CTE33242R_1000-PD01

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

DDCC-ChungLi

NOTES: Document is
1. Eltek P/N: CTE33242R.1000 Released
2. Eltek Doc No. REDM0000767459 2022.11.23
10:08:29 +08'00'

REV. Change Description Date Drawn

00 ISSUE NEW SPEC. (Attached file total 2 page) 21.03.2022 STHUSK

ECN 103E-22B058 update ISSUE NEW SPEC.


01 (Attached file total 2 pages) 18.11.2022 IVAHUTSK

台達電子工業股份有限公司 DESCRIPTION :

DELTA ELECTRONICS, INC. PHYSICAL DIMENSIONS


THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY OF DELTA
ELECTRONICS, INC. AND SHALL NOT BE REPRODUCED OR USED AS THE
MODEL NO. :
BASIS FOR THE MANUFACTURE OR SELL OF APPARATUSES OR DEVICES
WITHOUT PERMISSION. CTE33242R.1000

Date Drawn Design (EE) Testing (TE) DOCUMENT NO. : REV.


18.11.2022 IVAHUTSK IVAHUTSK N/A PD-CTE33242R.1000 01
File Name:DF-PSLA4V-2R01.DOC SHEET: 1 OF 1
CTE33242R.1000

This Power system 96kW+12kVA consist of:


- 32 rectifiers 3kW slots and 8 rectiverters
42U slots
Mains Input 1, 2, 3, 4 01

1 1 1 1
- 4x AC Mains Input Configurable (TN, IT)
40U - FPC cabinet W600xD600xH2m, Top entry
- SP2 Basic Industrial (A2),Smartpack 2 Touch
AC Load distribution 01

38U (A1),I/O Monitor type 2

36U
Battery distribution
- 4x TPS2/1600 fuse holder [FB1 – FB4]
34U Positive load connections 01
- 4x 800A Fuse

32U LOAD distribution


- 8X TPS00 , 8X250A fuse [F1-F8]
30U
01
Load distribution 8x TPS00
AC Load Distribution Siemens 10kA w/AUX
28U - 1x 20A /B 2P + AUX (Q1)
F1
F1 F2
F2 F3
F3 F4
F4 F5 F6 F7 F8 - 2x 16A/C 2p +AUX( Q2,Q3)
F1
- 4x 10A/C 2p +AUX (Q4 – Q7)
26U
Positive battery connections 01 - 2x 6A /C 2P+AUX (Q8, Q9)
24U

22U
FB 1 FB 2 FB 3 FB 4
IO monitor Customer connection
20U
Battery distribution FB1-FB4 01 CONFIGURABLE INPUTS ALARM OUTPUTS

1 12 1 18
18U
Positive DC GND 01

16U
SP Basic Industrial
I/O monitor - + - + NO C NC NO C NC
14U
2x Rectiverter rack
REC1
12U
REC2
PR1
10U

8U 8x Rectifier rack

6U

4U
PR8
01

2U Date Design Draw Approved Scale


11.03.2022 STHUSK STHUSK PTC -

Copyright Elt ek.


01 Al l rights re served
FP2 96kW+12kVA 3X3D230V BD FPC Part no.
CTE33242R.1000
HxDxW: 2000x600x600mm Sym.
01
Alternation Date/Sign Format Page Drawing no. Rev.
103E-22B058 18.11.2022/ IVAHUTSK A3 1 of 2 PD-CT E33242R.1000 01
Customer connection
Customer connection (Factory setting)

Mains1 Mains2 Mains3 Mains4


Mains1 Mains2 Mains3 Mains4
N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3
L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3

TN IT
1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7
1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7

Customer connection

RV1/L1 RV2 /L1 RV3/L1 RV4 /L1 REC1


RV5/L1 RV6/L1 RV7/L1 RV8 /L1 REC2
N L N L PE
R1/ L1 R2/ L2 R3/ L3 R13/ L1 PR1 01 01
Mains input 1 PE PE PE PE PE PE

R14/ L2 R15/ L3 R25/ L1 R26/ L2 PR2


R4/ L1 R5/ L2 R6/ L3 R16/ L1 PR3 AC LOAD Distribution
Mains input 2
R17/ L2 R18/L3 R27/ L1 R28/ L2 PR4
R7/ L1 R8/ L2 R9/ L3 R19/ L1 PR5
Mains input 3
R20/ L2 R21/ L3 R29/ L1 R30/L2 PR6
Q1 Q9
R10/ L1 R11/ L2 R12/ L3 R22/ L1 PR7
Mains input 4
R23/ L2 R24/L3 R31/ L1 R32/ L2 PR8

Note: Position of rectifier and


rectiverter modules

Date Design Draw Approved Scale


11.03.2022 STHUSK STHUSK PTC -

Copyright Elt ek.


Al l rights re served
FP2 96kW+12kVA 3X3D230V BD FPC Part no.
CTE33242R.1000
Sym. Alternation Date/Sign Format Page Drawing no. Rev.
01 PD-CT E33242R.1000
103E-22B058 18.11.2022/ IVAHUTSK A3 2 of 2 01