Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 6

List of Content:

Sl.No Description Page No

1 Relay Details 2

2 CT Details 2

3 Visual Check 2

4 Measured Value Test 3

4.1. CT Measurement 3

5 LV REF Protection 4-5


5.1. Current Injection 4
5.2. Voltage Injection 4

6 Binary Input Test 5

7 Binary Output Test 5

8 LED Indication Test 5-6

9 Function Key Test 6

10 Scheme Check 6

11 Fault recorder signals 6

12 Instruments Required 6

Document Nr. Rev 0 Annex-1 Page 1 of 6


AUXILIARY TRAFO. LV REF PROTECTION RELAY
1. RELAY DETAILS:
Make : Designation :
MLFB : F. W. Version :
Nominal Current : 1.0 Amp P. Set. Version :
Relay Sl.No. : BF.Nr: Auxiliary Volt. : 110V DC

 Test Results
Please refer Annx-2
 Acceptance Norm
Relay Firmware and P. Set must be same as Approved Documents.

2. CT DETAILS:
CT Rated Primary Current : A
CT Rated Secondary Current : A
Ignd-CT rated primary current : A
Ignd-CT rated primary current : A

 Test Results
Please refer Annx-2
 Acceptance Norm
CT Ratio as per the Approved Scheme.

3. VISUAL CHECK: Tested ( )


Inspect for no physical damage. :
Verify the wiring connection as per approved drawing. :
Confirm that only ring type Lugs are used for all CT Circuits.
Confirm the LED & Function Key Labels are provided. :
Relay case connected to a local earth bar.

 Test Results
Please refer Annx-2
 Acceptance Norm
No discrepancies from visual check result.

Document Nr. Rev 0 Annex-1 Page 2 of 6


4. MEASURED VALUE TEST:

Test Setup 1:

CURRENT A
7SJ611
Omicron
1 Q1
CMC x56 Q2 CT
Q3 IL1
Q4
2 Q5
Q6
IL2
Q7
Q8
3
IL3

N INs

BI BO
LV REF

+VE

-VE

 Test Procedure
Connect the Test Set to the Relay as per the Test Setup 1 with Test Block in Service Position. Current
Injected at terminals as per scheme with Test Block S871 in service position.

Note: Make sure the Stabilizing Resistor is bypassed before injection.

4.1. CT Measurement: Inject current in the relay as per the table and observe the reading on the
relay display, in secondary and primary values.

 Test Results
Please refer Annex-2

 Acceptance Norm
Primary current value should be as per CT primary ratio.
Tolerance ±1.0% of measured value or ±0.5% of I Nominal.

Document Nr. Rev 0 Annex-1 Page 3 of 6


5. LV REF PROTECTION:

5.1. CURRENT INJECTION:

Test Setup 2:

CURRENT A Stab. Res.


7SJ611
Omicron
1 Q7
CMC x56 Q8 CT
INs
N

BI BO
LV REF

+VE

-VE

 Test Procedure
Connect the Test Set to the Relay as per the Test Setup 2 with Test Block in Service Position. Current
Injected at terminals as per scheme with Test Block S871 in service position.
Note: Make sure the Stabilizing Resistor is bypassed before injection.
Inject current in the relay as per the table and observe the Pickup and Trip Time values from the Test set.

 Test Results
Please refer Annex-2

 Acceptance Norm
Pickup Value 1.0 · Ip and Drop out Value approx. 0.95 for I/INom ≥0.5
Tolerance for Pickup/Drop out ±3 % of setting value or 1 % of nominal current at INom = 1 A or 5 A
Trip Time Tolerance ±1 % of setting value or 10 ms

5.2. VOLTAGE INJECTION:

Test Setup 3:

VOLTAGE
Stab. Res. 7SJ611
Omicron
1 Q7
CMC x56 Q8 CT
INs
N

BI BO
LV REF

+VE

-VE

Document Nr. Rev 0 Annex-1 Page 4 of 6


 Test Procedure
Connect the Test Set to the Relay as per the Test Setup 3 with Test Block in Service Position. Inject
Voltage at terminals X630 -1, 4 with Test Block S871 in service position.
Note: Make sure the Stabilizing Resistor is not bypassed before injection.
Inject Voltage in the relay as per the table and observe the Pickup and Trip Time values from the Test
set.

 Test Results
Please refer Annex-2

 Acceptance Norm
Pickup Value 1.0 · Vcalc and Drop out Value approx. 0.95 · Vcalc for I/INom ≥0.5
Tolerance for Pickup/Drop out ±3 % of Vcalc value.

6. BINARY INPUT TEST:

 Test Procedure
Activate the Binary Input by making jumper in the respective terminal blocks on the relay Panel.

Note: Spare inputs shall be checked with External voltage initiation. Don’t check the Spare BI with
Hardware test from Digsi.

 Test Results
Please refer Annex-2

 Acceptance Norm
Value of Binary Input should vary from Low to High during activation of BI.

Appropriate Event should be appearing in the Spontaneous Annunciation. This is not applicable if it is a
Spare input.

7. BINARY OUTPUT TEST:

 Test Procedure
Activate the Binary Outputs by Hardware test from Digsi. And Measure the Resistance value of the BO’s.

 Test Results
Please refer Annex-2

 Acceptance Norm
Value of Binary Output should vary from Low to High during activation of BO.
Resistance Value ≤0.2 Ohms

8. LED INDICATION TEST:

 Test Procedure
Activate the assigned function by making jumper and check the LED indication.

Note: Spare LED’s shall be checked with Hardware test from Digsi.

 Test Results
Please refer Annex-2

Document Nr. Rev 0 Annex-1 Page 5 of 6


 Acceptance Norm
Value of LED should vary from Low to High during activation of Function.
Alarm Functions should be Unlatched LED’s and Pickup and Trip functions should be Latched LED’s.

9. FUNCTION KEY TEST:

 Test Procedure
Press the Function Key and check the display.

 Test Results
Please refer Annex-2

 Acceptance Norm
It should operate the assigned function. Make sure the spare keys are not assigned to any functions.

10. SCHEME CHECK:

 Test Procedure

o Tripping of 86 relay checked through on LV REF Protn.


o Test Block Operation checked for protection tripping.
o Test Block Operation checked for CT Isolation.

 Test Results
Please refer Annex-3

 Acceptance Norm
Trip and Isolation should be as per the approved Scheme.

11. FAULT RECORDER SIGNALS:

 Test Procedure
Digsi Online -> Test Fault Record -> Open Last recorded file and check the signals are configured as per
the table.

 Test Results
Please refer Annex-3

 Acceptance Norm
All Protection Pickup, R/Y/B Pickup, All Trip, Protection Block should be configured as minimum signals.

12. INSTRUMENTS REQUIRED:

Sl. No Description Make / Model

1. Secondary Injection Kit Omicron CMC 256/356 or Freja 300

2. Multimeter Fluke 87V

Document Nr. Rev 0 Annex-1 Page 6 of 6

You might also like