No Description Page No
2 CT Details …………………………………………………………………………………………….... 2
3 Visual Check…………………………………………………………………………………………….. 2
5.1. CT Measurement……………………………………………………………………………… 3
11 Instruments Used……………………………………………………………………………………. 7
Signature Signature
Name Name
Date Date
Doc.No. Rev. 0 Annex- 2 Page No. 1 of 6
AUXILIARY TRAFO. LV REF PROTECTION RELAY
1. RELAY DETAILS:
2. CT DETAILS:
Confirm that only ring type Lugs are used for all CT Circuits. :
Signature Signature
Name Name
Date Date
Doc.No. Rev. 0 Annex- 2 Page No. 2 of 6
5. MEASURED VALUE TEST:
5.1. CT Measurement: Inject current in the relay as per the table below and observe the reading on the
relay display, in primary and secondary values.
Current Injected at terminals As per scheme and as per scheme with Test Block S871 in service position.
R-E 1.0
Y-E 1.0
B-E 1.0
R-Y 1.0
Y-B 1.0
B-R 1.0
R-Y-B 1.0
INs 1.0
Acceptance Norm
Primary current value should be as per CT primary ratio.
Tolerance ±1.0% of measured value or ±0.5% of I Nominal.
Signature Signature
Name Name
Date Date
Doc.No. Rev. 0 Annex- 2 Page No. 3 of 6
6. LV REF PROTECTION:(87NL)
6.1. CURRENT INJECTION:
50 1Ph-1
Phase Pickup Trip Time @2
Drop out
current x setting
current (A)
(A) (msec)
R
INs
Acceptance Norm
Pickup Value 1.0 · Ip and Drop out Value approx. 0.95 for I/INom ≥0.5
Tolerance for Pickup/Drop out ±3 % of setting value or 1 % of nominal current at INom = 1 A or 5 A
50 1Ph-1
Voltage Trip Time
Phase Pickup Drop out
Across @2 x Cal. V
Voltage Voltage
Resistor Pickup
(V) (V)
(V) (msec)
INs
Acceptance Norm
Pickup Value 1.0 · Vcalc and Drop out Value approx. 0.95 · Vcalc for I/INom ≥0.5
Tolerance for Pickup/Drop out ±3 % of Vcalc value.
Signature Signature
Name Name
Date Date
Doc.No. Rev. 0 Annex- 2 Page No. 4 of 6
7. BINARY INPUT:
BI01
BI02
BI03
BI04
BI05
BI06
BI07
8. BINARY OUTPUT:
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
Acceptance Norm
Signature Signature
Name Name
Date Date
Doc.No. Rev. 0 Annex- 2 Page No. 5 of 6
9. LED INDICATION:
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
10.FUNCTION KEY:
11.INSTRUMENTS USED:
Remarks:
Signature Signature
Name Name
Date Date
Doc.No. Rev. 0 Annex- 2 Page No. 6 of 6