after
configured, download
download active
APPL blinks, OFF Normal status None
(green) every 2 s
LED No power supply Check power supply
OFF Application Press service pin. If
software missing not OK, double reset
on GCIOB
PCB defective Replace PCB
OFF, ON LON Check LON bus for
every 2 s communication not correct wiring. Also
working properly check for short circuit
62 K 604503_04
Switches
Switch Pos. Description Fault Rectification
H. Entr SZ1/Z2 Hoistway access side
Floor Num- O-F Floor number Setting always decimal
ber HIGH/ and starts at lowest
LOW floor with 01. For ex-
2 rotary ample above:
switches 0 = High 1 = Low
K 604503_04 63
LEDs
LED Status Description Fault Rectification
Input DE-U/D OFF Input inactive None
(green)
ON Input active None
Watch Dog blinks Normal status None
(green)
LEDs
LED Status Description Fault Rectification
SHORT (red) OFF Normal status None
ON Output has overload Check with
current/short circuit installation wiring
diagram
P0 (green) ON Supply voltage None
available
WDOG (green) blinks Normal status None
IN1-4 (green) ON Input active None
OUT1-4 (green) ON Output active None
Switches
For working correctly on Miconic MX-GC, the switches CFG1 and
CFG2 on SLCUX PCB should be both in OFF position.
64 K 604503_04
4.5 * Drive
4.5.1 * VARIOcon PCB
K 604503_04 65
Pos. Designation Description
5,6,7 X5 / X6 / X7 Power module interface phase W / V / U (Ski-
iP) (VARIOcon V11 only)
8 X8 To motor encoder Sincos 2048 EnDat
9 X9 24 VDC voltage supply from NG24 (motor fan)
10 X10 THMH and VEMH (temperature sensor and
fan motor)
11 X11 RS232 to PC (diagnostics and SW-download)
12 X12 RS422 connection to elevator ctrl (ASIXA..)
13 X13 CAN interface (not applied) (V11 only)
14 X14 CAN interface parallel to X13 (not applied)
15 X15 24 VDC voltage supply from NG24
16 X16 KTHBR; brake resistor temperature contact
17 X17 To ASIXA.. contacts RSK - RSK1 - to FC coil
SH - back to VARIOcon
18 X18 Fan braking chopper, fan FC and logic signal
feedback from SH
19 X19 1) VKK to ASIXA.. RSK1 - VFSH - feedback to
VARIOcon X17.5
2) All other pins are for reserve
20 Reset Push button for SW-Reset
21 Boot Switch ON = enables SW download
OFF = normal position
22 CAN_OK CAN bus communication OK (currently not
used)
23 PWM_ON ON = Pulse Width Modulation ON
24 FLASH_B ON = writing data to Flash EPROM
25 WATCHD ON = fatal error
26 PARAMETER ON = parameter missing
27 OK Functional state of FC; ON = FC ready to oper-
ate
66 K 604503_04
Pos. Designation Description
28 ERROR ON = error display
29 CAN bus ter- ON = Termination active (120 Ohm);
mination OFF = no termination (open) (not used)
30 Extension Interface to external PCB’s
sockets (e.g.VIP PCB). VARIOcon only.
LED Indicators
LED Color Meaning
ERROR red System error (fatal error)
OK green FC available
PARAMETER yellow Commissioning state
CAN_OK green CAN bus communication OK (currently
not used)
PWM_ON red Pulse Width Modulation ON
FLASH_B red ON = writing data to Flash EPROM
WATCHD red Watchdog; ON = display of a fatal error
K 604503_04 67
Diagnosis via LEDs
Description Fault Rectification
Parameter
ERROR
OK
68 K 604503_04
Description Fault Rectification
Parameter
ERROR
OK
K 604503_04 69
Description Fault Rectification
Parameter
ERROR
OK
70 K 604503_04
LED Status Description Fault Rectifica-
tion
FLASH_B OFF Normal display when FC ready None
ON Normal display when writing None
data to Flash EPROM
WATCHD OFF Normal display when no None
internal fault, FC ok
ON Watchdog detects SW error Download cor-
rect VARIOsys
SW (version)
Fatal internal HW/SW fault Report error and
warning log and
ask EBI RD-DR
for help
K 604503_04 71
5 * Fault Rectification acc. to Symptoms
5.1 Miconic MX-GC
Component Symptom Possible Fault Rectification/Re-
Cause mark
Load Mea- “Overload” LMS not Install and commission
surement displayed connected, LMS using
LMS not put into SMLCD or CADI-GC
operation or
defect
Elevator After “Instal- Lift Id. on Adjust Lift Id.
Control - lation Travel” ASIXA..
Travel elevator con- wrong
Control trol blocked KNE opened Reduce “Learning Travel”
at end of speed.
“Learning Shift KNE
Travel”
Door not Commission and exe-
commis- cute “Learning Travel”
sioned yet again
Elevator Final timer Door drive With SSM adjustment
Control - active defined as tool define elevator
Door (acoustic master (with control as master
Control signal) SSM tool)
although
doors closed
Elevator Car stands Minimal load 1) Execute new
Control - with PI mode control active commissioning of load
Load Mea- 3 minutes (load measuring system (the
suring (default measuring closer you get to 100%
value) with inaccuracy) the more accurate load
opened measuring will be)
doors on 2) If load measurement
floor (load still inaccurate,
measuring increase "Minimal
inaccuracy) Load" by CADI
72 K 604503_04
Component Symptom Possible Fault Rectification/Re-
Cause mark
Elevator Measuring Final limit Before doing measuring
Control - travel can not switch have travel move car using
Measuring be not been recall control station.
Travel terminated fixed at Check that the LED
correctly correct "LUET" displays when
distance traveling through KUET/
KUET1 area
Decrease learning travel
speed
Travel has Always start measuring
not been travel in uppermost floor
started from (within the KUET zone)
uppermost
floor
Elevator During ZSB on 1) Check if contactor dirty
Control - installation brake mod- 2) Replace brake control
Installation travel every ule not work- module
Travel 30 cm an ing properly
emergency
"Overcurrent Correct according to
stop occurs
Factor" false "CADI Help"
Elevator Changes of Changing of 1) Make changes in COP
Control - COP COP 2) Remove LONTC plug
Car Operat- configuration configuration on LONCOP
ing Panel not working not read in 3) Perform double reset
(new key correctly by on elevator
switch, elevator 4) Plug in LONTC plug on
changing of control LONCOP
"S/R" switch,
etc.)
K 604503_04 73
5.2 * Drive System
Fault rectification acc. to symptoms (without LED or SMLCD display).
74 K 604503_04
Symptoms Possible Fault Rectification
Causes
Carrying out Motor Check/correct. Examples:
"Zero Posi- temperature PT100 = 100 Ω at 0° C.
tion Test", el- sensor (+0.39 Ω/1° C). E.g. 139 Ω = 100° C
evator does wrongly KTY84-30 = 581 Ω at 20° C, 882 Ω
not move al- connected or at 80° C, 1560 Ω at 180° C.
though "DC- defective.
Link Test" VARIOsys SW ≥ 1.06 only:
and "Current Check value of "Motor Temp Limit"
Loop Test" parameter (must match motor type).
were suc- Mechanical brake does not open:
cessful
Wrong brake Correct, then execute "Drv End
type Commis". In order to avoid faulty
configured chip card expansion again, order a
correct one (LOC).
KB, KB1 Correct using relevant installation
wrongly wired wiring diagram
Check whether LED "RB" on
ASIXA.. PCB lights when activating
DRH-D/U and check LED display on
brake control module (at standstill):
BCM2, LED KB = ON
BCMZA.NPE, LED XB.12 = ON
BCMZA 1 PCB, LED KB = ON
BCM420 PCB, LED KB = ON
SB = ON, SB1 = ON
No travel ini- Malfunction of JH OFF. Operate SB and SB1
tialization Brake mechanically
possible contactors
though SK SB/SB1
closed
KB/KB1 Check wiring acc. to installation wir-
contacts ing diagram. On brake control mod-
wrongly ule check LEDs "KB" (ON) and KB1
wired/adjusted (OFF) when car at standstill
K 604503_04 75
Symptoms Possible Fault Rectification
Causes
No travel ini- Elevator con- Set JMOF to "1" (Installation Travel
tialization trol failure Mode). Using "Recall Control
possible Device", initiate a travel. When OK,
set JMOF back to "0" and continue
with MX-GC Diagnostics K 604454.
VF or Con- Not followed Verify MC_CommissStat with
troller is exactly the SMLCD "Status/MC CommissStat"
blocked with commissionin • Wait until sequences are finished.
unknown g instruction. • Set back the MC_CommissStat
reason at to Zero. Immediately disconnect
first commis- After a Drv RS422 from ASIXA.
sionning End Reset GCIOB and reconnect the
Commissionin cable again (new parameter
g the new transmission from controller to
changed VARIOsys will be executed)
-- with MX-GC and SMLCD
values are not "Commands / MC_CommissStat
updated or =0
wrong -- with MX-GC and CADI
"Drive/Command/MCError &
Drv End Commiss"
Commissionin • Verify for correct elevator
g cannot be parameters in the System after
setting the MC_CommissStat to
executed 0 and reset on GCIOB (K
(takes too 604441 "Parameter FC and
long) MH")
• Force a Chip card download (Lift
ID new number, power up,
change Lift ID back)
76 K 604503_04
Symptoms Possible Fault Rectification
Causes
Blocked with FC not Check that counterweight is equal to
error "Speed enough pow- car weight plus 50% of rated load.
Difference" er to follow
or "Under- speed refer-
speed" ence
Wrong FC Rectify FC - or motor settings and
setting, motor parameters. K 604441
setting or Commissioning or K 604503 Quick
parameters Reference.
Wrong brake Correct setting (SB-Einschütz). In
type setting. order to avoid wrong chip card
Brake does expansion later again, order
not fully open modified one (LOC).
(attraction/hol
ding power
too low).
Bad If necessary adjust,
adjustment. PMS230: Maintenance K 604134
Mechanical SM250: SM Operation K 604501
brake does PMS400: Maintenance EJ 604735
not fully open PMS420: Maintenance K 604516.
Parameter "In- Adjust. See K 604441
ertias" inexact Commissioning or K 604503 Quick
Reference. Then order modified
chip card.
Car runs Over current Correct according to Error
about 20 cm factor too low Description or CADI Help.
and stops
K 604503_04 77
Symptoms Possible Fault Rectification
Causes
Car runs with Encoder badly Correct.
strong vibra- fixed PMS230: Maintenance K 604134
tions SM250: SM Operation K 604501
PMS400: Maintenance EJ 604735
PMS420: Maintenance K 604516.
Encoder cable Plug in cable properly. See
S 41400332 (VARIOsys)
Encoder Replace.
defective PMS230: Maintenance K 604134
SM250: SM Operation K 604501
PMS400: Maintenance EJ 604735
PMS420: Maintenance K 604516.
Defective Replace Counterweight bearing
counterweight
bearing
Starting jerk LMS not Commission LMS. See K 604451
commissioned Overall Commissioning.
Creeping "TractnDia- Adjust "TractnDiameter" or "Ta-
approach of meter" or choFactor" for direct floor approach
floor "Tacho Factor" (no creeping travel allowed):
too high • "TractnDiameter" in 1mm
decreasing steps
• "Tracho Factor" in small
decreasing steps
Over-travel- "TractnDia- • Adjust "TractnDiameter" in 1 mm
ing and meter" or "Ta- increasing steps.
creeping cho Factor" • Fine adjustment: Adjust "Tacho
back too low Factor" in small increasing steps
Unequal floor "Unbalance Adjust in small steps using CADI
approach at Bot" and and CADI Help
bottom and "Unbalance
top Top" not
correct
78 K 604503_04
Symptoms Possible Fault Rectification
Causes
Speed not Parameter "In- • NI: Contact LOC for recalculation.
constant ertias" too low. Order a modified chip card.
when travel- • Thumb rule for gearless
ing over long machines: ~ 25 ... ~ 85 kg/m2
distance
The Check functioning. If required,
mechanical adjust brake with help of proper
brake does maintenance document.
not fully open.
Motor fan Low No fault. Check VEMH by simulating
VEMH does temperature high temperature:
not work • Unplug X10
• Disconnect wire from pin 4
• Plug in X10 THMH & VEMH
• Check that MH air flow correct
VEMH Check that VEMH is supplied with
defective correct voltage.
If VEMH is properly supplied, but
does not work, replace.
K 604503_04 79
5.3 Varidor30
Symptom Description Fault Rectification
Elevator in normal Door drive receives Use SSM to check
operation, door does no control signals for whether control mode
not respond opening or closing on "Lift" (control = 0)
Door drive switch
OFF/ON (Reset)
Door does not move Motor phase not Check motor
even though there is connected connections U, V, W
a command
Power supply Measure voltage
24 VDC missing between terminals
X1.12 and X1.18
Door opens/closes at Door opens Switch motor phases
creeping speed even completely and U and V
though there is a sends message
standard "door is stopped" to
"Open/Close door" SSM
command
Door opens on com- Door accelerates to Check connection
mand and stops be- maximum speed and between encoder and
fore opening then stops converter control and
completely immediately (no test signals
signals from
encoder)
Door opens Check connection
completely at between encoder and
creeping speed and converter control and
sends message test signals
"door is stopped" to
SSM
Door closes on com- Door accelerates to Check connection
mand and stops be- maximum speed and between encoder and
fore closing then stops immedi- converter control and
completely ately (no signals test the signals
from encoder)
80 K 604503_04
Symptom Description Fault Rectification
Lust VF1204S only: Force limit detection Use SSM (control = 1)
Door closed (in syn- KSKB has been acti-
Increase closing force
chronization mode). vated.
(parameter 1060)
After opening com-
mand, door tries to Check if door moves to
open but stops after close position
a few centimeters. Check door cycle with
SSM
Set control mode to
"Lift" (control = 0)
Check closing force
measurement again
K 604503_04 81
Symptom Description Fault Rectification
Door makes Coupling device claps to- Follow adjustment
noises when gether during travel instructions (position
closing closed 53 mm)
Door panel touch at end Check rubber stop, replace
stop if necessary
Coupling roller touches at 0.5 mm clearance
cam above/below should be
present
KTC makes grinding nois- Readjust KTC
es
Landing Actuating pin too short Unscrew actuating pin and
door lock increase or decrease
cannot be distance
activated
Lock not fixed in place Secure lock in place with
retaining plate
82 K 604503_04
1. Carry Out a Functionality Check
Trigger door movement with SSM according to table below:
K 604503_04 83
5.3.1 Operating Indicators (LEDs H1 and H2)
84 K 604503_04
LED H1 red Description Fault Rectification
Blinking
Interval
8x Inverter temperature Check inverter and
too high connections
9x Error in EEPROM Main switch OFF/ON (reset)
10 x Maximum allowable Parameter value too low (no.
torque exceeded 1064). Check parameter
encoder phase
K 604503_04 85
6 * Additional Diagnostics
6.1 * Unsuccessful Test Procedure
A test which was unsuccessfully aborted, causes an error display like
follows:
86 K 604503_04
Current Loop Test checks:
Functioning SkiiP-MH, closed circuit FC-MH, symmetrical current
flow.
Note!
Do not execute "Parameter Estimation Test".
Zero Position Test:
Determines Deviation from Zero Position of Hoisting Motor Rotor.
K 604503_04 87
Description Possible Fault Rectification
Causes
Test does Safety circuit • Check SK acc. LED display on MX-
not start not closed. UI and installation wiring diagram.
• Check whether LED "RB" on
ASIXA.. lights when activating
DRH-D/U and check LED display
on brake control module (at
standstill):
BCM2, LED KB = ON
BCMZA.NPE, LED XB.12 = ON
BCMZA 1 PCB, LED KB = ON
BCM420 PCB, LED KB = ON
Test is in- Uncertain In this case the final value of the
terrupted motor parameter "Zero Position" has
before com- not yet been calculated.
pletion. Execute/repeat the test.
Wrong timing The break time between the travels
were wrong. Follow exactly the
procedure "Zero Position Test" in K
604441 Commissioning.
Test was Restart "Zero Position Test" in K
interrupted 604441 Commissioning.
Test was Check Braking Module BCM420 for
interrupted correct functioning
with Err0058, KB = ON, SB = ON, SB1 = ON
see "LED Indicators at Stand Still"
SH_NoStop
The test has Check that the encoder is properly
after 30 fitted (Phillips screw). Then restart the
travels not test according
been to 604441 Commissioning.
successful.
88 K 604503_04
Description Possible Fault Rectification
Causes
Depending "Zero Solution 1: supposing car travels UP
on load Position" • If car has enough space to
(counter- value hoistway head, carry out three
weight), car opponent to travels
travels with correct one • If SMLCD displays "Overspeed"
DRH-D and and FC is blocked (red LED
DRH-U in "ERROR" ON), execute reset on
same both MX-GC and VARIOcon
direction • If car has enough space to
hoistway head, use UP-button for
three travels (system calculates
now first "Zero Position" value.
Next travels will be executed
applying new value). Then use
DOWN-button for continuation of
test procedure (car travels
downwards).
Solution 2
Change value of "Zero Position".
SMLCD - Login - Parameter - Motor
Control - Motor - Zero Position.
Execute "End Commissioning" and
execute "Zero Position Test".
Causes and remedies for unsuccessful Current Loop Test
Note!
Do not execute the "Inertia Measurement Test".
Truth table
In case the problem cannot be solved with help of following table, re-
fer to CADI GC.
K 604503_04 89
Components Remark
Test
no earth leak
Cable & MH
SKiiP MH
Cap Batt
Success
BR Res
BR Ch.
SGRW
GRKZ
DC-L SH
Yes Yes Yes
OK
OK
OK
OK
OK
OK
Curr-L
OK
OK
OK
OK
OK OK
OK OK
OK OK
Zero-P
OK
OK
OK
OK
uncertain
uncertain
OK
OK
OK
ChargeDCLTest
Yes
DischargDCLTst
CapFormingTest
90 K 604503_04
No Step
Ensure that following files are found in the same directory:
• FlashTypes.dat
• ServiceFlasher.exe
• ServiceFlasher.ico
1
• ServiceFlasher.ini
• ServiceFlasher.msg
• VARIOcon.cfg
• VARIOsys.hex
2 Switch JH OFF.
3 Set "Boot Switch" on VARIOcon PCB to "ON".
4 Insert RS232 cable from laptop COM1 port to VARIOcon X11.
5 Unplug X12 from VARIOcon PCB (connect to ASIXA.. PCB).
6 Switch JH ON.
7 Start "ServiceFlasher.exe" with a double click.
8 Chose target file "VARIOsys.hex".
9 Press "Open" button.
10 Select "port of service PC" com 1-4.
11 Select baud rate (max. 57600).
12 Select target system: "VARIOsys: VARIOcon".
13 Optional: Activate check box "Verify Flash after programming".
14 Press "Start" button.
15 Wait until procedure complete (3-6'). Then press "OK" button.
16 Terminate Service Flasher by closing "SW - Download" window.
17 Switch JH OFF.
18 Set "Boot Switch" on VARIOcon PCB to "OFF".
19 Disconnect RS232 cable from VARIOcon PCB X11.
20 Plug in connector VARIOcon PCB X12 (connect. to ASIXA..).
21 Switch JH ON.
K 604503_04 91
No Step
No Step
1 Switch JH OFF.
2 Unplug connector "BAT".
3 Unplug RS422 connector on ASIXA.. PCB.
4 Change Lift Id on ASIXA.. PCB to another value.
5 Switch JH ON and wait until booting and initialization complete.
6 Switch JH OFF.
7 Change Lift Id back to original value.
8 Switch JH ON and wait until booting and initialization complete.
9 Switch JH OFF.
10 Plug in RS422 cable on ASIXA.. PCB.
11 Switch JH ON and wait until booting and initialization complete.
12 Execute Double Reset and wait until booting is complete.
13 Proceed with "Parameterization Motor Control" (K 604441).
14 Check all drive parameters. (K 604441)
15 SMLCD, plug in connector "BAT".
92 K 604503_04
No Step
16 Execute DC Link Test and Current Loop Test.
17 Execute Zero Position Test (in case parameter "Zero Position"
is known, adjust it with SMLCD).
18 Save "Motor Control Parameters" (Drv End Commis).
19 Check drive functions.
20 In case parameters got changed again, execute "Drv End
Commis" again.
K 604503_04 93
A *Most Used BMK Codes
Function Code Critical Function Code Critical
DC 01 no JNO 3A no
DE-U 11 no JRV 3B no
DE-D 12 no JRVP 3D no
DT-O 2D no JSDCL 3F no
DT-S 2E no JSPE 69 no
JAB 31 no KBF 70 yes
JBF 63 yes LAB 83 no
JBFF 32 yes LBF CD no
JDC 02 no LBFC 88 no
JDE-U 13 no LNFC 9A no
JDE-D 14 no LNOC 9C no
JNFF 38 yes RNO 78 yes
94 K 604503_04
B * Changes since K 604503_03 Version
• VARIOsys SW changed from 1.07 to 1.08
• MX-GC SW changed from 2.56 to 2.58.
• Description of MC_CommissStat Parameter
• PMS400 motor for MR application included
• Menu tree SMLCD updated
• New chapter 2.7 Critical I/Os and Service TAB
K 604503_04 95
Notes:
96 K 604503_04