S.

No Description Page No

1. Purpose of Test………………………………………………………………………………………………………………. 2

2. Reference Drawing and Documents………………………………………………………………………………. 2

3. Initial Checks…………………………………………………………………………………………………………………. 2

4 List of Schematic Drawings…….…………………………………………………………………………………….. 2

5 Transformer name plate details………………………………………………………………………………….. 3

6 Setting Verification………..…………………………………………………………………………………………… 3

7 transformer Sensitivity & Stability Test F871 (87NL)

7.1. Test set up & Test procedure …………………………..……………………………………………….. 4

7.2. Test result……………………………………………………………………………………………………………. 5

8 Instruments used…………………………………………………………………………………………………………… 6

9 Remarks…………………………………………………………………………………………………………………………… 6

List of Content

Signature Signature

Name Name

Date Date
Doc.No. Rev. 0 Annexure 1 Page:1 of 6
1. PURPOSE OF TEST:
These tests are intended to check the Transformer Protection Operation, Sensitivity of relay and
CT Circuit verification.

2. REFERENCE DRAWING AND DOCUMENTS :

Electrical drawing for Aux Tx & LVAC Scheme.

3.INITIAL CHECKS: Checked ( )


Internal and External Wiring Tightness/Ferrules Checked :

Internal and External Wiring Checked as per approved scheme :

Confirm that REF relay final setting test completed :

While carrying out stability test there should not be any spill current :

Before start LV REF stability LV Side Tx Phase & Neutral to be Bypassed :

4.LIST OF SCHEMATIC DRAWINGS:


Drawing No. Category

11/0.415 Auxiliary Transformer Feeder Relay Panel


I
Schematic_A10
11/0.415 Auxiliary Transformer Feeder SWGR Panel
I
Schematic _A10
Transformer Control cabinet Drawing I
415 LVAC Switchgear Schematic Diagram --

415V LVAC Switchgear Single Line Diagram and GA Drawing --

Signature Signature

Name Name

Date Date
Doc.No. Rev. 0 Annexure 1 Page:2 of 6
5. TRANSFORMER NAME PLATE DETAILS

Serial Number :

Rating :

Rated HV Voltage : 11000 V

Rated LV Voltage : 415 V

Vector group :

Tap Min. : 1

Tap Max. : 5

Nominal Tap : 3

% Impedance (Z) : % at Nominal Tap

HV Rated Current : A

LV Rated Current : A

Neutral CT Ratio : A

LVAC side CT Ratio : A

6. SETTING VERIFICATION:
Actual/Measured
S.No Description Final setting value Setting Verified
value

1.

2.

4.

5.

Note: Setting to be confirmed as per approved final setting Document.

Signature Signature

Name Name

Date Date
Doc.No. Rev. 0 Annexure 1 Page:3 of 6
7. 1000 KVA TRANSFORMER LV REF PROTECTION SENSITIVITY AND STABILITY TEST
F871(87NL)

7.1. TEST SETUP & TEST PROCEDURE:

415V LVAC

P1

P2 A10.RP MCCB
INCOMER
BREAKER F871
A10.RP 7SJ61
87NL

1 PRI INJ
LO
OP PH KIT
P2 P1 230 0-2000A
1000kVA NCT1
11/0.415kV 1500/1A V
Dyn11
5.56%

A10.SWGR
1. Transformer Side Phase and Neutral is Shorted.
2. Transformer neutral earth is not removed.
3. LVAC Incomer & Injection feeder MCCB should be closed.
4. Stabilizing resistor is service condition.
5. Isolate LVAC CB tripping.
6. Inject Current between Phase and Neutral and then note down the value.

Signature Signature

Name Name

Date Date
Doc.No. Rev. 0 Annexure 1 Page:4 of 6
7.2. TEST RESULT:

INJECTED CURRENT @ REVERSE (A): R: Y: B:


INJECTED CURRENT @ STABLE (A): R: Y: B:

Ins
MEASURED CURRENT AT A10.RP
(mA)
VOLTAGE ACROSS Display
DESCRIPTION Current in
F871 NL:
Neutral CT F871 relay
R Y B
Current (KA)
F871 F871 F871 RELAY Metrosil Resistor
X630 X630 Q7 Q8 Pri Sec
NL NL NL F871 (B1) (R102)
:5 :7 (mA (mA) (kA) (mA)
Q1 Q3 Q5 (mV) (V) (V)
R Phase: Reverse
Neutral: Normal

R Phase: Normal
Neutral: Normal

Y Phase: Reverse
Neutral: Normal

Y Phase: Normal
Neutral: Normal

B Phase: Reverse
Neutral: Normal

B Phase: Normal
Neutral: Normal

B Phase: Normal
Neutral: Reverse

B Phase: Normal
Neutral: Normal

Note:
PH CT Polarity Reverse at LVAC- R-1CTX2:1&3, Y-1CTX2:5&7, B-1CTX2:9&11
Neutral CT Polarity Reverse at Aux. transformer TCC-X7:5&6

Signature Signature

Name Name

Date Date
Doc.No. Rev. 0 Annexure 1 Page:5 of 6
8. INSTRUMENTS USED:
Equipment Calibration Calibration due
Sl.no Description Make
Sl.no date date
1 Pri Current Inj Kit

2 Clamp meter

3 Multimeter

4 Mini Clamp meter

9. REMARKS:

Signature Signature

Name Name

Date Date
Doc.No. Rev. 0 Annexure 1 Page:6 of 6