1. PURPOSE OF TEST:
These tests are intended to check the Transformer Protection Operation, Sensitivity of relay and
CT Circuit verification.
While carrying out stability test there should not be any spill current :
Signature Signature
Name Name
Date Date
Doc.No. Rev. 0 Annexure 1 Page:2 of 6
5. TRANSFORMER NAME PLATE DETAILS
Serial Number :
Rating :
Vector group :
Tap Min. : 1
Tap Max. : 5
Nominal Tap : 3
HV Rated Current : A
LV Rated Current : A
Neutral CT Ratio : A
6. SETTING VERIFICATION:
Actual/Measured
S.No Description Final setting value Setting Verified
value
1.
2.
4.
5.
Signature Signature
Name Name
Date Date
Doc.No. Rev. 0 Annexure 1 Page:3 of 6
7. 1000 KVA TRANSFORMER LV REF PROTECTION SENSITIVITY AND STABILITY TEST
F871(87NL)
415V LVAC
P1
P2 A10.RP MCCB
INCOMER
BREAKER F871
A10.RP 7SJ61
87NL
1 PRI INJ
LO
OP PH KIT
P2 P1 230 0-2000A
1000kVA NCT1
11/0.415kV 1500/1A V
Dyn11
5.56%
A10.SWGR
1. Transformer Side Phase and Neutral is Shorted.
2. Transformer neutral earth is not removed.
3. LVAC Incomer & Injection feeder MCCB should be closed.
4. Stabilizing resistor is service condition.
5. Isolate LVAC CB tripping.
6. Inject Current between Phase and Neutral and then note down the value.
Signature Signature
Name Name
Date Date
Doc.No. Rev. 0 Annexure 1 Page:4 of 6
7.2. TEST RESULT:
Ins
MEASURED CURRENT AT A10.RP
(mA)
VOLTAGE ACROSS Display
DESCRIPTION Current in
F871 NL:
Neutral CT F871 relay
R Y B
Current (KA)
F871 F871 F871 RELAY Metrosil Resistor
X630 X630 Q7 Q8 Pri Sec
NL NL NL F871 (B1) (R102)
:5 :7 (mA (mA) (kA) (mA)
Q1 Q3 Q5 (mV) (V) (V)
R Phase: Reverse
Neutral: Normal
R Phase: Normal
Neutral: Normal
Y Phase: Reverse
Neutral: Normal
Y Phase: Normal
Neutral: Normal
B Phase: Reverse
Neutral: Normal
B Phase: Normal
Neutral: Normal
B Phase: Normal
Neutral: Reverse
B Phase: Normal
Neutral: Normal
Note:
PH CT Polarity Reverse at LVAC- R-1CTX2:1&3, Y-1CTX2:5&7, B-1CTX2:9&11
Neutral CT Polarity Reverse at Aux. transformer TCC-X7:5&6
Signature Signature
Name Name
Date Date
Doc.No. Rev. 0 Annexure 1 Page:5 of 6
8. INSTRUMENTS USED:
Equipment Calibration Calibration due
Sl.no Description Make
Sl.no date date
1 Pri Current Inj Kit
2 Clamp meter
3 Multimeter
9. REMARKS: