Sl.

No Description Page No

1 Relay Details …………………………………………………………………………………………… 2

2 CT Details …………………………………………………………………………………………….... 2

3 Visual Check…………………………………………………………………………………………….. 2

4 Watchdog Contact Check………………………………………………………………………….. 2

5 Measured Value Test……………………………………………………………………………….. 3

5.1. CT Measurement……………………………………………………………………………… 3

6 LV REF Protection Test………………….………………………………………………………. 4


6.1. Current Injection…………………. .………………………………………………………. 4
6.2. Voltage Injection……..……………………………………………………………………… 4

7 Binary Inputs Test…………………………………………………………………………………. 5

8 Binary Outputs Test………………………………………………………………………………… 5

9 LED Indication Test………………………………………………………………………………… 6

10 Function Key Test…………………………………………………………………………………… 6

11 Instruments Used……………………………………………………………………………………. 7

Signature Signature

Name Name
Date Date
Doc.No. Rev. 0 Annex- 2 Page No. 1 of 6
AUXILIARY TRAFO. LV REF PROTECTION RELAY

1. RELAY DETAILS:

Make : Relay Designation :


MLFB : Firmware Version :
Nominal Current : 1.0 Amp Parameter Set Version :
Relay Sl.No. : BF.Nr: Auxiliary Volt. : 110V DC
IP Address : Rated Frequency : 50 Hz

2. CT DETAILS:

Rated Primary Current : A


Rated Secondary Current : A
Ignd-CT rated primary current : A
Ignd-CT rated primary current : A

3. Initial Checks: Tested ( )


Inspect for no physical damage. :

Verify the wiring connection as per approved drawing. :

Confirm that only ring type Lugs are used for all CT Circuits. :

Relay case connected to a local earth bar. :

Final setting verified as approved setting document :

Confirm the LED & Function Key Labels are provided. :

4. WATCHDOG CONTACT CHECKS:

Supply OFF- F3 & F5 Terminals are Closed :

Supply ON- F3 & F5 Terminals are Open :

Signature Signature

Name Name
Date Date
Doc.No. Rev. 0 Annex- 2 Page No. 2 of 6
5. MEASURED VALUE TEST:

5.1. CT Measurement: Inject current in the relay as per the table below and observe the reading on the
relay display, in primary and secondary values.

Current Injected at terminals As per scheme and as per scheme with Test Block S871 in service position.

Note: Make sure the Stabilizing Resistor is bypassed before injection.

Primary current read on relay Secondary current read on relay display


Current display in kA in Amp
Phase injected
injected (Amps)
Ia Ib Ic 3I0 INs Ia Ib Ic 3I0 INs

R-E 1.0

Y-E 1.0

B-E 1.0

R-Y 1.0

Y-B 1.0

B-R 1.0

R-Y-B 1.0

INs 1.0

 Acceptance Norm
Primary current value should be as per CT primary ratio.
Tolerance ±1.0% of measured value or ±0.5% of I Nominal.

Signature Signature

Name Name
Date Date
Doc.No. Rev. 0 Annex- 2 Page No. 3 of 6
6. LV REF PROTECTION:(87NL)
6.1. CURRENT INJECTION:

50 1Ph-1(87NL-1) Pickup Setting (A): Delay Setting (s):


50 1Ph-2(87NL-2) Pickup Setting (A): Delay Setting (s):
Note: Make sure the Stabilizing Resistor is bypassed before injection.

50 1Ph-1
Phase Pickup Trip Time @2
Drop out
current x setting
current (A)
(A) (msec)
R

INs

 Acceptance Norm
Pickup Value 1.0 · Ip and Drop out Value approx. 0.95 for I/INom ≥0.5
Tolerance for Pickup/Drop out ±3 % of setting value or 1 % of nominal current at INom = 1 A or 5 A

6.2. VOLTAGE INJECTION:

Stabilizing Resistor Setting (Ω) :


Calculated Pickup Voltage (V) : 50 1Ph-1 : 50 1Ph-2 :
Note: Make sure the Stabilizing Resistor is not bypassed before injection.

50 1Ph-1
Voltage Trip Time
Phase Pickup Drop out
Across @2 x Cal. V
Voltage Voltage
Resistor Pickup
(V) (V)
(V) (msec)

INs

 Acceptance Norm
Pickup Value 1.0 · Vcalc and Drop out Value approx. 0.95 · Vcalc for I/INom ≥0.5
Tolerance for Pickup/Drop out ±3 % of Vcalc value.

Signature Signature

Name Name
Date Date
Doc.No. Rev. 0 Annex- 2 Page No. 4 of 6
7. BINARY INPUT:

Binary Input check:

BI No. BI Assigned to as per approved Schematic drawings Tested( ) Remarks

BI01

BI02

BI03

BI04

BI05

BI06

BI07

8. BINARY OUTPUT:

Binary Output check:


BO No. BO Assigned to as per approved Schematic drawings Tested( ) Resistance in Ω

BO1

BO2

BO3

BO4

BO5

BO6

BO7

BO8

Live Contact Relay Fail

 Acceptance Norm

Resistance Value ≤0.2 Ohms

Signature Signature

Name Name
Date Date
Doc.No. Rev. 0 Annex- 2 Page No. 5 of 6
9. LED INDICATION:

LED Indication check:


LED No. LED Assigned to as per approved Schematic drawings Tested ( ) Remarks

LED 1

LED 2

LED 3

LED 4

LED 5

LED 6

LED 7

10.FUNCTION KEY:

Function Key check:


F.Key No. Function Key Assigned to Tested ( ) Remarks
F1 Event Log
F2 Measurements Primary Values
F3 Last Fault
F4 Spare

11.INSTRUMENTS USED:

Sl. Equipment Calibration due


Description Make / Model Calibration date
No Sl No. date
Secondary
1.
Injection Kit

2. Multimeter Fluke / 87V

Remarks:

Signature Signature

Name Name
Date Date
Doc.No. Rev. 0 Annex- 2 Page No. 6 of 6