CCN NO.

43 R3
Subject: Janitorial Room on 3rd floor
Project Name: GOC5033045 – ESDC PDOC Project No.: 22038

Issued To: Finn Madsen, Double V Construction Ltd. Issue Date: April 10, 2024

Copied To: ☒ Houman Alijani, BGIS ☒ Brock Elliot, Northstar


☒ Brenda Moritz, Double V ☒ Jeff Brown, Northstar
☒ James Emery, IA ☒ Boban Ratkovich, CES
☒ Sahar Bahrami, IA ☒ Alula Yadete, CES
Status ☒ Contemplated Change Notice (CCN) ☐ Change Order ☐ Change Directive
Provide all coordination and work as required per the attached. Scope includes any required demo, and also any
Re&Re of existing building components as required to access the work. “Make Good” all areas affected by the work.

Issue:
RFI 103 – There is an enclosed space on the southeast side of the freight elevator, accessible only through
the freight elevator door. Schindler's Project Manager expressed concern that the BC Safety Authority
might disapprove of this setup, even if the freight elevator door were secured to prevent opening on that
side. The concern is that a maintenance person could enter the space from the elevator but might be
unable to exit.

Instruction:
Please provide us with detail and pricing for Architectural (infill wall was added), Mechanical and Electrical
scope as per attached drawings.

IREDALE ARCHITECTURE

Denis Gautier Architectural Technologist AIBC


Associate Principal, Senior Project Manager, Vancouver

220 – 12 Water Street, Vancouver, BC V6B 1A5 Vancouver Victoria t 604-736-5581 e architect@iredale.ca iredale.ca
You are hereby authorized, subject to the provisions of your Contract, to proceed with the Work described herein.
Any variance between the attached quotation and this document, this document governs.The amount of the Contract
Sum adjustment is represented below and is the total change to the Contract in Contract Price and Schedule.
Cost of Work: Credits Extras

Schedule Adjustment: Days Added Days Reduced

Authorization:

The Architect, with the recommendation of the relevant design professionals, deems that this Work is reasonably
priced and is not part of the Contractor's responsibility within the approved contract.
Recommended by Architect:

Name and Title: James Emery, Architect of Record – Iredale Date: April 10, 2024

Receipt of this Change is hereby acknowledged and the terms thereof agreed to. Any cumulative effect to the
Contract Price and Schedule as a result of this Change Order have been taken into account within the approved
Cost of Work and Schedule Adjustment.
Agreed by Contractor:

Name and Title: Finn Madsen, Senior Project Manager – Double Date:
V Construction Ltd.
Described Work to not commence until approved by Owner.

Approved by Owner:

Name and Title: Jeff Brown, Executive Vice President – North Date:
Star
Change Order: 43 R3

220 – 12 Water Street, Vancouver, BC V6B 1A5 Vancouver Victoria t 604-736-5581 e architect@iredale.ca iredale.ca
WALL TYPES GENERAL CONSTRUCTION NOTES:
GYPSUM CONSTRUCTION Public Services and Services publics et
W1a 1. THIS DRAWING AND NOTES TO BE READ IN CONJUNCTION WITH THE Procurement Canada Approvisionnement Canada
(FLOOR SLAB TO U/S OF SUSPENDED CEILING) PER WALL SCHEDULE.
OTHER DRAWINGS AND SPECIFICATIONS, INCLUDING THE M&E
DRAWINGS BY ENGINEERING CONSULTANTS. Real Property Direction générale
GYPSUM CONSTRUCTION WITH PLENUM BARRIER
2. OBTAIN APPROVAL FROM ARCHITECT, FOR ALL CHANGES MADE TO THE Branch des biens immobiliers
W2 (FLOOR SLAB TO U/S OF SUSPENDED CEILING & T.O. SUSPENDED
CEILING TO U/S OF SLAB WITH PLENUM BARRIER) PER WALL SCHEDULE. DOCUMENTS PRIOR TO PROCEEDING WITH WORK.
3. VERIFY ALL DRAWINGS, SPECIFICATIONS, DIMENSIONS, MEASUREMENTS
GYPSUM CONSTRUCTION FROM SLAB TO SLAB AND SITE CONDITIONS, NOTIFY ARCHITECT/ PM, OF ANY ERRORS,
W3a
(CONT FROM FLOOR SLAB TO CEILING SLAB) PER WALL SCHEDULE. DISCREPANCIES OR OMISSIONS PRIOR TO PROCEEDING WITH WORK. E F H J
4. CONFIRM THAT ALL DELIVERIES MEET THE CONSTRUCTION SCHEDULE.
GYPSUM CONSTRUCTION FROM SLAB TO SLAB WITH GLAZING SECTION
W3b (CONT FROM FLOOR SLAB TO CEILING SLAB) PER WALL SCHEDULE.
SUBSTITUTIONS DUE TO LATE ORDERING WILL NOT BE ACCEPTED. IF
MATERIALS WILL NOT BE AVAILABLE IN TIME TO MEET SCHEDULE
GYPSUM CONSTRUCTION FROM SLAB TO SLAB WITH WITH MESH COMPLETION DATES, THE CONTRACTOR MUST PROVIDE PROOF OF
W3c D
(CONT FROM FLOOR SLAB TO CEILING SLAB) PER WALL SCHEDULE. DATE OF ORDER OF MATERIALS PRIOR TO REQUESTING SUBSTITUTION.
5. REFER TO DOOR SCHEDULE AND KEYING SCHEDULE FOR DETAILS ON
GYPSUM CONSTRUCTION FROM SLAB TO SLAB WITH WIRE MESH AND FIRE
W4A RATED PLY. (CONTINUOUS FROM FLOOR SLAB TO CEILING SLAB WITH WIRE
LOCKING, KEYING, AND OTHER SECURITY ITEMS. 1'
6. MAKE GOOD THE JUNCTION BETWEEN EXISTING AND NEW WALL AND
MESH, BUILD AS PER RCMP G13-01) PER WALL SCHEDULE.
INFILL WALL TO EXISTING WALL. TAPE, FILL AND SAND SMOOTH
GYPSUM CONSTRUCTION FROM SLAB TO SLAB WITH WIRE MESH. DRYWALL, READY TO RECEIVE SPECIFIED FINISH.
W4B (CONTINUOUS FROM FLOOR SLAB TO CEILING SLAB WITH WIRE MESH,
ALIGN WALLS WITH
7. OUTSIDE EDGES OF DOOR FREAMES ARE LOCATED 100mm FROM
BUILD AS PER RCMP G13-01) PER WALL SCHEDULE. MULLIONS
ADJACENT FINISHED WALLS UNO.
8. PASSAGE OPENINGS THROUGH WALLS TO BE 2135mm HIGH UNO.
EXIST WALLS

NEW WALLS
QUIET
W2 ROOM
OPEN OFFICE
FIRE SEPARATION 1 HOUR

CONSTRUCTION PLAN KEY NOTES:


SECURE ZONE

TEMP ELEC & HVAC


301E 310
W2
IREDALE
A R CHI T EC T UR E
Sim Sim
THE EQUIPMENT MOVEMENT PATH FROM THE 12 2'
ALL EXTERIOR WINDOWS FACING PUBLIC REQUIRE GLASS BREAKAGE WS 6 D310
1 LOADING DOCK TO THE EPPS ROOM WS A302 A301
SENSOR SEE ELEC, SECURITY AND PRIVACY FILM. 1 W2 1895 900 FOCUS 220 - 12 Water Street

7'-6"
2285
D311
SI-37 1995 3130 WS ROOM Vancouver, BC V6B 1A5
3660 12'-0"
WASHROOMS TO BE BUILT AS PER PWGSC STANDARDS AND MEET W2a 604 - 736 - 5581
2 6'-6 1/2" 10'-3 1/4" W2 W2 311
BARRIER FREE DESIGN (CSA B651-18) AND ALL APPLICABLE CODES.
C W2
Vancouver Victoria

1335
PROVIDE REINF FOR WALL MOUNTED AV UNIT/ OTHER EQUIPMENT. W2 W1 W2
iredale.ca

8'-0"
2440
3 PROVIDE PLY BACKING ON WALLS - 914 (36") AFF TO 2134 (84") AFF. KITCHENETTE 316
319 WOMEN'S WC MEN'S WC W2
IT STORAGE &

14'-3"
W2

4345
PROVIDE PLY BLOCKING FOR SHELVING UNIT ANCHORAGE ALONG 318 317 D316 D300d
4 WORKLAB

1280
ENTIRE WALL AT 2134 AFF. 3280 1520 1100
D315

6'-3 1/2"
315 312 4

1920
CONT OPERABLE PARTITION, UP TO CEILING, MIN STC-52, REFER TO W2 W1
STAIR 3
5 W1 W2 D312

850
SPECS AND ELECTRICAL. COORD DEPTH OF ALCOVE WITH SHOP
DRAWING STACK DEPTH.

5'-6 1/4"
ELEC CLOSET, EXIT

1525
1680
D300a 2690 8'-10" W2a D313 W2

6'-7"
1880

2005
REFER TO ELEC.

VIF
W4a SMALL
W2 MEETING
D320 300

1120
W4a W2 ROOM

760
320

3'-6"
610

1065
8'-8 1/2"
5000 16'-4 3/4" 313

2655
W4a LAN ROOM W2
D300c
321

5'-8"
W2

1725
131
W5a W2

.23
W1 5

°
W4a STAIR 2 EXIT

4'-11"
CLEAR
4'-6"
1370

1500
D321

635

3'-6"
1065
W1

6'-3 1/4"
3660 12'-0"
D314

1915
1855 W2 D300b W2
OPEN OFFICE W1 WS WS LARGE

"
'-0
6'-1"
301D Sim MEETING
30 12 OPEN OFFICE
ROOM
45

A301 301A
91

6'-5"
1840

1955
314
WS
W2

OPEN OFFICE WS
301B 950 W2

14'-10 1/4"
Contractor to verify all dimensions &
70

4525
conditions on site and immediately notify
13

4
5"

the departmental representative of all


4'

discrepancies.
"

MAIL / FILE
'-2
10

ROOM
00

W2 309
31

47
25
3'
D309
0"

QUIET 15
'-1

D307 '-6 13 10 Apr 2024


W2 Issued for CCN 43 R1
10

"

ROOM "
'-9

D308
10

B
00

307 14 Issued for CCN 50 1 Feb 2024


33

75

QUIET W2 W2
32

D305 96 1980 7670


ROOM 5 11 Issued for RFI #79 19 Oct 2023
QUIET W5a
W2 6'-6" 25'-2"
305 ROOM 21 10 Issued for RFI #70 27 Sep 2023
35
306 ROOM W2
7' 9 Issued For CCN-09 R1 18 Jul 2023
D306 -0
W2 308 "
"

W2 23
'-8

75 8 Issued For Construction 17 Mar 2023


12

W2
ALIGN WALLS WITH 7'
60

-9 7 Issued For Addendum 05 30 Jan 2022


1/
38

MULLIONS D322 QUIET


W2 26 D302 2
A 40 32 " Revisions Description Date
WS
ROOM 0 G'
8'
QUIET -8
" 303 A detail no.

te
ROOM 16 W6 D303 Si no. du detail
QUIET A A
on
D304 25 W2
304 B location drawing no.
C

5' ROOM
TB

-4 W1 W2a sur dessin no.


"
302 C C drawing no. B C
W2 STAIR 1 dessin no.
EXIT
36 Project Projet
1 60
12
'-0
"
G GOC 5033045 ESDC PDOC
0
77

TENANT IMPROVEMENT
W1

15330 54a Ave. Surrey, BC


2 OPEN OFFICE
301C
Drawing Dessin

Level 3 Construction Plan

1 : 100

Designed By Conçu
DG
Date 12 Jan 2024 (yyyy/mm/dd)

Drawn By Dessiné par


FL
Date 12 Jan 2024 (yyyy/mm/dd)

Reviewed By Examiné par


JSE
N Date 12 Jan 2024 (yyyy/mm/dd)

Approved By Approuvé par

Date (yyyy/mm/dd)

Tender Soumission
JSE
Project Manager Administrateur de projets

Project No. No. du projet


3
Level 3 Construction Plan
22038
1
1 : 100
Drawing No. No. du dessin

A107
C:\Users\sahar bahrami\Documents\22038-BGIS PDOC Tenant Improvement_Central_saharL6TYF.rvt
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Public Services and Services publics et

WALL ASSEMBLY SCHEDULE Procurement Canada Approvisionnement Canada

Real Property Direction générale


Branch des biens immobiliers

EXISTING FLOOR SLAB EXISTING FLOOR SLAB EXISTING FLOOR SLAB EXISTING FLOOR SLAB EXISTING FLOOR SLAB

ACOUSTIC SEALANT BEAD


PLENUM BARRIER NOTES: ACOUSTIC SEALANT BEAD PLENUM BARRIER NOTES: ACOUSTIC SEALANT BEAD CONTINUOUS ON BOTH SIDES
- ALL JOINTS TAPED (BOTH SIDES) CONTINUOUS ON BOTH SIDES - ALL JOINTS TAPED (BOTH SIDES) CONTINUOUS ON BOTH SIDES ACOUSTIC SEALANT BEAD
PLENUM BARRIER NOTES: PLENUM BARRIER NOTES:
- ALL PENETRATIONS MUST BE - ALL PENETRATIONS MUST BE CONTINUOUS ON BOTH SIDES
- ALL JOINTS TAPED - ALL JOINTS TAPED
SEALED WITH ACOUSTIC CAULKING SEALED WITH ACOUSTIC CAULKING - ALL PENETRATIONS MUST BE - ALL PENETRATIONS MUST BE
EXISTING CEILING TILE EXISTING CEILING TILE 18 GA STEEL TRACK
EXISTING CEILING TILE IN SEALED WITH ACOUSTIC CAULKING SEALED WITH ACOUSTIC CAULKING
SUSPENDED T-BAR CEILING IN SUSPENDED T-BAR CEILING IN SUSPENDED T-BAR CEILING
18 GA STEEL TRACK 18 GA STEEL TRACK
SOUND ATTENUATING BATT INSULATION 18ga STEEL TRACK

EXISTING WALL SECURE BOTTOM TRACK TO STRUCT SLAB


W/ FASTENER @ 400mm OC TYP
SOUND ATTENUATING BATT INSULATION
ACOUSTIC SEALANT BEAD EXISTING CEILING TILE IN SUSPENDED T- EXISTING CEILING TILE IN SUSPENDED T-
ACOUSTIC SEALANT BEAD
CONTINUOUS ON BOTH SIDES SOUND ATTENUATING BATT INSULATION SOUND ATTENUATING BATT INSULATION SOUND ATTENUATING BATT INSULATION BAR CEILING. PROVIDE NEW EDGE TRACK BAR CEILING. PROVIDE NEW EDGE TRACK
CONTINUOUS ON BOTH SIDES
TO MATCH EXISTING AND CUT BACK TO MATCH EXISTING AND CUT BACK
INSIDE CEILING TILE TO FIT. RESTRAIN PER INSIDE CEILING TILE TO FIT. RESTRAIN PER
SECURE BOTTOM TRACK TO STRUCT 18 GA STEEL TRACK SECURE BOTTOM TRACK TO STRUCT SLAB 18 GA STEEL TRACK SECURE BOTTOM TRACK TO 18 GA STEEL TRACK SECURE BOTTOM TRACK TO STRUCT SLAB SEISMIC REQUIREMENTS SEISMIC REQUIREMENTS
SLAB W/ FASTENER @ 400mm OC TYP W/ FASTENER @ 400mm OC TYP STRUCT SLAB W/ FASTENER @ W/ FASTENER @ 400mm OC TYP
400mm OC TYP 18 GA STEEL TRACK
NEW RESILIENT WALL BASE NEW RESILIENT WALL BASE NEW RESILIENT WALL BASE
ACOUSTIC SEALANT BEAD ACOUSTIC SEALANT BEAD NEW RESILIENT WALL BASE GLAZING SECTION:
ACOUSTIC SEALANT BEAD
CONTINUOUS ON BOTH SIDES, CONTINUOUS ON BOTH SIDES - CLEAR TEMPERED GLASS
NEW CARPET OR TILE CONTINUOUS ON BOTH SIDES, NEW CARPET OR TILE NEW CARPET OR TILE NEW CARPET OR TILE NEW CARPET OR TILE SINGLE PANE
- SECURITY FILM TO COVER ENTIRE

IREDALE
FACADE ON INSIDE FACE IN A
SEAMLESS APPLICATION AND BE
FASTENED UNDER METAL BLOCKING
EXISTING FLOOR SLAB EXISTING FLOOR SLAB EXISTING FLOOR SLAB EXISTING FLOOR SLAB

A R CHI T EC T UR E
W1 W1 - GYPSUM CONSTRUCTION W2 W2 - GYPSUM CONSTRUCTION WITH PLENUM BARRIER W2a W2 - GYPSUM CONSTRUCTION WITH PLENUM BARRIER W3a W3a - GYPSUM CONSTRUCTION FROM SLAB TO SLAB
(FLOOR SLAB TO U/S OF SUSPENDED CEILING & T.O. SUSPENDED (FLOOR SLAB TO U/S OF SUSPENDED CEILING & T.O. SUSPENDED
W3b W3b - GYPSUM CONSTRUCTION FROM SLAB TO SLAB 220 - 12 Water Street
(FLOOR SLAB TO U/S OF SUSPENDED CEILING) (CONT FROM FLOOR SLAB TO CEILING SLAB)
CEILING TO U/S OF SLAB WITH PLENUM BARRIER) CEILING TO U/S OF SLAB WITH PLENUM BARRIER) (CONT FROM FLOOR SLAB TO CEILING SLAB)

- 1 LAYER OF 13mm GYPSUM BOARD - 1 LAYER OF 16mm GYPSUM BOARD


Vancouver, BC V6B 1A5
- 1 LAYER OF 16mm GYPSUM BOARD
-
-
92mm METAL STUDS @ 400mm O.C. W/ SOUND ATTENUATING BATTS (STC-52) IN CAVITY
1 LAYER OF 13mm GYPSUM BOARD
-
-
1 LAYER OF 13mm GYPSUM BOARD
92mm METAL STUDS @ 400mm O.C. W/ ATTENUATION BATTS IN CAVITY
- 152mm METAL STUDS @ 400mm O.C. W/ ATTENUATION BATTS IN CAVITY
INSULATION (STC-52) IN CAVITY
- 92mm METAL STUDS @ 400mm O.C. W/ ATTENUATION BATTS
INSULATION (STC-52) IN CAVITY
- 92mm METAL STUDS @ 400mm O.C. W/ ATTENUATION BATTS 604 - 736 - 5581
INSULATION (STC-52) IN CAVITY
- ACOUSTIC CAULKING TOP & BOTTOM - 1 LAYER OF 16mm GYPSUM BOARD
- STC-50 -
INSULATION (STC-52) IN CAVITY
1 LAYER OF 13mm GYPSUM BOARD
-
-
1 LAYER OF 13mm GYPSUM BOARD
ACOUSTIC CAULKING TOP & BOTTOM - ACOUSTIC CAULKING TOP & BOTTOM
- 1 LAYER OF 16mm GYPSUM BOARD Vancouver Victoria
- ACOUSTIC CAULKING TOP & BOTTOM
- ACOUSTIC CAULKING TOP & BOTTOM - STC-50 - STC-50
- STC-50
- STC-50 iredale.ca

EXISTING FLOOR SLAB EXISTING FLOOR SLAB EXISTING FLOOR SLAB

PLENUM BARRIER NOTES: ACOUSTIC SEALANT BEAD PLENUM BARRIER NOTES: ACOUSTIC SEALANT BEAD
- ALL JOINTS TAPED (BOTH SIDES) CONTINUOUS ON BOTH SIDES - ALL JOINTS TAPED (BOTH SIDES) CONTINUOUS ON BOTH SIDES
ACOUSTIC SEALANT BEAD - ALL PENETRATIONS MUST BE - ALL PENETRATIONS MUST BE
PLENUM BARRIER NOTES:
CONTINUOUS ON BOTH SIDES SEALED WITH ACOUSTIC CAULKING SEALED WITH ACOUSTIC CAULKING
- ALL JOINTS TAPED
600T200-43 STEEL TRACK 600T200-43 STEEL TRACK
- ALL PENETRATIONS MUST BE
EXIST CEILING TILE IN SUSPENDED T- EXIST CEILING TILE IN SUSPENDED T-
600T200-43 STEEL TRACK SEALED WITH ACOUSTIC CAULKING
BAR CEILING. PROVIDE NEW EDGE BAR CEILING. PROVIDE NEW EDGE
TRACK TO MATCH EXIST ON CLIENT SIDE SOUND ATTENUATING BATT INSULATION TRACK TO MATCH EXIST ON CLIENT SIDE SOUND ATTENUATING BATT INSULATION
CONTINUOUS WIRE MESH FROM OF WALL AND CUT BACK CEILING TILE OF WALL AND CUT BACK CEILING TILE
FLOOR TO U/S OF SLAB TO FIT. RESTRAIN PER SEISMIC TO FIT. RESTRAIN PER SEISMIC
REQUIREMENTS SECURE WIRE MESH REQUIREMENTS SECURE WIRE MESH
TO STEEL STUD TO STEEL STUD

SOUND ATTENUATING BATT INSULATION FIRE RATED PLYWOOD UP TO 2440 AFF.


EXISTING CEILING TILE IN SUSPENDED T-
CONTINUOUS WIRE MESH FROM CONTINUOUS WIRE MESH FROM 13MM GYPSUM BOARD
BAR CEILING. PROVIDE NEW EDGE TRACK
FLOOR TO U/S OF SLAB FLOOR TO U/S OF SLAB
TO MATCH EXISTING AND CUT BACK
INSIDE CEILING TILE TO FIT. RESTRAIN PER
INSIDE LAN ROOM INSIDE
SECURE BOTTOM TRACK TO STRUCT SLAB SEISMIC REQUIREMENTS SECURE BOTTOM TRACK TO STRUCT SLAB SECURE BOTTOM TRACK TO STRUCT SLAB
W/ FASTENER @ 400mm OC TYP W/ FASTENER @ 400mm OC TYP W/ FASTENER @ 400mm OC TYP
600T200-43 STEEL TRACK 600T200-43 STEEL TRACK 600T200-43 DOUBLE
600T200-43 STEEL TRACK
METAL STUDS
ACOUSTIC SEALANT BEAD NEW RESILIENT WALL BASE ACOUSTIC SEALANT BEAD NEW RESILIENT WALL BASE
ACOUSTIC SEALANT BEAD NEW RESILIENT WALL BASE
CONTINUOUS ON BOTH SIDES CONTINUOUS ON BOTH SIDES WIRE MESH
CONTINUOUS ON BOTH SIDES
NEW CARPET OR TILE NEW CARPET OR TILE NEW CARPET OR TILE

EXISTING FLOOR SLAB GENERAL NOTE:


13MM
GYPSUM PROVIDE PHOTOS OF SECURE WALL CONSTRUCTION (W3c, W4a, W4b)
BOARD ATTACK SIDE
PRIOR TO CLOSING WITH GWB FOR CONSULTANT AND SECURITY REVIEW.
W4a W4a - GYPSUM CONSTRUCTION 1HR FRR (ULC Des W453) WITH PLENUM BARRIER AND FIRE RATED PLY W4b W4b - GYPSUM CONSTRUCTION 1HR FRR (ULC Des W453) WITH PLENUM BARRIER PHOTOS MUST DOCUMENT SECURE WALL COMPONENTS INCLUDING
(CONTFROM FLOOR SLAB TO CEILING SLAB WITH WIRE MESH AND PLYWOOD. (CONT FROM FLOOR SLAB TO CEILING SLAB WITH WIRE MESH, BUILD AS PER RCMP G13-01) W3C W3C - CORNER PLAN DETAIL FRAMING, BRACING, SECURITY MESH AND STEEL SHEETING AROUND
W3c W3c - GYPSUM CONSTRUCTION FROM SLAB TO SLAB W/ MESH
BUILD AS PER RCMP G13-01 SECURE STORAGE ROOM SPECIFICATIONS)
(CONT FROM FLOOR SLAB TO CEILING SLAB, BUILD AS PER RCMP G13- 02 SECURE DEMISING WALL) CIRITICAL ATTACK AREAS, DUCTS, AND DUCT REINFORCEMENT
- 16mm TYPE X GYPSUM BOARD - 16mm TYPE X GYPSUM BOARD
- 16mm TYPE X GYPSUM BOARD TO BE USED TO PROVIDE FIRE RATING - 152mm 18ga STEEL STUDS @300mm O.C. W/ - 152mm 18ga STEEL STUDS @300mm O.C. W/
W4A W4A - CORNER PLAN DETAIL
- 152mm METAL STUDS @ 300mm O.C. W/ ATTENUATION BATTS INSUL (STC-52) IN CAVITY STUDS TO MEET G13-01 REQUIREMENTS. STUDS TO MEET G13-01 REQUIREMENTS.
- CONT WIRE MESH16ga FROM FLOOR TO U/S OF SLAB, RIVETED OR WELDED PER RCMP G13-02 - 152mm 2.8 kg/m² MINERAL WOOL INSULATION (STC-47) IN CAVITY. - 152mm 2.8 kg/m² MINERAL WOOL INSULATION (STC-47) IN CAVITY.
- 1 LAYER OF 16mm TYPE X GYPSUM BOARD - CONT WIRE MESH16ga FROM FLOOR TO U/S OF SLAB, RIVETED OR WELDED PER RCMP G13-01 - CONT WIRE MESH16ga FROM FLOOR TO U/S OF SLAB, RIVETED OR WELDED PER RCMP G13-01
- ACOUSTIC CAULKING TOP & BOTTOM - 16mm TYPE X GYPSUM BOARD - 16mm TYPE X GYPSUM BOARD W4B W4B - CORNER PLAN DETAIL
-
-
STC-50
REFER TO PROJECT TRA FOR PERIMITER WALL REQUIREMENTS
-
-
19mm FIRE RATED PLYWOOD UP TO 2440 AFF. GRADE AC. GRADE A ON EXPOSED SIDE, PAINTED.
ACOUSTIC CAULKING TOP & BOTTOM
- ACOUSTIC CAULKING TOP & BOTTOM
Contractor to verify all dimensions &
NOTE: DOORS THROUGH W4b WALLS REQUIRE CRITICAL ATTACK AREA DOOR BRACING, SEE DETAIL 1/A002
REFER TO RCMP G13-01 SECURE STORAGE ROOM GUIDE
conditions on site and immediately notify
NOTE: DOORS THROUGH W3c WALLS REQUIRE CRITICAL ATTACK AREA DOOR BRACING, SEE DETAIL 1/002 NOTE: DOORS THROUGH W4a WALLS REQUIRE CRITICAL ATTACK AREA DOOR BRACING, SEE DETAIL 1/A002
FOR MORE INFORMATION
the departmental representative of all
discrepancies.

13 Issued for CCN 43 10 Apr 2024

EXISTING FLOOR SLAB 8 Issued for RFI #70 27 Sep 2023


EXISTING FLOOR SLAB EXISTING FLOOR SLAB
EXISTING FLOOR SLAB EXISTING FLOOR SLAB 7 Issued For Construction 17 Mar 2023

PLENUM BARRIER NOTES: ACOUSTIC SEALANT BEAD 6 Issued For Tender 21 Nov 2022
PLENUM BARRIER NOTES:
- ALL JOINTS TAPED (BOTH SIDES) CONTINUOUS ON BOTH SIDES
- ALL JOINTS TAPED (BOTH SIDES) STEEL TRACK
ACOUSTIC SEALANT BEAD
- ALL PENETRATIONS MUST BE
80 - ALL PENETRATIONS MUST BE
5 Issued For Building Permit 07 Nov 2022
PLENUM BARRIER NOTES: ACOUSTIC SEALANT BEAD CONTINUOUS ON BOTH SIDES SEALED WITH ACOUSTIC CAULKING
- ALL JOINTS TAPED (BOTH SIDES) CONTINUOUS ON BOTH SIDES SEALED WITH ACOUSTIC CAULKING
PLENUM BARRIER NOTES: ACOUSTIC SEALANT BEAD EXISTING CEILING TILE
- ALL PENETRATIONS MUST BE - ALL JOINTS TAPED
EXIST CEILING TILE IN SUSPENDED T- IN SUSPENDED T-BAR CEILING 4 Issued For 99% Review 31 Oct 2022
SEALED WITH ACOUSTIC CAULKING - ALL PENETRATIONS MUST BE 18 GA STEEL TRACK
18 GA STEEL TRACK BAR CEILING. PROVIDE NEW EDGE
EXISTING CEILING TILE SEALED WITH ACOUSTIC CAULKING
IN SUSPENDED T-BAR CEILING
TRACK TO MATCH EXIST ON CLIENT SIDE 3 Issued For 90% CP Review 03 Oct 2022
18 GA STEEL TRACK OF WALL AND CUT BACK CEILING TILE
EXISTING WALL
TO FIT. RESTRAIN PER SEISMIC
REQUIREMENTS INSIDE OF SHAFT 2 Issued For 66% Review 31 Aug 2022

1 Issued For 33% Review 21 Jun 2022


SOUND ATTENUATING BATT INSULATION
EXISTING CEILING TILE IN SUSPENDED T-
ACOUSTIC SEALANT BEAD
SOUND ATTENUATING BATT INSULATION BAR CEILING. PROVIDE NEW EDGE TRACK SECURE BOTTOM TRACK TO STRUCT SLAB SECURE BOTTOM TRACK TO 18 GA STEEL TRACK
Revisions Description Date
CONTINUOUS ON BOTH SIDES
TO MATCH EXISTING AND CUT BACK W/ FASTENER @ 400mm OC TYP STRUCT SLAB W/ FASTENER @
INSIDE CEILING TILE TO FIT. RESTRAIN PER 400mm OC TYP A detail no.
SECURE BOTTOM TRACK TO STRUCT SLAB 18 GA STEEL TRACK SECURE BOTTOM TRACK TO STRUCT SLAB SEISMIC REQUIREMENTS NEW RESILIENT WALL BASE
NEW RESILIENT WALL BASE STEEL TRACK
no. du detail
W/ FASTENER @ 400mm OC TYP

NEW RESILIENT WALL BASE


W/ FASTENER @ 400mm OC TYP
18 GA STEEL TRACK
CONT ACOUSTIC SEALANT BEAD NEW CARPET OR TILE
A B location drawing no.
A
ACOUSTIC SEALANT BEAD NEW RESILIENT WALL BASE
ACOUSTIC SEALANT BEAD sur dessin no.
CONTINUOUS ON BOTH SIDES, NEW CARPET OR TILE
CONTINUOUS ON BOTH SIDES
NEW CARPET OR TILE NEW CARPET OR TILE C C drawing no. B C
dessin no.
EXISTING FLOOR SLAB
Project Projet
EXISTING FLOOR SLAB EXISTING FLOOR SLAB

W6 W6 - GYPSUM CONSTRUCTION WITH PLENUM BARRIER GOC 5033045 ESDC PDOC


(FLOOR SLAB TO U/S OF SUSPENDED CEILING & T.O. SUSPENDED
WS WS - SHAFT WALL 1HR FRR (ULC Des W452) CB CB - CONCRETE BLOCK 1.5HR FRR
CEILING TO U/S OF SLAB WITH PLENUM BARRIER)
W5a W5a - GYPSUM CONSTRUCTION WITH PLENUM BARRIER W5b W5b - GYPSUM CONSTRUCTION FROM SLAB TO SLAB (CONT FROM FLOOR SLAB TO CEILING SLAB (CONT FROM FLOOR SLAB TO CEILING SLAB
(FLOOR SLAB TO U/S OF SUSPENDED CEILING & T.O. SUSPENDED (CONT FROM FLOOR SLAB TO CEILING SLAB)
CEILING TO U/S OF SLAB WITH PLENUM BARRIER)
-
-
64mm METAL STUDS @ 400mm O.C.
1 LAYER OF 16mm GYPSUM BOARD
TENANT IMPROVEMENT
- 16mm TYPE X GYPSUM BOARD - 203mm (8") CONCRETE BLOCK - APPENDIX D TABLE D-2.1.1 BCBC 2018
- 64mm 25ga C-H STUDS @600mm O.C. - ACOUSTIC CAULKING TOP & BOTTOM
- SAME AS W2 EXCEPT WITH: - SAME AS W3a EXCEPT WITH:
- 25mm SOUND ATTENUATING BATT INSULATION IN CAVITY
- 152mm METAL STUDS @ 400mm O.C. W/ ATTENUATION BATTS IN CAVITY - 152mm METAL STUDS @ 400mm O.C. W/ ATTENUATION BATTS IN CAVITY
- 25mm TYPE X GYPSUM BOARD
INSULATION (STC-52) IN CAVITY INSULATION (STC-52) IN CAVITY
- ACOUSTIC CAULKING TOP & BOTTOM 15330 54a Ave. Surrey, BC

Drawing Dessin

EXISTING FLOOR SLAB Wall Schedule

PLENUM BARRIER NOTES: ACOUSTIC SEALANT BEAD


- ALL JOINTS TAPED (BOTH SIDES) CONTINUOUS ON BOTH SIDES
- ALL PENETRATIONS MUST BE
SEALED WITH ACOUSTIC CAULKING
EXISTING CEILING TILE 1 : 10
IN SUSPENDED T-BAR CEILING
18 GA STEEL TRACK

Designed By Conçu
DG
Date 12 Jan 2024 (yyyy/mm/dd)
ACOUSTIC SEALANT BEAD
CONTINUOUS ON BOTH SIDES SOUND ATTENUATING BATT INSULATION Drawn By Dessiné par
FL
SECURE BOTTOM TRACK TO STRUCT SLAB 18 GA STEEL TRACK Date (yyyy/mm/dd)
W/ FASTENER @ 400mm OC TYP
12 Jan 2024
NEW RESILIENT WALL BASE Reviewed By Examiné par
ACOUSTIC SEALANT BEAD
JSE
CONTINUOUS ON BOTH SIDES, NEW CARPET OR TILE
Date 12 Jan 2024 (yyyy/mm/dd)

Approved By Approuvé par

EXISTING FLOOR SLAB Date (yyyy/mm/dd)

Tender Soumission
JSE
W6 W6 - GYPSUM CONSTRUCTION WITH PLENUM BARRIER (1HR FRR ULC U453)
(FLOOR SLAB TO U/S OF SUSPENDED CEILING & T.O. SUSPENDED Project Manager Administrateur de projets
CEILING TO U/S OF SLAB WITH PLENUM BARRIER)

Project No. No. du projet


- 1 LAYER OF 16mm GYPSUM TYPE X BOARD
- 92mm METAL STUDS @ 400mm O.C. W/ ATTENUATION BATTS IN CAVITY

-
INSULATION (STC-52) IN CAVITY
1 LAYER OF 16mm GYPSUM TYPE X BOARD
22038
- ACOUSTIC CAULKING TOP & BOTTOM

Drawing No. No. du dessin

A001
C:\Users\sahar bahrami\Documents\22038-BGIS PDOC Tenant Improvement_Central_saharL6TYF.rvt
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Door Schedule

Maglock (Delayed Egress)


Locat Public Services and Services publics et
ion Material Finish Procurement Canada Approvisionnement Canada
DOOR SCHEDULE LEGEND GENERAL DOOR HARDWARE NOTES:
1. PASSAGE LOCKSETS (ANSI F75) TO BE OPERATED BY LEVER FROM EITHER SIDE AT ALL TIMES Real Property Direction générale
Branch des biens immobiliers

Frame Material
2. PRIVACY LOCKSETS TO HAVE OCCUPANCY INDICATORS

Door Operator
HM HOLLOW METAL H1 REGULAR CONCEALED HINGE

Door Material

Placeholder 1

Placeholder 2

Placeholder 3
High Security
Frame Finish
3. CLASSROOM LOCKSETS (ANSI F84) TO HAVE DEADLOCKING LATCH-BOLT OPERATED BY LEVER

Locking Bars
SCW SOLID CORE WOOD H2 CONCEALED HINGE WITH NRP

Card Reader

Door Viewer
Door Closer
Door Finish

Storeroom
PS PRESSED STEEL L1 MORTISE LEVER LOCKSET

Kick Plates
Classroom
FROM EITHER SIDE, EXCEPT WHEN OUTSIDE LEVER IS LOCKED FROM OUTSIDE BY KEY. WHEN

Elec Strike
Thickness

Door Seal

Push Bar
PT PAINTED L2 CYLINDRICAL LEVER LOCKSET
OUTSIDE LEVER IS LOCKED, LATCH-BOLT IS OPERATED BY INSIDE LEVER.

Astragal
Passage
Room #

Keypad
Privacy
V VENEER - BIRCH

Hinges
4. STOREROOM LOCKSETS (ANSI F07) TO HAVE DEADLOCKING LATCH-BOLT OPERATED BY KEY IN
Door Fire PF2 PRIVACY FILM
OUTSIDE LEVER, OR BY OPERATING INSIDE LEVER. OUTSIDE LEVER ALWAYS LOCKED, INSIDE
Mark Type Rating Height Width Remarks LEVER ALWAYS UNLOCKED.
5. INSTITUTIONAL LOCKSETS (ANSI F30) TO HAVE LATCH-BOLT RETRACTED BY KEY FROM EITHER
SIDE. LEVER ON BOTH SIDES ALWAYS INOPERATIVE. AUXILIARY LATCH DEADLOCKS LATCH-BOLT
D102a 102 F-1 2134 1524 45 SCW PS PT5 PT4 ● ● ● ● WHEN DOOR IS CLOSED.
6. HIGH SECURITY LOCKSET DOORS REQUIRE CRITICAL ATTACK AREA DOOR BRACING, SEE BELOW.
D102b 102 A 2134 914 45 HM PS PT5 PT4 ● ● ● ● 7. FIRE-RATED DOORS MUST BE FITTED WITH DOOR HARDWARE THAT IS ALSO FIRE-RATED
INCLUDING LOCKSETS, DOOR STRIKES / PLATES, HINGES AND EXITING HARDWARE.
D103 103 A 2134 914 45 HM PS PT5 PT4 ● ● ● ● ●
8. DO NOT PRECUT DOORS FOR ELECTRIC STRIKES.
D104 104 F 2134 1524 45 SCW PS PT5 PT4 ● ● ● ● ● 9. DELAYED EGRESS HARDWARE IS TO COMPLY WITH 3.4.6.16.(4) OF THE BCBC. THE TOTAL TIME
DELAY FOR ALL ELECTROMAGNETIC LOCKS IN ANY PATH OF EGRESS CANNOT BE MORE THAN
D105 105 A 2134 914 45 HM PS PT5 PT4 ● ● ● ● 15 SECONDS.
D106 106 F 2134 1524 45 SCW PS PT5 PT4 ● ● ● ● ● 10. ALL OTHER CARD READER DOORS MUST ALSO BE CONFIGURED TO BE FAIL SECURE.
11. KICKPLATE REQUIREMENTS TO BE ON BOTH INTERIOR AND EXTERIOR FACE OF DOORS, WHERE
D112 112 A 1hr 2134 914 45 HM PS PT5 PT4 ● ● ● ● ● ● REQUIRED, NEW KICKPLATES TO BE 305mm HIGH.
12. ALL DOORS TO HAVE A DOOR STOP.
D113
D114
113
114
A-2
A-2
2134
2134
914
914
45
45
SCW
SCW
PS
PS
PT5 PT4
PT5 PT4


13. DOOR SEALS - PROVIDE SEAL SET WITH SURFACE MOUNTED DROP SEAL.
14. DOOR OPERATORS TO BE COMPLETE WITH PUSH BUTTONS.
15. HINGES TO BE HEAVY DUTY GRADE 2 SECURITY HINGES WITH NON REMOVABLE PINS.
IREDALE
A R CHI T EC T UR E
D117 101 EXIST 2134 1829 ●
D120 G 2134 1829 45 HM PS ● ELECTRIC DOOR STRIKES TO BE:
220 - 12 Water Street
1. COMPATIBLE WITH DOOR HARDWARE AND DOOR TYPE (I.E. FIRE-RATED DOORS)
D121 121 A-2 2134 914 45 SCW PS PT5 PT4 ● ● ● ● 2. SUITABLE FOR USE WITH BORED LOCKS, MORTISE LOCKS OR MORTISE EXIT DEVICES HAVING A
Vancouver, BC V6B 1A5
(Active Leaf) (Inactive Leaf)
½” OR ⅝” THROW DEAD-LATCH BOLT. 604 - 736 - 5581
D122 122 A-2 2134 914 45 SCW PS PT5 PT4 ● ● ● ● NOTE: 3. MADE OF STAINLESS STEEL FOR HEAVY CONSTRUCTION, CORROSION RESISTANCE, STRENGTH Vancouver Victoria
D124 124 A 2134 914 45 SCW PS PT5 PT4 ● ● ● LOCKING BARS TO BE HEAVY DUTY, INSTALLED AT BOTH TOP AND TAMPER RESISTANCE
AND BOTTOM OF INACTIVE (SMALL) LEAF, AND C/W PADLOCKS. 4. COMMERCIAL / INDUSTRIAL GRADE iredale.ca
D125 125 A 2134 914 45 SCW PS PT5 PT4 ● ● ● ● ● BARS TO HAVE MIN DIAMTER 30mm AND PROJECT MIN 30mm 5. HORIZONTALLY ADJUSTABLE
INTO POCKET OR GUIDE. SECURE WITH RIVETS OR WELDING. 6. NON-HANDED
D126 126 A-2 2134 914 45 SCW PS PT5 PT4 ● ●
7. FAIL-SECURE STANDARD
D127 127 A-2 2134 914 45 SCW PS PT5 PT4 ● ● LOCKING BARS
1
D200a 200 E-1 2134 1016 45 SCW PS PT5 PT4 ● ● ● ● ● 1 : 50
D200b 200 A-1 2134 914 45 HM PS PT5 PT4 ● ● ● ● ●
TYP CRITICAL ATTACK AREA DOOR
D200c 200 A-1 2134 914 45 SCW PS PT5 PT4 ● 610 1220
BRACING (FOR W3c, W4a, W4b WALLS)
D200d 2134 914 45 50 510 50 50 1120 50
D200g 2134 1829 45

50
D201 201 G 2134 1829 45 HM PS PT5 PT4
25
D202 202 A-3 2134 914 45 SCW PS PT5 PT4 ● ● ● ●
D203 203 A-2 2134 914 45 SCW PS PT5 PT4 ●

1200 3'-11 1/4"

305
D204 204 A-1 2134 914 45 SCW PS PT5 PT4 ●
PRIVACY FILM;

25
2 2
D205 205 A-3 2134 914 45 SCW PS PT5 PT4 ● ● DENSER ON 2

305
2085

2185
BOTTOM
D206 206 A-3 2134 914 45 SCW PS PT5 PT4 ● ● PANELS &
1
D207 207 A-3 2134 914 45 SCW PS PT5 PT4 ● LIGHTER ON 2

305
1675
2440 8'-0"
TOP PANELS
D208 208 A-3 2134 914 45 SCW PS PT5 PT4 ● TYP.
3
D209a 209 A 2134 914 45 HM PS PT5 PT4 ● ● ● ● ● ●

1220 4'-0"

610
D209b 209 A 2134 914 45 HM PS PT5 PT4 ● ● ● ● 4

D210 210 F 2134 1524 45 HM PS PT5 PT4 ● ● ● ● 5

25
50
D211 211 F-1 1hr 2134 1524 45 HM PS PT5 PT4 ● ● ● ● ● ● ● ● CARD READER WITH INTEGRATED PIN PAD
Window A Window B Window C
1200 3'-11 1/4" 1200 3'-11 1/4"
D212 212 F 1hr 2134 1524 45 HM PS PT5 PT4 ● ● ● ● ● ● CARD READER WITH INTEGRATED PIN PAD Window Legend Contractor to verify all dimensions &
1 : 25 conditions on site and immediately notify
D214 214 A 2134 914 45 SCW PS PT5 PT4 ● ● KEYNOTES:
the departmental representative of all
1. WELDED DOUBLE STUD DOOR FRAME SUPPORT.
D215 215 A 2134 914 45 SCW PS PT5 PT4 ● ● ● discrepancies.
2. BRACE BETWEEN STUDS AT HORIZONTAL JOINTS
D216 216 A 2134 914 45 SCW PS PT5 PT4 ● ● ● 3. FRAME REINFORCEMENT: 6.4MM X 25MM X 610MM STEEL PLATE TACK
WELDED INSIDE FRAME, CENTER ON LOCK BOLT.
D220 200 G 2134 1829 45 HM PS PT5 PT4 ● 4. ANTI-SPREAD BRACING AT DOOR FRAME BETWEEN WALL STUD AND
D221 221 A 1hr 2134 914 45 HM PS PT5 PT4 ● ● ● ● ● ● DOUBLE STUD - TYP.
5. 16 GA SHEET STEEL ASTM 366, MATTE, INSTALLED ON INSIDE OF SECURE
D225 225 G 2134 1829 45 HM PS PT5 PT4 ● ● ● ● ● ● STORAGE ROOM. EXTEND 1200MM FROM EDGE OF DOOR FRAME.
13 Issued for CCN 43 R1 10 Apr 2024
ATTACH PER RCMP G13-01 RIVET OR WELDING REQUIREMENTS. NO
D226a 226 G 2134 1829 45 HM PS PT5 PT4 ● ● ● ● ● ELECTRICAL OR MECHANICAL PENETRATIONS PERMITTED. 11 Issued for RFI-115 19 Jan 2024
D226b 226 G 2134 1829 45 HM PS PT5 PT4 ● ● ● ●
10 Issued for CCN-08 R1 06 Nov 2023
D228 228 A-3 2134 914 45 SCW PS PT5 PT4 ● ● CRITICAL ATTACK AREA BRACING
2
1 : 50 9 Issued For CCN-09 R2 8 Sept 2023
D229 229 A-3 2134 914 45 SCW PS PT5 PT4 ● ●
125150 150 610 150 150 610 150 8 Issued For CCN-08 06 Jul 2023
D230 230 A-1 2134 914 45 SCW PS PT5 PT4 ●
7 Issued For Construction 17 Mar 2023

150

150

150
D231 231 G 2134 1829 45 SCW PS PT5 PT4 ● ● ● ● ● ●
Revisions Description Date
D232 232 A 1hr 2134 914 45 SCW PS PT5 PT4 ● ● ● ● ●
A detail no.
D300a 300 A-1 2134 914 45 HM PS PT5 PT4 ● ● ● ● no. du detail
A A

760

870
B location drawing no.
D300b 300 G 2134 1829 45 HM PS PT5 PT4 ● ● ● ● sur dessin no.
D300c 300 A-1 2134 914 45 HM PS PT5 PT4 ● ● ● ● C C drawing no. B C
dessin no.

1725
D300d 300 A-1 2134 914 45 SCW PS PT5 PT4 ● ● ● ●

2135
Project Projet
D302 302 A-3 2134 914 45 SCW PS PT5 PT4 ● ●
D303 303 A-2 2134 914 45 SCW PS PT5 PT4 ● ● GOC 5033045 ESDC PDOC
D304 304 A-3 2134 914 45 SCW PS PT5 PT4 ● ● 915 915 915 915
TENANT IMPROVEMENT
D305 305 A-3 2134 914 45 SCW PS PT5 PT4 ● ●
D306 306 E-2 2134 1016 45 SCW PS PT5 PT4 ● ●

255
15330 54a Ave. Surrey, BC
D307 307 E-2 2134 1016 45 SCW PS PT5 PT4 ● ●
D308 308 G 2134 1829 45 SCW PS PT5 PT4 ● ● ● ● TYPE A TYPE A-1 TYPE A-2 TYPE A-3
Drawing Dessin
D309 309 G 2134 1829 45 SCW PS PT5 PT4 ● ● ● ● ● ●
610 915 610 915 915 915
D310 310 E-3 2134 1016 45 SCW PS PT5 PT4 ● ● Door Schedule
D311 311 E-3 2134 1016 45 SCW PS PT5 PT4 ● ●

400
125150
D312 312 A 2134 914 45 SCW PS PT5 PT4 ● ● ● ●
D313 313 A-2 2134 914 45 SCW PS PT5 PT4 ●
As indicated
D314 314 A-2 2134 914 45 SCW PS PT5 PT4 ●

510
D315 315 A 2134 914 45 SCW PS PT5 PT4 ● ● ● Designed By Conçu
DF
D316 316 A 2134 914 45 SCW PS PT5 PT4 ● ● ●

2135
Date 12 Jan 2024 (yyyy/mm/dd)

D320 300 G 2134 1829 45 HM PS PT5 PT4 ● Drawn By Dessiné par


FL
D321 321 A 1hr 2134 914 45 HM PS PT5 PT4 ● ● ● ● ● ● Date (yyyy/mm/dd)
12 Jan 2024

1225
D322 322 A 1hr 2134 813 45 HM PS PT5 PT4 ● ● ● Reviewed By Examiné par
1015 1525 1525 1830 JSE
D-003 003 G 1hr 2134 1829 45 HM PS ● ● ● ● ● Date (yyyy/mm/dd)
12 Jan 2024
D-004 004 G 1hr 2134 1829 45 HM PS ● ● ● ● ● Approved By Approuvé par

E100b EXIST 2134 914 44 EXIST EXIST ● ● ● ● ● Date (yyyy/mm/dd)


E100c EXIST 2134 914 45 EXIST EXIST PT5 PT4 ● ● ● ● ● TYPE E TYPE E-# SIM A-# TYPE F TYPE F-1 TYPE G
Tender Soumission
JSE
E100d EXIST 2134 914 45 EXIST EXIST PT5 PT4 ● ● ● ● ●
Door Type Legend Project Manager Administrateur de projets
E100e EXIST 2134 914 45 EXIST EXIST PT5 PT4 ● ● ● ● ●
1 : 25 Project No. No. du projet
E111 111 EXIST 2134 914 44 ●
E201 201 EXIST 2134 1829 ●
22038
Drawing No. No. du dessin

A002
C:\Users\sahar bahrami\Documents\22038-BGIS PDOC Tenant Improvement_Central_saharL6TYF.rvt
0 10 20mm 40 60 80 100 120 140 160 180 200mm
E F H J
Public Services and Services publics et
Procurement Canada Approvisionnement Canada

Real Property Direction générale


D Branch des biens immobiliers

1'
PT1 RB

1220

1220
AP2 AP2 310

1220

PT1 RB
AP2

1220
AP2

1220
AP2

2440

2440
AP2

2135
12
20 F1
301E

1220
AP2 PT1

2440

2135
RB
24 311

1220

1220

1220
40 F5
AP2 AP2 AP2

915
AP2 TS
12
20
2'
1 TS
SCG
SI-37 SCG 316 SCG SCG
AP1 SCG AP1
SCG PT1 RB SCG 318 317 PT1
RB
F5
C
12
20
AP2
PT1 RB T1
T3
PT1 RB IREDALE
A R C HI T E C T UR E
24 T2
40 F2
TS F2
AP2
319 220 - 12 Water Street
12 TS 312
20 STAIR 3 F2 Vancouver, BC V6B 1A5
T3
AP2 604 - 736 - 5581
ACOUSTIC WALL COVERING PANELS 12 T1

850
20 T2 TS TS
Vancouver Victoria
TS TS TS TS iredale.ca
24 PT1 RB
40 SCG
SCG SCG SCG 315 F1 SCG SCG AP1
AP2
AP2 12
12 20
20 AP2
320
PT1 RB
300 PT1 RB
313
321 AP1
24 12

1220
40 20 AP2

131
RB
F3 F2 F1 SCG
AP2

.23
12

1
F5

PT
12 20

1220
20 STAIR 2 AP2
TS
18 TS
30
AP2 AP2
AP2 301A
12
20 301D AP2
12 SCG
20 SCG

1220
24 SCG AP2
40 AP2 12

1220
12 20 AP2
SCG F1
AP2 20
12 SCG
12 301B 20 AP1
20 12 F5

1220

1220
F1 F1

2440
20 AP2
61 AP2
0 12 AP2

2440
20
AP2
12 314
20
SCG

2440

2440

1220
AP2 AP1 AP2
12 SCG
24

1220
20 40 AP2

RB 1
AP2

PT
24 SCG AP2

1220
12

1220
40 20 AP2 AP2
PT1 RB
AP2 309 3'
RB 1

12 SCG
PT

20 TS
305 AP2
PT 12 Contractor to verify all dimensions &
TS 1 20
24 307 RB conditions on site and immediately notify
B 40
F5 24 the departmental representative of all
SCG AP2 F2 40
RB 1

FLOOR AND WALL FINISH SCHEDULE:


PT

12 discrepancies.
RB 1
PT

TS 20
AP2 ITEM TAG PRODUCT NAME/ NUMBER/ COLOUR SUPPLIER
308 F1
SCG
303 12
306 20
RB

TS UNO, ALL COLUMN AND GYPSUM ABOVE AND BELOW WINDOW WALLS (BUILDING PERIMETER), BULKHEADS AND CEILING REVEALS TO BE PAINTED TO MATCH:
F5
1

SCG PT1 - BENJAMIN MOORE COLOUR SNOW WHITE 2122-70, 100% ACRYLIC, EGGSHELL

RB
PT

F5

1
• SECTION 06 40 00 - ARCHITECTURAL WOODWORK

PT
302
304 F2
SCG MILLWORK - CABINET PL1 DOWNTOWN URBAN WALNUT W475 ARBORITE
A

RB 1
AP2

PT
F2 TS G' COUNTERTOP PL2 BAROQUE SOAPSTONE P1017 ARBORITE
20

SCG
12

TS • SECTION 06 80 00 - COMPOSITE FABRICATIONS


RB 1
RB 1

F5
P
PT

TS
W

RB 1
PT
FIBERGLASS REINFORCED PLASTIC WP1 CHROME CANVAS - 011C CRANECOMPOSITE
40

SCG F5
24

F5
• SECTION 08 71 00 - DOOR HARDWARE
AP2
STAIR 1 THRESHOLD TS
INSTALLED IN LOCATIONS WHERE THERE IS A TRANSITION BETWEEN
REFER TO SPECS
20

DIFFERENT TYPES OF FLOORING MATERIALS. 13 Issued For CCN 43 1 Feb 2024


12

1 • SECTION 08 87 00 - PRIVACY FILMS


Revisions Description Date
40
24

G PRIVACY FILM [EXTERIOR GLAZING AS INDICATED] PF1 APPLIED ON WINDOWS ON TOP OF SECURITY FILM. REFER TO SPECS
A detail no.
AP2 301C no. du detail
DECO PRIVACY FILM [INTERIOR GLAZING] PF2 DECORATIVE, APPLY TO DOOR LITES. SEE DOOR AND WINDOW LEGENDS REFER TO SPECS
A A
20

B location drawing no.


12

SCG • SECTION 08 87 53 - SECURITY FILMS sur dessin no.


C C drawing no. B C
SECURITY FILM [ALL EXTERIOR & ENTRY VEST. GLAZING] SF APPLIED ON ALL PERIM. WINDOWS, AS INDICATED IN PLAN. PATTERN TBD REFER TO SPECS
40

20

dessin no.
24

12

AP2 • SECTION 09 30 13 - CERAMIC TILING Project Projet


2 AP2
20

SCG
12
20

PORCELAIN TILE WASHROOM FLOORING T1 STONES STOGM24 | 24"X 24" GREY AMES
GOC 5033045 ESDC PDOC
12

TORNARES 6"X21" ORDESA SILVER TOROS621 AND GREDOS SILVER


PORCELAIN TILE WASHROOM WALL TILES T2 AMES
40

TORGS621
24

PORCELAIN TILE WASHROOM WALL TILES T3 TORNARES 6"X21" HIRU WHITE TORHW621 AMES
AP2 TENANT IMPROVEMENT
AP2
20

PORCELAIN TILE KITCHEN BACKSPLASH TILES T4 SLASH | 3"X12" SAGE SLSH73SV CENTURA
12
20

F1
PT
12

1 PORCELAIN TILE ENTRANCE FLOORING T5 DELEGATE - OFF WHITE DL25 24X24 DALTILE
RB 15330 54a Ave. Surrey, BC
40
24

• SECTION 09 51 99 - ACOUSTICAL CEILING


RB

AP1 AP2 Drawing Dessin


1

ACOUSTICAL CEILING PANEL ACP CEILING CLOUDS - 6" BAFFLE ASSEMBLY - MARBLE/ MOSS GREEN THE QUIET ROOM
PT
20
12

• SECTION 09 65 16 - RESILIENT FLOORING


Level 3 Finishes Plan
LINOLEUM FLOORING F2 FORBO MARMOLEUM CONCRETE METEROID FORBO
40
24

FLOORING STATIC DISSIPATIVE TILE [LAN ROOM] F3 FORBO EVEREST SD 150201 FORBO
AP2
TRANSITION STRIP TS TRANSITION STRIP TO MATCH WALL BASE REFER TO SPECS
20
12

RUBBER WALL BASE RB 55 SILVER GREY REF. 44999300161 TARKETT


As indicated
• SECTION 09 68 13 - TILE CARPETING
Designed By Conçu
FINISH NOTES CARPET TILE - ACCENT CARPET F5 18" X 36" EXCHANGE TILE 5T304 - ARGAN 01100 - BASKETWEAVE SHAW WALL
CONTRACT DG
METRO COVERINGS
1. NEW PAINT APPLIED TO ALL WALLS AS NOTED ON FINISHES PLAN. CARPET TILE - FIELD CARPET F1 9" X 36" FLAT WEAVE TILE V - ARGAN 01100 - HERRINGBONE SHAW CONTRACT Date 12 Jan 2024 (yyyy/mm/dd)

Drawn By Dessiné par


2. ALL PAINTED WALLS TO RECEIVE NEW WALL BASE, PER FINISH SCHEDULE WALK-OFF MAT ENTERY F4 NEW YORK COLLECTION - CHARCOAL SPLASH MATS INC FL
3. INSTALL NEW FLOOR FINISHES THROUGHOUT ENTIRE TENANT SPACE AS NOTED ON FINISHES PLAN. GC TO PROVIDE AN Date 12 Jan 2024 (yyyy/mm/dd)
• SECTION 09 72 16 - VINYL-COATED FABRIC WALL COVERINGS
ADDITIONAL 10% OF CARPET TILE AND RESILIENT FLOORING, TO REMAIN ON SITE FOR FUTURE REPLACEMENT REQUIREMENTS.
Reviewed By Examiné par
N WALL COVERING WC1 KOROSEAL - FLEX COLLECTION - UPL1-13 JSE
4. ALL FILMS TO BE APPLIED TO INTERIOR SIDE OF GLAZING. USE APPROPRIATE STRUCTURAL CAULKING TO SECURE TO WINDOW
FRAMES. VALIDATE WITH SUPPLIER ON THE APPLICATION OF A PRIVACY FILM OVER SECURITY FILM. INSTALLATION WILL NEED TO Date 12 Jan 2024 (yyyy/mm/dd)
• SECTION 09 80 00 - ACOUSTIC TREATMENT
3 BE COORDINATED CLOSELY TO ALLOW FOR DRY TIMES FOR FILM AND CAULKING. Approved By Approuvé par
ACOUSTICAL PANEL - WALL COVERING AP1 HEXAGON TILE - MOSS GREEN/ MARBLE/ DARK MARBLE THE QUIET ROOM
5. FILM SAMPLES TO BE SUBMITTED TO ARCHITECT FOR APPROVAL PRIOR TO ORDERING.
Date (yyyy/mm/dd)
Level 3 Finishes Plan ACOUSTICAL PANEL - SPACE DIVIDERS AP2 4' X 4' BROKEN WINDOWS - MARBLE THE QUIET ROOM
1 6. AP 1 ACOUSTIC WALL PANELS TO BE INSTALLED CENTERED ON WALLS AND BOTTOM PANEL AT 1065mm (42") AFF. Tender Soumission
1 : 100 • SECTION 09 91 00 - PAINTING JSE
7. AP 2 ACOUSTIC SPACE DIVIDER PANELS TO BE INSTALLED BETWEEN WORKSTATIONS AT 100mm ABOVE FURNITURE PANELS,
COORDINATE WITH FURNITURE INSTALL. FIELD PAINT PT1 SNOW WHITE 2122-70 BENJAMIN MOORE Project Manager Administrateur de projets

8. WHERE TILES ARE USED AS FLOORING, RUN 4" UP WALLS AS BASE. TRIM PAINT PT4 TO MATCH WALL BASE COLOUR BM / SW Project No. No. du projet

9. GROUT COLOUR TBC.


DOOR PAINT PT5 STUDIO BLUE GREEN SW 0047 SHERWIN WILLIAMS 22038
• SECTION 10 26 13 - CORNER GUARDS
Drawing No. No. du dessin
STAINLESS STEEL CORNER GUARD SCG 50mm X 50mm X 1220mm REFER TO SPECS.
A113
C:\Users\sahar bahrami\Documents\22038-BGIS PDOC Tenant Improvement_Central_saharL6TYF.rvt
0 10 20mm 40 60 80 100 120 140 160 180 200mm
GENERAL NOTES :
Public Services and Services publics et
1. COORDINATE WITH ELECTRICAL (LIGHTING PLAN) AND Procurement Canada Approvisionnement Canada
MECHANICAL (DIFFUSER & HVAC PLAN)
2. T-BAR SYSTEMS, METAL FRAMING AND SEISMIC RESTRAINT TO E F H J Real Property Direction générale
BE DESIGNED TO MEET ALL APPLICABLE CODES. PROVIDE Branch des biens immobiliers
LETTER OF ASSURANCE ON COMPLETION OF INSTALLATION OF
THE WORK THAT IT HAS BEEN FABRICATED AND INSTALLED IN
ACCORDANCE WITH THE REQUIREMENTS OF THE BCBC.
LETTER TO BE SIGNED AND SEALED BY A PROFESSIONAL
ENGINEER REGISTERED IN THE PROVINCE OF BRITISH D
COLUMBIA.
3. NEW DIFFUSERS AND RETURN GRILLES TO MATCH COLOUR OF
NEW T-BAR GRID. 1'
4. NO SUSPENDED CEILING TO BE INSTALLED IN LAN ROOMS.

CEILING LEGEND BLK-P


ACT-1 T-BAR CEILING
NEW 2X4 T-BAR CEILING

GB-1 GWB CEILING


NEW 5/8" TYPE 'X' GWB PAINTED WHITE

BLK-P GWB BULKHEAD


NEW BULKHEAD AT PERIM WINDOWS, SEE RELEVANT DETAIL

301E 310
CEILING FIXTURE LEGEND

300 X 1200 PENDANT LUMINAIRE (LED)


ACT-1 2'
600 X 600 FLUSH MOUNTED LUMINAIRE (LED) 1
SI-37
BLK-P 3048 A.F.F.
IREDALE
A R C HI T E C T UR E
2X4 NEW LED LIGHT 311
C
1 X 4 NEW LED LIGHT 220 - 12 Water Street
316
Vancouver, BC V6B 1A5
4" RECESSED POT LIGHT (LED)
GWB-1 604 - 736 - 5581
2438 A.F.F.
4" SUSPENDED PENDANT LIGHT (LED)
317 Vancouver Victoria
319 318 GWB-1
CABLE TRAY iredale.ca
2438 A.F.F. 312
4' X [VARIES] ACOUSTIC CEILING PANELS, 315 STAIR 3
REFER TO FINISH SCHEDULE

CEILING LEGEND
ACT-1
GWB ON STEEL STUD CEILING 3048 A.F.F.
313

T-BAR CEILING ON 24 X 24 GRID (NOT USED) 320 300


321
T-BAR CEILING ON 24 x 48 GRID

MECHANICAL FIXTURE LEGEND


ACT-1
STAIR 2 3048 A.F.F.
SUPPLY AIR DIFFUSER

SUPPLY AIR DIFFUSER (LINEAR)


ACT-1
RETURN GRILLE 3048 A.F.F.

EXHAUST GRILLE

FLOW HEATER 301D


301A
SPRINKLERS
314
CONVEX MIRRORS, GC TO SUPPLY AND INSTALL

ACT-1 301B
3029 A.F.F.

309 Contractor to verify all dimensions &


conditions on site and immediately notify
ACT-1
3' the departmental representative of all
3029 A.F.F. discrepancies.
ACT-1
307 3029 A.F.F.
B

305 308
ACT-1
306 3029 A.F.F.

FREIGHT
ELEVATOR 13 Issued For CCN 43 1 Feb 2024
A 303 G'
GWB-1 11 Issued for SI-37 22 Jan 2024
2438 A.F.F.
5 Issued for CCN-13 21 Sep 2023
302
Revisions Description Date
STAIR 1
A detail no.
no. du detail
304 A B location drawing no.
A
1 sur dessin no.
G C C drawing no. B C
dessin no.

Project Projet

GOC 5033045 ESDC PDOC

2 301C TENANT IMPROVEMENT

15330 54a Ave. Surrey, BC

Drawing Dessin

Level 3 RCP

1 : 100

Designed By Conçu
DG
Date 12 Jan 2024 (yyyy/mm/dd)

Drawn By Dessiné par


FL
Date 12 Jan 2024 (yyyy/mm/dd)

Reviewed By Examiné par


JSE
N Date 12 Jan 2024 (yyyy/mm/dd)

Approved By Approuvé par

Date (yyyy/mm/dd)

Tender Soumission
3 JSE
Level 3 RCP
1 Project Manager Administrateur de projets
1 : 100
Project No. No. du projet

22038
Drawing No. No. du dessin

A110
C:\Users\sahar bahrami\Documents\22038-BGIS PDOC Tenant Improvement_Central_saharL6TYF.rvt
0 10 20mm 40 60 80 100 120 140 160 180 200mm
C.E.S. Engineering Ltd
402 - 4601 Canada Way
Burnaby, BC, Canada, V5G 4X7
604.239.4424

ELECTRICAL SITE INSTRUCTION #33

Project No: BC10028 Date: 08.03.2024.


Project Name: PDOC Surrey TI
Site Instruction No: ESI #33
Subject: Electrical – Enclosed space on the 3rd floor

Proceeding with work in accordance with these instructions indicates the Contractor's acknowledgment that there will
be no change in the Contract Price and Contract Time. If the Contractor believes that this instruction affects the
Contract Price or Contract Time, the Contractor shall promptly notify the Consultant.

Reference: RFI 122

Reason for change:


☐ 1. Cash Allowance ☒ 4. Site Condition ☐ 7. Procurement
☐ 2. Design Discrepancy ☐ 5. Cost Saving Conditions
☐ 3. Regulatory Change ☐ 6. Design Improvement ☐ 8. Contract Reconciliation
☐ 9. User Change

Response: Lighting Design

1. Provide and supply duplex receptacle, as per attached drawing E2.03.


2. Provide and supply lighting fixtures type C (1500lm, 4000K, Lightolier model no. CR8RLMCCT),
qty. 2, as per attached drawing E3.03.
3. Provide and supply toggle switch on/off, as per attached drawing E3.03.
4. Provide and supply remote heads type ERW, as per attached drawing E3.03.

END OF SITE INSTRUCTION #33

_______
Boban Ratkovich, P. Eng
Principal Engineer
CES Engineering
T: 604.239.4424
bratkovich@cesgroupglobal.ca

NORTH AMERICA | UNITED KINGDOM | EUROPE Engineering Beyond Expectations

Page 1 of 1
Canada
Biens Immobiliers, Real Property,
Gestion du Change Management
Changement et and Regional
Services Régionaux Services
(BIGCSR) (RPCMRS)

Key Plan Plan Clé

4 3
D2-16,18,20,22 3 D2-16,18,20,24 3 1 D-1,3,5,9 3 1
4 D-11,13,54,58 7 N
7 PP
7 PP D-1,3,5,7 7 PP 3 D-11,13,54,56 7 PP PP
3 D-18,19,21,60
D2-16 D2-16 D2-16 D2-20 D-1 D-1 3 D-5 D-1 D-5 D-11 D-11 D-11 D-54 2D QUIET ROOM
D2-18 D2-22 D2-18 D2-24 D-3 D-7 D-3 D-9 D-13 D-56 D-13 D-58 D-18 310
2D 2D 2D 2D 2D 2D 2D 2D 2D 2D 2D 2D D-60
D-5 D-54
3 D2-9,21,33,35 D2-35 D2-20 D2-20 D2-16 D2-20 D-5 D-1 D-5 D-54 D-11 D-54
D2-33 MBB-5,7 MBB-9,11
PP 2D
7 2D D2-22 D2-22 MBB-1,3 D2-24 D2-24 D-7 D-7 D-9 D-9 D-56 D-56 D-58 D-58 MB-2,4 8 PP
D-19
D2-33 2D 2D 2D 2D 2D 2D 2D 2D 2D 2D 2D 2D D-6
D2-9 D2-35 D-21 2D
D2-21
2D 2D D2-16 D2-18 D2-18 D2-18 D-1 D-3 D-3 D-3 D-11 D-13 D-13 D-13 2D
OPEN MB-9,11
D2-9 D2-22 D2-22 D2-24 D2-24 2 D-7 D-7 D-9 D-9 D-56 D-56 D-58 D-58 D-18
OFFICE D-6
D2-21 D2-9 2D 2D 2D 2D 2D 2D 2D 2D 2D 2D 2D 2D D-60
2D D2-21 301E 2 2 2

D2-21 2 2
3 D2-15,17,19,21
PP D2-19 MB-38,40 2D 2 MBB-2,4 MBB-6,8
7 2D D2-23 2D
D-2 D-2 D-6 PP 8
D2-21 D-2 D-2
D2-15 D2-19
D2-17 MB-34,36
2D 2D D-35 MB-72,74 2D D-6 FOCUS ROOM
MBB-13,15 D-35 D-17 2D D-15 2D D-15 D-4 311
D2-15 D2-21 D2-6 D-35 GENDER MB-5,7
2D
D2-17 D2-19 D2-14 D2-14 D2-14 NEUTRAL WC
2D 2D BS2
MB-62,64
D2-21 EM-13 316
D2-15 D2-19 KITCHENETTE
D2-17 MEN'S WC D-62,64 EM31-6
2D
BS1
STAIR D-4 PP 8
2D 319 EM-13 317 D-37 2D
7 P D2-44 D-35
P D2-13 D2-15 WOMEN'S WC 3
D2-33 D2-17 D2-12 318 HC WC IT STORAGE &
2D MB-33,35 2D 2 D2-14 D2-14 D2-8 D2-10 D-62,64 MB-18,20
3 D2-9,11,13,33 315 WORKLAB
D2-13 D2-42 EM31-7 D-4
D2-9 EM31-6 312
D2-11 D2-33
2D 2D EM31-4 D2-6 MB-72,74 CORRIDOR D-8 SMALL MEETING
D2-9 D2-13 D2-6 D-2 2D ROOM
3 D2-37,39,41,43 300 MB-13,15
D2-41 D2-11 D2-33 MBB-10,12 PNL PNL PNL
2D 2D EM-10,12 LOCKER (57) 313
7 PP D2-43 D-2 'EM31' MB MBB D-2
2D 320 PNL D D-26 D-30
D2-9 PNL
D2-41 D2-11 D2-7 EM-9,11 D-22 D-26 D-30 D-22

D
2D 2 2 'D2' D D D D D D D D EM31-7
1 D2-37 D2-43 D2-5 4D 8D 8D 2D

D
D2-39 2D 2D 3D SP-23 D-22 D-28 D-28 D-32 D-32
MB-37,39 D2-6 EM31-5 5 FB FB 5

D
D2-41
D2-37 STAIR D-10 D-10
D2-3

D
D2-39 D2-43 7 D-8
4 D1-28 2D 2D D2-1 LAN ROOM 2 MB-17,19
D2-7 3D

PP
D2-41 2 321
D2-37 D2-5 2
D1-32 D2-39 D2-43 D2-1,3,5,7 MB-26,28
3 D1-28,30,32,34 OPEN OFFICE 3D D-39
D1-34 2D 2D E-7.02 EM31-4
D2-3 3
2D 310D D2-7
D2-37 2 D2-5 D2-1 MB-42,44 D2-6 MB-30,32
D1-28 D1-32 D2-39 3D 3D
D1-34 2D 3D 1 D-36 D-36 D-14 C.E.S Engineering Ltd.
D1-30 OPEN OFFICE 2 D2-2 2D D2-4 2D 2 #402 - 4601 Canada Way, Burnaby, BC, V5G 4X7
2D 2D D2-3 D2-34 2
MB-41,43 301B D2-36 T: 604.239.4424
D1-32 D2-1 3D EM31-5 2 D-19 D-19

PP
D1-28 3D D2-1,3,5,7 www.cesgroupglobal.com
D1-30 D1-34 D2-7 2 D-21 D-21 D-14
D2-5 3D D2-38 D-29 D-33 D-23 D-27 OPEN D-21 D-60 7 EGBC Permit To Practice # 1002458
2D 2D 7 3 D2-34
3D D2-40 D-31 D-57 D-25 D-59OFFICE 2D 2D D-12 FB 5
4 D1-28 D1-32 D2-36 2 PP AV
D1-34 3D 3D 3D 2D 2D 2 3
3 D1-20,22,24,26 D1-20 D1-30 D2-7 D2-3 3D 301A D-34 D-34 2D 2D LES ENTREPRENEURS DOIVENT VÉRIFIER TOUTES LES
D1-22 2D 2D D2-5 D2-34 D2-38 D-33 D-18,19,21,60 DIMENSIONS ET CONDITIONS EXISTANTES DE
D2-1 D1-45 D-29 D-23 D-27 MB-14,16
3D D2-40 D-20 D-53 D-61 D-61
2D D1-28 3D D1-42 D2-36 2 D-31 D-57 D-25 D-59
L'EMPLACEMENT ET DE RAPPORTER TOUT ANOMALIES AU
D1-24 D1-30 D2-3 D2-1,3,5,7 3D D2-30 D-24 D-55 MB-21,23 2D 2D 7 PP D-16 GESTIONNAIRES DU PROJECT.
1 D1-20 D1-26 2D 2 MB-25,27 MB-29,31 D-12 FB 5 NE PAS MESURER SUR LES DESSINS.
D1-22 MB-10,12 D2-1 D2-38 D2-32 3D D-18,19,21,60 3
2D 3D 3D 3D

PP
2D 3D 3 D2-34,36,38,40 P 3D 2D D-19 D-34
MB-45,47 P D2-40 2D CONTRACTORS TO VERIFY ALL DIMENSIONS &
D1-24 D1-20 3 D2-30 2D
7 4D 7 D2-26 D-20 D-53 D-29 D-33 D-23 D-27 D-21 D-61 2 CONDITIONS ON SITE AND IMMEDIATELY NOTIFY THE
D1-20 D1-26 D1-22 D2-32 D-23
2D 2D D2-7 D2-28 D-57 D-59 2D 2D D-18 PROJECT MANAGER OF ALL DISCREPANCIES.
3D 3D D-24 D-55 D-31 D-25 D-12 FB 5 DO NOT SCALE DRAWINGS.
D1-24 D2-5 D-19,21,34,61 3 D-19 D-14
D1-20 D1-26 3D D2-3 D1-42 D2-30 3D 3D 3D 3D 2D 2D
3 D1-12,14,16,18 D1-12 D2-1 D2-26
D1-14 D1-22 2D 3 MB-49,51 D2-28 D2-32 D-33 D-27 1
2D 3D D2-1,3,5,7 3D D-20 D-53 D-29 D-23 4
7 PP 3D
2D D-24 D-55 D-31 D-57 D-25 D-59 WP
D1-16 D1-24 D1-45 D2-26 D2-30
PP

D1-26 2 D-20 3D 3D 1 D-40


D1-12 D1-18 2 D1-5 D2-28 D2-32 3D 3D 2D 2D
D1-14 2D 3D 3D 4
QUIET 2D 2D MB-6,8 2 7 D1-45 MB-58,60 D1-3
3 PP 7 PP 7 16. ISSUED FOR ESI#33 08.03.2024
D1-40 D1-45 3D 3 D-29,31,33,57
D1-12 D1-42 D2-26 D-20,24,53,55 D-23,25,27,59
ROOM D1-16 1V/1D D1-5 D2-28 LARGE MEETING
D1-14 D1-7 PP 3
304 D1-18 QUIET ROOM D1-3 3D D2-26,28,30,32 3 ROOM 15. ISSUED FOR ESI#40 23.02.2024
2D 2D EM32-4 MAIL /FILE ROOM D1-36
D1-35 D1-16 3D 3D 6 314
307 309
D1-12 D1-18 D1-44 D1-5
D1-14 D1-40 D1-6 D1-7 14. ISSUED FOR ESI#27 25.09.2023
2D 2D D1-8,10 D1-3
D1-36
D1-40 3D 3D
8 D1-16 PNL D1-5 13. ISSUED FOR ESI#19 25.08.2023
2 1V/1D D1-7
PP

2D D1-18 'D1' D1-42 D1-3


2D QUIET ROOM PNL D1-36
D1-35 MB-1,3 MB-50,52 3D 3D
306 'EM32' ROOM D1-3,5,7,36 D1-3 12. ISSUED FOR ESI#1, ESI#3, 31.07.2023
D1-35 308 PP D1-44 D1-7 ESI#8, ESI#13
2D D1-40 7 D1-5 D1-3,5,7,36
D1-50 D1-2 3D D1-36 11. ISSUED FOR CONSTRUCTION 17.03.2023
D1-50 3D 3
QUIET D1-37 2D D2-26
D1-44 MB-54,56
ROOM FREIGHT D1-7 BASE BUILDING
D1-9 10. 21.02.2023
304 D1-37 D1-50 STAIR ELEVATOR COORDINATION
D1-36
D1-50 1 3D REISSUED FOR BUILDING
2 4 9. 10.02.2023
8 D1-44 PERMIT
D1-37 MB-22,24
2D
PP

1 D1-42 2D 8. ISSUED FOR ADDENDUM 4 18.01.2023


D1-35 D1-9 D1-9
D1-39 MB-46,48 2D
D1-46 16 DRAWING NOTE: 7. ISSUED FOR ADDENDUM 1 16.12.2022
D1-39 D1-41 D1-47 2D
D1-39 D1-39 2D D1-9
2D MB-57,59 PROVIDE AND INSTALL TWO COMPARTMENTS (POWER AND DATA) OF WIREMOLD RACEWAY SYSTEM OR EQUAL.
D1-33 D1-46 1 No. description date
PROVIDE A RACEWAY SYSTEM THAT CAN BE INSTALLED ALONG WALL AT LOW LEVEL. REFER TO DETAIL DRAWINGS.
D1-37 D1-31 EM32-5
QUIET
D1-35 2D ROOM QUIET 2
2D
D1-33
D1-29 D1-48
ROOM
DESK FURNITURE 120VAC RECEPTACLE. PROVIDED BY FURNITURE SUPPLIER. FOR DETAILS SEE DRAWING A A detail no . / no. de détail
D1-27 2D 303 7.08/DETAIL #3.
D1-41 2D
D1-39
D1-31 2 D1-48 302 B B location drawing no. / sur dessin no.
2D 2D 2D 3 DESK 120VAC POWER WHIP CONNECTION. PROVIDED BY FURNITURE SUPPLIER.
MB-53,55 D1-33
D1-29 D1-31 D1-48 Project Projet
D1-37 D1-27 2D 4 EXTEND HORIZONTAL WIREMOLD CHANNEL (MODEL AL5200) UP INTO CEILING VOID FOR FEEDER WIRING FROM
7 PP D1-35 2D D1-25 2 PANEL AND DATA CABLING, DOWN TO WORKSTATION AREA. REFER TO DETAIL DRAWINGS.
3 D1-35,37,39,41
2D
D1-33
D1-29
D1-27
D1-23 GOC5033045 ESDC PDOC
2D 3D 5 PROVIDE A 6-INCH POKE-THRU FLUSH FURNITURE FEED TYPE FLOOR BOX WITH MIN REQUIREMENT 2 DUPLEX
D1-31 D1-21
2D OPEN OFFICE D1-25 D1-19 WP RECEPTACLE 120VAC AND 1 DATA OUTLET, AS SHOWN ON DRAWINGS. COORDINATE WITH ARCHITECT REGARDING
D1-33 D1-23 3D FLOOR BOX COVER LID COLOUR AND FINISH. TENANT IMPROVEMENT
D1-29 D1-31 301C
2D 3D D1-4
D1-27 D1-25
D1-21 6 PROVIDE AND INSTALL TWO COMPARTMENTS (POWER AND DATA) PAC-POLE WITH OPENING AT LOWER LEVEL TO
2D D1-23
D1-29 D1-19 3D ACCEPT ELECTRICAL WHIP (MODEL: CP5C150-BA BY CANADIAN ELECTRICAL RACEWAYS INC OR EQUAL). 15330 54a Ave. Surrey, B.C. V3S 8R7
D1-27 3D MB-65,67
2D D1-21 D1-11
3 D1-27,29,31,33 7 PROVIDE AND INSTALL TWO COMPARTMENTS (POWER AND DATA) PAC-POLE WITH OPENINGS AT LOWER LEVEL TO
D1-25 D1-19 D1-13 2
D1-11 D1-23 3D ACCEPT ELECTRICAL WHIP (MODEL: CP2C150-BA BY CANADIAN ELECTRICAL RACEWAYS INC OR EQUAL). Drawing Dessin
4 3D
3D D1-15 D1-15
D1-25
PAPER SIZE: B1 27.8 x 39.4 (707 x 1000) ● PLOT DATE & TIME: 2024-3-08 10:12:29 ● READ DRAWING ACCORDINGLY.

1 D1-21 D1-17 D1-17 8 PROVIDE AND INSTALL TWO COMPARTMENTS (POWER AND DATA) PAC-POLE WITH 2 POWER DUPLEX RECEPTACLES
D1-23 3D AND 2 DATA OUTLETS (MODEL: CP2B150-2E BY CANADIAN ELECTRICAL RACEWAYS INC OR EQUAL).
D1-19 3D 3D
D1-15
3D
D1-21 D1-11 D1-17
6 PP
D1-19 D1-13
3D
MB-61,63
THIRD FLOOR
3D 3D
3 D1-19,21,23,25
D1-15 D1-11 POWER LAYOUT
D1-17 D1-13 GENERAL NOTES:
3D
3D
D1-11 D1-15
D1-13 D1-17 1. ELECTRICAL CONTRACTOR IS TO ALLOW FOR INSTALLATION OF THE WHIP FROM THE SYSTEM FURNITURE TO
3D THE BASE BUILDING JUNCTION BOX.
3D Designed By Conçu par
6 PP
D1-11
D1-13 2. THE SIZE OF ALL WIRES FROM PANELS TO WORKSTATION JUNCTION BOXES WILL BE 10AWG.
BR
3D Date (yyyy/mm/dd)
3 D1-11,13,15,17 3. WHERE PAC POLE ARE PROVIDED (AS PER NOTES #6 & 7) THE WHIP FROM SYSTEM FURNITURE IS TO BE RUN Reviewed By Examiné par
UP THROUGHT THE PAC POLE (POWER COMPARTMENT) TO A 150mm x 150mm x 75mm DEEP JUNCTION BOX
(WITH COVER) WITHIN THE CEILING VOID WITHIN 450mm OF THE TOP OF THE PAC POLE. Date
BR (yyyy/mm/dd)
Approved by CFBO Apprové par DGAPF
4. ELECTRICAL CONTRACTOR TO COORDINATE WITH THE SYSTEM FURNITURE MANUFACTURER FOR THE
VOICE/DATA REQUIREMENTS AND TO ALLOW FOR INSTALLATION OF TWO 40mm LIQUID TIGHT FLEXIBLE
CONDUITS BETWEEN THE PACK POLE AND THE SYSTEM FURNITURE, EACH WITH A 90 DEGREE BEND AND Date (yyyy/mm/dd)
MALE TERMINATION AND LOCK OUT (ALLOW FOR EACH FLEXIBLE CONDUIT TO BE 6 FEET IN LENGTH). Approved by ISB Apprové par DGSI

Date (yyyy/mm/dd)
Client Approval Approbation du client

Date (yyyy/mm/dd)
Project no. No. du projet

GOC5033045
THIRD FLOOR POWER LAYOUT Drawing no. No. du dessin
1
E2.03
SCALE 1:100
c

0 10 20mm 40 60 80 100 120 140 160 180 200mm


Canada
Biens Immobiliers, Real Property,
Gestion du Change Management
Changement et and Regional
Services Régionaux Services
(BIGCSR) (RPCMRS)

Key Plan Plan Clé

ZONE c WPS ZONE b ZONE a


A3 A3 A3 A3 A3 A3 A3 A3 A3 A3

D-47 D-47 D-47 D-47 D-47 D-47 D-47 D-47 D-47 D-47
A3
D2-25
OPEN
A3 WOS A3 A3 WOS A3 A3 WOS OFFICE A3 WOS A3 A3 WOS A3

A3 EM31-1 D-47 D-47 D-47 D-47 301E D-47 D-47 D-47 BRG Z D-47 C-5A BRG
A3 BRG Z BRG Z QUIET
D2-25 D-47 WPS
D2-25 ROOM B2
E
E D-48
A3 A3 A3 A3 A3 A3 A3 A3 A3 310 WOS
E
EM31-1
A3 D-47 D-47 D-47 EM31-1 D-47 D-47 D-47 EM31-1 D-47 B2
A3 D2-25 D-48
D2-25 WOS EXC EXC D-47 D-47 EM31-3 WKA
E D-42 EXC EXC
D-42
EM31-3 D-42 EM31-1 ZONE d D-42 D-42 EM31-3 EM31-1 D-42 WOS D-48
EM12 D-42 D-42 D-42 FOCUS
A3 A3 WOS EM31-3 A3 A3 A3
WOS
A3 A3 A3 WOS A3
E A3 EM31-1 A3 B2
WPS
ROOM
A3 EM12
D-42 311
D2-25 EM31-1 WKC WKB 200W D-42 EM12 WKA WOS
WKC WKB
D2-25 D46

WKC WKC WKC


ZONE f D2-25 D2-25 EM31-1 C-5A BRG
D2-25 D-42 5 A3
D-48
B2
GENDER NEUTRAL EMN
D2-25 A3 EM31-1 D-42 H1 H1 E-8.03 A3 D-48 E
A3 D2-25 A3
A1 A1 A1
H MEN'S WC H WC H
D2-25 E H D-42 D-42 H D-42 D-48
KITCHENETTE 3 317 H1 D-42 316 D-42 A2
D2-25 D2-25 W D-46 D-46 EM5 IT STORAGE &WOS
319 WOS E-8.03 BRG Z WOMEN'S WC D-42 D-42
D-42 E EXW WKB D-48 WORKLAB A2
BRG Z E 318 D-42 EM12 OS H1
HC WC ERC STAIR
EM31-1
D2-25 D2-25 EM31-3 WKB D-48

WKB
D2-25 A3
A3 D-42 315 EM12 3 312
A3 WOS
D2-29 D2-25 OS H A4
E E WPS
A1 A1 A1 EM12 D-42 H EM12 D-48 A2 BRG Z A2
D2-25 EM31-1 EM31-1 ECR
D-42 H D-42 D-42 W EM31-1 EM5 EM31-3
E EXC WKB
H D-42 A2
EM31-3
A3 A3 EM31-3 ERC EM12
A3 EM31-1 A3 EM31-3
D2-27 D2-25 EM31-3 ERC WOS E EM31-3 EXC WOS ZONE e WOS WOS D ZONE b D D
A2 A2 EM12D-48
D2-29 ECR BU-5
D-48 EM31-1 CORRIDOR EM31-3 EXC D-48 BRG Z D-48

WKC WKC
WOS

WKB WKB
ZONE g D2-25 WKB BRG Z EM11 BRG Z E
A2 A2 A2 A2 A2
BU-5 D-48
LOCKER (57) 300 D-48 EXWL D-48
A3 EM31-1 D-48 EM31-1 WOS WPS
A3
A3
D2-27 A3 GW D2-25 D-48 D-48
A1 A1
D2-27 320 D-48 D EM31-1 D-48 D
ZONE k A1
D-48
D2-29 D2-25 WKB
D2-27 EM13 D2-25 S EM4 WOS D-48 D-48
A3 A3 A3 A3 A3 A3 D-48 D-48
LAN ROOM S EM4 ECR
D2-27 A3 EM31-3 D-49 D-49 D-49 D-49 D-49 D-49 D D
D2-27 A3 A3 321 STAIR D46 ZONE x A1 A1
A3 A3
D2-25 E EM31-3 D-48 D-48

WKC WKC
WOS E E ECR WOS BRG Z ZONE w WOS SMALL MEETING ROOM
EM31-1 ERC 2 C D-49
D2-29 D2-29 E D-46 ZONE d 313
D2-27 D-49 D-49 D-49 D-49 D-49 EM31-1 D D D
E EM31-1 S
BU-5 D-46 EM4 A1
D-48 D-48
C.E.S Engineering Ltd.
EM31-1 E D-48 #402 - 4604 Canada Way
A3 EM32-1 A3 WKC D-46 A3 A3 A3 A3 A3 A3
A3 D2-27 A3 A3 BU-5 D-48 Burnaby, BC, V5G 4X7

WKB
D2-27 WOS WKC WKC EXC D D D T: 604.221.8715
5 OPEN EXC

WKC
EM32-1 D2-29 EM31-3 D-48 D-48 D-48 www.cesgroup.ca
WPS D2-27 D2-29 OFFICE EM31-3 ERC
D2-27 E-8.03
D-44 EM11 EM12
E EXW 301A EM31-3 D D EGBC Permit To Practice # 1002458

WKB WKB
A3 A3
D2-27 A3
D2-27 A3 A3 WOS ZONE m ZONE n D-44 A2 A2
A3 A3 EM4 EM12 D-48 D-48 LARGE MEETING D-48 D-48
OPEN OFFICE D-44 EM31-1 D-49 D-49 EM31-1 D-49 D-49 D-49
WOS D2-29 D-44 ZONE y ROOM
D2-27 D2-27 D2-27 301B A E
A3 A3 A3 A3 A3 E A3 A3 A3 D-48 LES ENTREPRENEURS DOIVENT VÉRIFIER TOUTES LES
OPEN OFFICE ZONE j 3 314
ZONE h EM31-1 A3 E WOS DIMENSIONS ET CONDITIONS EXISTANTES DE
D-49 D D
D2-27 310D
A3 A3 A3 BRG Z ZONE ax L'EMPLACEMENT ET DE RAPPORTER TOUT ANOMALIES AU
A3 A3 D2-29 WOS ZONE z
A3 D2-27 D-44 D-48 WPS GESTIONNAIRES DU PROJECT.
E
EXC D2-27 D-49 WOS A2 A2 NE PAS MESURER SUR LES DESSINS.
D2-27 WOS D2-27 A3 BRG Z EM11 WOS EM31-1 EM31-1 D-48
E A3
D2-29 A3 E D-44 WOS D-44 D-49 D-49
EM32-3 D-48 BRG Z CONTRACTORS TO VERIFY ALL DIMENSIONS &
EM31-1 EM31-1 E D CONDITIONS ON SITE AND IMMEDIATELY NOTIFY THE
A3 A3 BRG Z D2-29 EM31-3 A3 A3 A3 A3 A3 A3 A3 A3 D
A3 D1-49 EM32-1 A3 A3 D-44 D-44 ZONE a PROJECT MANAGER OF ALL DISCREPANCIES.
D-49 D-49 D-49 D-48 D-48
D2-27 E A3 EM31-3 DO NOT SCALE DRAWINGS.
A1
ZONE i D2-27 D2-27 D2-29 EXC EXC
A3 A2 A2
D-44
A3 D1-49 A3 EM32-1 D2-29 BRG Z
A3
D-44 D-44 D-49 D-49 D-49 D D-48 D-48 D
A3 D1-49 A3 ERC A3 A1 D-44 D-44
D2-27 D-44 D46 D46 D-48 D D D D-48
BU-4 A3 D-44 WOS A3 WPS A3 A3 A3 A3
A1 D-48 WPS D-48 D-48
D1-49 D2-27 AA ZONE c
BU-4 A3 A3 AA
KB

D1-49 E WOS EM31-1


W

D1-49 EM32-1 D2-27


A3
WOS A3 QUIET ROOM EXC A3 A1
D-44 A3
D-44 D-44
A3 D1-49 D-44
E 307
-4

D1-49 W
KA D1-1 A1 MAIL /FILE ROOM BRG Z A3
BU

EXC BRG Z B3 EM32-1 D-44 WPS


WOS EM32-3
W

EM32-3 E D2-29 309 A3 E A3


-4

D1-49 EM13
KC

ERC E
BU

BRG
W

BRG A3 EM32-1 BRG E


D2-29 WOS A3
KC

A3 W A1
KA

C-5A D1-49 C-5A C-5A KA A4 D-44 D-44


W

EM32-1 D-44
W

B2 A3
KC

B1 D1-49 QUIET ROOM EM32-1 D2-29


WOS E D1-49 ZONE o
WPS C-5A A3
306 WOS ROOM
WOS A3
D-44 12. ISSUED FOR ESI #33 06.02.2024
QUIET ROOM B1
WOS ZONE l D-44
E D1-51 ERC B3 B2
KC

308 A3
305 D1-49 A3 BU-4 EM32-1 D2-29 A
D-44
W

D1-49 EM13 4 11. ISSUED FOR ESI #32 08.12.2023


W D1-49
KB

D1-49 A3
EM32-1 E KA 200W
W

A3 BU-4 W D-44 WOS


KC D1-1 D1-1 C ERC A3
WOS W B2 FREIGHT BU-4 ZONE p QUIET ROOM 10. ISSUED FOR ESI #27 25.09.2023
KC
A3 EM32-1 E ELEVATOR ERW EM32-1 303
BU-4 A3 EXC
D1-51 STAIR D1-1 E D-44 QUIET ROOM 9. ISSUED FOR CONSTRUCTION 17.03.2023
BRG D1-49 A3 WOS
S

D1-51 C B3 W
QUIET ROOM D1-1 1 C 302 KA
C-5A
D1-49 EM3 D1-51 EM32-3 E
BRG REISSUED FOR BUILDING
A3 BRG WOS WPS 8. 10.02.2023
B1
304 EM32-1 EM32-1 C-5A PERMIT
A3 W C-5A
WPS WOS D1-49 C D-44 KA
KA

EM32-3 E B3 7. ISSUED FOR ADDENDUM 1 16.12.2022


W

B1 D1-51 D1-51 12 A3
A3 D1-51
E D1-49 EM32-1 EM32-1
EXC No. description date
WOS A3 E EM32-3 BRG Z D-44
A3 D1-49 WOS
BRG Z
E
D1-1 WOS A3 D1-51
A3 D1-51 EM3 WPS A A detail no . / no. de détail
KB

D1-51 AA
W

B
KC

BRG Z A3 ZONE q B location drawing no. / sur dessin no.


A3 EM32-1
W

A3 ZONE v A3 E
KC

D1-49 D1-51
D1-49
W

WPS D1-49 Project Projet


A3
EM32-1
D1-49 D1-49 EXC A3 EM32-1
A3
A3 WOS A3
D1-51 GOC5033045 ESDC PDOC
OPEN OFFICE D1-51 EM32-3
D1-49 E
301C A3
ZONE r TENANT IMPROVEMENT
ZONE u D1-51
A3 EM32-1 D1-51 AA
A3 A3 WOS
D1-49 D1-49 A3
D1-51
EM13 EM32-1 15330 54a Ave. Surrey, B.C. V3S 8R7
D1-49 D1-51 D1-51
A3 WOS A3
A3
A3 Drawing Dessin
D1-51 EM32-3
D1-51
● READ DRAWING ACCORDINGLY.

D1-51 EXC
ZONE t A3
A3 BRG Z
A3
D1-51
E THIRD FLOOR
D1-51
D1-51
A3
WOS

EM32-1
A3 WPS LIGHTING LAYOUT
A3
D1-51

ZONE s
A3 D1-51
A3 Designed By Conçu par
D1-51
Date
BR (yyyy/mm/dd)
D1-51
A3 Reviewed By Examiné par

Date
BR (yyyy/mm/dd)
Approved by CFBO Apprové par DGAPF
PAPER SIZE: B1 27.8 x 39.4 (707 x 1000) ● PLOT DATE & TIME:

Date (yyyy/mm/dd)
Approved by ISB Apprové par DGSI

Date (yyyy/mm/dd)
Client Approval Approbation du client

Date (yyyy/mm/dd)
Project no. No. du projet

THIRD FLOOR LIGHTING LAYOUT GOC5033045


1 SCALE 1:100
Drawing no. No. du dessin
c E3.03
0 10 20mm 40 60 80 100 120 140 160 180 200mm
CES Engineering Ltd
402–4601 Canada Way
Burnaby, BC V5G 4X7
Tel 604.221.8715
Fax 604.221.8714
www.cesgroup.ca

MECHANICAL SITE INSTRUCTION #13

Project No: BC10028 Date: 08.03.2024.


Project Name: PDOC Surrey TI
Site Instruction No: MSI #13
Subject: New Mop Sink on Third Floor: Plumbing + Fire (CES Response to CCN-43)

Proceeding with work in accordance with these instructions indicates the Contractor's acknowledgment that there will
be no change in the Contract Price and Contract Time. If the Contractor believes that this instruction affects the
Contract Price or Contract Time, the Contractor shall promptly notify the Consultant.

Reference: Contractor CCN#43 (included below)

Reason for change:


☐ 1. Cash Allowance ☒ 4. Site Condition ☐ 7. Procurement
☐ 2. Design Discrepancy ☐ 5. Cost Saving Conditions
☐ 3. Regulatory Change ☐ 6. Design Improvement ☐ 8. Contract Reconciliation
☐ 9. User Change

Instruction/Response:

1. Add a mop sink and all accessories (3/4” ⌀ DCW, 3/4” ⌀ DHW, 1 ½ 2”“⌀
⌀ Vent Pipe, 2” ⌀ Sanitary Pipe)
as shown in the attached drawings.
2. Add a 3”⌀ floor drain.
3. Add a sprinkler head.
4. Refer to the architectural site instructions for the model number and manufacturer information of
the Mop sink.
5. The plumbing contractor to route the sanity pipe on the send floor ceiling space.

END OF MECHANICAL SITE INSTRUCTION #13

Alula Yadete, P.Eng., MASc.,


Project Engineer – Mechanical Engineer
CES Engineering
T: 778 939 1907
ayadete@cesgroup.ca

Page 1 of 1
Canada
Biens Immobiliers, Real Property,
Gestion du Change Management
Changement et and Regional
Services Régionaux Services
(BIGCSR) (RPCMRS)

Key Plan Plan Clé

HP-3-33 HP-3-34 HP-3-35 HP-3-4

3/4" CD @1% 3/4" CD @1% OPEN OFFICE 3/4" CD @1%


3/4" CD @1%
301E
CO 3/4" CD @1% CO
CD CD QUIET ROOM
HP-3-18 310
HP-3-37
HP-3-38 HP-3-3

CD

CD
CD
3/4" CD @1%
GENDER

CD
3/4" CD @1%
HP-3-17 3/4" CD @1% NEUTRAL FOCUS ROOM
CD 3/4" CD @1%
WC 311
4" STM @1% 1" CD @1% 3"FD-1 1" CD @1%
CD
CD

CD
CD

CD
CD
CD

CD
CD

CD

CD
4" STM T/B

CD
4" STM T/B

CD

CD
316

CD
CD

CD

CD

CD
4" STM @1%

CD
CD CD

CD

CD
CD

CD
CD CD

CD
CD
CD
CD CD

CD
CD
CD

CD
CD

CD CD

HP-3-2
CD
CD

CD
CD

CD

CD

CD
CD

CD
CD

CD
CD
CD

KS
CD

CD
CD

ST
CD

CD

CD

CD

SAN
SAN

SAN

SAN

SAN
SAN

SAN
SAN

SAN
SAN

SAN
SAN

SAN

SAN
SAN

SAN
ST

ST
ST ST

SAN
CO
ST

ST
ST

SAN

ST

CD
SAN

ST
SAN
CD

ST
CD

CD
CD
SAN
ST

ST ST ST
ST ST

CD
CD

SAN

ST

ST
CD CD CD

SAN

ST
ST ST CD

SAN

ST
SAN

SAN

ST
ST

CD
ST
SAN

SAN ST

CD
SAN

SAN SAN CD
SAN

ST
SAN SAN
SAN

CD
SAN

CD
SAN

ST
AN

SANS

SAN
SAN CD

SAN
V

SAN
SAN
SAN ST CD

SAN

SAN
SAN

ST
ST

CD
SAN
SAN

SAN
ST ST

SAN
ST SAN SAN SAN CD

SAN
SAN SAN

SAN
SAN

SAN

SAN
SAN

SAN
SAN SAN

SAN

SAN
SAN SAN

SAN
SAN

SAN
SAN
SAN

SAN
SAN

SAN
SAN

SAN

SAN
SAN
SAN

SAN

SAN
SAN
SAN

SAN
SAN

SAN
SAN

SAN

SAN
SAN

SAN
SAN

SAN
SAN

SAN
SAN
CD

SAN

SAN

SAN
SAN

SAN

SAN
SAN SAN
SAN

SAN
SAN

CD

SAN

SAN
SAN

SAN

SAN
SAN

SAN

SAN
SAN

SAN
SAN
CD

SAN
SAN

SAN

SAN

SAN

SAN
SAN

SAN

SAN

SAN
3/4" CD @1%
CD

SAN

SAN

SAN
SAN SAN
SAN

SAN
V
SAN

SAN
SAN

SAN
CD

SAN
SAN

SAN
SAN
SAN SAN
CD
SAN SAN

SAN
SAN SAN SAN

SAN
SAN SAN

SAN

SAN
CD
ALL WASHROOM FIXTURES AND SERVICES

SAN

SAN
SAN
SAN
SAN

SAN

SAN
SAN

SAN
SAN

CD

SAN

SAN
SAN

SAN
SAN SAN

SAN
SAN

SAN
CD
3" DCW F/B

SAN
SAN SAN

SAN

SAN
SAN

SAN

SAN
SAN

SAN
SAN
SAN

CD
SAN

SAN
SAN

SAN
SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN

SAN

SAN

SAN
CD SAN
SAN

SAN
CD

CD
CD

SAN
CD

CD

SAN
CD

SAN
CD
HP-3-36
CD CD
SAN
SAN

CD
SAN SAN

3"FD-1

CD
CD

CD

CD

CD

CD
SAN

IN WASHROOMS MARKED WITH DASHED

CD
SAN SAN

LV
SAN

SAN

CD
SAN

CD

KS

SAN
SAN
SAN

SAN
SAN
CD

SAN

SAN
SAN
3/4" CD @1%

SAN

SAN

SAN
SAN
CD
CD CD

SAN

SAN

CD
HP-3-8

CD
SAN

SAN

SAN

CD
CD

CD CD

SAN
SAN
SAN

SAN

SAN
SAN

SAN
SAN

SAN

SAN

SAN

SAN
SAN

SAN
SAN

SAN
SANS

SAN
SAN

AN
SAN

SAN
LINE SUPPLIED AND INSTALLED BY BASE

SAN
SAN
SAN
SAN

HP-3-20 WC 4" STM @1%


BUILDING CONTRACTOR

ST
KITCHENETTE 3/4" CD @1% HP-3-9
4" STM @1% STAIR

ST
LV
SAN

SAN
SAN

SAN
4" SAN T/B 4" STM

SAN
V

SAN
SAN

SAN
SAN
SAN

SAN

SAN
3/4" CD @1%
SAN SAN
SAN

SAN

SAN
319 2"Ø SAN VENT LINE

SAN

SAN
SAN
SAN

SAN
SAN
SAN

SAN

SAN
V
SAN
SAN
SAN
SAN SAN

3
SAN SAN SAN

SAN
SAN

IT STORAGE & WORKLAB


SAN

SAN

SAN
F/A T/B

SAN

SAN
SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN

SAN

SAN
SAN

SAN
SAN

SAN

CO

SAN
SAN SAN

HC WC

CD
SAN SAN
SAN

SAN
SAN

SAN

SAN
SAN
SAN

SAN
SAN
3"FD-1

SAN
SAN

SAN
SAN
SAN

SAN
SAN SAN

SAN
SAN

SAN

SAN
SAN
SAN

SAN
SAN

SAN

SAN

SAN
SAN
SAN SAN SAN

SAN

SAN

SAN
SAN
SAN

SAN
SAN
SAN

SAN
312

SAN

SAN

SAN
SAN

CD
SAN SAN SAN

SAN

SAN
SAN
CD

SAN
SAN

SAN

SAN

SAN
SAN
CD

SAN
SAN

SAN
CD
SAN

CD

SAN
SAN SAN

SAN
CD

SAN
CD

SAN

SAN

SAN
SAN
CD

SAN
CD
SAN SAN SAN

SAN

CD
SAN

SAN

SAN
CD
SAN
SAN

SAN
CD

SAN
SAN

SAN

SAN
CD

SAN
SAN

SAN

SAN
SAN

SAN
CD SAN

SAN
SAN
SAN SAN

315

SAN

SAN
CD

SAN
SAN
SAN

SAN
SAN

V V V V SAN SAN
G
G

G
WC

SAN

SAN
ST G
ST ST G

ST

SAN

SAN

ST
G
G

ST
ST

SAN
SAN
G

G
ST

ST
SAN
G

SAN
G

ST
ST

SAN
G

SAN

G
ST

ST

G
G

SAN

SAN
ST

ST
G

G
G G

ST

ST
G

FD
ST ST

RD
ST

ST

ST

ST

ST
ST

ST ST

ST
ST

ST
ST

ST
ST
ST

ST
ST

ST ST

ST
ST
ST

1" CD T/B SAN

SAN

SAN
SAN

SAN
SAN

SAN
SAN

SAN
SAN

SAN
SAN

SAN
SAN
SAN

SAN

SAN
SAN

SAN
SAN

CD 3/4" CD T/B 3" 600x300 CORRIDOR 500x300 SMALL MEETING ROOM

CD

CD
LOCKER (57)
CD

CD

600x350

CD
3/4" CD T/B

CD
767 l/s
CD

CD

CD
CD

1033 l/s 313


CD

CD

CD
CD CD

CD
CD
CD

CD
CD
CD

3/4" CD @1% 300 3/4" CD @1%


320 CO
CD CD

1132 l/s

CD

CD
CD CD

CD

CD
CD

CD
V

CD

CD
CD

CD
1" CD @1% CD

1" CD @1%
CD

CD
CD

CD
CD

CD
CD

CD
CD CD CD

CD

CD
CD CD

CD
CD

CD

CD

CD
CD CD CD
FC-1B FC-1A HP-3-39

CD

CD

CD
CD

CD
CD

CD
CD

CD

CD
CO 1" CD @1% 1" CD @ 1%
HP-3-21 ST
LAN ROOM STAIR

V
CD HP-3-10
3/4" CD @1% 321 2
4" STM @1%

CD
ST
ST
ST
3/4" CD @1%

ST
ST

450x200 400x250

ST
ST
RD

ST
ST

ST

ST
ST

ST
ST

ST
ST

ST
ST

ST
ST

350 l/s 465 l/s

CD
HP-3-13 C.E.S Engineering Ltd.
HP-3-22 450x200 450x250 CD CD LARGE MEETING ROOM #402 - 4601 Canada Way, Burnaby, BC, V5G 4X7

V
350 l/s 700 l/s 314 T: 604.239.4424
2"Ø SAN VENT LINE HP-3-12 www.cesgroupglobal.com
HP-3-19 3/4" CD @1%
3/4" CD @1% 3/4" CD @1% EGBC Permit To Practice # 1002458
OPEN OFFICE 350x200 OPEN OFFICE

CD
CO OPEN OFFICE 3/4" CD @1%
301B 218 l/s 301A
CD
CD

CD

LES ENTREPRENEURS DOIVENT VÉRIFIER TOUTES LES


CD
CD

CD
CD

310D
CD

CD CD CD CD
CD

CD
CD

CD

V
CD

CD

DIMENSIONS ET CONDITIONS EXISTANTES DE

CD
CD CD
HP-3-6 L'EMPLACEMENT ET DE RAPPORTER TOUT ANOMALIES AU
CD GESTIONNAIRES DU PROJECT.
400x200 HP-3-7 NE PAS MESURER SUR LES DESSINS.
3/4" CD @1%
245 l/s
3/4" CD @1%
CONTRACTORS TO VERIFY ALL DIMENSIONS &
HP-3-16 CONDITIONS ON SITE AND IMMEDIATELY NOTIFY THE

V
1" CD @1% CD CD PROJECT MANAGER OF ALL DISCREPANCIES.
CD CD CD CD CD CD

HP-3-23
CD CD CD CD CD CD
CD CD CD CD CD CD

CD CD CD CD CD CD

CO HP-3-14 HP-3-15 CO DO NOT SCALE DRAWINGS.


CD HP-3-28
3/4" CD @1%
HP-3-5 3/4" CD @1% 3/4" CD @1%
CO 1" CD @1%
3/4" CD @1%

V
ST ST ST ST ST ST ST ST ST

ST
ST

ST
CD
CD ST

ST

ST
CD
CD

ST

ST
ST
ST
CD

CD

ST

ST
CD

ST
CD

ST

ST
CD

ST

ST
ST

ST
ST

HP-3-24

ST

ST
CD

ST

ST
ST

ST
CD

ST

ST
ST
CD

ST

ST
ST

ST
ST

ST

ST

ST
ST

ST
CD

ST
ST

ST
ST
ST ST

CD
ST

ST
ST

ST
ST

ST
ST

ST
ST
CD

ST
ST
ST
ST

ST
ST ST

MAIL /FILE ROOM


CD
ST
ST

ST
ST

ST

ST
ST
CD

ST
ST

ST
ST ST ST ST ST ST ST ST ST
CD
CD
CD

3"DD-1
309 350x200
CO (300 L)
3/4" CD @1% 186 l/s
QUIET ROOM RD 3/4" CD @1%

V
ST
ST ST
ST
ST

ST

ST

ST
ST

ST
ST

ST

ST

ST

307
ST

CD
ST

ST

ST ST
ST
ST

4" STM @1% 4" STM @1%


HP-3-1 CD 350x200 11. ISSUED FOR MSI 13 08.03.2024
V

1" CD @1% QUIET ROOM ROOM 172 l/s


QUIET ROOM CO 308 300x200 CD 10. ISSUED FOR CONSTRUCTION 17.03.2023
CD

CD

306
CD
CD

CD

CD CD

CD
CD
CD

CD

CD CD

CD

305
CD

CD

HP-3-26 144 l/s


6" STM @1% REISSUED FOR BUILDING
9. 10.02.2023
V

CD PERMIT
4" STM @1% HP-3-11
CD

6" STM FREIGHT 8. ISSUED FOR ADDENDUM 4 18.01.2023


ST

ST
ST

CD
ST

ST
ST

ST

ST
ST

T/B.
ST

ST

ST
ST
ST

ST
ST

STAIR ELEVATOR
QUIET ROOM
V

CD CD

1 7. ISSUED FOR ADDENDUM 1 16.12.2022


CD
CD

NEW 3"FD-1
CD
CD

CD
CD CD

CD
CD
CD

CD

CD

303
CD

CD

CD

HP-3-27
CD

CD

CD

HP-3-25 SAN
SAN SAN

SAN
SAN

SAN
SAN
SAN

SAN
SAN
SAN

SAN
SAN
SAN

SAN
SAN

SAN
SAN

SAN
SAN
SAN

SAN

SAN
SAN
SAN

SAN

SAN

SAN
SAN

SAN

SAN
SAN

SAN

SAN
SAN

SAN

SAN
SAN
SAN

SAN
SAN
SAN

SAN

SAN

SAN
SAN

SAN
SAN

SAN

SAN
SAN

SAN
SAN
SAN
SAN

SAN

4" STM @1%


SAN

SAN
SAN

SAN

SAN

SAN

SAN
SAN

SAN

SAN

SAN
CD

SAN

CO
SAN

SAN

SAN
SAN

SAN
SAN
SAN

SAN

SAN
SAN

SAN
SAN
SAN

SAN
SAN

SAN
SAN

3/4"CD @1%
SAN SAN

QUIET
CD
CD

CD

CD

CD
CD
CD

CD

CD

QUIET 2"Ø SAN VENT LINE ROOM


V

CD

ROOM CD
CD
CD
CD

CD
CD

CD CD
CD

CD
CD
CD

CD CD
CD

CD
CD

CD

CD

302
304 3/4" CD @1%
11 NEW MOP SINK 3/4" CD @1% No. description date
CD

CD
ST

3/4" CD @1% HP-3-30 4" STM @1% A A detail no . / no. de détail

ST
B B location drawing no. / sur dessin no.
ST

ST
ST

ST

ST
ST
ST
ST

ST

ST
ST
ST

ST

ST

ST
ST

ST
ST
ST

RD
CD 3/4" CD300x200
@1% Project Projet
112 l/s
GOC5033045 ESDC PDOC
ST ST ST ST ST ST ST ST ST

ST
ST

ST

HP-3-29
ST
ST

ST
ST

ST
ST
ST
ST

ST

ST
ST

ST
ST

ST
ST

ST
ST

ST

ST
ST

ST
ST

ST
ST

ST

ST
ST

ST
ST

ST
ST

ST

ST

ST
ST

ST

ST
ST

ST
ST
ST

ST
ST

ST
ST

ST

ST ST
ST

ST
ST

ST
ST
ST

ST
ST

ST

ST
ST
ST

ST
ST

ST ST
ST
ST
ST

ST

ST ST ST ST ST ST ST ST ST

OPEN OFFICE 3"DD-1


301C (300 L)
CO TENANT IMPROVEMENT

3/4" CD @1%
CD

15330 54a Ave. Surrey, B.C. V3S 8R7

Drawing Dessin
3/4" CD @1%
HP-3-32
PAPER SIZE: B1 27.8 x 39.4 (707 x 1000) ● PLOT DATE & TIME: 2024-3-08 10:31:41 ● READ DRAWING ACCORDINGLY.

CD

THIRD FLOOR
PLUMBING LAYOUT
HP-3-31

Designed By Conçu par


AY
Date (yyyy/mm/dd)
Reviewed By Examiné par
BR
Date (yyyy/mm/dd)
Approved by CFBO Apprové par DGAPF

Date (yyyy/mm/dd)
Approved by ISB Apprové par DGSI

Date (yyyy/mm/dd)
Client Approval Approbation du client

Date (yyyy/mm/dd)
Project no. No. du projet

GOC5033045
3RD FLOOR PLAN - PLUMBING
1 SCALE 1:100 Drawing no. No. du dessin
c M1.04
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Canada
Biens Immobiliers, Real Property,
Gestion du Change Management
Changement et and Regional
Services Régionaux Services
(BIGCSR) (RPCMRS)

Key Plan Plan Clé

SMALL MEETING ROOM QUIET ROOM


203 205

3/4" CD @1% 3/4" CD @1% HP-2-6


STAFF HP-2-12 HP-2-1 HP-2-3
ENTRANCE HP-2-4 HP-2-2 HP-2-5

CD
DIRECTOR OFFICE
201 CO
CD
CD

CD
CD

CD
CD

CD
CD

CD
CD

CD
CD

CD
CD

CD
CD

CD

OPEN OFFICE 207


204 QUIET ROOM
HP-2-10
COMMISS DESK 206
3/4" @1% 3/4" CD @1%
HP-2-16 202
CD 3/4" CD @1% GENDER

CD
3/4" CD @1% DIRECTOR OFFICE

CD
NEUTRAL

CD
CD
CD
4" STM WC 3/4" CD @1% 3/4" CD @1% 208
4" STM 2" SAN F/A T/B
1" CD @1% 1" CD @1% 1" CD @1% F/A T/B (3FU) 216
F/A, T/B 1" CD @1%
CO CD
KS LV 3/4" CD @1%

CD
CD CD

SAN
SAN SAN
CD CD SAN SAN
SAN

SAN
SAN

SAN
SAN

SAN
CD

CD

SAN
SAN
SAN

SAN
CD

SAN
SAN
SAN

SAN
SAN
SAN

SAN
CD

SAN
SAN
CD
SAN SAN SAN SAN
SAN SAN

SAN
SAN

SAN
SAN
CD CD

CD

CD
SAN

LOCKER (86)
ST

CD CD
CD ST ST

CD
CD

CD CD ST

SAN

ST

SAN
CD

CD

CD
ST
ST
CD

SAN

SAN
CD

ST
ST
CD CD CD
CD

SAN
CD

CD

SAN
CD

CD
CD

CO

ST
CD CD CD CD
CD

SAN

CD
ST
CD

1" CD @1%
ST CD

CD
CD ST ST

CD
CD CD

SAN
CD CD CD

SAN

CD

CD
ST

ST
SAN

CD
CD

ST

ST
CD

ST

SAN
ST

CD
CD

SAN

SAN

CD

CD
SAN

CD
ST

SAN
ST
CD

CD
CD ST

SAN

SAN
ST

SAN
ST

CD

CD

CD
ST CD

CD

SAN

SAN
SAN
ST ST
ST

CD

CD
ST
ST SAN SAN

SAN
SAN SAN

CD

CD
SAN
CD

CD
ST

ST
CD
CD

CD

CD
CD
CD

ST

ST
CD

CD

CD

CD
ST

ST
CD CD

Ø200
SAN SAN

HP-2-8
ST ST SAN

SAN
ST

SAN SAN

SAN
SAN
SAN

SAN
SAN
SAN
SAN

SAN
SAN
SAN

SAN SAN SAN

SAN

SAN

SAN
SAN

SAN
SAN

SAN

SAN

SAN
SAN

SAN
SAN
V

SAN
SAN SAN SAN

SAN
SAN

SAN
SAN
SAN

SAN
SAN

SAN

SAN

SAN

SAN

SAN
SAN
SAN

SAN
SAN

SAN
SAN
SAN SAN SAN

SAN
SAN

SAN

SAN
SAN

SAN

SAN

SAN
SAN
SAN
SAN

SAN
ALL WASHROOM FIXTURES AND SERVICES

SAN
SAN
SAN SAN SAN SAN
SAN

SAN
SAN SAN

SAN
SAN
SAN

SAN

SAN

SAN
SAN
233

SAN
SAN

SAN
SAN

SAN

SAN

SAN
SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN

SAN

SAN
SAN

SAN

SAN
SAN SAN

SAN
SAN SAN

SAN
SAN

SAN
SAN

SAN
WC

SAN

You might also like