Professional Documents
Culture Documents
03_ Aux. Tx. LV REF SAT Procedure_Annex 1
03_ Aux. Tx. LV REF SAT Procedure_Annex 1
1 Relay Details 2
2 CT Details 2
3 Visual Check 2
4.1. CT Measurement 3
10 Scheme Check 6
12 Instruments Required 6
Test Results
Please refer Annx-2
Acceptance Norm
Relay Firmware and P. Set must be same as Approved Documents.
2. CT DETAILS:
CT Rated Primary Current : A
CT Rated Secondary Current : A
Ignd-CT rated primary current : A
Ignd-CT rated primary current : A
Test Results
Please refer Annx-2
Acceptance Norm
CT Ratio as per the Approved Scheme.
Test Results
Please refer Annx-2
Acceptance Norm
No discrepancies from visual check result.
Test Setup 1:
CURRENT A
7SJ611
Omicron
1 Q1
CMC x56 Q2 CT
Q3 IL1
Q4
2 Q5
Q6
IL2
Q7
Q8
3
IL3
N INs
BI BO
LV REF
+VE
-VE
Test Procedure
Connect the Test Set to the Relay as per the Test Setup 1 with Test Block in Service Position. Current
Injected at terminals as per scheme with Test Block S871 in service position.
4.1. CT Measurement: Inject current in the relay as per the table and observe the reading on the
relay display, in secondary and primary values.
Test Results
Please refer Annex-2
Acceptance Norm
Primary current value should be as per CT primary ratio.
Tolerance ±1.0% of measured value or ±0.5% of I Nominal.
Test Setup 2:
BI BO
LV REF
+VE
-VE
Test Procedure
Connect the Test Set to the Relay as per the Test Setup 2 with Test Block in Service Position. Current
Injected at terminals as per scheme with Test Block S871 in service position.
Note: Make sure the Stabilizing Resistor is bypassed before injection.
Inject current in the relay as per the table and observe the Pickup and Trip Time values from the Test set.
Test Results
Please refer Annex-2
Acceptance Norm
Pickup Value 1.0 · Ip and Drop out Value approx. 0.95 for I/INom ≥0.5
Tolerance for Pickup/Drop out ±3 % of setting value or 1 % of nominal current at INom = 1 A or 5 A
Trip Time Tolerance ±1 % of setting value or 10 ms
Test Setup 3:
VOLTAGE
Stab. Res. 7SJ611
Omicron
1 Q7
CMC x56 Q8 CT
INs
N
BI BO
LV REF
+VE
-VE
Test Results
Please refer Annex-2
Acceptance Norm
Pickup Value 1.0 · Vcalc and Drop out Value approx. 0.95 · Vcalc for I/INom ≥0.5
Tolerance for Pickup/Drop out ±3 % of Vcalc value.
Test Procedure
Activate the Binary Input by making jumper in the respective terminal blocks on the relay Panel.
Note: Spare inputs shall be checked with External voltage initiation. Don’t check the Spare BI with
Hardware test from Digsi.
Test Results
Please refer Annex-2
Acceptance Norm
Value of Binary Input should vary from Low to High during activation of BI.
Appropriate Event should be appearing in the Spontaneous Annunciation. This is not applicable if it is a
Spare input.
Test Procedure
Activate the Binary Outputs by Hardware test from Digsi. And Measure the Resistance value of the BO’s.
Test Results
Please refer Annex-2
Acceptance Norm
Value of Binary Output should vary from Low to High during activation of BO.
Resistance Value ≤0.2 Ohms
Test Procedure
Activate the assigned function by making jumper and check the LED indication.
Note: Spare LED’s shall be checked with Hardware test from Digsi.
Test Results
Please refer Annex-2
Test Procedure
Press the Function Key and check the display.
Test Results
Please refer Annex-2
Acceptance Norm
It should operate the assigned function. Make sure the spare keys are not assigned to any functions.
Test Procedure
Test Results
Please refer Annex-3
Acceptance Norm
Trip and Isolation should be as per the approved Scheme.
Test Procedure
Digsi Online -> Test Fault Record -> Open Last recorded file and check the signals are configured as per
the table.
Test Results
Please refer Annex-3
Acceptance Norm
All Protection Pickup, R/Y/B Pickup, All Trip, Protection Block should be configured as minimum signals.